Symaro
Immersion Temperature Sensors
Use
QAE21...
Passive sensors for acquiring the water temperature in pipes and tanks.
The QAE21 immersion temperature sensors are for use in ventilation and air conditioning plants for: Controlling or limiting the flow temperature Limiting the return temperature Controlling the DHW temperature Type summary Type reference QAE2110.010 QAE2110.015 QAE2120.010 QAE2120.015 QAE2121.010 QAE2122.013 QAE2140.010
1) 4)
Outfit Including protection pocket with threaded nipple G A Including protection pocket with threaded nipple G A Including protection pocket with threaded nipple G A Including protection pocket with threaded nipple G A With clamp for protection pocket 1) Including compression fitting with threaded nipple G A Including protection pocket with threaded nipple G A
Immersion length 100 mm 150 mm 100 mm 150 mm 100 mm max. 130 mm 2) 100 mm
Nominal pressure PN 10 PN 10 PN 10 PN 10 PN 4) PN 16 PN 10
Sensing element Pt 100 Pt 100
Degree of protection IP 54 IP 54
LG-Ni 1000 IP 42 (IP 54) 3) LG-Ni 1000 IP 42 (IP 54) 3) LG-Ni 1000 IP 42 (IP 54) 3) LG-Ni 1000 IP 42 (IP 54) 3) T1 IP 42 (IP 54) 3)
Protection pocket required 2) Adjustable immersion length Depending on the type of protection pocket used
3) IP 54 with cable entry gland M16 (not included as standard)
CE1N1781en 27.04.2004
Siemens Building Technologies HVAC Products
Ordering When ordering, please give name and type reference, e.g. : Immersion temperature sensor QAE2120.010 or protection pocket ALT-SS100 Equipment combinations All systems or devices capable of acquiring and handling the sensor's passive Pt 100, LG-Ni 1000 or T1 output signal. Function The sensor acquires the medium temperature via its sensing element whose resistance value changes as a function of the temperature. The signal is delivered for further handling by a suitable controller. Sensing elements LG-Ni 1000
R []
1781D01
Characteristic
[K]
Accuracy
1600
1.0
1400
0.5
1200
0.0
1000
0.5
800
1.0
600 40 30 20 10
10
20 30 40 50 60 70 80 90 100 110 120 130 [C]
1.5 40 30 20 10
10
20 30 40 50 60 70 80 90 100 110 120 130
Pt 100 (class B)
R []
Characteristic
[K]
0.8 0.4 0.0 0.4 0.8
Accuracy
140
120
100
80 40 30 20 10
10
20 30 40 50 60 70 80 90 100 110 120 130
[C]
40 30 20 10
10 20 30 40 50 60 70 80 90 100 110 120 130
2/6 Siemens Building Technologies HVAC Products Immersion temperature sensors QAE21... CE1N1781en 27.04.2004
1781D04
160
1781D03
1781D02
1800
1.5
[C]
[C]
T1 (PTC)
R []
3600 3400 3200 3000 2800 2600 2400 2200 2000 1800 30 20 10 0 10
Characteristic
1781D05
Accuracy
[K]
4.0 3.0 2.0 1.0 0.0 1.0 2.0 3.0 4.0
1781D06
5.0
20 30 40 50 60 70 80 90 100 110 120 130
[C]
5.0 30 20 10
10 20 30 40 50 60 70 80 90 100 110 120 130
[C]
Legend
Resistance value in Ohm Temperature in degrees Celsius Temperature differential in Kelvin
Mechanical design The immersion temperature sensors consist of the following components: Two-sectional plastic housing comprised of base with connection terminals and removable cover (snap-on design) Immersion rod complete with sensing element The connection terminals can be accessed after removing the cover. With the QAE2110.010 and QAE2110.015, cable entry is made via a cable entry gland M16. With the other types of sensors, cable entry is via a grommet which, if required, can be replaced by a cable entry gland M16 (IP 54). Accessories (not included in standard delivery) Name Protection pocket Protection pocket Protection pocket Protection pocket Material V4A (1.4571) V4A (1.4571) V4A (1.4571) V4A (1.4571) Nominal pressure PN16 PN16 PN40 PN40 Type of sealing Threaded with sealing means Threaded with sealing means With flange for flat seal With flange for flat seal Immersion length 100 mm 150 mm 100 mm 150 mm Type reference ALT-SS100 ALT-SS150 ALT-SSF100 ALT-SSF150
For other protection pocket accessories, refer to Data Sheet N1194.
3/6 Siemens Building Technologies HVAC Products Immersion temperature sensors QAE21... CE1N1781en 27.04.2004
Engineering notes If the nominal pressure exceeds PN10 or the medium temperature exceeds 130 C, a protection pocket made of stainless steel (V4A) is required. Mounting and installation notes Depending on use, the sensor should be located as follows: For flow temperature control: In the heating flow: Directly after the pump if the pump is located in the flow 1.5 to 2 m after the mixing valve if the pump is located in the return For return temperature limitation: In the return at a location where the temperature can be correctly acquired The sensor should be installed in an elbow such that the immersion rod or the protection pocket faces the direction of flow. The water must be well mixed where the temperature is acquired. This is downstream from the pump or, if the pump is mounted in the return, at least 1.5 m after the mixing point. The sensor should be mounted such that the cable does not enter from the top. With all types of sensors, the immersion length must be a minimum of 60 mm! The sensor must not be covered by lagging. To fit the sensor, a threaded fitting or T-piece G must be welded into the pipe. Mounting
min. 60 mm
Note!
For sensors with non-sealing threaded nipples G , sealing means must be used with the threaded connection (e.g. hemp, Teflon tape or similar) Tighten compression fitting of the QAE2122.0130 on the sensor's immersion rod When tightening for the first time: Turn the nut about 1 turns until strong resistance is felt. Then, slightly loosen the nut again and retighten turn For premounted compression fittings or repeated fitting: Screw the nut on until finger-tight. Then, tighten with a spanner turn for the final fit Mounting Instructions are printed on the packaging.
4/6 Siemens Building Technologies HVAC Products Immersion temperature sensors QAE21... CE1N1781en 27.04.2004
1781Z01
1781Z02
Technical data Functional data Measuring range Sensing element Time constant With protection pocket Without protection pocket Measuring accuracy Immersion length Nominal pressure Protective data Electrical connections Degree of protection of housing Safety class Screw terminals for Cable entry via Grommet Cable entry gland Perm. cable lengths Environmental conditions Operation Climatic condition Temperature (housing) Humidity (housing) Transport Climatic condition Temperature Humidity Mechanical environmental conditions Materials and colors Base Cover Immersion rod Protection pocket Compression fitting Cable entry gland M 16 x 1.5 Packaging Weight Incl. packaging QAE2110.010 QAE2110.015 QAE2120.010 QAE2120.015 QAE2121.010 QAE2122.013 QAE2140.010 30...+ 130 C refer to "Type summary" approx. 30 s approx. 8 s refer to "Function" refer to "Type summary" refer to "Type summary" refer to "Type summary" III to EN 60 730 1 x 2.5 mm2 or x 1.5 mm2 for 5.5...7.2 mm dia. cable M 16 x 1.5 refer to Data Sheet of controller to IEC 721-3-3 class 3K5 40...+ 70 C 5...95 % r.h. to EC 721-3-2 class 2K3 25...+ 70 C < 95 % r.h. class 2M2 polycarbonate, RAL 7001 (silver-grey) polycarbonate, RAL 7035 (light-grey) stainless steel to DIN 17 440, steel 1.4571 brass (CuZn37) stainless steel 1.4404, 1.4435, 1.4571 PA, RAL 7035 (light-grey) corrugated cardboard approx. 0.21 kg approx. 0.23 kg approx. 0.21 kg approx. 0.23 kg approx. 0.13 kg approx. 0.19 kg approx. 0.21 kg
5/6 Siemens Building Technologies HVAC Products Immersion temperature sensors QAE21... CE1N1781en 27.04.2004
Internal diagram
1781G01
The internal diagram is identical for all types of immersion temperature sensors covered by this Data Sheet. The connecting wires are interchangeable.
Dimensions (in mm) QAE2110.010 QAE2110.015 QAE2120.010 QAE2120.015 QAE2140.010
SW 22 G A
45,5
80
Typ QAE2110.010 QAE2110.015 QAE2120.010 QAE2120.015 QAE2140.010
L 100 mm 150 mm 100 mm 150 mm 100 mm (IP 54)
6,5
QAE2121.010
31,5
110
80
SW 14 SW 22
QAE2122.013
max. 130 6,5
G A
31 31,5 40
14
5,5 ... 7,2 80
1781M03
6/6 Siemens Building Technologies HVAC Products
2004 Siemens Building Technologies AG Immersion temperature sensors QAE21... CE1N1781en 27.04.2004
60
1781M02
31
5,5 ... 7,2
60
28
M16 x 1,5
1781M03
31
13
5,5 ... 7,2
60