Kuhlman 69kV Voltage Transformer Guide

This document provides information on the Kuhlman Electric Corporation's 69000 Volt Instrument Transformers, including the POF-350 (DB) Wound, Oil-Filled Voltage Transformer and the DDB-72 Wound, Oil-Filled Capacitive Voltage Transformer. It describes the mechanical design, accuracy performance, mounting, testing, options, and ordering information for each model.

Uploaded by

Kay Karthi
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
328 views14 pages

Kuhlman 69kV Voltage Transformer Guide

This document provides information on the Kuhlman Electric Corporation's 69000 Volt Instrument Transformers, including the POF-350 (DB) Wound, Oil-Filled Voltage Transformer and the DDB-72 Wound, Oil-Filled Capacitive Voltage Transformer. It describes the mechanical design, accuracy performance, mounting, testing, options, and ordering information for each model.

Uploaded by

Kay Karthi
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Kuhlman Electric Corporation

69000 Volt Instrument Transformers

69000 Volt
March 2008

Table of Contents
Model POF-350 (DB) DDB-72 CE-069 COF(CXM)-350 SSVT-350 KA-72(KXM-350) Page 3-4 5-6 7-8 9-10 11-12 13-14

Description Wound, Oil-Filled VT (High Accuracy available) Wound, Oil-Filled CCVT (High Accuracy available) Wound, Dry-Type CT Wound, Oil-lled CT (High Accuracy available) Wound, Oil-Filled, Station Service Voltage Transformer Wound, Oil-Filled, Single Phase Metering Unit (High Accuracy available)

Dry type: 3022 NC 43 North Pinetops, NC 27864 Phone: +1 252 827-3212 [Link]/mediumvoltage Oil type: 101 Kuhlman Blvd Versailles, Kentucky 40383 Phone: +1 859 879-2999 [Link]/highvoltage

POF350 (DB) Voltage Transformer


Outdoor 69kV, 350kV BIL, Single & Dual Ratios (w/ Tertiary) Oil-Filled, Wound Type, Metering/Relaying

69000 Volt
March 2008

application The POF-350 (DB) outdoor voltage transformer is rated for use on 69,000 volt systems with 350kV BIL. Primary voltage ratios are available from 300:1 to 1039:1 for use on 69,000 volt systems, at 60 Hertz (Hz). This oil-lled instrument voltage transformer will operate with high accuracy for metering or relay applications. mechanical description The tank and expansion chambers are steel plate, pressure and vacuum tight and hermetically sealed at the factory to prevent breathing and oil contamination. Expansion chambers allow for the expansion/contraction of oil for temperature and load uctuations. Tank components are washed and coated with anticorrosive iron phosphate and then nished with ANSI 70 Gray baked-on electrostatic polyester powder. The primary bushing(s) are ANSI 70 Gray, high strength porcelain with a high degree of stability for transportation and seismic withstand. The primary terminal(s) are stainless steel NEMA 4-hole pad(s). The secondary terminals are -20 copper studs with associated hardware located inside a removable terminal box with three (3) 1 NPT conduit hubs. The ground terminal is a stainless steel NEMA 2-hole pad. The unit is tted with a 5kV H0 Bushing (for single bushing designs), pressure relief valve, oil level indicator, oil ll plug, and drain valve. accuracy performance The POF-350 (DB) will operate with 0.3 Class accuracy for metering applications with burdens of 0, W, X, M, Y, Z and ZZ. Upon request, 0.15 Class metering accuracy is available with burdens of 0, W, X, M, Y and Z, as well as 0.3 ZZ. The transformer is accurate from 90% to 110% of rated primary voltage. mounting The POF is designed for mounting on substation structures with mounting feet in an upright position. Single bushing units can be mounted on poles with ANSI type A hanger brackets. NOTE: Must be installed per NESC electrical clearances. testing The unit is individually tested per the IEEE C57.13 standard, including applied and induced voltage, accuracy and polarity. Additional tests include dissipation and partial discharge tests. Partial discharge testing is performed to guarantee the unit is free of partial discharge through 135% of the nominal system voltage. options The POF is available in single or double bushing models, with Extra Creep Bushing(s), Polymer Bushing(s), Stainless Steel Tank, and/or -50C oil. Contact factory for other needs.

ORDERING INFO FOR POF-350 (DB)


Ratio 300/[Link] 175/300:1 or 350/600:1 350/[Link] 350/[Link] 350/[Link] 350/600:1 & 600/1039:1 600/[Link] 600/[Link] Primary 34500 20125 or 40250 40250 40250 40250 or 69000 40250 or 69000 69000 69000 Secondary 115/69 & 115/69 115/67.08 or 115/67.08 115/67.08 & 115/67.08 (3) 115/67.08 115/67.08 & 115/67.08 or 115 & 115 115/69 & 115 or 115 & 115/66.4 115/69 & 115/69 115/69 & 115/69 Catalog Number 1 Bushing J710500TD TBD *J710600TD J710600MD ----2 Bushing ----**J820600TA J821039TA J821039ZA J821039ZA Accuracy/ Burden 0.3 0,W,X,M,Y,Z,ZZ 0.3 0,W,X,M,Y 0.3 0,W,X,M,Y,Z,ZZ 0.3 0,W,X,M,Y,Z,ZZ 0.3 0,W,X,M,Y,Z,ZZ 0.3 0,W,X,M,Y,Z 0.3 0,W,X,M,Y,Z,ZZ 0.3 0,W,X,M,Y,Z 0.3 0,W,X,M,Y,Z,ZZ 0.3 0,W,X,M,Y,Z,ZZ 0.3 0,W,X,M,Y,Z,ZZ

HIGH ACCURACY POF-350 (DB) Catalog Number Accuracy/ Burden 0.15 0 to Z, 0.3 ZZ 0.15 0 to X, 0.3 Y Add AAEW to the end of the standard catalog number 0.15 0 to Z, 0.3 ZZ 0.15 0 to Z, 0.3 ZZ 0.15 0 to Z, 0.3 ZZ 0.15 0 to Y, 0.3 Z 0.15 0 to Z, 0.3 ZZ 0.15 0 to Y, 0.3 Z 0.15 0 to Z, 0.3 ZZ 0.15 0 to Z, 0.3 ZZ 0.15 0 to Z, 0.3 ZZ

- Thermal Burden Rating (Typical): 6000VA. Dual primary units (4000VA L-G, 7000VA L-L). - Overvoltage Rating: 1.1x cont., 1.9x 8 hours (single bushing designs). - IC Approval *(AE-0870), **(AE-0922).

Dry type: 3022 NC 43 North Pinetops, NC 27864 Phone: +1 252 827-3212 [Link]/mediumvoltage Oil type: 101 Kuhlman Blvd Versailles, Kentucky 40383 Phone: +1 859 879-2999 [Link]/highvoltage

69000 Volt
March 2008

POF350 (DB) Voltage Transformer

NOTE: OUTLINES ARE FOR REFERENCE ONLY. CONTACT FACTORY FOR ACTUAL DESIGN DRAWINGS. Dry type: 3022 NC 43 North Pinetops, NC 27864 Phone: +1 252 827-3212 [Link]/mediumvoltage Oil type: 101 Kuhlman Blvd Versailles, Kentucky 40383 Phone: +1 859 879-2999 [Link]/highvoltage

DDB72 Capacitive VT
Outdoor 69kV, 350kV BIL, Single & Dual Ratios (w/ Tertiary) Oil-Filled, Wound Type, Metering/Relaying

69000 Volt
March 2008

application The DDB-72 outdoor coupling capacitive voltage transformer is rated for use on 69,000 volt systems with 350kV BIL. Primary line to ground connected voltage ratios are available from 300:1 to 600:1 for use on 69,000 volt systems, at 60 Hertz (Hz). This oil-lled coupling capacitive voltage transformer will operate with high accuracy for metering, monitoring, carrier communication, or relay applications. mechanical description The transformer contains mechanically stabilized capacitor layers, a multi-tap inductive voltage transformer, and a reactor for calibration of the voltage output built into a fully insulated, oil-lled base assembly. The tank is steel plate, pressure and vacuum tight and hermetically sealed at the factory to prevent breathing and oil contamination. The dome is aluminum and contains stainless steel expansion bellows to allow for the expansion/contraction of oil for temperature and load uctuations. The bellows maintain constant pressure on the oil under various ambient and load conditions to allow for horizontal shipment. Tank components are shot-blasted, washed and coated with a heavy galvanized nish, effectively making the unit paint-free. The primary bushing is ANSI 70 Gray, high strength porcelain with a high degree of stability for transportation and seismic withstand. The primary terminal is a tin-plated copper alloy stud supplied with a NEMA 4-hole pad connector. The secondary terminals are M8 hex head bolts with associated hardware located inside a removable cover, terminal box with a 1 conduit opening in the bottom plate. The ground terminal is an integral NEMA 2-hole conguration on the base. The unit is tted with a reconnectable ground terminal, for direct tank ground connection or for use with carrier accessories for high frequency injection, a voltage tap ground switch, oil level indicator, and oil sampling valve. accuracy performance The DDB-72 will operate with 0.3 Class accuracy for metering applications with burdens of 0, W, X, M, Y, Z and up to ZZ and 0.6 Class accuracy for relaying applications with burdens of 0, W, X, M, Y, Z and up to ZZ. Upon request, 0.15 Class metering accuracy is available and burden capability up to Z on each secondary winding. The transformer is accurate from 90% to 110% of rated primary voltage.

mounting The DDB is designed for mounting on substations structures in an upright position with four mounting holes in the base. testing The unit is individually tested per the ANSI C93.1 standard, including applied and induced voltage, accuracy and polarity. Additional tests include dissipation and partial discharge tests. Partial discharge testing is performed to guarantee the unit is free of partial discharge through 135% of the nominal system voltage. options The DDB is available with an additional secondary winding (3 total), Extra Creep Bushing, Polymer Bushing, Stainless Steel Tank, Carrier Accessories (Drain Coil, Carrier Ground Switch, Spark Gap), and/or -50C oil. Line traps also available. Contact factory for other needs.

ORDERING INFO FOR DDB-72


Capacitance (pF) 7400 7400 7400 16700 16700 17200 17200 40000 40000 Ratio - 350/[Link] Primary Secondary 40250 40250 40250 40250 40250 40250 40250 40250 40250 115/67.08 & 115/67.08 115/67.08 & 115/67.08 115/67.08 & 115/67.08 115/67.08 & 115/67.08 115/67.08 & 115/67.08 115/67.08 & 115/67.08 115/67.08 & 115/67.08 115/67.08 & 115/67.08 115/67.08 & 115/67.08 Catalog Number J76074P0600N J76074R0600N J76074M0600N J76167R0600N J76167M0600N J76172R0600N J76172M0600N J76400M0600N J76400Z0600N Accuracy/ Burden 1.2 0,W,X,M,Y,Z 0.6 0,W,X,M,Y,Z 0.3 0,W,X,M,Y,Z 0.6 0,W,X,M,Y,Z 0.3 0,W,X,M,Y,Z 0.6 0,W,X,M,Y,Z 0.3 0,W,X,M,Y,Z 0.3 0,W,X,M,Y,Z 0.3 0,W,X,M,Y,Z,ZZ

HIGH ACCURACY DDB-72


Catalog Number Accuracy/ Burden --0.15 0,W,X,M,Y -0.15 0,W,X,M,Y -0.15 0,W,X,M,Y 0.15 0,W,X,M,Y 0.15 0,W,X,M,Y,Z

Contact factory for cataloging information

- Thermal burden rating (Typical): 1000VA (1500VA for 0.3 ZZ rated units). - Overvoltage Ratings: 1.1x cont., 1.4x 1 min. - Units available with carrier accessories. Change last letter of catalog number from N to C. Dry type: 3022 NC 43 North Pinetops, NC 27864 Phone: +1 252 827-3212 [Link]/mediumvoltage Oil type: 101 Kuhlman Blvd Versailles, Kentucky 40383 Phone: +1 859 879-2999 [Link]/highvoltage

69000 Volt
March 2008

DDB72 Capacitive VT

NOTE: OUTLINES ARE FOR REFERENCE ONLY. CONTACT FACTORY FOR ACTUAL DESIGN DRAWINGS. Dry type: 3022 NC 43 North Pinetops, NC 27864 Phone: +1 252 827-3212 [Link]/mediumvoltage Oil type: 101 Kuhlman Blvd Versailles, Kentucky 40383 Phone: +1 859 879-2999 [Link]/highvoltage

CE069 Current Transformer


Outdoor 69kV, 350kV BIL, Single & Dual Ratios Molded Epoxy, Wound Type, Metering/Relaying

69000 Volt
March 2008

application The CE-069 outdoor current transformer is rated for use on 69,000 volt systems with 350kV BIL. Primary current ratios are available from 25:5 to 3000:5 at 60 Hertz (Hz) with a Rating Factor of up to 2.0. This dry-type, solid-cast current transformer will operate with high accuracy for metering or relay applications. mechanical description The core and coil assembly is wound and encapsulated in a high dielectric strength epoxy resin to provide high withstand capabilities. The external line to ground insulation consists of a cycloaliphatic epoxy resin that provides excellent arc track properties in addition to ultraviolet resistance and strong physical strength. The primary terminals are tin-plated copper alloy studs supplied with NEMA 4-hole pad connectors. The clamp-type post secondary terminals have -20 slotted screws and associated hardware located inside a removable terminal box with two (2) 1 NPT conduit hubs. The ground terminal is an integral NEMA testing The unit is individually tested per the IEEE C57.13 standard, 2-hole conguration on the CT base. including applied and induced voltage, accuracy and polarity. Partial discharge testing is performed to guarantee the unit is accuracy performance The CE-069 will operate with 0.3 Class accuracy for metering free of partial discharge through 120% of the nominal system with burdens of B0.1 to B1.8 and up to T800 for some relay voltage. applications. The transformer is accurate through its Rating options Factor, and can be used continuously to this level. A primary spark gap is available for capacitor bank or other applications where high transients will be present. The unit can mounting The CE is designed for mounting on substation structures in an be offered in single, dual or multiple core designs. Contact factory for other needs. upright position with four mounting holes in the base.

ORDERING INFO FOR CE-069


Ratio 25:5 30:5 100:5 150:5 200:5 1500:5 2000:5 3000:5 25/50:5 50/100:5 600/1200:5 1000/2000:5 1500/3000:5 Catalog Number J060025S0 J060030S0 J060100S0 J060150S0 J060200S0 J061500S0 J062000S0 J063000S0 J060025D0 J060050D0 J060600D0 J061000D0 J061500D0 Accuracy/Burden Metering Relay 0.3 B1.8 0.3 B1.8 0.3 B1.8 0.3 B1.8 0.3 B1.8 0.3 B1.8 0.3 B1.8 0.3 B1.8 0.3 B1.8/B1.8 0.3 B1.8/B1.8 0.3 B1.8/B1.8 0.3 B1.8/B1.8 0.3 B1.8/B1.8 T400 T400 T400 T400 T400 T400 T400 T800 T200/T400 T200/T400 T200/T400 T200/T400 T400/T800 Rating Factor 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.0 2.0/1.5 2.0/1.5 2.0/1.5 2.0/1.5 2.0/1.0

HIGH ACCURACY N/A


Catalog Number ----------------Accuracy/ Burden ----------------Rating Factor -----------------

- 1 Second Thermal/Mechanical Ratings: 100x Inom (63kA max) Thermal / 180x (150x for 3000:5 & 1500/3000:5) Mechanical.

Dry type: 3022 NC 43 North Pinetops, NC 27864 Phone: +1 252 827-3212 [Link]/mediumvoltage Oil type: 101 Kuhlman Blvd Versailles, Kentucky 40383 Phone: +1 859 879-2999 [Link]/highvoltage

69000 Volt
March 2008

CE069 Current Transformer

NOTE: OUTLINES ARE FOR REFERENCE ONLY. CONTACT FACTORY FOR ACTUAL DESIGN DRAWINGS. Dry type: 3022 NC 43 North Pinetops, NC 27864 Phone: +1 252 827-3212 [Link]/mediumvoltage Oil type: 101 Kuhlman Blvd Versailles, Kentucky 40383 Phone: +1 859 879-2999 [Link]/highvoltage

COF(CXM)350 Current Transformer


Outdoor 69kV, 350kV BIL, Single, Dual & Multi Ratios Oil-Filled, Wound Type, Metering/Relaying

69000 Volt
March 2008

application The COF(CXM)-350 outdoor current transformer is rated for use on 69,000 volt systems with 350kV BIL. Primary current ratios are available from 5:5 to 3000:5 at 60 Hertz (Hz) with a Rating Factor of up to 4.0 (3200A max). This oil-lled current transformer will operate with high accuracy for metering or relay applications. mechanical description The tank dome is fabricated from carbon or stainless steel, depending on current rating. The units are pressure and vacuum tight and hermetically sealed at the factory to prevent breathing and oil contamination. Tank components are washed and coated with anticorrosive iron phosphate and then nished with ANSI 70 Gray baked-on electrostatic polyester powder. The bushing is ANSI 70 Gray, high strength porcelain with a high degree of stability for transportation and seismic withstand. The primary terminals are tin plated aluminum, NEMA 4-hole pads for units rated 400A (copper for units rated 2000A) and NEMA 2-hole pads for units rated <400A. A bypass protector is provided for all units rated below 1200:5 to protect from transients. The secondary terminals are #10 slotted screws on a short circuiting terminal block located behind a removable cover in the CT base with three (3) 1 NPT conduit hubs. The ground terminal is a stainless steel NEMA 2-hole pad. The unit is tted with a pressure relief valve, oil level gauge, and drain valve. accuracy performance The COF-350 will operate with 0.3 Class accuracy for metering applications with burdens of B0.1 to B1.8. The unit can be designed with relay accuracy up to C800. The transformer is accurate through its Rating Factor, and can be used continuously to this level. The CXM-350 will operate with 0.15 Class high accuracy for metering applications with burdens of B0.1 to B1.8. The transformer maintains 0.15 Class accuracy from 0.5% of Inom through its Rating Factor, and can be used continuously to this level.

mounting The COF(CXM) is designed for mounting on substations structures in an upright position with four mounting holes in the base. testing The unit is individually tested per the IEEE C57.13 standard, including applied and induced voltage, accuracy and polarity. Additional tests include dissipation and partial discharge tests. Partial discharge testing is performed to guarantee the unit is free of partial discharge through 135% of the nominal system voltage. options The COF(CXM) is available with an Extra Creep Bushing, Polymer Bushing, Stainless Steel Tank, 4kV spark gap and/or -50C oil. The unit can be offered in single, dual or multiple core designs. Contact factory for other needs.

ORDERING INFO FOR COF-350


Ratio 5:5 10:5 150:5 200:5 3000:5 5/10:5 10/20:5 100/200:5 150/300:5 1000/2000:5 1500/3000:5 Catalog Number* J950005SA J950010SA J950150SA J950200SA J953000SA J950010DA J950020DA J950200DA J950300DA J952000DA J953000DA Accuracy/ Burden 0.3 B1.8 0.3 B1.8 0.3 B1.8 0.3 B1.8 0.3 B1.8 0.3 B1.8/B1.8 0.3 B1.8/B1.8 0.3 B1.8/B1.8 0.3 B1.8/B1.8 0.3 B1.8/B1.8 0.3 B1.8/B1.8 Rating Factor 1.5 1.5 1.5 1.5 1.0 2.0/1.5 2.0/1.5 2.0/1.5 2.0/1.5 2.0/1.5 2.0/1.0

HIGH ACCURACY CXM-350


Catalog Number J890005SA J890010SA J890150SA J890200SA J893000SA -------- 0.15 B1.8 Acc Range 0.025 to 20A 0.05 to 40A 0.75 to 600A 1 to 800A 15 to 3200A -------- Rating Factor 4.0 4.0 4.0 4.0 1.07 --------

- Available in multi-ratio designs (full tap ratings same as single ratio above). - 1 Second Thermal/Mechanical Rating: Single Ratio (150x lnom), Dual Ratio (75x full winding Inom), 144kA max. * IC Approval AE-0869 for 600/1200:5. Dry type: 3022 NC 43 North Pinetops, NC 27864 Phone: +1 252 827-3212 [Link]/mediumvoltage Oil type: 101 Kuhlman Blvd Versailles, Kentucky 40383 Phone: +1 859 879-2999 [Link]/highvoltage

69000 Volt
March 2008

COF(CXM)350 Current Transformer

10

NOTE: OUTLINES ARE FOR REFERENCE ONLY. CONTACT FACTORY FOR ACTUAL DESIGN DRAWINGS. Dry type: 3022 NC 43 North Pinetops, NC 27864 Phone: +1 252 827-3212 [Link]/mediumvoltage Oil type: 101 Kuhlman Blvd Versailles, Kentucky 40383 Phone: +1 859 879-2999 [Link]/highvoltage

SSVT350 Station Service VT


Outdoor 69kV, 350kV BIL, Power Winding, Single & Dual Ratios (w/ Tertiary) Oil-Filled, Wound Type, Control Power/Metering/Relaying

69000 Volt
March 2008

application The SSVT-350 outdoor station service voltage transformer is rated for use on 69,000 volt systems with 350kV BIL. The unit is a station service voltage transformer with power and can be supplied with metering rated secondary winding(s). It provides a convenient and cost effective means of serving small power and/or metering requirements directly from a transmission line. Standard 125/250V nominal power winding designs are available with thermal ratings of 10, 25, 50, 100 kVA and higher. Primary voltage measurement ratios are available from 300:1 to 600:1 for use on 69,000 volt systems, at 60 Hertz (Hz). This oil-lled station service voltage transformer will provide control power and can provide high accuracy for metering or relay applications. mechanical description The tank and expansion chambers are steel plate, pressure and vacuum tight and hermetically sealed at the factory to prevent breathing and oil contamination. Expansion chambers allow for the expansion/contraction of oil for temperature and load uctuations. Tank components are washed and coated with anticorrosive iron phosphate and then nished with ANSI 70 Gray bakedon electrostatic polyester powder. The primary bushing is ANSI 70 Gray, high strength porcelain with a high degree of stability for transportation and seismic withstand. The primary terminal is a stainless steel, NEMA 4-hole pad. The secondary station service power terminals are 1-14 externally mounted studs housed in an ANSI 4X low voltage terminal box separate from metering with a removable plate and 6 x 20 opening in the bottom for conduit entry. They are offered with high conductivity, tin plated aluminum, 2-hole set screw connectors suitable for 1/0 to 750MCM conductors terminals. The neutral, tank ground connector accepts 1/0 to 750 MCM conductors. The secondary metering terminals are -20 copper studs with associated hardware located inside a removable terminal box with three (3) 1 NPT conduit hubs. The ground terminal is a stainless steel NEMA 2-hole pad. The unit is tted with a 5kV H0 Bushing, pressure relief valve, oil level gauge, oil ll plug, and drain valve. accuracy performance The SSVT-350 will operate with nominal 125/250V control power output and if specied, a 0.15 Class metering accuracy for burdens of 0, W, X, M, Y, Z and ZZ (0.3 ZZ for 10kVA size power units). The transformer is accurate from 90% to 110% of rated primary voltage. Unique to the SSVT design is the ability to power motor loads of up to 10% of the transformer kVA rating and metering/relaying simultaneously.

mounting The SSVT is designed for mounting on substations structures in an upright position with four mounting holes in the base. testing The unit is individually tested per the IEEE C57.13 standard, including applied and induced voltage, accuracy and polarity. Additional tests include dissipation and partial discharge tests. Partial discharge testing is performed to guarantee the unit is free of partial discharge through 135% of the nominal system voltage. options The SSVT is available with an Extra Creep Bushing, Polymer Bushing, Stainless Steel Tank and/or Dome, one or two secondary metering windings, one or two CTs, de-energized taps and/or -50C oil. Other secondary terminal connectors include Clamp Type for up to 1000MCM or NEMA 4-hole Pads. Contact factory for other needs.

ORDERING INFO FOR SSVT-350


kVA Rating 10 25 50 100 Primary Voltage 40250 40250 40250 40250 Secondary Volts Power Metering 125/250 125/250 125/250 125/250 115/67.08 115/67.08 115/67.08 115/67.08 Catalog Number w/o Metering w/ Metering* J97N323010A J99N323025B J99N323050B J99N328100B J97M323010A J99M323025B J99M323050B J99M328100B Metering Accuracy/Burden 0.3 0,W,X,Y,Z,ZZ 0.15 0,W,X,Y,Z,ZZ 0.15 0,W,X,Y,Z,ZZ 0.15 0,W,X,Y,Z,ZZ

*For two metering secondaries, change M to D in catalog no. Nominal output. Actual rated output is supplied on unit nameplate. - Overvoltage Ratings: 1.1x cont., 1.73x 1 min.

Dry type: 3022 NC 43 North Pinetops, NC 27864 Phone: +1 252 827-3212 [Link]/mediumvoltage Oil type: 101 Kuhlman Blvd Versailles, Kentucky 40383 Phone: +1 859 879-2999 [Link]/highvoltage

11

69000 Volt
March 2008

SSVT350 Station Service VT

12

NOTE: OUTLINES ARE FOR REFERENCE ONLY. CONTACT FACTORY FOR ACTUAL DESIGN DRAWINGS. Dry type: 3022 NC 43 North Pinetops, NC 27864 Phone: +1 252 827-3212 [Link]/mediumvoltage Oil type: 101 Kuhlman Blvd Versailles, Kentucky 40383 Phone: +1 859 879-2999 [Link]/highvoltage

KA72(KXM350) 1 Metering Unit


Outdoor 69kV, 350kV BIL, Single, Dual & Multi Ratios Oil-Filled, Wound Type, 1 Metering

69000 Volt
March 2008

application The KA-72(KXM-350) outdoor single phase metering unit is rated for use on 69,000 volt systems with 350kV BIL. Primary current ratios are 5:5 to 4000:5 for 60 Hertz (Hz) with a Rating Factor of up to 4.0 (4800A max). Primary line to ground rated voltage ratios are available from 300:1 to 600:1 for use on 69,000 volt systems. This oil-lled metering unit will operate with high accuracy for metering applications. mechanical description The transformer contains two fully insulated coils for both current and voltage measurement. The tank is steel plate, pressure and vacuum tight and hermetically sealed at the factory to prevent breathing and oil contamination. The dome is corrosion resistant aluminum and contains stainless steel expansion bellows to allow for the expansion/contraction of oil for temperature and load uctuations. The bellows maintain constant pressure on the oil under various ambient and load conditions to allow for horizontal shipment. Tank components are shot-blasted, washed and coated with a heavy galvanized nish, effectively making the unit paint-free. The primary bushing is ANSI 70 Gray, high strength porcelain with a high degree of stability for transportation and seismic withstand. The primary terminals are tin plated aluminum, NEMA 4-hole pads (copper for units rated above 1800A). An adjustable primary spark gap is provided for all units to protect from high transients. The secondary terminals are M8 hex head bolts with associated hardware located inside a hinged cover, terminal box with three (3) 1 NPT conduit hubs. The ground terminal is an integral NEMA 2-hole conguration on the tank wall. The unit is tted with a 5kV H0 terminal, oil level indicator, and oil sampling valve. accuracy performance The KA-72 will operate, for the current transformer, with 0.3 Class accuracy for metering with burdens of B0.1 to B1.8. The CT is accurate through its Rating Factor, and can be used continuously to this level. The unit will operate, for the voltage transformer, with 0.3 Class accuracy for metering with burdens of 0, W, X,

M, Y, Z and ZZ. The VT is accurate from 90% to 110% of rated primary voltage. The KXM-350 will operate, for the current transformer, with 0.15 Class high accuracy for metering applications with burdens of B0.1 to B1.8. The transformer maintains 0.15 Class accuracy from 0.5% of Inom through its Rating Factor, and can be used continuously to this level. The unit can be provided, for the voltage transformer, with 0.15 Class accuracy for metering with burdens of 0, W, X, M, Y and Z. The VT is accurate from 90% to 110% of rated primary voltage. mounting The KA(KXM) is designed for mounting on substation structures in an upright position with four mounting holes in the base. testing The unit is individually tested per the IEEE C57.13 standard, including applied and induced voltage, accuracy and polarity. Additional tests include dissipation and partial discharge tests. Partial discharge testing is performed to guarantee the unit is free of partial discharge through 135% of the nominal system voltage. options The KA(KXM) is available with an Extra Creep Bushing, Polymer Bushing, Stainless Steel Tank, and/or -50C oil. The unit can be offered in single, dual or multiple core designs. Contact factory for other needs.

ORDERING INFO FOR KA-72


Voltage Ratings Current Ratio 5:5 10:5 100:5 150:5 4000:5 5/10:5 10/20:5 2000/4000:5 Ratio* - 350/[Link] Pri*:Sec - 40250:115/67.08 & 115/67.08 Catalog Number J750600T005S J750600T010S J750600T100S J750600T150S J750600T402S J750600T005D J750600T010D J750600T202D Accuracy/Burden 0.3 0,W,X,M,Y,Z,ZZ Accuracy/ Burden 0.3 B1.8 0.3 B1.8 0.3 B1.8 0.3 B1.8 0.3 B1.8 0.3 B1.8/B1.8 0.3 B1.8/B1.8 0.3 B1.8/B1.8 Rating Factor 1.5 1.5 1.5 1.5 1.0 2.0/1.5 2.0/1.5 2.0/1.0

HIGH ACCURACY KXM-350


Accuracy/Burden 0.3 0,W,X,M,Y,Z,ZZ Catalog Number J750600T005X J750600T010X J750600T100X J750600T150X J750600T402X ---- 0.15 B1.8 Acc Range 0.025 to 20A 0.05 to 40A 0.5 to 400A 0.75 to 600A 20 to 4800A ---- Rating Factor 4.0 4.0 4.0 4.0 1.2 ----

* Available in other Primary Voltage Ratings. - Thermal Burden Rating (Typical): 2000VA. - Overvoltage Ratings: 1.1x cont., 1.9x 8 hours. - 1 Second Thermal/Mechanical Rating: KA (75x full winding Inom), KXM (150x Inom), 80kA max.

Dry type: 3022 NC 43 North Pinetops, NC 27864 Phone: +1 252 827-3212 [Link]/mediumvoltage Oil type: 101 Kuhlman Blvd Versailles, Kentucky 40383 Phone: +1 859 879-2999 [Link]/highvoltage

13

69000 Volt
March 2008

KA72(KXM350) 1 Metering Unit

14

NOTE: OUTLINES ARE FOR REFERENCE ONLY. CONTACT FACTORY FOR ACTUAL DESIGN DRAWINGS. Dry type: 3022 NC 43 North Pinetops, NC 27864 Phone: +1 252 827-3212 [Link]/mediumvoltage Oil type: 101 Kuhlman Blvd Versailles, Kentucky 40383 Phone: +1 859 879-2999 [Link]/highvoltage