EN 50346
EN 50173-1
EN 50173-2
EN 50173-3
EN 50173-4
EN 50173-5
EN 50174-1
EN 50174-2
EN 50174-3
CONTENTS
Background EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status
National Regulations DESIGN INSPECTION TESTING PLANNING INSTALLATION
The Key Changes Further Integration EN 50310 Risk Management Approved Installer Schemes
National Standards
EN 50174-1 and EN 50174-2: 2008
Integrated standards for telecommunications cabling installation
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
EN 50310
Mike Gilmore
CONTENTS Background EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status The Key Changes Further Integration EN 50310 Risk Management Approved Installer Schemes Mike Gilmore Managing Director e-Ready Building Standards Activities Member JTC1 SC25 WG3: Generic Cabling Convenor JTC1 SC25 WG3 CITG: Cabling Implementation Task Group JTC1 SC25 WG3 IPTG: Industrial Premises (Cabling) Task Group Convenor TC215 WG1: IT Cabling Secretary TC215 WG2 Leader - Special Task Force 362 Energy Efficiency and Broadband Deployment Chairman TCT7: Telecommunications - Installation Requirements Chairman TCT7/-/1: Cabling infrastructure design, planning and commissioning TCT7/-/3: Cabling: Infrastructure standards - UK implementation panel FIA www.fia-online.co.uk Technical and Standards Director Fibreoptic Industry Association Director Telecommunications Infrastructure Advisory Board e-mail: [email protected]
www.fia-online.co.uk/TIAB Mobile: +44 (0) 7860 110563
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
THE SECOND COMING EN 50174-1 and EN 50174-2:2008 Background CONTENTS Background EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status The Key Changes Further Integration EN 50310 Risk Management Approved Installer Schemes
Problems with EN 50174-1/-2 Ed.1
PRODUCED BY CENELEC TC215 EN 50174-1:2000 EN 50174-2:2000 EN 50174-3:2003 Information technology - Cabling installation Part 1: Specification and quality assurance Information technology - Cabling installation Part 2: Installation planning and practices inside buildings Information technology - Cabling installation Part 3: Installation planning and practices outside buildings
Some SHOULDS should be SHALLS and some SHALLS should be SHOULDS
Segregation of circuits
Mismatch of terms Confuses optical fibre and copper requirements Too much tutorial Focus on specifics rather than requirements
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
THE SECOND COMING EN 50174-1 and EN 50174-2:2008 Background CONTENTS Background EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status The Key Changes Further Integration EN 50310 Risk Management Approved Installer Schemes
Linkage to EN 50173 series
EN 50173-2:2007, EN 50173-3:2007, EN 50173-4:2007, EN 50173-5:2007
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
THE SECOND COMING EN 50174-1 and EN 50174-2:2008 EN 50174-1 and EN 50174-2 CONTENTS Background EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status The Key Changes Further Integration EN 50310 Risk Management Approved Installer Schemes
EN 50174-X Ed.2
PRODUCED BY CENELEC TC215 EN 50174-1:2008 EN 50174-2:2008 Information technology - Cabling installation Part 1: Installation Specification and quality assurance Information technology - Cabling installation Part 2: Installation planning and practices inside buildings
CLC approval
November 2008
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
THE SECOND COMING EN 50174-1 and EN 50174-2:2008 EN 50174-1 and EN 50174-2 CONTENTS Background EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status The Key Changes Further Integration EN 50310 Risk Management Approved Installer Schemes
EN 50174-1:2008
PRODUCED BY CENELEC TC215 EN 50174-1:2008 Information technology - Cabling installation Part 1: Installation Specification and quality assurance EN 50174-1:2008
EN 50174-1:2000 Introduction Scope Normative references Definitions and abbreviations Specification considerations Quality assurance Documentation Cabling administration Repair and maintenance Compatibility between transmission systems (balanced and unbalanced) sharing the same cable sheath within information technology cabling Terminating cables on terminating blocks in floor distributors
1 2 3 4 5 6 7 8 A A B B C D
Introduction Scope Conformance Normative references Terms, definitions and abbreviations Requirements for specifying installations of information technology cabling Requirements for installers of information technology cabling Infrastructure complexity
Minimum requirements for technical specifications and quality plans Polarity maintenance: connecting hardware for multiple optical fibres Terminating cables on terminating blocks in distributors Compatibility between transmission systems (balanced and unbalanced) sharing the same cable sheath within information technology cabling
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
THE SECOND COMING EN 50174-1 and EN 50174-2:2008 EN 50174-1 and EN 50174-2 CONTENTS Background EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status The Key Changes Further Integration EN 50310 Risk Management Approved Installer Schemes
EN 50174-2:2008
PRODUCED BY CENELEC TC215 EN 50174-2:2008 Information technology - Cabling installation Part 2: Installation planning and practices inside buildings EN 50174-2:2008
EN 50174-2:2000 Introduction Scope Normative references Definitions and abbreviations General installation practices for metallic and optical fibre cabling Additional installation practices for metallic cabling Additional installation practices for optical fibre cabling
1 2 3 4 5 6 7 8 9 10 11
Introduction Scope Conformance Normative references Terms, definitions and abbreviations Requirements for planning installations of information technology cabling Requirements for the installation of information technology cabling Segregation of metallic information technology cabling and mains power cabling Electricity distribution systems and lightning protection Office (commercial) premises Industrial premises Homes Data centres EMC and protection Application of responsibilities
Coupling mechanisms and counter-measures
A B
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
THE SECOND COMING EN 50174-1 and EN 50174-2:2008 EN 50174-1 and EN 50174-2 CONTENTS Background EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status The Key Changes Further Integration EN 50310 Risk Management Approved Installer Schemes
Infrastructure Complexity
PRODUCED BY CENELEC TC215 EN 50174-1:2008 Information technology - Cabling installation Part 1: Installation Specification and quality assurance
Installation Complexity Office Industrial Homes Multi-tenant residential premises Data centres
No. of fixed cable elements (E) 2 to 200 201 to 1000 >1000 2 2 3 3 3 4 1 1 1 2 2 3 2 2 3
LEVEL
E= The number of fixed cables multiplied by the number of cable elements per cable. It is the total for all cables (coaxial, balanced pair and optical fibre)
Operational Complexity Office Industrial Homes Multi-tenant residential premises Data centres 2 to 100 1 1 1 1 2
No. of administered ports (P) 101 to 500 501 to 5000 >5000 1 2 3 1 2 3 1 1 1 1 2 3 3 4 4
LEVEL
P= The number of user-accessible equipment interfaces including those on the connected equipment
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
THE SECOND COMING EN 50174-1 and EN 50174-2:2008 EN 50174-1 and EN 50174-2 CONTENTS Background EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status The Key Changes
Segregation Classification
SEGREGATION BETWEEN INFORMATION TECHNOLOGY AND MAINS POWER CABLING
S/FTP Further Integration EN 50310 Risk Management Approved Installer Schemes F/UTP 5 or 6 Balanced
CABLE CATEGORY Segregation Classification d c b
Unscreened Screened 7 or BCT-B 5 or 6
Coaxial
BCT-C
Other or None U/UTP
Segregation Classification a shall be applied if: the applications to be supported are unrestricted; the type of cabling to be installed is unrestricted. Segregation Classification b and above may be applied if the applications are supported by the EN 50173 series of standards
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
THE SECOND COMING EN 50174-1 and EN 50174-2:2008 EN 50174-1 and EN 50174-2 CONTENTS Background EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status The Key Changes Further Integration EN 50310 Risk Management Approved Installer Schemes
Separation Distance Overview
SEGREGATION BETWEEN INFORMATION TECHNOLOGY AND MAINS POWER CABLING CABLE MANAGEMENT SYSTEM
None
Segregation Classification d c b a 10 50 100 300
Open metallic containment
Perforated metallic containment
Solid metallic containment
S = Basic separation distance (mm, min) 8 38 75 225 5 25 50 150 0
Electrical circuit type 20 amp 230 V AC 1- phase 3-phase cables = 3 off 1-phase cables > 20 A = multiples of 20 A
Quantity of circuits
Separation multiplier 0,2 0,4 0,6 0,8 1 2 3 4 5 6
60 A 120 A 180 A 240 A 300 A 600 A 900 A 1200 A 1500 A
1500 A
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
THE SECOND COMING EN 50174-1 and EN 50174-2:2008 EN 50174-1 and EN 50174-2 CONTENTS Background EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status The Key Changes Further Integration EN 50310 Risk Management Approved Installer Schemes and
Zero Separation Get-Out
SEGREGATION BETWEEN INFORMATION TECHNOLOGY AND MAINS POWER CABLING No segregation is required between information technology cabling and mains power cabling (other than that required by national or local regulation) provided that all the following conditions are met: the environmental classification for the information technology cabling complies with E1 of EN 50173-1; the power conductors form single phase circuits; provide a total current 32 amps (max); comprising a circuit are maintained in close proximity (e.g. within an overall sheath or twisted, taped or bundled together);
the information technology cables meet the requirements of Segregation Classifications b, c or d; or where the cabling is application(s)-specific and the application(s) supports a zero segregation relaxation.
This allowance should be not applied in spaces allocated to distributors in accordance with EN 50173 standards or equivalent concentrations of transmission equipment
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
THE SECOND COMING EN 50174-1 and EN 50174-2:2008 EN 50174-1 and EN 50174-2 CONTENTS Background EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status The Key Changes Further Integration EN 50310 Risk Management Approved Installer Schemes
Mains Power Cabling Standards
SEGREGATION BETWEEN INFORMATION TECHNOLOGY AND MAINS POWER CABLING PROPOSALS WITHIN EUROPEAN HD 60364-4-444
S = Basic separation distance (mm, min)
CABLE MANAGEMENT SYSTEM
None
200
Open metallic containment
200
Perforated metallic containment
150
Solid metallic containment
0
ASSUMPTIONS the total current in the LV cables does not exceed 600A balanced information telecommunication cables have electromagnetic immunity performance in accordance with EN 50288 series standards for Category 5 and above coaxial information technology cables have electromagnetic immunity performance in accordance with EN 50177-4-1 standard for Category BCT-C the applications supported by the cabling are designed to operate using the information technology cabling installed or to be installed
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
THE SECOND COMING EN 50174-1 and EN 50174-2:2008 Further Integration CONTENTS Background EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status The Key Changes Further Integration EN 50310 Risk Management Approved Installer Schemes
Conformance to EN 50174-1/-2
PRODUCED BY CENELEC TC215 EN 50174-1:2008: For a cabling installation to conform to this European Standard:
the specification of the installation shall meet the requirements of clause 4; the installer shall meet the requirements of clause 5; the equipotential bonding (and earthing) system within the premises shall be in accordance with EN 50310; where a lightning protection system is required, it shall conform to the integrated lightning protection system according to EN 62305-4; other lightning protection systems, including the isolated lightning protection system according to EN 62305-3 are allowed provided that specific restrictions are applied both to the implementation of the information technology cabling and the requirements of EN 50310 as agreed between the planners of the lightning protection system and the information technology cabling; local regulations, including safety, shall be met.
EN 50174-2:2008: For a cabling installation to conform to this European Standard:
the planning of the installation shall meet the requirements of clause 4; the installation practices shall meet the requirements of clause 5; the additional requirements of the applicable premises-specific clause shall be met; the equipotential bonding (and earthing) system within the premises shall be in accordance with EN 50310; where a lightning protection system is required, it shall conform to the integrated lightning protection system according to EN 62305-4; other lightning protection systems. cabling; local regulations, including safety, shall be met.
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
THE SECOND COMING EN 50174-1 and EN 50174-2:2008 Further Integration CONTENTS Background EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status The Key Changes Further Integration EN 50310 Risk Management Approved Installer Schemes HD 384/60364 PROTECTION/SAFETY EN 50310:2009
EN 50310:2009
PRODUCED BY CENELEC TC215 Application of equipotential bonding and earthing in buildings with information technology equipment
Equipment-specific FUNCTIONAL PURPOSE OF EARTHING IMMUNITY
For a given protective earthing system EN 50310 provides requirements for additional bonds for equipotentiality
Defines performance/characteristics of bonds
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
THE SECOND COMING EN 50174-1 and EN 50174-2:2008 Further Integration CONTENTS Background EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status The Key Changes Further Integration EN 50310 Risk Management Approved Installer Schemes
Star and Ring Earth Improvements
PRODUCED BY CENELEC TC215 EN 50310:2009 Application of equipotential bonding and earthing in buildings with information technology equipment
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
THE SECOND COMING EN 50174-1 and EN 50174-2:2008 Further Integration CONTENTS Background EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status The Key Changes Further Integration EN 50310 Risk Management Approved Installer Schemes
Mesh Earth Improvements
PRODUCED BY CENELEC TC215 EN 50310:2009 Application of equipotential bonding and earthing in buildings with information technology equipment
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
THE SECOND COMING EN 50174-1 and EN 50174-2:2008 Risk Management CONTENTS Background EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status The Key Changes Further Integration EN 50310 Risk Management Approved Installer Schemes
FIA Approved Installers Scheme
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
THE SECOND COMING EN 50174-1 and EN 50174-2:2008 Related activities and actions CONTENTS Background EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status The Key Changes Further Integration EN 50310 Risk Management Approved Installer Schemes
FIA AID
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
THE SECOND COMING EN 50174-1 and EN 50174-2:2008 Related activities and actions CONTENTS Background EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status The Key Changes Further Integration EN 50310 Risk Management Approved Installer Schemes
FIA AID Assistant
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
CONTENTS Background
EN 50346 EN 50173-1 EN 50173-2 EN 50173-3 EN 50173-4 EN 50173-5 EN 50174-1 EN 50174-2 EN 50174-3
EN 50174-1/-2:2000 The Need for Change EN 50174-1 and EN 50174-2:2008 Status The Key Changes Further Integration EN 50310 Risk Management
INSPECTION TESTING DESIGN
PLANNING INSTALLATION
The End
EN 50174-1 and EN 50174-2: 2008
Integrated standards for telecommunications cabling installation
2008 The Cabling Partnership
www.it-cabling.com www.e-readybuilding.com P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721 Fax: +44 (0) 113 293 2632
National Standards
Approved Installer Schemes
National Regulations
EN 50310