Data Sheet Calibrasi GTG p2

This document contains test results for pressure switches, temperature switches, and level switches on a power plant. It lists the device, item monitored, set values, actual readings and test results including date and technician ID. Pressure switches monitored gas, hydraulic and lube oil pressures. Temperature switches monitored lube oil temperature, compartments and fire detectors. Level switches monitored lube oil tank levels. All readings were within tolerance except those marked with dashes.

Uploaded by

Lusi Arsenal
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
38 views2 pages

Data Sheet Calibrasi GTG p2

This document contains test results for pressure switches, temperature switches, and level switches on a power plant. It lists the device, item monitored, set values, actual readings and test results including date and technician ID. Pressure switches monitored gas, hydraulic and lube oil pressures. Temperature switches monitored lube oil temperature, compartments and fire detectors. Level switches monitored lube oil tank levels. All readings were within tolerance except those marked with dashes.

Uploaded by

Lusi Arsenal
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd

DATASHEETCALIBRASI

TEMPERATURESWITCHGTGP2
Pressureswitchtest
ACTUAL
SETVALUE
(kg/cm2)

63FG

Gasfuelpress.Low

11.60.14

12.0

Return
(CLOSE
)
11.0

63HG

HYD.Gaslinepress.Low

1.400.07

1.7

63HG

HYD.Gaslinepress.Low

1.400.07

63HQ

HYD.Supplypress.low

63HR

No.

ITEM

DEVICE

Action
(OPEN)

SH.NO..

DATE

T282

6/24

1.4

T282

6/24

1.7

1.4

T081

6/26

74.00.7

84.15

74.65

T281

6/24

HYD.Ratchetpress.low

14.00.35

14.0

T181

6/26

63QT

Lubeoilpress.Low

0.560.07

0.70

0.55

T081

6/24

63QA

Lubeoilpress.Low

0.800.07

1.1

0.8

T281

6/24

63QQ

0.700.07

1.1

0.65

T282

6/24

63WG

Load coupling oil FILT. Press.


low.
GEN.Coolingwaterpress.low

2.50.1

2.4

T081

6/24

10

63WGA

GEN.Coolingwaterpress.low

3.00.1

3.0

T283

6/24

11

63TF

Turbineinletairtrouble

T283

6/26

Temperatureswitchtest
No.

DEVICE

ITEM

ACTUAL

SETVALUE

Action
(OPEN)

()

Return
(CLOSE
)

SH.NO..

DATE

26QT

Lubeoilheadertemp.high

79.51

79

T081

6/25

26QA

Lubeoilheadertemp.high

74.01

74

T282

6/25

26QN

Lubeoiltanktemp.normal

10.01

T281

6/26

26CT

Controlcompartmentthermostat

30

T283

6/25

26T3

GEN.AUX.Comp.thermostat

35

T283

6/25

45FG

GEN.Firedetector

120

T351

6/25

45FA1

ACC.Firedetector

164

T352

6/25

45FA2

ACC.Firedetector

164

T352

6/25

45FT1

TBN.Firedetector

230

T352

6/25

10

45FT2

TBN.Firedetector

230

T352

6/25

11

45FT5

TBN.Firedetector

230

T352

6/26

12

45FT3

TBN.Firedetector

345

T352

6/25

13

45FT4

TBN.Firedetector

345

T352

6/25

Levelswitchtest
No.
1

DEVICE

71QH

ITEM
Lubeoiltanklevelhigh

SETVALUE
(mm)
432

ACTUAL
Action

Return

SH.NO..
T282

DATE
6/26

71QL

Lubeoiltanklevellow

254

T282

6/26