DATASHEETCALIBRASI
TEMPERATURESWITCHGTGP2
Pressureswitchtest
ACTUAL
SETVALUE
(kg/cm2)
63FG
Gasfuelpress.Low
11.60.14
12.0
Return
(CLOSE
)
11.0
63HG
HYD.Gaslinepress.Low
1.400.07
1.7
63HG
HYD.Gaslinepress.Low
1.400.07
63HQ
HYD.Supplypress.low
63HR
No.
ITEM
DEVICE
Action
(OPEN)
SH.NO..
DATE
T282
6/24
1.4
T282
6/24
1.7
1.4
T081
6/26
74.00.7
84.15
74.65
T281
6/24
HYD.Ratchetpress.low
14.00.35
14.0
T181
6/26
63QT
Lubeoilpress.Low
0.560.07
0.70
0.55
T081
6/24
63QA
Lubeoilpress.Low
0.800.07
1.1
0.8
T281
6/24
63QQ
0.700.07
1.1
0.65
T282
6/24
63WG
Load coupling oil FILT. Press.
low.
GEN.Coolingwaterpress.low
2.50.1
2.4
T081
6/24
10
63WGA
GEN.Coolingwaterpress.low
3.00.1
3.0
T283
6/24
11
63TF
Turbineinletairtrouble
T283
6/26
Temperatureswitchtest
No.
DEVICE
ITEM
ACTUAL
SETVALUE
Action
(OPEN)
()
Return
(CLOSE
)
SH.NO..
DATE
26QT
Lubeoilheadertemp.high
79.51
79
T081
6/25
26QA
Lubeoilheadertemp.high
74.01
74
T282
6/25
26QN
Lubeoiltanktemp.normal
10.01
T281
6/26
26CT
Controlcompartmentthermostat
30
T283
6/25
26T3
GEN.AUX.Comp.thermostat
35
T283
6/25
45FG
GEN.Firedetector
120
T351
6/25
45FA1
ACC.Firedetector
164
T352
6/25
45FA2
ACC.Firedetector
164
T352
6/25
45FT1
TBN.Firedetector
230
T352
6/25
10
45FT2
TBN.Firedetector
230
T352
6/25
11
45FT5
TBN.Firedetector
230
T352
6/26
12
45FT3
TBN.Firedetector
345
T352
6/25
13
45FT4
TBN.Firedetector
345
T352
6/25
Levelswitchtest
No.
1
DEVICE
71QH
ITEM
Lubeoiltanklevelhigh
SETVALUE
(mm)
432
ACTUAL
Action
Return
SH.NO..
T282
DATE
6/26
71QL
Lubeoiltanklevellow
254
T282
6/26