Distribution Innovation
Distribution Innovation
Contents
The family ............................................................................................................ 23 Miniature circuit-breakers Residual current operated circuit-breakers - General, technical data ..................................................................................... 69 - Order data .................................................................................................... 1019 Manual motor starters MS325 Surge arresters SA4 SC/SA4 Disconnectors IS463 Auxiliary switches and signal contacts Residual current operated circuit-breaker FIP2/FI4 General, technical data ....................................................................................... 20 Order data .......................................................................................................... 21 Delayed residual current operated circuit-breaker and selective type FIKP2, FIK4 and FIS4 General, technical data ................................................................................. 22, 23 Order data .......................................................................................................... 23 Residual current operated circuit-breaker with integral overcurrent protection FI-LP2 and delayed type FIK-LP2 General, technical data ................................................................................. 24, 25 Order data .......................................................................................................... 26 Residual current monitor FISG General, technical data ....................................................................................... 27 Order data .......................................................................................................... 27 Residual current operated circuit-breakers for 162/3 Hz and 400 Hz General, technical data ....................................................................................... 28 Order data .......................................................................................................... 29
- General, technical data ................................................................................. 3032 - Order data .......................................................................................................... 33 - General, technical data ................................................................................. 34, 35 - Order data .......................................................................................................... 36 - General, technical data ....................................................................................... 37 - Order data .......................................................................................................... 37 General, function ................................................................................................ 38 Assembly directives ............................................................................................ 39 Technical data ..................................................................................................... 40 Order data .......................................................................................................... 41
- General ............................................................................................................... 42 - Order data .......................................................................................................... 43 - Sockets .............................................................................................................. 44 - Accessories, socket ................................................................................... 45, 46 - Starter pack ....................................................................................................... 46 - Feeder element for external units ............................................................. 47, 48 - Incoming terminal block and component ................................................ 4951 - Accessories, additional socket ................................................................. 52, 53 - UL Recognizer .................................................................................................. 54 - Power supplies ........................................................................................... 5556 Dimensions ..................................................................................................... 5760
Products in this catalogue comply with the relevant standards as stated, and should always be installed in accordance with the requirements of relevant regulations, standards and legislation 1
20165/C
Overview
24 10 11 1
23
22
21 20
18 17 16
19
4 15 5 6 14 13 11 12 10 7
1 2 3 4 5 6 7 8 9 10 11 12
Incoming supply terminal Incoming terminal block Cover Supply cables Residual current operated circuit-breaker with integral overcurrent protection Residual current operated circuit-breaker Manual motor starter Miniature circuit-breaker Plug contacts Extension adaptor Busbar cover Latch
13 14 15 16 17 18 19 20 21 22 23 24
Busbar L3 Busbar L2 Busbar L1 Busbar N Socket base Auxiliary busbars LA Auxiliary busbars LB Busbar N, external Busbar PE, external Additional socket base PE conductor terminal Load conductor
2
20165/C
[Link]
Time-saving
The consistent use of the smissline provides decisive advantages for planning engineers, switchgear designers and operators at all project stages: q Considerably simplified planning q Rapid construction and time-saving assembly by the innovative assembly. q Simple and rapid installation of units with the required numbers of poles also with auxiliary switches. q Component replacement in seconds. q Straightforward extension possibilities.
[Link]
Cost-reducing
The socket system also enables significant savings to be achieved in labour costs: q All units can be plugged in quickly by hand. The KEMA tested plug-in technique automatically ensures safe and reliable connection to the busbar. q This new technique enables assembly and wiring time to be reduced by up to 50%: no input wiring is necessary. q The units can be transferred simply and easily to any desired position over the entire length of the busbar system. No special new connections are required.
1 0
[Link]
12:24 0
[Link]
20165/C
40411
in A 0.5 1 1.6 2 3 4 6 8 10 13 16 20 25 32 40 50 63
Pv W
0.055 0.038 0.013 0.013 0.007 0.0063 0.005 0.0036 0.003 0.0012 0.0009
2.00 2.43 1.30 2.20 1.79 2.52 3.13 3.69 4.80 3.00 3.57
Accessories
Resistance per line terminal Ri 0.0065 0.00005 0.00005 0.00004 0.00017 0.00012 Power loss per line terminal PV W 0.24 0.5 0.5 0.4 0.17 0.12
Auxiliary switch and signal contact SDH, SDS, SBH, SBS Feeder block External terminal 100 A N External terminal 100 A PE External terminal 32 A N External terminal 32 A PE
4
20165/C
General
The smissline miniature circuit-breaker LP is an energy limiting circuit-breaker with a high performance, equally suitable for industrial or domestic applications. In the event of a short-circuit it ensures excellent selectivity with upstream circuit-breakers, while the stresses imposed on the following switchgear is limited to a minimum. The high short-circuit rating of 10 kA of the smissline miniature circuit-breakers makes them ideal for the use in fuseless distribution systems.
40125
Major features
q q q q q q q
High rated short-circuit capacity of 10 kA (LP) Energy-limiting (current limiting class 3) Snap-on neutral disconnector Snap-on auxiliary switch and signal contact Optimum ease of assembly and connection Line terminals protected against accidental contact Trip characteristic B, C, D, K, UCZ/UCC
Technical data
Series: LP... Rated voltage Ue~: Rated voltage Ue=: (Connection diagram LPDC see page 9) Rated current In: 230/400 V~ 60 V=/1pole Series: LPUC... 125 V=1pole 250 V=2pole polarity-dependent
663 A (C) 10...63 A (B, D) 0.5...63 A (K) B, C, D, K, G C Z (semiconductor protection) 1+2 6...50 kA stranded/flexible 25/16 mm2 16/10 mm2 IP20
Trip characteristic:
Number of poles: Rated frequency: Rated short-circuit capacity Icn: Energy limiting class: Conductor cross-section Cu: stranded/flexible, top terminal stranded/flexible, bottom terminal Degree of protection: Endurance: mechanical electrical Climatic resistance: Position of use: Ambient temperature: Resistance to vibrations:
20,000 4,000 DIN 50016 any 25 C...+55 C 5g 5...150...5 Hz BSEN 60898 SEV, VDE, VE 120 g Free of halogens and cadmium
20,000 4,000 DIN 50016 any 25 C...+55 C 5g 5...150...5 Hz 150 g Free of halogens and cadmium
5
20165/C
Miniature circuit-breaker
Back-up protection
Back-up protection
a) If the short-circuit current at the place of installation of a miniature circuit-breaker is not higher than the specified rated breaking capacity of the MCB, no back-up fuse link is necessary. If a back-up fuse is connected for installation reasons, its rated current may be selected as high as required. b) If the short-circuit current at the place of installation of the miniature circuit-breaker is higher than its breaking capacity, the rated currents of the back-up fuse link must not exceed the values in the following table. Maximum fuse ratings for back-up protection
Characteristic Rated current of miniature circuit-breaker B, C, D 6A 8A 10 A 13 A 10 kA 16... 40 A 10 kA 50... 63 A 10 kA 0.5... 2A 50 kA 3A 4A K, G 6A 8... 13 A 10kA 16... 40 A 10kA 50... 63 A 10kA
Rated breaking capacity LP Max. rated current of back-up fuse link gG (A)
10 kA
10 kA
10 kA
10 kA
10 kA
40
63
100
125
160
any
50
63
80
100
125
160
Using the back-up table These tables provide the value (in kA) for which back-up protection is ensured between a given combination of circuit-breakers. The tables cover possible combinations between ABB SACE moulded-case circuit-breakers in Tmax ranges and between the above mentioned circuitbreakers and the ABB range of miniature circuit-breakers. The values given in the table refer to a rated voltage Vn of 415 V AC for combinations between moulded-case circuit-breakers and to a rated voltage VN of 400 V AC for combinations between moulded-case and miniature circuit-breakers.
B C
6 to 63 A 8 to 63 A
5 In 10 In 20 In 12 In 14 In up to 32A up 40A
> 0,1 s < 0,1 s > 0,1 s < 0,1 s > 0,1 s < 0,1 s > 0,2 s < 0,2 s
10 to 63 A
0,5 to 63 A
0,5 to 63 A
1,05 In
2 In
3 In
6
20165/C
Miniature circuit-breaker
Trip characteristic
Characteristic
B Miniature circuit-breaker for circuits supplying loads generating no or only minor inrush currents (boilers, electric heaters, cookers).
C The Standard miniature circuit-breaker for circuits supplying loads producing inrush currents particular to inductive loads (TV sets, fluorescent and discharge lamps) and for socket outlets.
Trip diagram
40070
10 000
10 000
1000
1000
100
100
Tripping time in s
10
Tripping time in s
10
40071
0,1
0,1
0,01
[Link]
0,01
[Link]
0,002 1 2 3 5 10 20 30
0,002 1 2 3 5 10 20 30
Trip characteristic
40070
Thermal release
1.13...1.45xIn
1.13...1.45xIn
Electromagnetic release
3...5xIn
5...10xIn
Reference temperature
30 C
30 C 7
20165/C
Miniature circuit-breaker
Trip characteristic
D Miniature circuit-breaker for circuits supplying loads producing very high inrush currents (transformers, capacitor banks). Main circuit-breaker for the protection of circuit-breakers connected downstream.
G, K Circuit-breaker for equipment: The characteristics of these types enable the close protection requirements for equipment to be met.
UC Circuit breaker for equipment supplied with either direct or alternating current.
10 000
10 000
10 000
1000
1000
1000
100
100
100
Tripping time in s
10
Tripping time in s
10
Tripping time in s
10
1 K
1 C 0,1 Z
0,1
0,1
0,01
[Link]
0,01
[Link]
0,01
[Link]
0,002 1 2 3 5 10 20 30
0,002 1 2 7 12 1 2 3 8 14
0,002 1 2 3 5 1 2 3 7 14
UC D G K Z C
1.13...1.45xIn
1.05...1.35xIn
1.05...1.2xIn
1.05...1.35xIn
1.13...1.45xIn
10...20xIn
7...12xIn
8...14xIn
3...5xInDC 2...3xInAC
7...14xInDC 5...10xInAC
30 C 8
20165/C
20 C
40 C
30 C
Miniature circuit-breaker
Selectivity
Discrimination
Short circuit discrimination is provided by the smissline miniature circuit-breaker up to limits given in the following table. The values refer to the mean trip characteristic of the back-up fuse link.
Limits of discrimination
Rated current of miniature circuit-breaker Trip characteristic Back-up fuse link gG (VDE 0636) B, C, D, K, G 20 A 25 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 6A 8A 10/13 A 16 A 520 A 750 A 960 A 1200 A 1700 A 2500 A 3200 A
1) 1)
600 A 560 A 850 A 800 A 1200 A 1100 A 1600 A 1400 A 2400 A 2200 A 8000 A 6000 A 10000 A 10000 A 3 200 1) 3 200 1) 32 00 1) 32 00 1)
1)
not permissible if the short-circuit current produced is higher than the rated breaking capacity.
S500 Should a short-circuit occur selective break action will be performed of the MCB up to the current values as listed in the following table. MCBs
Upstream Rated current (A) Downstream B6 / C6 B10 / C10 B13 / C13 B16 / C16 B20 / C20 B25 / C25 B32 / C32 B40 / C40 B50 / C50 Rated current (A) 6 10 13 16 20 25 32 40 50
S500-C, D C40
D40
C50
D50
C63
D63
Max. short-circuit current (A) 600 550 550 550 500 450 1200 1100 1100 1100 1000 900 900 800 700 700 700 600 550 550 1400 1300 1300 1300 1200 1100 1100 950 850 850 850 800 750 700 700 700 1800 1700 1700 1700 1550 1400 1400 1400 1400
9
20165/C
Miniature circuit-breaker
Series LP...B
Order data
Circuit protection Characteristic
Icn kA 6 10 10 10 10 10 10 10 10 10
B
Rated current 6A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A Order data LP1B6-S LP1B10-S LP1B13-S LP1B16-S LP1B20-S LP1B25-S LP1B32-S LP1B40-S LP1B50-S LP1B63-S Module 1 1 1 1 1 1 1 1 1 1 Packaging unit 10 10 10 10 10 10 10 10 10 10
1P
40123
2P
6 10 10 10 10 10 10 10 10 10
6A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A
LP2B6-S LP2B10-S LP2B13-S LP2B16-S LP2B20-S LP2B25-S LP2B32-S LP2B40-S LP2B50-S LP2B63-S
2 2 2 2 2 2 2 2 2 2
5 5 5 5 5 5 5 5 5 5
40124
3P
6 10 10 10 10 10 10 10 10 10
6A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A
LP3B6-S LP3B10-S LP3B13-S LP3B16-S LP3B20-S LP3B25-S LP3B32-S LP3B40-S LP3B50-S LP3B63-S
3 3 3 3 3 3 3 3 3 3
3 3 3 3 3 3 3 3 3 3
40125
Detachable neutral conductor terminals for additional socket Order data see page 52 Auxiliary switch and signal contacts SDH and SDS Order data see page 41 Accessories Order data from page 42
40276
SDH SDS
10
20165/C
40148
40149
40432
Miniature circuit-breaker
Series LP...C
Order data
Circuit protection Characteristic
Icn kA 10 10 10 10 10 10 10 10 10 10 10
C
Rated current 6A 8A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A Order data LP1C6-S LP1C8-S LP1C10-S LP1C13-S LP1C16-S LP1C20-S LP1C25-S LP1C32-S LP1C40-S LP1C50-S LP1C63-S Module 1 1 1 1 1 1 1 1 1 1 1 Packaging unit 10 10 10 10 10 10 10 10 10 10 10
1P
40127
2P
10 10 10 10 10 10 10 10 10 10 10
6A 8A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A
LP2C6-S LP2C8-S LP2C10-S LP2C13-S LP2C16-S LP2C20-S LP2C25-S LP2C32-S LP2C40-S LP2C50-S LP2C63-S
2 2 2 2 2 2 2 2 2 2 2
5 5 5 5 5 5 5 5 5 5 5
40128
3P
10 10 10 10 10 10 10 10 10 10 10
6A 8A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A
LP3C6-S LP3C8-S LP3C10-S LP3C13-S LP3C16-S LP3C20-S LP3C25-S LP3C32-S LP3C40-S LP3C50-S LP3C63-S
3 3 3 3 3 3 3 3 3 3 3
3 3 3 3 3 3 3 3 3 3 3
40129
LPN63-S
Detachable neutral terminals for additional socket Order data see page 52 Auxiliary switch and signal contacts SDH and SDS Order data see page 41 Accessories Order data from page 42
40148
40276
SDH SDS
40149
11
20165/C
Miniature circuit-breaker
Series LP...D
Order data
Circuit protection Characteristic
Icn kA 10 10 10 10 10 10 10 10 10
D
Rated current 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A Order data LP1D10-S LP1D13-S LP1D16-S LP1D20-S LP1D25-S LP1D32-S LP1D40-S LP1D50-S LP1D63-S Module 1 1 1 1 1 1 1 1 1 Packaging unit 10 10 10 10 10 10 10 10 10
1P
40131
2P
10 10 10 10 10 10 10 10 10
10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A
2 2 2 2 2 2 2 2 2
5 5 5 5 5 5 5 5 5
40132
3P
40133
10 10 10 10 10 10 10 10 10
10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A
3 3 3 3 3 3 3 3 3
3 3 3 3 3 3 3 3 3
Detachable neutral terminals for additional socket Order data see page 52
40432
40276
Auxiliary switch and signal contacts SDH and SDS Order data see page 41 Accessories Order data from page 42
SDH SDS
12
20165/C
40148
40149
Miniature circuit-breaker
Series LP...G
Order data
Equipment/circuit protection Characteristic
Icn kA 50 50 50 50 10 10 10 10 10 10 10 10 10 10 10 10 10
G
Rated current 0.5 A 1A 1.6 A 2A 3A 4A 6A 8A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A Order data LP1G0.5-S LP1G1-S LP1G1.6-S LP1G2-S LP1G3-S LP1G4-S LP1G6-S LP1G8-S LP1G10-S LP1G13-S LP1G16-S LP1G20-S LP1G25-S LP1G32-S LP1G40-S LP1G50-S LP1G63-S Module 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Packaging unit 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
1P
40135
2P
50 50 50 50 10 10 10 10 10 10 10 10 10 10 10 10 10
0.5 A 1A 1.6 A 2A 3A 4A 6A 8A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A
LP2G0.5-S LP2G1-S LP2G1.6-S LP2G2-S LP2G3-S LP2G4-S LP2G6-S LP2G8-S LP2G10-S LP2G13-S LP2G16-S LP2G20-S LP2G25-S LP2G32-S LP2G40-S LP2G50-S LP2G63-S
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
40136
3P
50 50 50 50 10 10 10 10 10 10 10 10 10 10 10 10 10
0.5 A 1A 1.6 A 2A 3A 4A 6A 8A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A
LP3G0.5-S LP3G1-S LP3G1.6-S LP3G2-S LP3G3-S LP3G4-S LP3G6-S LP3G8-S LP3G10-S LP3G13-S LP3G16-S LP3G20-S LP3G25-S LP3G32-S LP3G40-S LP3G50-S LP3G63-S
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
40137
Auxiliary switch and signal contacts SDH and SDS Order data see page 41
40148
SDH SDS
40149
13
20165/C
Miniature circuit-breaker
Series LP...K
Order data
Equipment/circuit protection Characteristic
Icn kA 50 50 50 50 10 10 10 10 10 10 10 10 10 10 10 10 10
K
Rated current 0.5 A 1A 1.6 A 2A 3A 4A 6A 8A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A Order data LP1K0.5-S LP1K1-S LP1K1.6-S LP1K2-S LP1K3-S LP1K4-S LP1K6-S LP1K8-S LP1K10-S LP1K13-S LP1K16-S LP1K20-S LP1K25-S LP1K32-S LP1K40-S LP1K50-S LP1K63-S Module 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Packaging unit 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
1P
40135
2P
50 50 50 50 10 10 10 10 10 10 10 10 10 10 10 10 10
0.5 A 1A 1.6 A 2A 3A 4A 6A 8A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A
LP2K0.5-S LP2K1-S LP2K1.6-S LP2K2-S LP2K3-S LP2K4-S LP2K6-S LP2K8-S LP2K10-S LP2K13-S LP2K16-S LP2K20-S LP2K25-S LP2K32-S LP2K40-S LP2K50-S LP2K63-S
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
40136
3P
50 50 50 50 10 10 10 10 10 10 10 10 10 10 10 10 10
0.5 A 1A 1.6 A 2A 3A 4A 6A 8A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A
LP3K0.5-S LP3K1-S LP3K1.6-S LP3K2-S LP3K3-S LP3K4-S LP3K6-S LP3K8-S LP3K10-S LP3K13-S LP3K16-S LP3K20-S LP3K25-S LP3K32-S LP3K40-S LP3K50-S LP3K63-S
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
40137
Auxiliary switch and signal contacts SDH and SDS Order data see page 41
40148
SDH SDS
14
20165/C
40149
Miniature circuit-breaker
Series LPUC direct current application
Order data
Equipment/circuit protection Characteristic
Icn kA 50 50 50 50 6 6 6 6 6 6 6 6 6 6 6 6 6
Z
Rated current 0.5 A 1A 1.6 A 2A 3A 4A 6A 8A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A Order data LPUC1Z0.5-S LPUC1Z1-S LPUC1Z1.6-S LPUC1Z2-S LPUC1Z3-S LPUC1Z4-S LPUC1Z6-S LPUC1Z8-S LPUC1Z10-S LPUC1Z13-S LPUC1Z16-S LPUC1Z20-S LPUC1Z25-S LPUC1Z32-S LPUC1Z40-S LPUC1Z50-S LPUC1Z63-S Module 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Packaging unit 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
1 P 125 V=
40139
2 P 250 V=
50 50 50 50 6 6 6 6 6 6 6 6 6 6 6 6 6
0.5 A 1A 1.6 A 2A 3A 4A 6A 8A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A
LPUC2Z0.5-S LPUC2Z1-S LPUC2Z1.6-S LPUC2Z2-S LPUC2Z3-S LPUC2Z4-S LPUC2Z6-S LPUC2Z8-S LPUC2Z10-S LPUC2Z13-S LPUC2Z16-S LPUC2Z20-S LPUC2Z25-S LPUC2Z32-S LPUC2Z40-S LPUC2Z50-S LPUC2Z63-S
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
40140
Auxiliary switch and signal contacts SDH and SDS Order data see page 41 Accessories Order data from page 42
40148
SDH SDS
40149
Connection diagram single-pole (max. 125 V=) LPUC1 Connection diagram double-pole (max. 250 V=) LPUC2 Load Load
2
[Link]
4
[Link]
Mains
Mains
15
20165/C
Miniature circuit-breaker
Series LPUC direct current application
Order data
Circuit protection Characteristic
Icn kA 50 50 50 50 6 6 6 6 6 6 6 6 6 6 6 6 6
C
Rated current 0.5 A 1A 1.6 A 2A 3A 4A 6A 8A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A Order data LPUC1C0.5-S LPUC1C1-S LPUC1C1.6-S LPUC1C2-S LPUC1C3-S LPUC1C4-S LPUC1C6-S LPUC1C8-S LPUC1C10-S LPUC1C13-S LPUC1C16-S LPUC1C20-S LPUC1C25-S LPUC1C32-S LPUC1C40-S LPUC1C50-S LPUC1C63-S Module 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Packaging unit 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
1 P 125 V=
40141
2 P 250 V=
50 50 50 50 6 6 6 6 6 6 6 6 6 6 6 6 6
0.5 A 1A 1.6 A 2A 3A 4A 6A 8A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A
LPUC2C0.5-S LPUC2C1-S LPUC2C1.6-S LPUC2C2-S LPUC2C3-S LPUC2C4-S LPUC2C6-S LPUC2C8-S LPUC2C10-S LPUC2C13-S LPUC2C16-S LPUC2C20-S LPUC2C25-S LPUC2C32-S LPUC2C40-S LPUC2C50-S LPUC2C63-S
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
40142
Auxiliary switch and signal contacts SDH and SDS Order data see page 41 Accessories Order data from page 42
40148
SDH SDS
40149
Connection diagram single-pole (max. 125 V=) LPUC1 Connection diagram double-pole (max. 250 V=) LPUC2 Load Load
2
[Link]
4
[Link]
Mains
Mains
16
20165/C
Order data
Circuit protection Characteristic
Icn kA 10 10 10 10 10 10 10 10 10
B
Rated current 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A Order data LP1NAB10-S LP1NAB13-S LP1NAB16-S LP1NAB20-S LP1NAB25-S LP1NAB32-S LP1NAB40-S LP1NAB50-S LP1NAB63-S Module 2 2 2 2 2 2 2 2 2 Packaging unit 5 5 5 5 5 5 5 5 5
1 P + NA
40206
3 P + NA
10 10 10 10 10 10 10 10 10
10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A
4 4 4 4 4 4 4 4 4
2 2 2 2 2 2 2 2 2
40207
Characteristic
C
6A 8A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A LP1NAC6-S LP1NAC8-S LP1NAC10-S LP1NAC13-S LP1NAC16-S LP1NAC20-S LP1NAC25-S LP1NAC32-S LP1NAC40-S LP1NAC50-S LP1NAC63-S 2 2 2 2 2 2 2 2 2 2 2 5 5 5 5 5 5 5 5 5 5 5
1 P + NA
10 10 10 10 10 10 10 10 10 10 10
40143
3 P + NA
10 10 10 10 10 10 10 10 10 10 10
6A 8A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A
LP3NAC6-S LP3NAC8-S LP3NAC10-S LP3NAC13-S LP3NAC16-S LP3NAC20-S LP3NAC25-S LP3NAC32-S LP3NAC40-S LP3NAC50-S LP3NAC63-S
4 4 4 4 4 4 4 4 4 4 4
2 2 2 2 2 2 2 2 2 2 2
40145
Auxiliary switch and signal contacts SDH and SDS Order data see page 41 Accessories Order data from page 42
40148
SDH SDS
40149
17
20165/C
Order data
Circuit protection Characteristic
Icn kA 10 10 10 10 10 10 10 10 10
D
Rated current 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A Order data LP1NAD10-S LP1NAD13-S LP1NAD16-S LP1NAD20-S LP1NAD25-S LP1NAD32-S LP1NAD40-S LP1NAD50-S LP1NAD63-S Module 2 2 2 2 2 2 2 2 2 Packaging unit 5 5 5 5 5 5 5 5 5
1 P + NA
40208
40280
10 10 10 10 10 10 10 10 10
10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A
4 4 4 4 4 4 4 4 4
2 2 2 2 2 2 2 2 2
3 P + NA
Characteristic
IIcn kAA 50 50 50 50 10 10 10 10 10 10 10 10 10 10 10 10 10
K
Rated current 0.5 A 1A 1.6 A 2A 3A 4A 6A 8A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A Order data LP1NAK0.5-S LP1NAK1-S LP1NAK1.6-S LP1NAK2-S LP1NAK3-S LP1NAK4-S LP1NAK6-S LP1NAK8-S LP1NAK10-S LP1NAK13-S LP1NAK16-S LP1NAK20-S LP1NAK25-S LP1NAK32-S LP1NAK40-S LP1NAK50-S LP1NAK63-S Module 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Packaging unit 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
1 P + NA
40281
3 P + NA
50 50 50 50 10 10 10 10 10 10 10 10 10 10 10 10 10
0.5 A 1A 1.6 A 2A 3A 4A 6A 8A 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A
LP3NAK0.5-S LP3NAK1-S LP3NAK1.6-S LP3NAK2-S LP3NAK3-S LP3NAK4-S LP3NAK6-S LP3NAK8-S LP3NAK10-S LP3NAK13-S LP3NAK16-S LP3NAK20-S LP3NAK25-S LP3NAK32-S LP3NAK40-S LP3NAK50-S LP3NAK63-S
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
40282
Auxiliary switch and signal contacts SDH and SDS Order data see page 41
40148 40149
SDH SDS
18
20165/C
Order data
Circuit protection Characteristic
Icn kA 10 10 10 10 10 10 10 10 10
C
Rated current 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A Order data LP1NPC10-S LP1NPC13-S LP1NPC16-S LP1NPC20-S LP1NPC25-S LP1NPC32-S LP1NPC40-S LP1NPC50-S LP1NPC63-S Module 2 2 2 2 2 2 2 2 2 Packaging unit 10 10 10 10 10 10 10 10 10
1 P + NA protect
40959
2 P + NA protect 10 10 10 10 10 10 10 10 10 10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A LP3NPC10-S LP3NPC13-S LP3NPC16-S LP3NPC20-S LP3NPC25-S LP3NPC32-S LP3NPC40-S LP3NPC50-S LP3NPC63-S 4 4 4 4 4 4 4 4 4 3 3 3 3 3 3 3 3 3
40987
10 10 10 10 10 10 10 10 10
10 A 13 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A
3 3 3 3 3 3 3 3 3
5 5 5 5 5 5 5 5 5
Characteristic
40960
K
0.5 A 1A 1.6 A 2A 3A 4A 6A 8A LP1NPK0.5-S LP1NPK1-S LP1NPK1.6-S LP1NPK2-S LP1NPK3-S LP1NPK4-S LP1NPK6-S LP1NPK8-S 2 2 2 2 2 2 2 2 10 10 10 10 10 10 10 10
3 P + NA protect
50 50 50 50 10 10 10 10
50 50 50 50 10 10 10 10
0.5 A 1A 1.6 A 2A 3A 4A 6A 8A
3 3 3 3 3 3 3 3
5 5 5 5 5 5 5 5
50 50 50 50 10 10 10 10
0.5 A 1A 1.6 A 2A 3A 4A 6A 8A
4 4 4 4 4 4 4 4
3 3 3 3 3 3 3 3
40148
40149
Auxiliary switch and signal contacts SDH and SDS Order data see page 41 Accessories Order data from page 42
SDH SDS
19
20165/C
General
The residual current circuit-breaker makes a decisive contribution to the prevention of injury to persons and damage to material caused by electric currents. It is specified in national and international standards. Modern residual current circuit-breakers already respond to the smallest currents. Disconnection takes place within fractions of a second before danger can arise for persons, animals or material. The principle of permanent magnetic release ensures an optimum, reliable action, even with undervoltage and neutral disconnection.
40075
Major features
q q q q q q
High short-circuit capacity 10 kA Sensitive to AC and pulsating DC fault currents 2- and 4-pole versions Rated tripping currents 10, 30, 100 and 300 mA Snap-on auxiliary switch and signal contacts Rated currents 16, 25, 40, 63 A
Technical data
40085
FIP2 Rated voltage Un: Rated current In (A): Rated tripping current In (mA): 10 30 100 300 Number of poles: Frequency fn: Surge current withstand capability: 230 V 16 25 40 q q q q
FI4 230/400 V 16 25 40 63 q q q q q q q q
2 45 60 Hz 250 A 8/20 s
4 45 60 Hz 250 A 8/20 s
Total breaking time (mean value) for In for 5 In Delay time for 5 In: Short-circuit capacity(kA): Cable cross-section Cu: Type-S, top Type-S, bottom Protection class: Life endurance to Mechanical operations Electrical operations Climatic resistance to: Mounting position: Ambient temperature: Resistance to vibrations:
40 ms 25 ms 10 kA Cable/strand 25/16 mm2 16/10 mm2 IP 40 BSEN 61008 4,000 2,000 EN 61008 any 25 C +40 C 5g 5 150 5 Hz BSEN 61008 SEV, VDE, VE 250 g Free of halogens and cadmium
40 ms 25 ms 10 kA Cable/strand 25/16 mm2 16/10 mm2 IP 40 BSEN 61008 4,000 2,000 EN 61008 any 25 C +40 C 5g 5 150 5 Hz BSEN 61008 SEV, VDE, VE, SEMKO, NEMKO 380 g Free of halogens and cadmium
20
20165/C
Order data
Rated tripping current FIP 2 10 mA 30 mA 30 mA 100 mA Rated current Order data Module Packaging unit
16 A 25 A 40 A 40 A
2 2 2 2
2 2 2 2
Auxiliary switch and signal contacts SDH and SDS Order data see page 43
40148
40078
SDH SDS
40149
16 A 25 A 40 A 63 A 40 A 63 A 40 A 63 A
4 4 4 4 4 4 4 4
1 1 1 1 1 1 1 1
Auxiliary switch and signal contacts SBH and SBS Order data see page 41 Accessories Order data from page 42
SBH SBS
40289
40291
21
20165/C
q q
Long line capacitances Large numbers of fluorescent lamps (particularly when using electronic ballast units) Electronic equipment and components (PC terminals, PLCs, voltage converters, etc.) Transient line overvoltages
The short time-delay residual current circuit-breakers FIKP2 and FIK4 differ from the selective standard type FIS4 by their significantly lower delay times. The FIKP2 and FIK4 G should therefore be used to prevent unwanted or nuisance tripping. With a preceding series connected FIS s the FIKP2 and FIK4 G behave in a similar, selective way to the standard FI.
40155
300 mA s
22
20165/C
[Link]
30 mA 10 mA
Technical data
FIKP2 Rated voltage Un: Rated current In (A): Rated tripping current In (mA): 10 30 100 300 Number of poles: Frequency fn: 230 V 40 FIK4 230/400 V 16 40 63 q q q q q q q 2 45 60 Hz 4 45 60 Hz 3 kA 8/20 s 4 45 60 Hz 5 kA 8/20 s FIS4 230/400 V 25 63
40074
Surge current withstand capability: 3 kA 8/20 s Total breaking time (mean value) for In for 5 In Delay for 5 In:
40148 40149
240 ms 35 ms 10 ms 10 kA Cable/strand 25/16 mm2 16/10 mm2 IP 40 BSEN 610008 4,000 2,000 BSEN 61008 any 25 C +40 C 5g 5 150 5 Hz BSEN 61008 SEV, VDE, VE 250 g Free of halogens and cadmium
240 ms 35 ms 10 ms 10 kA Cable/strand 25/16 mm2 16/10 mm2 IP 40 BSEN 610008 4,000 2,000 BSEN 61008 any 25 C +40 C 5g 5 150 5 Hz BSEN 61008 SEV, VE, SEMKO 400 g Free of halogens and cadmium
300 ms 115 ms 90 ms 10 kA Cable/strand 25/16 mm2 16/10 mm2 IP 40 BSEN 610008 4,000 2,000 BSEN 61008 any 25 C +40 C 5g 5 150 5 Hz BSEN 61008 SEV, VE, SEMKO 400 g
Short-circuit capacity (kA): Cable cross-section Cu: Type-S, top Type-S, bottom Protection class: Life endurance to Mechanical operations Electrical operations Climatic resistance to: Mounting position: Ambient temperature:
SDH SDS
40085
Resistance to vibrations:
Order data
40289 40291
Rated current
Order data
Module
Packaging unit
SBH SDS
FIKP240/30-S
Auxiliary switch and signal contacts SDH and SDS Order data see page 43
FIK4 short time-delay 10 mA 30 mA 100 mA 30 mA FIS4 selective 100 mA 300 mA
16 A 40 A 40 A 63 A
4 4 4 4
1 1 1 1
25 A 63 A
FIS425/100-S FIS463/300-S
4 4
1 1
Auxiliary switch and signal contacts SBH and SBS Order data see page 41 Accessories Order data from page 42 23
20165/C
The new, short time-delay residual current circuit-breaker FIK-LP2 G is specially suitable for unfavourable operating and mains conditions. Without influencing the personal protection function, the electronic delay suppresses faulty tripping, which can occur as a result of capacitive discharge currents. Capacitive discharge currents accompanied by high current peaks can be caused by:
q q q q
Long line capacitances A large number of fluorescent lamps (particularly when using electronic ballast units) Electronic equipment and components (PC terminals, PLCs, voltage converters, etc.) Transient line overvoltages
Major features
q q q q q q
Sensitive to AC and DC-pulsating fault currents Combined overcurrent and residual-current protection in one unit High rated breaking capacity of 10 kA Rated residual tripping currents 10 and 30 mA Snap-on auxiliary switch and signal contacts blocks Short time-delay version FIK-LP2 G
24
20165/C
30 30
30
Page 8 (LP) Page 8 (LP) 2-pole (1PN) 45 60 Hz 10 kA 230 V ~ (1016 A) 6 kA 230 V ~ (2032 A) 3 3 kA-8/20ms BSEN 61009 240 ms 35 ms 10 ms Cable/strand L = 25/16 mm2 L = 16/10 mm2 IP40 BSEN 61009 4,000 2,000 BSEN 61009 any 25 C...+40 C 5g 5...150...5 Hz BSEN 61009 SEV, VE, VDE 250 g Free of halogens and cadmium
25
20165/C
B
Rated current Order data Module Packaging unit
40076
13 A 16 A 16 A
2 2 2
2 2 2
Characteristic
FI-LP2 10 mA 30 mA 10 mA 30 mA 10 mA 30 mA 30 mA 30 mA 30 mA
C
10 A 10 A 13 A 13 A 16 A 16 A 20 A 25 A 32 A FI-LP2C10/10-S FI-LP2C10/30-S FI-LP2C13/10-S FI-LP2C13/30-S FI-LP2C16/10-S FI-LP2C16/30-S FI-LP2C20/30-S FI-LP2C25/30-S FI-LP2C32/30-S 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
40148
SDH SDS
40149
2 2 2
2 2 2
Auxiliary switch and signal contacts SDH and SDS Order data see page 41 Accessories Order data from page 42
26
20165/C
General
The FISG is specifically prescribed or at least recommended for many applications. In some systems, however, there could be a danger to persons, animals or material by the tripping of a residual current circuit-breaker with the associated interruption of circuits. The RC-sensor is ideal for systems of this kind. It has a permanent auxiliary contact on the left-hand side, and the main circuits are not switched for the reasons mentioned. This contact is used to operate an optical or acoustic signalling device if residual currents with dangerous magnitudes flow to earth.
40780
Important note
The FISG is not a protective device in the sense of the regulations, but it is able to detect and signal residual currents immediately. The FISG can be recognised by the red operating lever which distinguishes it clearly from current circuit-breakers.
Technical data
FISG Rated voltage Un: Rated current In: Rated tripping current In : 230/400 V 40, 63 A 30 mA, 300 mA s 1 SBH11 permanently fitted at side incl.. ZLS 930 6A 2 A/230 V~ 0.5 A/400 V~
Application
q q q q q q q q q q
Medical devices and equipment (hospitals, etc.) Heating, air-conditioning and ventilating systems Cooling systems Pump systems with important functions Street and building site lighting Chemical companies Electroplating companies Dairy plants Joinery and wood-working Traffic control systems
Connection example
acoustic
optical
signalling
Order data
Rated tripping current 30 mA 30 mA 300 mA s Rated current 40 A 63 A 63 A Order data FISG440/30-S FISG463/30-S FISG463S/300-S Module 5 5 5 Packaging unit 1 1 1
One auxiliary contact SBH11 is already fitted on the unit. Further auxiliary contacts can be snapped-on. Order data see page 41 Accessories Order data from page 42 27
20165/C
[Link]
General
For special applications, where the mains frequency is other than 50 Hz, corresponding residual current circuit-breakers are required. CMC offers a suitable range of special designs for these cases.
Major features
40417
q q q q q
Sensitive to AC and pulsating-DC current 4-pole breaker types Rated tripping currents 30 and 300 mA Snap-on auxiliary and signal contacts Rated currents 25, 63 A
Technical data
FI4 16 2/3 Hz Rated voltage Un: Rated current In (A): Rated tripping current In (mA): 30 50 300 Number of poles: Frequency fn: Surge current withstand capability: 230/400 V 25 63 q q 4 1518 Hz 250 A 8/20 s q q q q 4 360440 Hz 250 A 8/20 s q q FI4 400 Hz 230/400 V 25 63
Total disconnection time (mean value) for In for 5 In Delay time for 5 In: Short-circuit capacity (kA): Cable cross-section Cu: Type-S, top Type-S, bottom Protection class: Life endurance to Mechanical operations Electrical operations Climatic resistance to: Mounting position: Ambient temperature: Resistance to vibrations:
40 ms 25 ms 6 kA Cable/strand 25/16 mm2 16/10 mm2 IP 40 BSEN 61008 4,000 2,000 BSEN 61008 any 25 C +40 C 5g 5 150 5 Hz BSEN 61008 SEV Free of halogens and cadmium
40 ms 25 ms 6 kA Cable/strand 25/16 mm2 16/10 mm2 IP 40 BSEN 61008 4,000 2,000 BSEN 61008 any 25 C +40 C 5g 5 150 5 Hz BSEN 61008 SEV Free of halogens and cadmium
28
20165/C
Order data
Rated tripping current 16 2/3 Hz 30 mA 300 mA 30 mA 300 mA 400 Hz 50 mA 300 mA 50 mA 300 mA Rated current Order data Frequency Module Packaging unit
25 A 25 A 63 A 63 A
4 4 4 4
5 5 5 5
25 A 25 A 63 A 63 A
4 4 4 4
5 5 5 5
40417
Auxiliary and signal contact SBH and SBS Order data see page 41
SBH SBS
40289
40291
29
20165/C
General
The MS325 is a circuit-breaker with a motor protection characteristic. It is intended above all for industrial applications (MCC) or in distribution systems without a back-up fuse. It also fulfils its traditional function to provide thermal overload protection and short-circuit protection for other sectors of installation technology.
40073
Major features
q q q q q q q q q
Compact construction Very high rated breaking capacity Clear indication of switching position Phase failure protection Temperature compensation Test release possibility Provision for snap-on undervoltage release Snap-on auxiliary and signal contact blocks Further accessories
Technical data
MS325 Rated voltage Un: Rated current In (A): (14 adjustment ranges 0,1...25 A): Number of poles: Rated frequency fn: Rated breaking capacity Ics: Total disconnection time with short-circuit (50 kA/25 A range): Cable cross-section Cu cable or strand Type-S, top: Type-S, bottom: Protection class: Life endurance Electrical operations: (25 A, AC-3) Mechanical operations: Climatic resistance: Mounting position: Ambient temperature: Temperature compensation: Resistance to vibrations: 690 V~
25 3 50...60 Hz 100/50 kA
100,000 100,000 IEC/CEI 68-2-30 any 25 C...+50 C 25 C...+50 C 5g (50 m/s2) 5...150...5 Hz IEC 157-1, 292-1, 337-1 VDE 0660, IEC 947-2, 947-4-1 947-5-1 VDE 0106 Part 100 SEV 1090-1, 1092-1, 1093-1 SEV, KEMA, UL CSA 340 g Free of halogens and cadmium
Standards:
30
20165/C
(A) 0.1 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 9 12.5 16 20 0.16 0.25 0.4 0.63 1 1,6 2.5 4 6.3 9 12.5 16 20 25
Back-up protection
Maximum rated tripping currents a) If the short-circuit current at the place of installation of a motor protection circuit-breaker MS325 is not higher than the specified service breaking capacity, a back-up fuse link can be omitted. If a back-up fuse is fitted for installation reasons, its rated current may be selected as high as required. b) If the short-circuit current at the place of installation of a motor protection circuit-breaker MS325 is higher than its service breaking capacity, the rated current of the back-up fuse link must not exceed that given in the following table.
(A) 0.1 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 9 12.5 16 20 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 9 12.5 16 20 25
Magnetic release, Response current (mean value) independent of thermal setting 690 V~ (A) (kA) 1.6 2.5 4 6.3 12 19 30 48 75 108 150 192 240 300
500 V~ (kA)
400 V~ (kA)
230 V~ (kA)
50 80 80 100 125
31
20165/C
The motor protection circuit-breaker MS325 is suitable for DC applications, DC1-DC5 operation. On DC the electromagnetic release responds to values 1.35 times higher than at 50 Hz. The polarity is immaterial when connecting. The MS325 can be used with the following voltages:
Thermal release, Adjustment ranges Magnetic release, Max. voltage Ue 3 poles in series Response current1) (mean value) independent of the thermal setting (A) (V=) 2.2 3.4 5.4 8.5 16 26 40.5 65 101 146 202.5 260 325 405 450 420* 330* 270* 450 450 450 450 450 450 450 450 450 450 Rated breaking capacity
(A) 0.1 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 9 12.5 16 20 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 9 12.5 16 20 25
Direct starter, co-ordination to IEC 947-4-1 Normal start 400 V 50 Hz, ambient temperatures 40 C
50 kA type 1/type 2 Motor Motor protection Contactor Contactor Copper cable Max. permissible current for this combination A 1.6 1.6 2.5 4.0 4.0 6.3 9.0 9.0 12.0 16.0 25.0
Type
Range of adjustment A 1.0 1.6 1.0 1.6 1.6 2.5 2.5 4.0 2.5 4.0 4.0 6.3 6.3 9.0 6.3 9.0 9.0 12.5 12.5 16.0 20.0 25.0
Type 1
Type 2
Minimum cable cross-section in mm2 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5
MS 325 1.6 MS 325 1.6 MS 325 2.5 MS 325 4.0 MS 325 4.0 MS 325 6.3 MS 325 9.0 MS 325 9.0 MS 325 12.5 MS 325 16.0 MS 325 25.0
A9 A9 A9 A9 A9 A9 A9 A9 A 12 A 16 A 26
A9 A9 A9 A 12 A 26 A 26 A 26 A 26 A 26 A 26 A 26
Ambient temperature 30 C
for: Oil burner motors Small fans q Valve motors q Conveyor pumps q Special drives q Batching systems, etc.
q q
[Link]
Circuit-breakers ready for fitting with special base-plate and the corresponding plug contacts (L1 and N), according to order data page 35.
32
20165/C
Order data
Adjustment ranges in A 0.1 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 9 12.5 16 20 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 9 12.5 16 20 25 Order data MS325-0.16-S MS325-0.25-S MS325-0.4-S MS325-0.63-S MS325-1-S MS325-1.6-S MS325-2.5-S MS325-4-S MS325-6.3-S MS325-9-S MS325-12.5-S MS325-16-S MS325-20-S MS325-25-S Module 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Packaging unit 1 1 1 1 1 1 1 1 1 1 1 1 1 1
400 V~ 3P
40073
Adapter plate for contact to busbars with plug contacts 3L 3L+N (20A reduced) 2L (reversible) 1L+N (reversible)
Packaging unit 10 10 10 10
40160
Auxiliary switch and signal contact SBH and SBS Order data see page 41 Accessories Order data from page 42
40289 40291
SBH SBS
Technical data
Rated voltage Un Voltage tap in MS325: With connection leads 200 mm long (external voltage): Rated frequency: Power consumption: Actuation voltage (to IEC 292-1) dropout: pickup: Duty cycle: Dimensions B x H x L:
40156
Weight:
SMUA400 SMUA230
1 1
Connection support snap-on to smissline MS325 Width 9 mm for undervoltage release with external voltage
40150 40151
AS
10
ZLS930
10
33
20165/C
Product description
The surge arrester SA4/SA4 SC is a 4-pole arrester meeting the requirements of class C to DIN VDE 0675 Part 6, Part 6/A1 and Part 6/A2. It also complies with requirement class II of the international standard II IEC 61643-1 (1998-02). The SA4 SC is used for the protection of low voltage consumer systems and equipment from overvoltages (DIN VDE 100) caused by remote lightning strikes or switching operations. A typical place of application is the low voltage main and subsidiary distributor, where the arrester is attached directly to the smissline busbar system. If the unit is connected correctly, the green operating lamp (LED) lights. The protection elements are provided with thermal monitoring according to the current guidelines. In the event of an overvoltage the protective element is disconnected from the mains and the operating lamp changes from green to red. Actuation of the mechanism can be indicated remotely via the integrated telemetry contact. This remote display is only available with the SA4 SC.
40730
Assembly
Installation and electrical connection The surge arrester SA4/SA4 SC is installed at the input of the distribution board supplying the installation to be protected. It is snapped directly onto the smissline busbars immediately following the incoming power supply unit. The earth terminal of the arrester must be connected to the installation main earthing terminal by the shortest possible route, as close as possible to the earthing conductor of the installation, using a conductor (as supplied) of cross section no less than 6 mm2. The operating lamp will only show green if the connection is correct and the arrester is fully serviceable.
34
20165/C
PE Connection with preassembled conductor or shorter 11 main earthing terminal bar ABB SA4 SC L1 L2 L3 N 12 14
F1 L1 L2 L3
[Link]
PEN Connection with preassembled conductor or shorter 11 main earthing terminal bar ABB SA4 SC L1 L2 L3 N 12 14
F1 L1 L2 L3
[Link]
35
20165/C
Technical data
Rated voltage: UN Rated voltage: UC Requirement class: to VDE 0675, Part 6 Requirement class: to IEC 61643-1 (1998-2) Rated surge arrester current: Isn (8/20) multi shot Max. surge arrester current: Ismax (8/20) single shot Protection level: Up for Isn Up for Is = 5 kV 230 / 400 V AC 275 V AC C II 15 kA 30 kA 1.5 kV 1 kV 25 ns 1 mA 16 mm2 cable / 10 mm2 litz wire 25 mm2 cable / 16 mm2 litz wire 125 A gL/gG / 25 kA max. operating voltage max. switching current 1 changeover 250 V AC 2A S11/S12 N/C, S11/S14 N/O 25 ... + 60 C IP 20 Isg (8/20 s) 90 kA Free of halogens and cadmium
Temperature range: Protection class: Limit surge arrester current per unit: Plastic components:
Order data
Type With integrated telemetry contact Without integrated telemetry contact Order data SA4 SC-S SA4 Modules 4 4 Packaging unit 1 1
40730
36
20165/C
40731
General
The load switch can be used instead of an incoming terminal block up to 63 A in the smissline socket system. The external shape and dimensions correspond with the 4-pole residual-current circuit-breaker. The smissline IS463 load switch can be used to disconnect or connect individual loads, groups of loads or complete sections of the system to the power supply.
40157
Major features
q q q q q
As power supply switch On-Off switch function Clear switch position indication Snap-on auxiliary contact possible Uniform smissline design
Technical data
Load switch IS463 Rated voltage Un: Rated current In: Number of poles: Cable cross-section Cu: Type-S, top: Type-S, bottom: Protection class: Life endurance mechanical/electrical: Mounting position: Ambient temperature: Standards: Approvals: Weight (approx.): User category: Plastic components: 230/400 V~ 63 A 4 Cable/strand 25 / 16 mm2 16 / 10 mm2 IP40 5000 switching cycles any 25 C...+40 C EN 60947 SEV/ASE/VE 250 g AC22-A Free of halogens and cadmium
Order data
Order data IS463-S Modules 4 Packaging unit 1
Auxiliary switch and signal contact SBH Order data see page 41 Accessories Order data from page 42
SBH
40289
37
20165/C
General
The auxiliary switch and signal contacts are snapped onto the left of the protective device in each case. For auxiliary and signal contacts powered via smissline auxiliary busbars LA or LB, the desired number of contact pins must be ordered at the same time as the device. In addition, a low current power supply may be taken via these switches.
40148
Function
The auxiliary contact works similarly to the main contacts. The signal contact only operates when the protective device trips. This can be simulated with the grey test button. After each trip, the signal contact should be returned to the starting position with the orange reset button. Auxiliary and signal contacts have contacts which ensure high switching reliability, even in systems with low voltages or low currents (PLC, signal systems, etc.).
Auxiliary contacts SDH and SBH switch at the same time as the contacts of the protective device (operated manually or automatically).
40149
joint-switching
counter-switching
Signal contacts SDS and SBS switch only when the protective device is electrically tripped due to shortcircuit, fault current or overcurrent (undervoltage for MS325). Closing contact NO Opening contact NC closes on automatic trip
40291
38
20165/C
40289
Unit type Miniature circuit-breaker LP... Residual-current circuit-breaker FIP2 / FIKP2 / FI-LP2 / FIK-LP2 Residual-current circuit-breaker FI4 / FIK4 / FIS4 FISG Load switch IS463 Motor-protection switch MS325
Auxiliary contacts
Signal contacts
SDH...
SDS...
OFF
SDH...
SDS...
OFF
SBH... SBH...
OFF
SBH...
not possible
OFF
SBH...
SBS...
OFF
q q q q
All additional contacts are always fitted on the left of the protective device. When an auxiliary switch and a signal contact block are used, the signal contact block must be first, snapped directly onto the circuit-breaker. It is not possible to mount two signal contact blocks on the same circuit-breaker. Additional contacts of series SDH..., SDS... and SBH..., SBS... are mounted onto circuit-breakers in the off position.
The following can be mounted on each circuit-breaker: 1 auxiliary switch block or 1 signal contact block or 2 auxiliary contact blocks or 1 auxiliary switch and 1 signal contact block
SDH
13 21
SBH
13 21
SDH 11
14 13 22 23
SBH 11
14 13 22 23
SDH 20
14 11 24 21
SBH 20
14 11 24 21
SDH 02
12 22
SBH 02
12 22
SDS
97 05
SBS
97
SDS 11
98 97 06 07
SBS 10
98 95
SDS 20
98 95 08 05
SBS 01
[Link]
96
SDS 02
96 06
39
20165/C
SDS /SBS Rated voltage Un: Rated current: Ith: AC15 DC13 Minimum value (contact security): Cable cross-section: Plastic components: 400 V
6A 2 A/230 V / 1 A/400 V 0.5 A/125 V= 10 mA 12 V= 2 x 2.5 mm2 strand with end ferrule Free of halogens and cadmium
6A 2 A/230 V / 0,5 A/400 V 0.5 A/125 V= 10 mA 12 V= 2 x 2.5 mm2 strand with end ferrule Free of halogens and cadmium
2. Power supply to the auxiliary busbars LA or LB via the auxiliary terminals in the power supply block
3. Connection support and auxiliary or signal contact block with power supply via auxiliary busbars LA and return via LB
40
20165/C
[Link]
Order data
Mounted on: Miniature circuit-breaker LP Auxiliary switch contact block SDH 1S and 1 2S 2 Signal contact block SDS 1S and 1 2S 2
40148 40149
Order data
Module
Packaging unit
10 10 10
SDH SDS
10 10 10
MS325, FI4, FIK4, FIS4, IS463, FISG Auxiliary switch contact block SBH 1S and 1 2S 2 MS325, FI4, FIK4, FIS4 Signal contact block SBS 1S 1
40289 40291
10 10 10
SBS10 SBS01
0.5 0.5
10 10
SBH SBS
40150
Auxiliary switch and signal contacts, connection support Dummy housing Equalization to 18 mm ZLS930
0.5
10
40151
40152
Auxiliary switch and signal contacts, connection support Contact pin, short for power supply via auxiliary busbars ZLS630
10
41
20165/C
Combi-modules
General
The advantage of the Combi modules is that any desired combinations of smissline units can be formed into a unit with conventional devices. These can be replaced very quickly and keeps the downtime of systems to a minimum. The Combi module is a mounting plate of 4 or 8 modules (PLE). The lower part is snapped directly onto the smissline socket. The upper part is supported by a snap fastening on an additional DIN profile rail. The rail separation is fully variable between 125 and 150 mm. The power supply is taken directly from the busbars at the back of the Combi module by means of an adapter plate, rated current 32 A, and fed by stranded wires to the input terminal of the unit. Auxiliary and signal contacts can also be contacted on the auxiliary rails LA and LB.
40158
Two versions of Combi modules are available. If more space is required, two modules can be permanently connected side by side (Combi module Duo).
40287
42
20165/C
40285
Combi-module
Order data
Order data Combi module single containing: Combi module DIN-profile 60 mm Module Packaging unit
ZLS802
40158
ZLS805
40159
Adapter plate for contacts with busbars with plug contacts 3L 3L+N (20A reduced) L1, N (In max. 20A) L2, N (In max. 20A) L3, N (In max. 20A) L1 (In max. 32A, L1 reversible to L2, L3) 3L+N
40160
10 10 10 10 10 10 10
40165
Fixierung The fastener is required to attach the units to the combi-module. for MCBs ZLS517 Bag of 10 Stop-piece for 1-pole LP ZLS516 for MS or MCB Bag of 10 ZLS518
1 1 1
Auxiliary switch and signal contact, connection support Contact pin, long for use with Combi module ZLS520
40152
10
40166
Rafix for LP This is required when fitting a miniature circuit-breaker smissline on to DIN rail. Bag of 10 ZLS923
43
20165/C
Sockets
Accessories
Socket bases
The smissline-S socket system brings a completely new mounting and connection technique to distribution construction. Besides the classical method of snapping units onto a 35 mm Din rail, this new family of devices can be snapped directly onto socket bases containing busbars. This eliminates the time consuming process of making cable or bolted connections to the power supply. In addition, in the event of rearrangement or expansion, the replacement of devices in existing systems is made significantly easier. The socket sections and the wide range of accessories make it possible to plan with the capability for expansion and to construct distribution systems of any desired size in a short period of time. The 6- or 8-module sockets are installed either by screwing them onto any flat surface or by snapping them onto a 35 mm DIN rail. Lateral movement or detachment of the sockets again is possible before final fixing. To determine the required socket length the space required for q the required components q the feeder block and q spare positions must be determined. (table pages 55 and 56) Snap mounting Pull down the slide with a screwdriver until it latches (socket can be moved) Press on front: Fixed position (Sockets fixed)
40414
40771
Major features
q q q q q
Expansion to any desired length (even number of poles) Integral busbars Simple exchange of units Long-term planning and problem-free extension possible Significant time savings for mounting and connection
Technical data
Sockets Rated voltage Un: Rated current In: Busbars: Auxiliary busbars: Socket length (modules) 6-module socket length 108 mm: 8-module socket length 144 mm: Fastening:
40772
690 V~
100 A 40 A
6 8 Snapped onto 35-mm mounting rails and screw fixing Free of halogens and cadmium
Plastic components:
Order data
Order data Socket base (Socket selection table see pages 55 and 56) - 8-module socket length 144 mm - 6-module socket length 108 mm Module Packaging unit
8 6
10 10
44
20165/C
Sockets
Accessories
Socket end-piece
To prevent displacement of sockets and busbars (particularly when installed vertically) end-pieces can be fitted at the start and finish of each row of sockets. These simultaneously ensure electrically protected covering of the busbar end faces and mechanical fixing of the sockets on the mounting rail.
Order data Socket end-piece for lateral, electrically-protected closure and mech. fixing of a row of sockets on the supporting rail. Width: 20 mm
40919
Module
ZLS730
Intermediate piece
The light-grey intermediate piece matches the unit profile and fills empty module spaces. The busbars are safely covered, so that they cannot be touched and at the same time the corresponding holes in the cover is filled up.
Order data Intermediate piece light-grey for electrically-protected filling of spare socket position, 18 mm Bag of 5 ZLS722 Module 1 Packaging unit 1
40182
Busbar insulator
The dark grey busbar insulator electrically isolates the interrupted busbar ends from each other, (e.g. in the case of several residual-current circuit-breaker groups) and simultaneously identifies the isolation point. It conforms with the unit profile and its space requirement is 1 module.
Order data Busbar insulator dark grey, for isolation and spacing of the busbar interruption at the isolation point, 18 mm ZLS239 Module 1 Packaging unit 10
40180
Busbar cover
If component modules or spare modules are not required, the busbar cover ensures electrically-protected covering of the main and auxiliary busbars. The cover (4 modules) can be divided anywhere. The openings allow voltage measurements on the busbars without removing cover.
Order data Busbar cover electrically-protected covering of busbars, 4-module, can be divided. Suitable to accept extension adapter ZLS101 4 x 18 mm Bag of 5
40170
Module 1
Packaging unit 1
ZLS100
Extension adapter
The extension adapter, single or several side by side, can be plugged into the busbar cover via the built-in holding device. This enables conventional DIN devices with 45 mm cap size to be snapped onto the smissline socket. By plugging in several extension adapters one on top of the other, heights can be equalized in multiples of 7 mm.
Order data Extension adapter 18 mm wide, for plugging into busbar cover ZLS100. For fixing REG units
40183
Module 1
Packaging unit 10
ZLS101
Module 1
Packaging unit 10
Mounting rail adapter Height equalization 22.5 mm, for equalizing insertion depth of mounting rail devices alongside smissline units
ZLS741
45
20165/C
Starter pack
Accessories
Order data
Solutions available: Starter pack with 22 modules Starter pack with 22 modules Starter pack with 24 modules Starter pack with 24 modules Starter pack with 30 modules Starter pack with 30 modules Starter pack with 32 modules Starter pack with 32 modules Starter pack with 38 modules Starter pack with 38 modules Starter pack with 40 modules Starter pack with 40 modules Starter pack with 48 modules Starter pack with 48 modules Starter pack with 64 modules Starter pack with 64 modules Starter pack with 80 modules Starter pack with 80 modules 393 mm 393 mm 429 mm 429 mm 537 mm 537 mm 573 mm 573 mm 681 mm 681 mm 717 mm 717 mm 861 mm 861 mm 1150 mm 1150 mm 1438 mm 1438 mm 3P 3P+N 3P 3P+N 3P 3P+N 3P 3P+N 3P 3P+N 3P 3P+N 3P 3P+N 3P 3P+N 3P 3P+N Order data ZLS760 ZLS761 ZLS750 ZLS751 ZLS762 ZLS763 ZLS752 ZLS753 ZLS764 ZLS765 ZLS754 ZLS755 ZLS756 ZLS757 ZLS766 ZLS767 ZLS758 ZLS759 Module Packaging unit 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
40277
40174
ZLS200
110
10
40175
ZLS202
110
10
46
20165/C
General
The incoming terminal component for non smissline devices has an installation width of one module of (18 mm). This adapter can be combined to multiple pole versions to meet specific needs (L1, L2, L3, N, dummy). The connecting wires can carry a maximum of 63A (In).
Order data
Module
Packaging unit
Single Adapter 32A bottom feed Adapter 32A L1 bottom feed Adapter 32A L2 bottom feed Adapter 32A L3 bottom feed Adapter 32A N bottom feed Adapter dummy element Single Adapter 32A top feed Adapter 32A L1 top feed Adapter 32A L2 top feed Adapter 32A L3 top feed Adapter 32A N top feed Combination 32A bottom feed Adapter 32A L1, N bottom feed Adapter 32A L2, N bottom feed Adapter 32A L3, N bottom feed Adapter 32A L1, L2, L3 bottom feed Adapter 32A L1, L2, L3, N bottom feed Single Adapter 63A bottom feed Adapter 63A L1 bottom feed Adapter 63A L2 bottom feed Adapter 63A L3 bottom feed Adapter 63A N bottom feed Adapter dummy element Single Adapter 63A top feed Adapter 63A L1 top feed Adapter 63A L2 top feed Adapter 63A L3 top feed Adapter 63A N top feed Combination 63A bottom feed Adapter 63A L1, N bottom feed Adapter 63A L2, N bottom feed Adapter 63A L3, N bottom feed Adapter 63A L1, L2, L3 bottom feed Adapter 63A L1, L2, L3, N bottom feed
40915
1 1 1 1 1
1 1 1 1 1
1 1 1 1
1 1 1 1
40941
1 1 1 1 1
1 1 1 1 1
40918
1 1 1 1 1
1 1 1 1 1
1 1 1 1
1 1 1 1
1 1 1 1 1 1
1 1 1 1 1 1
Combination set for multiple pole adapter (Packets with 100 pieces for 50 adapters)
40920
47
20165/C
Adapter
Accessories
General
The adapter is designed for a rated current of 100A and is a plug-in module used to supply power directly to the smissline system. The adapter can accommodate an ABB OT-M load switch with a rated current of 80A or 100A. Power supply to the smissline system is therefore possible via a load switch. The construction height of the adapter is 13 mm, which means that devices on the adapter have a 13-mm higher shoulder than smissline devices plugged-in directly.
Major features
q q q
40925
Plug-in adapter solution for rated currents up to 100A Power supply to smissline-S system via ABB load switch OT-M Same construction height as 32A and 63A adapters for smissline-S
Technical data
Rated voltage Un: Rated short-time current withstand capability Icw: Rated current In: Space required (module): Rated insulation voltage Ui: Rated withstand voltage strength Uimp: Ambient temperature: 400/690 V 6kA 100A 4 (72 mm) 2500 V 8000 V 30 C
Oder data
40926
Type Adapter with 3 connector leads (L1, L2, L3) Adapter with 4 connector leads (L1, L2, L3, N)
Modules 4
Packaging unit 1
ZLS241
40981
Order data
Type Number of poles le Th 400V A 80 100 80 100 Rated current AC22/400V A 80 100 80 100 Rated current AC23/400V A 45 55 45 55 Connection mm2
3 3 4 4
48
20165/C
40982
General
This incoming terminal block is used to connect cables dirctly to the busbars. The base-plate can be fitted with a maximum of 4 main terminals L1, L2, L3 and N for the busbars, and 2 auxiliary terminals LA and LB for the auxiliary busbars. The terminals act directly on the busbars and therefore fix the incoming terminal block. Removable terminal tops permit the connection of continuous conductors (risers) while horizontal or vertical cable entry is also possible. The cover can be labelled. Instead of the incoming terminal block, the power supply can also be made via a unit (e.g. residual current circuit-breaker, miniature circuit-breaker or load switch). Power supply left or right max. 100A.
40269
Power supply center max. 160A. But on each side max. 100A.
40271
Major features
q q q q
Horizontal or vertical connection Connection of continuous conductors possible Labelled cover Power supply also possible via a unit
Technical data
Incoming terminal block Rated voltage Un: Rated current In: Main terminals: Auxiliary terminals: Space required (modules): Main terminals Cu: 400/690 V~
40426
40424
49
20165/C
40425
General
The incoming terminal component is used to connect the feeder cable to the busbars. The incoming terminal component with an installation width of 36 mm is available as a single-pole component for line terminals L1, L2 and L3, as well as for the neutral disconnector. The terminals act directly on the busbars and thus fix the incoming terminal component. The incoming terminal component L1, L2, L3 and N can be combined to meet specific needs. The incoming terminal component can accommodate a maximum cable cross-section of 95 mm2 or 2 x 35 mm2. The cover can be labeled. Instead of the feeder component, the power can also be supplied via a unit (e.g. residual-current circuitbreaker, miniature circuit-breaker or load switch).
40808
Power supply center max. 200A. But on each side not more than 100A.
40903
40904
Important features
q q q
Modular solution, individual configuration The maximum connection cross-section per component is 95 mm2 or 2 x 35 mm2 Full electrical protection
Technical data
Sockets Rated voltage Un: Rated current In: Space required (modules) per component: Terminals: 400/690 V~ 200A 2 Flexible 95 mm2, 2 x 35 mm2 (200A) Free of halogens and cadmium
Plastic components:
50
20165/C
40847
Order data
Order data Standard incoming terminal block complete with main terminals, construction height 50 mm 3LN 3L Module Packaging unit
ZLS224 ZLS225
4 4
1 1
40269
Incoming terminal block, low complete with main terminals, construction height 36 mm 3LN 3L
ZLS228 ZLS229
4 4
1 1
Additional section for standard incoming terminal block Auxiliary terminals max. 2 10 mm2 (for auxiliary busbars LA, LB) N-terminal for feeder block
40178
ZLS233 ZLS212
Order data
Order data unit - Feeder component - Feeder component, line terminal L1 - Feeder component, line terminal L2 - Feeder component, line terminal L3 - Feeder component, neutral disconnector N - Feeder component, neutral disconnector N, Additional socket - Feeder component PE, Additional socket
40808
Module
Packaging unit
2 2 2 2 2 2
1 1 1 1 1 1
40904
40903
51
20165/C
Additional socket
Accessories
Additional socket
An additional socket base can easily be fitted into the system to accommodate the external N and/or PE busbars. This enables neutral connections to be made where single pole miniature circuit-breakers are used and their neutral conductors are unswitched. Neutral terminals are clipped onto the additional socket and can be used as detachable neutral links. Only one N busbar and/or one PE busbar can be fitted. Each socket can be fitted with an additional socket. Because of the integral snap fastening for 35 mm Din rails, the external N or PE busbars can be fitted anywhere on the distribution panel or even separately from the system. Additional sockets can be covered to prevent accidental contact with live parts.
Order data Additional socket base for external N- and PE-busbars 8-module additional socket (suitable for 8-module sockets) 6-module additional socket (suitable for 6-module sockets) Module Packaging unit
40452
ZLS811 ZLS810
8 6
10 10
N and PE terminals
Corresponding N terminals (light blue) or PE terminals (yellow-green) are available for the power supply and the outgoing conductors of the external N and PE busbars for cross-sections up to 10 mm2 and from 16 mm2 to 50 mm2. The terminals are fitted with label holders which can be used with the marking adapter or the self-adhesive marking label (Phoenix Contact Typ SBS).
Order data N-terminal for additional socket light blue, for external rail up to 10 mm2 up to 50 mm2 PE-terminal for additional socket yellow-green, for external rail up to 10 mm2 up to 50 mm2
40432 40434
Module
Packaging unit
ZLS812 ZLS813
10 10
ZLS815 ZLS816
10 10
40431
40433
Insulator block
The dark grey insulator block isolates the interrupted busbar ends and simultaneously marks the disconnection point externally.
Order data Insulator block for additional socket dark grey, for isolation and spacing of external busbars Module Packaging unit
ZLS831
0.5
10
40429
Dummy block
The light grey dummy block fills blank terminal positions. The busbars are simultaneously protected against contact.
Order data Dummy block for additional socket light grey, fills empty terminal positions Module Packaging unit
52
20165/C
40430
ZLS830
0.5
10
Additional socket
Accessories
Module
Packaging unit
ZLS832
10
A cable duct cover can also be used to cover longer sections. (Tehalit duct no. SL 18050/2)
Order data Duct cover for additional socket Duct for covering, length 144 mm Module Packaging unit
ZLS833
10
Marking adapter for all smissline units for 5 plug-in characters (made by Woertz) Bag of 100 ZLS823
ZLS825
Cover transparent, for designation of all smissline units and sockets Bag of 100
ZLS820
40185
ZLS821
ZLS800
10
53
20165/C
US
Approbation:
Socket ZLS 808, 806 Busbar ZLS 200 End-piece ZLS 730 Incoming terminal block ZLS 224, 225 Incoming terminal element ZLS 250-253 Busbar isolator ZLS 239 Busbar cover ZLS 100 Extensiv adapter ZLS 101 Adapter from page 47
40908
Technical data C
Rated voltage: Rated current (end feed): Rated current (center feed): Short circuit rating:
US
Incoming terminal block, standard: Maximum rated voltage: Maximum rated current: Main terminal: Incoming terminal element: Maximum rated voltage: Maximum rated current: Main terminal: Adapter 30A: Rated voltage: Rated current: Short circuit rating: Adapter 60A: Rated voltage: Rated current: Short circuit rating:
54
20165/C
Power supplies
Accessories
Power supply to busbars via a residual current circuit-breaker (or load switch IS463) Top series:
The power supply in this case is connected to the opposite end of a residual current circuit breaker to which its plug-in contacts are connected. When using this type of feed, the busbars and therefore all subsequent units have residual-current protection. If several residual current circuit-breaker groups are present, the busbars must be separated with the dark grey busbar insulator. Attention must then be paid to the regulations governing protection of the residual-current circuit-breaker by subsequent miniature circuitbreakers. The supply can also be fed in through the 4 pole 63 A load switch.
40428
units
The power supply can also be made via a unit instead of the feeder block. Power supply direct to busbars using miniature or residual current circuit-breaker terminals Parallel below: In this case the power supply cable is connected to the same end of the breaker to which its plug-in contacts are connected. It should be ensured that the operating current of all subsequently connected loads does not exceed the rated current of the plug contacts (32A for breakers up to and including 32A, 63A for breakers above 32A and up to 63A). For best possible use of the plug contacts rated current it is best to connect the power supply cable to the unit with the highest rated current. A feeder block should be used for higher operating currents.
40844
20165/C
40777
55
40424
Accessories
Order data
6 8 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59
1 1 2 1 2 3 1 2 3 4 2 3 4 5 3 4 5 6 4 5 6 7 5
1 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3
60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109
6 7 8 6 7 8 9 7 8 9 10 8 9 10 11 9 10 11 12 10 11 12 13 11 12
2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2
Planning for the incorporation of feeder block and spare places should be taken into account The total lengths given above were determined taking account of socket spacings and tolerances. They are not therefore necessarily a multiple of 18 mm (1 position unit).
56
20165/C
35
45 45
90
[Link]
18
36
54
5.5
Neutral disconnector
100
35
45
35
55
45 45
[Link]
90
18 21
5.5
72
5.5
3LN (FISG)
35
45
90
35
45
45
54
5.5
35
[Link]
36
5.5
50.5
95.5
45
[Link]
9 9
72
5.5
[Link]
45
90
[Link]
57
20165/C
35
45
66.5 84.5 90
72
35
45
45
90
5.5 9 9
[Link]
[Link]
5.5
45
90
35
90
45
45
90
7.5
[Link]
5.5 9 9
66.5 84.5
5.5 99
66.5 84.5
Adapter 100A
72 5.5 17 13 50.5
45
90
13
90
86.7
43 57 64 11
[Link]
17.75
58
20165/C
35
[Link]
sockets ZLS808
Sockets 8 modules Sockets 6 modules
sockets ZLS806
4.5
47.5
53.5
4.5
114
47.5
90
35
48.8 61
[Link]
7.3 60 144
3.5
5.4
17 28.6
7.3 60 108
3.5
5.4
133
83
47
[Link]
35
45
86
43
[Link]
35
18
5.5
66.5 84.5
18
5.5
66.5 84.5
[Link]
[Link]
59
20165/C
power supply
Feeder blocks
133
83
47
86
72
49.5
35.5
[Link]
49.5
35
221.5
125...150
168
240
35
43.5
35
42.5
61
[Link]
87
7.5
72
5.5
21.5
35
35
[Link]
18
60
20165/C
[Link]
[Link]
10 Incoming terminal block, Standard 100A left or right on the system 160A on Center Power supply of the system maximum 50 mm2 11 Incoming terminal oversize, Standard 200A on Center Power supply of the system maximum 95 mm2 12 Busbar isolator for isolate the interrupted busbars from each other 13 DIN Rail for cover for using on the busbar cover 14 Adapter for 32A, 63A and 100A single or Combination bottom or top feed
ABB Control Limited Grovelands House Longford Road Exhall, Coventry, CV7 9 ND United Kingdom Phone 01203 368 500 Fax 01203 368 401 ABB AS Automation Technology Products Division P.O. Box 797 Brakeroya NO-3002 Drammen Norway Tlf: 32 85 80 00 Fax: 32 85 80 10 E-Mail: komponent@[Link]. [Link] [Link]