MiCOM P443 Programmable Logic
Opto Input Mappings
CB OPEN
DDB #034
CB CLOSE
DDB #035
CB Aux 3ph(52-B)
DDB #424
CB Aux 3ph(52-A)
DDB #420
LINE VT MCB TRIP
DDB #036
MCB/VTS
DDB #438
SOTF INIT LO&REM
DDB #037
Init Close CB
DDB #440
SPARE
DDB #038
External Trips:
Initiate Breaker Fail,
and Autoreclose (if
enabled).
CB Healthy
DDB #436
WEAK FEED
DDB #040
SPRAE
DDB #041
AR Enable
DDB #1384
SPARE
DDB #042
SPARE
DDB #043
Block CB AR
DDB #448
DIST RECV
DDB #044
Aided1 Scheme Rx
DDB #493
DEF RECV
DDB #045
Aided2 Scheme Rx
DDB #507
Trip Outputs are
generated by the
internal single/thre
phase trip
conversion logic
Block Zone 1 Gnd
DDB #384
Block Zone 1 Phs
DDB #385
BLOCK DIST/DEF
DDB #039
Block Zone 2 Gnd
DDB #386
Block Zone 2 Phs
DDB #387
Block Zone 3 Gnd
DDB #388
Block Zone 3 Phs
DDB #389
Block Zone P Gnd
DDB #390
Block Zone P Phs
DDB #391
Block Zone 4 Gnd
DDB #392
Block Zone 4 Phs
DDB #393
Inhibit IN>1
DDB #467
0
SPARE
DDB #004
Pick-Up
0
Page 1
ee
MiCOM P443 Programmable Logic
Output Contacts
Zone 1 Trip
DDB #608
Aid 1 Dist Trip
DDB #503
ZONE1 OPTD
DDB #017
Straight
0
Aid 2 Dist Trip
DDB #519
0
Zone 2 Trip
DDB #613
ZONE2 OPTD
DDB #018
Straight
0
0
Zone 3 Trip
DDB #618
ZONE3 OPTD
DDB #019
Straight
0
Zone 4 Trip
DDB #628
ZONE4&P OPTD
DDB #021
Straight
Zone P Trip
DDB #623
0
Aid 1 DEF Trip
DDB #505
DEF TRIP
DDB #023
Straight
0
WEAK FEED
DDB #040
Aided 1 Receive
DDB #494
&
WEAK FEED
DDB #040
Aided 2 Receive
DDB #508
DIST WEI ECHO
DDB #026
Straight
&
DEF WEI ECHO
DDB #028
Straight
0
.
Zone P A Start
DDB #753
Zone P B Start
DDB #754
DIST REV START
DDB #030
Straight
Zone P C Start
DDB #755
Zone P N Start
DDB #756
0
DEF Reverse
DDB #997
DEF REV START
DDB #031
Straight
0
Trip Output A
DDB #523
Trip Output B
DDB #524
0
AR INITIATION
DDB #003
Straight
Trip Output C
DDB #525
AR 3pole in prog
DDB #844
AR 1pole in prog
DDB #845
CB Succ 3P AR
DDB #852
CB Succ 1P AR
DDB #1571
Latching
FnKey LED6 Red
DDB #1050
FnKey LED6 Grn
DDB #1051
1
0
A/R Lockout
DDB #306
AR Blocked
DDB #859
AR In Service
DDB #1385
AR BLOCK
DDB #006
Straight
0
Page 2
MiCOM P443 Programmable Logic
Output Contacts
SG-opto Invalid
DDB #288
Prot'n Disabled
DDB #289
Static Test Mode
DDB #290
Test Loopback
DDB #291
Test IM64
DDB #292
VT Fail Alarm
DDB #293
CT Fail Alarm
DDB #294
Power Swing
DDB #297
CB Fail Alarm
DDB #298
CB Monitor Alarm
DDB #299
CB Mon LO Alarm
DDB #300
CB Status Alarm
DDB #301
CB Trip Fail
DDB #302
CB Close Fail
DDB #303
Man CB Unhealthy
DDB #304
No C/S Man Close
DDB #305
A/R Lockout
DDB #306
A/R CB Unhealthy
DDB #307
A/R No Checksync
DDB #308
General Alarm
Signalling Fail
DDB #311
IM64 SchemeFail
DDB #314
IEEE C37.94 Fail
DDB #315
Aid 1 Chan Fail
DDB #317
Aid 2 Chan Fail
DDB #318
F out of Range
DDB #319
InValid Mesg Fmt
DDB #333
Main Prot. Fail
DDB #334
Comms Changed
DDB #337
Battery Fail
DDB #352
Field Volts Fail
DDB #353
Max Prop. Alarm
DDB #338
Backup Usr Curve
DDB #371
Page 3
MiCOM P443 Programmable Logic
Output Contacts
0
Aided 1 Send
DDB #498
DIST SEND
DDB #000
Straight
0
0
Aided 2 Send
DDB #514
DEF SEND
DDB #001
Straight
0
Zone 1 Trip
DDB #608
Aid 1 Dist Trip
DDB #503
INST TRIP
DDB #002
Straight
0
Aid 1 DEF Trip
DDB #505
SOTF Trip Zone 1
DDB #709
LED6 Red
DDB #1034
Latching
LED6 Grn
DDB #1035
SOTF Trip Zone 2
DDB #710
SOTF Trip Zone 3
DDB #711
SOTF TRIP
DDB #024
Straight
0
SOTF Trip Zone 4
DDB #712
SOTF Trip Zone P
DDB #713
Zone 2 Trip
DDB #613
Zone 3 Trip
DDB #618
Zone 4 Trip
DDB #628
DELAYED TRIP
DDB #007
Straight
Zone P Trip
DDB #623
I>1 Trip
DDB #655
I>2 Trip
DDB #659
IN>1 Trip
DDB #671
1
0
IN>2 Trip
DDB #672
AIDED TRIP
DDB #022
Straight
0
Aid 1 Dist Trip
DDB #503
0
Aid 2 DEF Trip
DDB #521
CARR AIDED TRIP
DDB #015
Straight
0
0
Any Trip
DDB #522
GENERAL TRIP
DDB #020
Straight
0
0
Power Swing
DDB #297
PSB OPTD
DDB #029
Pick-Up
0
0
Aid1 WI Trip 3Ph
DDB #642
DIST WEI TRIP
DDB #025
Straight
0
0
Aid2 WI Trip 3Ph
DDB #652
DEF WEI TRIP
DDB #027
Straight
0
Page 4
MiCOM P443 Programmable Logic
LEDs
Any Trip
DDB #522
Latching
Zone 1 Trip
DDB #608
Latching
Zone 2 Trip
DDB #613
Zone 3 Trip
DDB #618
Zone P Trip
DDB #623
Zone 4 Trip
DDB #628
Latching
Latching
Aided 1 Receive
DDB #494
Latching
Aided 2 Receive
DDB #508
Latching
Aided 1 Send
DDB #498
Latching
Aided 2 Send
DDB #514
Latching
AR Blocked
DDB #859
Latching
P Swing Detector
DDB #1014
Power Swing
DDB #297
I>1 Trip
DDB #655
IN>1 Trip
DDB #671
Latching
Latching
I>2 Trip
DDB #659
LED2 Red
DDB #1026
LED2 Grn
DDB #1027
LED3 Red
DDB #1028
LED3 Grn
DDB #1029
LED4 Red
DDB #1030
LED4 Grn
DDB #1031
LED5 Red
DDB #1032
LED5 Grn
DDB #1033
FnKey LED1 Red
DDB #1040
FnKey LED1 Grn
DDB #1041
FnKey LED2 Red
DDB #1042
FnKey LED2 Grn
DDB #1043
FnKey LED3 Red
DDB #1044
FnKey LED3 Grn
DDB #1045
FnKey LED4 Red
DDB #1046
FnKey LED4 Grn
DDB #1047
FnKey LED5 Red
DDB #1048
FnKey LED5 Grn
DDB #1049
FnKey LED8 Red
DDB #1054
FnKey LED8 Grn
DDB #1055
LED7 Red
DDB #1036
LED7 Grn
DDB #1037
IN>2 Trip
DDB #672
VT Fail Alarm
DDB #293
Latching
LINE VT MCB TRIP
DDB #036
Aid1 WI Trip 3Ph
DDB #642
Non Latching
FnKey LED7 Red
DDB #1052
FnKey LED7 Grn
DDB #1053
FnKey LED9 Red
DDB #1056
FnKey LED9 Grn
DDB #1057
Aid2 WI Trip 3Ph
DDB #652
Any Trip
DDB #522
Fault REC TRIG
DDB #702
Page 5
Non Latching
FnKey LED10 Red
DDB #1058
FnKey LED10 Grn
DDB #1059
MiCOM P443 Programmable Logic
Zone 1 A Start
DDB #741
Start Phase Mappings.
Used in Fault Record &
on LCD Display
Zone 2 A Start
DDB #745
Zone 3 A Start
DDB #749
Zone P A Start
DDB #753
Zone 4 A Start
DDB #757
Started Phase A
DDB #956
I>1 Start A
DDB #762
DIST PH-A START
DDB #008
Pick-Up
0
I>2 Start A
DDB #766
Caution: Do Not
remove "Started
Phase" DDB
signals
I>3 Start A
DDB #770
I>4 Start A
DDB #774
Zone 1 B Start
DDB #742
Any Phase Start >> page7
Zone 2 B Start
DDB #746
Zone 3 B Start
DDB #750
Zone P B Start
DDB #754
Zone 4 B Start
DDB #758
Started Phase B
DDB #957
I>1 Start B
DDB #763
DIST PH-B START
DDB #009
Pick-Up
0
I>2 Start B
DDB #767
I>3 Start B
DDB #771
I>4 Start B
DDB #775
Zone 1 C Start
DDB #743
Zone 2 C Start
DDB #747
Zone 3 C Start
DDB #751
Zone P C Start
DDB #755
Zone 4 C Start
DDB #759
I>1 Start C
DDB #764
Started Phase C
DDB #958
0
DIST PH-C START
DDB #010
Pick-Up
I>2 Start C
DDB #768
I>3 Start C
DDB #772
I>4 Start C
DDB #776
Page 6
MiCOM P443 Programmable Logic
Zone 1 N Start
DDB #744
Any Ground Start >> page8
Zone 2 N Start
DDB #748
Zone 3 N Start
DDB #752
>>
>>
Zone P N Start
DDB #756
Zone 4 N Start
DDB #760
IN>1 Start
DDB #777
IN>2 Start
DDB #778
IN>3 Start
DDB #779
Started Phase N
DDB #959
IN>4 Start
DDB #780
ISEF>1 Start
DDB #781
ISEF>2 Start
DDB #782
ISEF>3 Start
DDB #783
ISEF>4 Start
DDB #784
Phase Select N
DDB #1013
&
Any Trip
DDB #522
>> page6 Any Phase Start
Any Phase Start >> page8
Phase Select N
DDB #1013
&
10
Any Trip
DDB #522
Pulse
0
This logic ensures correct N
indications for faults involving
ground. The pulse prevents pole
scatter affecting the N indication.
AR In Service
DDB #1385
N Phase Start >> page8 then page 9 then page 10
&
Reset Relays/LED
DDB #444
This reset controls:
Reset latched relays,
Reset latched LEDs,
Reset A/R Lockout.
This logic clears all latched indications at the
start of Any Trip
>
Page 7
MiCOM P443 Programmable Logic
> page7 Any Ground Start
> page7 Any Phase Start
>> page 7 N Phase Start
LED1 Red
DDB #1024
Latching
LED1 Grn
DDB #1025
Any Trip
DDB #522
I2>1 Start
DDB #567
I2>2 Start
DDB #568
Any Start
DDB #736
I2>3 Start
DDB #569
Used in Fault Record
initiation
I2>4 Start
DDB #570
V<1 Start
DDB #788
Caution: Do Not
remove "Any Start"
DDB signal
V<2 Start
DDB #792
V>1 Start
DDB #796
V>2 Start
DDB #800
VN>1 Start
DDB #804
VN>2 Start
DDB #805
F<1 Start
DDB #1155
F<2 Start
DDB #1156
F<3 Start
DDB #1157
F<4 Start
DDB #1158
F>1 Start
DDB #1159
F>2 Start
DDB #1160
V1>1 Cmp Start
DDB #923
V1>2 Cmp Start
DDB #924
df/dt>1 Start
DDB #597
df/dt>2 Start
DDB #598
df/dt>3 Start
DDB #599
df/dt>4 Start
DDB #600
N Phase Start >>page 9 then page 10
Page 8
>> pag
MiCOM P443 Programmable Logic
Zone 1 A Trip
DDB #609
Zone 2 A Trip
DDB #614
Zone 3 A Trip
DDB #619
Zone P A Trip
DDB #624
Zone 4 A Trip
DDB #629
Aided 1 Trip A
DDB #633
Aid 1 WI Trip A
DDB #637
Aided 2 Trip A
DDB #643
Faulted Phase A
DDB #952
Aid 2 WI Trip A
DDB #647
I>1 Trip A
DDB #656
I>2 Trip A
DDB #660
I>3 Trip A
DDB #664
I>4 Trip A
DDB #668
AR Trip Test A
DDB #577
Faulted Phase Flag, Used in
Fault record and on LCD
display.
AR Trip Test 3Ph
DDB #576
ge 7 then page 8 N Phase Start
Caution: Do Not remove
"Faulted Phase" DDB signals
Zone 1 B Trip
DDB #610
Zone 2 B Trip
DDB #615
Zone 3 B Trip
DDB #620
Zone P B Trip
DDB #625
Zone 4 B Trip
DDB #630
Aided 1 Trip B
DDB #634
Aid 1 WI Trip B
DDB #638
Aided 2 Trip B
DDB #644
Faulted Phase B
DDB #953
Aid 2 WI Trip B
DDB #648
I>1 Trip B
DDB #657
I>2 Trip B
DDB #661
I>3 Trip B
DDB #665
I>4 Trip B
DDB #669
AR Trip Test B
DDB #578
AR Trip Test 3Ph
DDB #576
N Phase Start >> page 10
Page 9
>> page 7
MiCOM P443 Programmable Logic
Zone 1 C Trip
DDB #611
Zone 2 C Trip
DDB #616
Zone 3 C Trip
DDB #621
Zone P C Trip
DDB #626
Zone 4 C Trip
DDB #631
Aided 1 Trip C
DDB #635
Aid 1 WI Trip C
DDB #639
Aided 2 Trip C
DDB #645
Faulted Phase
DDB #954
Aid 2 WI Trip C
DDB #649
I>1 Trip C
DDB #658
I>2 Trip C
DDB #662
I>3 Trip C
DDB #666
I>4 Trip C
DDB #670
AR Trip Test C
DDB #579
Faulted Phase Flag, Used in
Fault record and on LCD
display.
AR Trip Test 3Ph
DDB #576
Caution: Do Not remove
"Faulted Phase" DDB signals
Zone 1 N Trip
DDB #612
Zone 2 N Trip
DDB #617
Zone 3 N Trip
DDB #622
Zone P N Trip
DDB #627
Zone 4 N Trip
DDB #632
Aided 1 Trip N
DDB #636
Aided 2 Trip N
DDB #646
IN>1 Trip
DDB #671
IN>2 Trip
DDB #672
IN>3 Trip
DDB #673
IN>4 Trip
DDB #674
VN>1 Trip
DDB #700
VN>2 Trip
DDB #701
ISEF>1 Trip
DDB #675
ISEF>2 Trip
DDB #676
ISEF>3 Trip
DDB #677
ISEF>4 Trip
DDB #678
7 then page 8 the page 9 N Phase Start
Page 10
Faulted P
DDB
Phase N
#955
MiCOM P443 Programmable Logic
Inputs to Trip Conversion
Logic:These Raw trip signals
are then processed in relay fixed
logic, to obtain the correct
single, or three pole trip
response.
Zone 1 A Trip
DDB #609
Aided 1 Trip A
DDB #633
Aid 1 WI Trip A
DDB #637
Trip Inputs A
DDB #530
Aided 2 Trip A
DDB #643
Aid 2 WI Trip A
DDB #647
Caution: Do Not
remove "Trip Inputs"
DDB signals
AR Trip Test A
DDB #577
Zone 1 B Trip
DDB #610
Aided 1 Trip B
DDB #634
Aid 1 WI Trip B
DDB #638
Trip Inputs B
DDB #531
Trip Inputs C
DDB #532
Aided 2 Trip B
DDB #644
Aid 2 WI Trip B
DDB #648
AR Trip Test B
DDB #578
Zone 1 C Trip
DDB #611
Aided 1 Trip C
DDB #635
Aid 1 WI Trip C
DDB #639
Aided 2 Trip C
DDB #645
Aid 2 WI Trip C
DDB #649
AR Trip Test C
DDB #579
Page 11
MiCOM P443 Programmable Logic
pa
V<1 Trip
DDB #683
V<2 Trip
DDB #687
V>1 Trip
DDB #691
V>2 Trip
DDB #695
VN>1 Trip
DDB #700
Caution: Do Not
remove "Trip Inputs"
DDB signals
VN>2 Trip
DDB #701
F<1 Trip
DDB #1161
F<2 Trip
DDB #1162
F<3 Trip
DDB #1163
CBF Non I Trip
DDB #874
F<4 Trip
DDB #1164
Caution: Non
Current Protections
required to Initiate
CB Fail
F>1 Trip
DDB #1165
F>2 Trip
DDB #1166
df/dt>1 Trip
DDB #601
df/dt>2 Trip
DDB #602
df/dt>3 Trip
DDB #603
df/dt>4 Trip
DDB #604
V1>1 Cmp Trip
DDB #925
V1>2 Cmp Trip
DDB #926
AR Trip Test 3Ph
DDB #576
Broken Line Trip
DDB #679
Thermal Trip
DDB #680
I2>1 Trip
DDB #571
I2>2 Trip
DDB #572
I2>3 Trip
DDB #573
I2>4 Trip
DDB #574
ISEF>1 Trip
DDB #675
Trip Inputs 3Ph >> page 13
Caution: Do Not
remove "Trip Inputs"
DDB signals
ISEF>2 Trip
DDB #676
ISEF>3 Trip
DDB #677
ISEF>4 Trip
DDB #678
IREF> Trip
DDB #682
Page 12
MiCOM P443 Programmable Logic
age 12 >> Trip Inputs 3Ph
Stub Bus Trip
DDB #591
Pred. OST
DDB #551
OST
DDB #553
Zone 2 Trip
DDB #613
Zone 3 Trip
DDB #618
Zone P Trip
DDB #623
Zone 4 Trip
DDB #628
I>1 Trip
DDB #655
I>2 Trip
DDB #659
I>3 Trip
DDB #663
I>4 Trip
DDB #667
IN>1 Trip
DDB #671
IN>2 Trip
DDB #672
IN>3 Trip
DDB #673
IN>4 Trip
DDB #674
Aid1 Delta Tr3Ph
DDB #640
Aid1 DEF Trip3Ph
DDB #641
Aid1 WI Trip 3Ph
DDB #642
Aid2 Delta Tr3Ph
DDB #650
Aid2 DEF Trip3Ph
DDB #651
Aid2 WI Trip 3Ph
DDB #652
Trip Inputs 3Ph
DDB #529
Caution: Do Not
remove "Trip Inputs"
DDB signals
Loss ofLoad Trip
DDB #654
Pole Discrepancy
DDB #699
TOR Trip Zone 1
DDB #704
TOR Trip Zone 2
DDB #705
TOR Trip Zone 3
DDB #706
TOR Trip Zone P
DDB #708
TOR Trip Zone 4
DDB #707
TOR Trip CNV
DDB #557
SOTF Trip CNV
DDB #558
SOTF Trip Zone 1
DDB #709
SOTF Trip Zone 2
DDB #710
SOTF Trip Zone 3
DDB #711
SOTF Trip Zone P
DDB #713
SOTF Trip Zone 4
DDB #712
Page 13
Aid 1 Dist Trip
DDB #503
Aid 2 Dist Trip
DDB #519
Aid 1 DEF Trip
DDB #505
Aid 2 DEF Trip
DDB #521
CB Open A ph
DDB #904
CB Closed A ph
DDB #908
CB Open B ph
DDB #905
CB Closed B ph
DDB #909
CB Open C ph
DDB #906
CB Closed C ph
DDB #910
A/R Lockout
DDB #306
AR In Service
DDB #1385
CB ARIP
DDB #1544
CB Succ 3P AR
DDB #852
CB Succ 1P AR
DDB #1571
DIST PH-A START
DDB #008
DIST PH-B START
DDB #009
DIST PH-B START
DDB #009
DIST PH-C START
DDB #010
DIST PH-C START
DDB #010
DIST PH-A START
DDB #008
DIST 3PH START
DDB #014
Pick-Up
&
0
DIST PH AB START
DDB #011
Pick-Up
&
0
0
&
DIST PH BC START
DDB #012
Pick-Up
&
0
DIST PH CA START
DDB #013
Pick-Up
0