0% found this document useful (0 votes)
2K views50 pages

Pirelli

ENERGY CABLES INDEX LOW VOLTAGE CABLES copper and ALUMINIUM CONTROL CABLES 6-35 kV OVERHEAD CONDUCTORS MEDIUMVOLTAGE (LV) CONSTRUCTION solid or stranded and compacted copper conductor, PVC insulation, black PVC jacket APPLICATION : For use inside, in cable trench or duct. In power stations, industrial plants and in switchgears

Uploaded by

mihailos
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Topics covered

  • Cable Diameter,
  • Cable Flexibility,
  • Flexible Cables,
  • Cable Standards,
  • Low Smoke Zero Halogen,
  • XLPE Insulation,
  • PVC Sheath,
  • Cable Manufacturing,
  • Cable Weight,
  • Technical Data
0% found this document useful (0 votes)
2K views50 pages

Pirelli

ENERGY CABLES INDEX LOW VOLTAGE CABLES copper and ALUMINIUM CONTROL CABLES 6-35 kV OVERHEAD CONDUCTORS MEDIUMVOLTAGE (LV) CONSTRUCTION solid or stranded and compacted copper conductor, PVC insulation, black PVC jacket APPLICATION : For use inside, in cable trench or duct. In power stations, industrial plants and in switchgears

Uploaded by

mihailos
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Topics covered

  • Cable Diameter,
  • Cable Flexibility,
  • Flexible Cables,
  • Cable Standards,
  • Low Smoke Zero Halogen,
  • XLPE Insulation,
  • PVC Sheath,
  • Cable Manufacturing,
  • Cable Weight,
  • Technical Data

LOW VOLTAGE AND MEDIUM VOLTAGE ENERGY CABLES

INDEX

1
LOW VOLTAGE CABLES COPPER AND ALUMINIUM PAG. 2-7
NIZKOVOLÊTNYE KABEL S MEDNYM I ALÎMINIEVYM
PROVODNIKOM CTP. 2-7

2 LOW VOLTAGE CONTROL CABLES


NIZKOVOLÊTNYE KONTROLÊNYE KABELI
PAG. 8-10
CTP. 8-10

3 LOW VOLTAGE FLEXIBLE CABLES


NIZKOVOLÊTNYE GIBKIE KABELI
PAG. 11-23
CTP. 11-23

4
LOW VOLTAGE LSOH AND RUBBER CABLES PAG. 24-32
NIZKOVOLÊTNYE KABELI V BEZGALOGENOVOJ IZOLÅCII S NIZKIM
DYMOVYDELENIEM I KABELI V REZINOVOJ IZOLÅCII CTP. 24-32

5 MEDIUM VOLTAGE CABLES 6-35 kV


KABELI NA NAPRłENIE 6-35 kV
PAG. 33-45
CTP. 33-45

6 OVERHEAD CONDUCTORS
PODVESNYE PROVODA
PAG. 46-48
CTP. 46-48

1
LOW VOLTAGE (LV) S I N G L E C O R E P V C I N S U L AT E D
CABLE WITH COPPER CONDUCTOR
ODNO‚ILÊNYJ KABELÊ V PVH
0,6/1 kV IZOLÅCII, MEDNYJ PROVODNIK
0,6/1 kB

NYY-J / NYY-O
DIN VDE 0276 / SOGLASNO DIN VDE 0276
CONSTRUCTION
solid or stranded and compacted copper conductor, PVC insulation, black PVC jacket

SAMPLE FOR MARKING :


NYY-O 1x95 RM 0,6/1 kV DIN VDE 0276

APPLICATION :
For use inside, in cable trench or duct. In power stations, industrial plants and in switchgears if mechani-
cal protection is not required, or in applications where the cable is not exposed to mechanical damages.

STROENIE KABELÅ
Mednaå Ÿila odno/mnogoprovoloxnaå, PVH izolåciå Ÿil, PVH vneqiåå oboloxka xernogo cveta

PRIMER OBOZNAXENIÅ :
NYY-O 1x95 RM 0,6/1 kB DIN VDE 0276

PRIMENENIE :
Vnutri pomewenij, v trybah i tranqeåh. Dlå ispol∫zovaniå v ™lektrostanciåh, promyqlennyh
sooruŸeniåh, nepodviŸnyh ustanovkah, tam, gde kabel∫ ne podvergaetså mehanixeskim povreŸ-
deniåm.

TECHNICAL DATA / TEHNIXESKIE HARAKTERISTIKI


No. of Ins. Thickness Outer Cu Weight Current load
cores & nom. Wallthickness of sheath diameter number In ground In the air
cross-sect. Min. Max.
(mm2) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

Kol-vo Tolwina Tolwina Vneqnij Ves Obwij Dopustimaå tokovaå nagruzka


Ÿil i izolåcii oboloxki diametr medi ves V zemle Na vozduhe
sexenie Min. Maks.
(mm2) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

10 RE 1,0 1,8 10 12* 96 180 83 64


16 RM 1,0 1,8 11 13* 154 250 107 84
25 RM 1,2 1,8 12 15* 240 365 138 114
35 RM 1,2 1,8 13 16* 336 495 164 139
50 RM 1,4 1,8 15 18* 480 645 195 169
70 RM 1,4 1,8 16 19* 672 855 238 213
95 RM 1,6 1,8 18 21* 912 1155 286 264
120 RM 1,6 1,8 20 23* 1152 1395 325 307
150 RM 1,8 1,8 22 26* 1440 1690 365 352
185 RM 2,0 1,8 24 28* 1776 2070 413 406
240 RM 2,2 1,8 27 31* 2304 2660 479 483
300 RM 2,4 1,9 29 33* 2880 3300 541 557
400 RM 2,6 2,0 33 38* 3840 4165 614 646
500 RM 2,8 2,1 37 42* 4800 5285 693 747
630 RM 2,8 2,2 – 44* 6048 6845 777 858
800 RM 2,8 2,3 – 48* 7680 8610 859 971
1000 RM 3,0 2,5 – 53* 9600 10715 936 1018
Remark: Informative data / Informative data

2
S H E AT E D C A B L E S F O R F I X E D W I R I N G LOW VOLTAGE (LV)

KABELI DLÅ STACIONARNOGO MONTA‚A


0,6/1 kV
0,6/1 kB

NYM-J / NYM-O
DIN VDE 0250 / SOGLASNO DIN VDE 0250
CONSTRUCTION
Up to 10 mm2 solid, from 16 to 35 mm2 stranded copper conductor, PVC insulation, extruded inner covering, PVC outer sheath
SAMPLE FOR MARKING :
NYM-J 1x1,5 mm2 / NYM-O 1x1,5 mm2
APPLICATION :
In power installations, for fixed wiring.
TECHNICAL PARAMETERS :
Rated voltage: U0 /U =300/500 V
Admissible temperature of conductor during operation max. 70 °C.
Permissible temperature limits on the outer surface of the cable
a. during storage, transportation and in operation, fixed wired: from – 40 °C to + 70 °C
b. during installation: from + 5 °C to + 70 °C (acc. to DIN VDE 0298-3)
Colouring of cores according to DIN VDE 0293:
for single core cables green-yellow or black
for two-core cables black - light blue
for three-core cables “J” green-yellow - black - light blue
for three-core cables “O” black - light blue - brown
for four-core cables “J” green-yellow - black - light blue - brown
for four-core cables “O” black - light blue - brown - black
for five-core cables “J” green-yellow - black - light blue - brown - black
for five-core cables “O” black - light blue - brown - black - black
for seven-core cables “J” one core green-yellow, the others black and numbered
for seven-core cables “O” each core is black and numbered

STROENIE KABELÅ
Do 10 mm2 odnoŸil∫yj, s 16 do 35 mm2 vkl¥xitel∫no – mnogorpovoloxnyj mednyj provodnik. / PVH izolåciå Ÿil,
™kstrudirovannoe zapolnenie, PVH vneqnåå oboloxka
PRIMER OBOZNAXENIÅ :
NYM-J 1x1,5 mm2 / NYM-O 1x1,5 mm2
PRIMENENIE :
V silovyh ustanovkah, dlå stacionarnogo montaŸa.
TEHNIXESKIE HARAKTERISTIKI :
Nominal∫noe napråŸenie: U0/U =300/500 V
Dopustimaå temperatura provodnika maks. 70 °S.
Dopustimaå temperatura okruŸa¥wej sredy:
a. Pri hranenii, transportirovke i stacionarnom montaŸe: ot – 40 °C do + 70 °C
v. Pri montaŸe: ot + 5 °C do + 70 °C (sogl. DIN VDE 0298-3)
Cveta Ÿil v sootvetstvii s DIN VDE 0293:
Dlå odnoŸil∫nyh kabelej – Ÿelto-zelenaå ili xernaå
Dlå dvuhŸil∫nyh: xernaå, golubaå
Dlå trehŸil∫nyh tipa “J”: Ÿelto-zelenaå, xernaå, golubaå
Dlå trehŸil∫nyh tipa “O”: xernaå, golubaå, korixnevaå
Dlå xetyrehŸil∫nyh tipa “J”: Ÿelto-zelenaå, xernaå, golubaå, korixnevaå
Dlå xetyrehŸil∫nyh tipa “O”: xernaå, golubaå, korixnevaå, xernaå
Dlå påtiŸil∫nyh tipa “J”: Ÿelto-zelenaå, xernaå, golubaå, korixnevaå, xernaå
Dlå påtiŸil∫nyh tipa “O”: xernaå, golubaå, korixnevaå, xernaå, xernaå
Dlå semiŸil∫nyh tipa “J”: Ÿelto-zelenaå, ostal∫nye xernye, markirovany ciframi
Dlå semiŸil∫nyh tipa “O”: xernye, markirovany ciframi

3
LOW VOLTAGE (LV) S H E AT E D C A B L E S F O R F I X E D W I R I N G
KABELI DLÅ STACIONARNOGO MONTA‚A
0,6/1 kV
0,6/1 kB

NYM-J / NYM-O
Type No. of cores Cu Max. average outer Weight
& nom. cross-sect number diameter
(mm2) (kg/km) (mm) (kg/km)

Tip Kol-vo Ÿil Ves medi Maks. vneqnij Obwij ves


i sexenie diametr
(mm2) (kg/km) (mm) (kg/km)

NYM-J, NYM-O
1 x 1,5 14,4 6,2 47
1 x 2,5 24 6,8 62
1x4 38,4 7,6 84
1x6 58 8,2 107
1 x 10 96 9,4 159
1 x 16 154 11,0 236
NYM-O
2 x 1,5 29 9,8 126
2 x 2,5 48 11,0 170
2x4 77 12,5 231
2x6 115 13,5 291
2 x 10 192 17,0 464
2 x 16 307 20,0 689
2 x 25 480 24,0 1 020
2 x 35 672 27,5 1 370
NYM-J, NYM-O
3 x 1,5 43 10,5 146
3 x 2,5 72 11,5 201
3x4 115 13,0 276
3x6 173 15,0 367
3 x 10 288 18,0 570
3 x 16 461 22,0 873
3 x 25 720 26,0 1 290
3 x 35 1 008 29,5 1 700
4 x 1,5 58 11,0 172
4 x 2,5 96 12,5 241
4x4 154 14,5 344
4x6 230 16,5 460
4 x 10 384 19,5 699
4 x 16 614 23,5 1 070
4 x 25 960 28,5 1 630
4 x 35 1 344 32,0 2 120
5 x 1,5 72 12,0 200
5 x 2,5 120 13,5 304
5x4 192 16,5 422
5x6 288 18,0 549
5 x 10 480 21,5 852
5 x 16 768 26,0 1 270
5 x 25 1 200 31,5 1 950
6 x 35 1 680 35,5 2 570
7 x 1,5 101 13,0 245
7 x 2,5 168 14,3 363

4
MULTICORE PVC INSULATED CABLE WITH LOW VOLTAGE (LV)
COPPER CONDUCTOR AND SCREEN
TREH‚ILÊNYJ KABELÊ V PVH IZOLÅCII, MEDNYJ
PROVODNIK MEDNYJ ÈKRAN 0,6/1 kV
0,6/1 kB

NYCWY
DIN VDE 0276 / SOGLASNO DIN VDE 0276
CONSTRUCTION
Solid or stranded and compacted copper conductor, PVC insulation, extruded belt sheath, copper wire
screen, black PVC jacket

SAMPLE FOR MARKING :


NYCWY 3x95 SM / 95 0,6/1 kV DIN VDE 0276

APPLICATION :
For use inside, in cable trench or duct and outdoors. In power stations, industrial plants and in switch-
gears if mechanical protection is not required, or in applications where the cable is not exposed to mecha-
nical damages.

STROENIE KABELÅ
Mednaå Ÿila odno/mnogoprovoloxnaå, PVH izolåciå Ÿil, ™kstrudirovannoe zapolnenie, ™kran
iz mednoj provoloki, PVH vneqiåå oboloxka xernogo cveta

PRIMER OBOZNAXENIÅ :
NYCWY 3x95 SM / 95 0,6/1 kV DIN VDE 0276

PRIMENENIE :
Vnutri pomewenij, v trybah i tranqeåh. Dlå ispol∫zovaniå v ™lektrostanciåh, promyqlennyh
sooruŸeniåh, nepodviŸnyh ustanovkah, tam, gde kabel∫ ne podvergaetså mehanixeskim povreŸdeniåm.

5
LOW VOLTAGE (LV) MULTICORE PVC INSULATED CABLE WITH
COPPER CONDUCTOR AND SCREEN
TREH‚ILÊNYJ KABELÊ V PVH IZOLÅCII, MEDNYJ
0,6/1 kV PROVODNIK MEDNYJ ÈKRAN
0,6/1 kB

NYCWY
No. of Insulation Thickness Outer Cu Weight Current load
cores & nom. Wallthickness of sheath diameter number In ground In the air
cross-section Min. Max.
(mm2) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

Kol-vo Tolwina Tolwina Vneqnij Ves Obwij Dopustimaå tokovaå nagruzka


Ÿil i izolåcii oboloxki diametr medu ves V zemle Na vozduhe
sexenie Min. Maks.
(mm2) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

3x 10RE/ 10 1,0 1,8 19 23 408 790 79 60


3x 16RE/ 16 1,0 1,8 21 25 643 1115 102 80
3x 25RM/ 25 1,2 1,8 25 31 1003 1665 133 108
3x 25RM/ 16 1,2 1,8 25 31 902 1570 133 108
3x 25SM/ 35 1,2 1,8 25 32 1402 1900 160 132
3x 35SM/ 16 1,2 1,8 25 32 1190 1725 160 132
3x 50SM/ 50 1,4 1,9 28 35 2000 2500 190 160
3x 50SM/ 25 1,4 1,9 28 35 1723 2295 190 160
3x 70SM/ 70 1,4 2,0 33 40 2796 3485 234 202
3x 70SM/ 35 1,4 2,0 32 39 2410 3135 234 202
3x 95SM/ 95 1,6 2,2 37 44 3791 4675 280 249
3x 95SM/ 50 1,6 2,2 37 44 3296 4195 280 249
3x120SM/120 1,6 2,3 41 48 4786 5705 319 289
3x120SM/ 70 1,6 2,3 40 47 4236 5180 319 289
3x150SM/150 1,8 2,4 45 52 5970 7015 357 329
3x150SM/ 70 1,8 2,4 44 51 5100 6210 357 329
3x185SM/ 95 2,0 2,6 49 56 6383 7740 402 377
3x240SM/120 2,2 2,8 56 63 8242 9980 463 443
4x 10RE/ 10 1,0 1,8 20 24 504 965 79 60
4x 10RE/ 16 1,0 1,8 23 27 796 1300 102 80
4x 25RM/ 16 1,2 1,8 27 34 1142 1870 133 108
4x 35SM/ 16 1,2 1,8 28 35 1526 2160 160 132
4x 50SM/ 25 1,4 2,0 32 39 2203 2925 190 160
4x 70SM/ 35 1,4 2,1 36 43 3082 3955 234 202
4x 95SM/ 50 1,6 2,3 42 49 4208 5305 280 249
4x120SM/ 70 1,6 2,4 46 53 6388 6570 319 289
4x150SM/ 70 1,8 2,6 50 57 6540 7915 357 329
4x185SM/ 95 2,0 2,8 - 56* 8159 9880 402 377
4x240SM/120 2,2 3,0 - 63* 10546 12665 463 443
Remark: Informative data / Informative data

6
M U LT I C O R E P V C I N S U L AT E D C A B L E LOW VOLTAGE (LV)
WITH ALUMINIUM CONDUCTOR
XETYREH‚ILÊNYJ KABELÊ V PVH IZOLÅCII,
ALÎMINIEVYJ PROVODNIK 0,6/1 kV
0,6/1 kB

NAYY-J / NAYY-O
DIN VDE 0276 / SOGLASNO DIN VDE 0276
CONSTRUCTION
Solid aluminium conductor, PVC insulation, extruded belt sheath, black PVC jacket

SAMPLE FOR MARKING :


NAYY-J 4x95 SE 0,6/1 kV DIN VDE 0276

APPLICATION :
For use inside, in cable trench or duct and outdoors. In power stations, industrial plants and in switch-
gears if mechanical protection is not required or in applications where the cable is not exposed to mecha-
nical damages.

STROENIE KABELÅ
Al¥minievaå monoŸila, PVH isolciå Ÿil, ™kstrudirovannoe zapolnenie, PVH vneqnåå obo-
loxka xernogo cveta

PRIMER OBOZNAXENIÅ :
NAYY-J 4x95 SE 0,6/1 kB DIN VDE 0276

PRIMENENIE :
Vnutri pomewenij, v trybah i tranqeåh i na otkrytom vozduhe. Dlå ispol∫zovaniå v ™lektro-
stanciåh, promyqlennyh sooruŸeniåh, nepodviŸnyh ustanovkah, tam, gde kabel∫ ne podvergaet-
så mehanixeskim povreŸdeniåm.

TECHNICAL DATA / TEHNIXESKIE HARAKTERISTIKI

No. of Insulation Thickness Outer Cu Weight Current load


cores & nom. Wallthickness of sheath diameter number In ground In the air
cross-section Min. Max.
(mm2) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

Kol-vo Tolwina Tolwina Vneqnij Ves Obwij Dopustimaå tokovaå nagruzka


Ÿil i izolåcii oboloxki diametr medu ves V zemle Na vozduhe
sexenie Min. Maks.
(mm2) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

4 x 25 RE 1,2 1,8 24 28 290 895 102 82


4 x 35 RE 1,2 1,8 27 31 406 1070 123 100
4 x 50 SE 1,4 1,9 28 33 580 1220 144 119
4 x 70 SE 1,4 2,1 33 38 812 1635 179 152
4 x 95 SE 1,6 2,2 37 42 1102 2045 215 186
4 x 120 SE 1,6 2,4 41 46 1392 2515 245 216
4 x 150 SE 1,8 2,5 44 49 1740 3120 275 246
4 x 185 SE 2,0 2,7 49 54 2146 3645 313 285
4 x 240 SE 2,2 2,8 - 56* 2784 5050 364 338

Remark: Informative data / Informative data

7
LOW VOLTAGE (LV) M U LT I C O R E C O N T R O L P V C I N S U L AT E D
CABLE WITH COPPER CONDUCTOR
PÅTI‚ILÊNYJ KABELÊ V PVH IZOLÅCII,
0,6/1 kV MEDNYJ PROVODNIK
0,6/1 kB

NYY-J / NYY-O
DIN VDE 0276 / SOGLASNO DIN VDE 0276
CONSTRUCTION
Solid or stranded and compacted copper conductor, PVC insulation, extruded belt sheath, black PVC
jacket

SAMPLE FOR MARKING :


NYY-J 5x25 RM 0,6/1 kV DIN VDE 0276

APPLICATION :
For use inside, in cable trench or duct and outdoors. In power stations, industrial plants and in
switchgears if mechanical protection is not required or in applications where the cable is not
exposed to mechanical damages.

TECHNICAL DATA :
Rated voltage: 0,6/1,0 kV / Test voltage: 4 kV
Ambient temperature during laying: from + 5 °C to + 50 °C
Ambient temperature after laying: from – 30 °C to + 70 °C
Maximum conductor temperature: + 70 °C
Admissible short circuit temperature: + 160 °C (max. 5 sec.)
Minimum bending radius: 15 x outer diameter of cable

STROENIE KABELÅ
Mednaå Ÿila odno/mnogoprovoloxnaå, PVH izolåciå Ÿil, ™kstrudirovannoe zapolnenie, PVH vneqiåå oboloxka
xernogo cveta

PRIMER OBOZNAXENIÅ :
NYY-J 5x25 RM 0,6/1 kB DIN VDE 0276

PRIMENENIE :
Vnutri pomewenij, v trybah i tranqeåh. Dlå ispol∫zovaniå v ™lektrostanciåh, promyqlennyh sooruŸeniåh, nepod-
viŸnyh ustanovkah, tam, gde kabel∫ ne podvergaetså mehanixeskim povreŸdeniåm.

TEHNIXESKIE HARAKTRERISTIKI :
Nominal∫noe napråŸenie: 0,6/1,0 kB / testovoe napråŸenie: 4 kV
Dopustimaå temperatura okruŸa¥wej sredy pri montaŸe: ot + 5 °C do + 50 °C
B. Pri stacionarnom montaŸe: ot – 30 °C do + 70 °C
Maksimal∫naå dopustimaå temperatura provodnika: + 70 °C
Maksimal∫naå dopustimaå temperatura provodnika: + 160 °C (maks. 5 sek.)
Minimal∫nyj radius izgiba: 15 diametrov kabelå

8
M U LT I C O R E C O N T R O L P V C I N S U L AT E D LOW VOLTAGE (LV)
CABLE WITH COPPER CONDUCTOR
PÅTI‚ILÊNYJ KABELÊ V PVH IZOLÅCII,
MEDNYJ PROVODNIK 0,6/1 kV
0,6/1 kB

NYY-J / NYY-O
TECHNICAL DATA / TEHNIXESKIE HARAKTERISTIKI
No. of cores & nom. cross-section Cu number Max. average outer diameter Weight
(mm2) (kg/km) (mm) (kg/km)

Kol-vo Ÿil i sexenie Ves medi Maks. vneqnij diametr Obwij ves
(mm2) (kg/km) (mm) (kg/km)

NYY-J, NYY-O
1 x 10 RE 96 12 176
1 x 16 RM* 154 13 252
1 x 25 RM 240 15 367
1 x 35 RM 336 16 474
3 x 1,5 RE 43 14 222
3 x 2,5 RE 72 15 271
3x4 RE 115 17 370
3x6 RE 173 18 449
3 x 10 RE 288 20 617
3 x 16 RM* 461 22 897
4 x 1,5 RE 58 16 254
4 x 2,5 RE 96 17 315
4x4 RE 154 19 436
4x6 RE 230 20 540
4 x 10 RE 384 22 754
4 x 16 RM* 614 25 1100
4 x 25 RM 960 32 1620
4 x 35 RM 1344 34 2100
5 x 1,5 RE 72 16 244
5 x 2,5 RE 120 17 308
5x4 RE 192 19 432
5x6 RE 288 21 552
5 x 10 RE 480 23 788
5 x 16 RM* 768 25 1160
5 x 25 RM 1200 33 1720
7 x 1,5 RE 101 17 299
10 x 1,5 RE 144 21 402
12 x 1,5 RE 173 21 452
14 x 1,5 RE 202 22 505
19 x 1,5 RE 274 25 637
24 x 1,5 RE 346 28 784
30 x 1,5 RE 432 29 932
40 x 1,5 RE 576 33 1190
7 x 2,5 RE 168 18 385
10 x 2,5 RE 240 22 524
12 x 2,5 RE 288 23 595
14 x 2,5 RE 336 24 671
19 x 2,5 RE 456 27 856
24 x 2,5 RE 576 30 1060
30 x 2,5 RE 720 32 1270
40 x 2,5 RE 960 36 1640
Remarks: RE = round, solid conductor; RM = round, stranded conductor; (*) = standard specifies solid conductor
Primexaniå: RE = kruglaå monoŸila; RM = kruglyj mnogoprovoloxnyj provodnik; (*) = standartom ustanovlen monoŸil∫nyj provodnik

9
LOW VOLTAGE (LV) M U LT I C O R E P V C I N S U L AT E D C A B L E
WITH COPPER CONDUCTOR
PÅTI‚ILÊNYJ KABELÊ V PVH IZOLÅCII,
0,6/1 kV MEDNYJ PROVODNIK
0,6/1 kB

NYY-J / NYY-O
TECHNICAL DATA / TEHNIXESKIE HARAKTERISTIKI
No. of Ins. Thickness Outer Cu Weight Current load
cores & nom. Wallthickness of sheath diameter number In ground In the air
cross-sect. Min.
(mm2) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

Kol-vo Tolwina Tolwina Vneqnij Ves Obwij Dopustimaå tokovaå nagruzka


Ÿil i izolåcii oboloxki diametr medi ves V zemle Na vozduhe
sexenie Min. Maks.
(mm2) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

4 x 10 RE 1,0 1,8 18 22* 384 770 79 59


4 x 16 RE 1,0 1,8 21 25 614 1105 102 79
4 x 25 RM 1,2 1,8 25 32 960 1675 133 106
4 x 35 SM 1,2 1,8 25 32 1344 1750 159 131
4 x 50 SM 1,4 1,9 29 36 1920 2325 188 157
4 x 70 SM 1,4 2,1 33 40 2688 3225 232 199
4 x 95 SM 1,6 2,2 38 45 3648 4370 280 246
4 x 120 SM 1,6 2,4 41 49 4608 5430 318 285
4 x 150 SM 1,8 2,5 46 54 5760 6650 359 326
4 x 185 SM 2,0 2,7 51 59 7104 8350 406 374
4 x 240 SM 2,2 2,9 – 57* 9216 10645 473 445
5 x 16 RE 1,0 1,8 22 25 768 1240 102 79
5 x 25 RM 1,2 1,8 27 33 1200 2040 133 106
5 x 35 RM 1,2 1,9 30 36 1680 2650 159 129
5 x 50 RM 1,4 2,1 34 40 2400 3515 188 157

10
SINGLE CORE CABLES FOR INTERNAL LOW VOLTAGE (LV)
WIRING AND CABLING
PROVODA DLÅ VNUTRENNEGO MONTA‚A
450/750 V
450/750 B

NO MA
RC
N07V-K <6 mm2

HIO
LIA
ITA

DI
QU
O
UT

AL
ITA
TIT

'
IS

L
NE
CA

I-U
VO

CE
CO

E
Ecology ®

RM
Line

NF
O

NO
RM
E
CEI 20-20

CHARACTERISTICS / TEHNIXESKIE HARAKTERISTIKI

70°C 160°C
SHORT CIRCUIT
OPERATING
TEMPERATURE UNLEADED
TEMPERATURE CEI 20-35 CEI 20-22 III FLEXIBLE
RABOXAÅ
TEMPERATURA
IEC 332-1 IEC 332-3C
CEI 20-37/2 NE SODER‚IT
GIBKIJ
PRI KOROTKOM SVINCA
TEMPERATURA
ZAMYKANII

Installation in free or built-in ducts and similar systems. Suitable for fixed and protected installation in/on lighting appliances, in
switch and control devices, up to 1000 V A.C., and up to 750 V DC phase to ground.
Ustanovka vo vstroennyh ili svobodno prolega¥wih trubah i shoŸih sistemah. Dlå fiksirovannoj i zawiwennoj
prokladki v osvetitel∫nom, raspredelitel∫nom i kontrol∫nom oborudovanii, s napråŸeniem pri K3 do 1000 V
postoånnogo i 750 V peremennogo toka.

DESCRIPTION / STROENIE KABELÅ


CORE / ‚ILA :
Conductor : flexible tinned copper conductor. / Provodnik : Gibkij, iz neluŸenoj medi.
INSULATION / IZOLÅCIÅ :
PVC quality R2.
PVH, kaxestvo R2.
New type with double coating: Internal softer coating-external horny anti-abrasive coating
Dvuslojnaå izolåciå: Vnutrennaå - mågkaå, vneqnåå - tverdaå, stokjaå k istirani¥
Superior performance: Extreme handiness of the cable,high fluency in duct fitting, high resistance
to abrasion,excellent strippability.
Prevoshodnye harakteristiki: Udobstvo, gibkost∫, stojkost∫ k istirani¥, legko zaxiwaetså.
Colours: Black, brown, light blue, grey, red, white, yellow/green, orenge, pink, dark blue, violet
Cveta: Xernyj, korixnevyj, goluboj, seryj, krasnyj, belyj, Ÿelto-zelenyj, oranŸevyj, rozovyj,
sinij, fioletovyj
Marking: Ink marking on the insulating each 0,5 m: CEI 20-22 II SPEEDY FLAM PIRELLI IEMMEQU
ECOLOGY LINE.
Markirovka: CEI 20-22 II SPEEDY FLAM PIRELLI IEMMEQU ECOLOGY LINE.

INSTALLATION / PRIMENENIE

Minimum
installation Encased or in
Electric panels temperature Cabling surface conduit
V witah 5°C MontaŸ V kabel∫nyh
upravleniå Minimal∫naå kanalah
temperatura
montaŸa 5°C

11
LOW VOLTAGE (LV) SINGLE CORE CABLES FOR INTERNAL
WIRING AND CABLING
PROVODA DLÅ VNUTRENNEGO MONTA‚A
450/750 V
450/750 B

NO MA
RC
N07V-K <6 mm2

HIO
LIA
ITA

DI
QU
O
UT

AL
ITA
TIT

'
IS

L
NE
CA

I-U
VO

CE
CO

E
Ecology ®

RM
Line

NF
OR

NO
M
E
CEI 20-20

Nominal Conductor Insulation Max Nominal Max D.C. Current Min. Max no. of cables
size nominal average external weight resistance capacity (A) at bending threatable, having int.
diameter thickness diameter at 20°C ambient radius diameter of mm
temperature
mm2 mm mm mm kg/km Ohm/km mm 14 18 21 24 31
Sexenie Diametr Srednåå Maks. Obwij Maks. Dopustimaå Min. Kop-vo provodov v puxke,
Ÿily provodnika tolwina vneqnij ves soprotivlenie tokovaå radius ukazannogo diametra
izolåcii diameter pri nagruzka (A) izgiba v mm, qt.
postoånnom
toke, pri 20°C
mm2 mm mm mm kg/km Ohm/km mm 14 18 21 24 31

1 1,3 0,7 3,2 14 19,50 12 13 6 9 13 17 29


1,5 1,5 0,7 3,5 19 13,30 15,5 14 5 8 10 14 23
2,5 1,9 0,8 4,2 30 7,98 21 17 3 5 8 9 16
4 2,5 0,8 4,8 45 4,95 28 19 2 4 6 8 12
6 3 0,8 6,3 63 3,30 36 25 1 2 3 4 7

12
INTERNAL WIRING AND CABLING LOW VOLTAGE (LV)

PROVODA DLÅ VNUTRENNEGO MONTA‚A


450/750 V
450/750 B

NO MA
RC
N07V-K >10 mm2

HIO
LIA
ITA

DI
QU
O
UT

AL
ITA
TIT

'
IS

L
NE
CA

I-U
VO

CE
CO

E
Ecology ®

RM
Line

NF
O

NO
RM
E
CEI 20-20
CHARACTERISTICS / TEHNIXESKIE HARAKTERISTIKI

70°C 160°C
SHORT CIRCUIT
OPERATING
TEMPERATURE UNLEADED
TEMPERATURE CEI 20-35 CEI 20-22 III FLEXIBLE
RABOXAÅ
TEMPERATURA
IEC 332-1 IEC 332-3C
CEI 20-37/2 NE SODER‚IT
GIBKIJ
PRI KOROTKOM SVINCA
TEMPERATURA
ZAMYKANII

Installation in free or built-in ducts and similar systems. Suitable for fixed and protected installation in/on lighting appliances, in
switch and control devices, up to 1000 V A.C., and up to 750 V DC phase to ground.
Ustanovka vo vstroennyh ili svobodno prolega¥wih trubah i shoŸih sistemah. Dlå fiksirovannoj i zawiwennoj
prokladki v osvetitel∫nom, raspredelitel∫nom i kontrol∫nom oborudovanii, s napråŸeniem pri K3 do 1000 V
postoånnogo i 750 V peremennogo toka.

DESCRIPTION / STROENIE KABELÅ


CORE / ‚ILA :
Conductor : flexible tinned copper conductor. / Provodnik : Gibkij, iz neluŸenoj medi.
INSULATION / IZOLÅCIÅ :
PVC type R2.
PVH, kaxestvo R2.
Colours: From 10 to 25mm.: black, brown, light blue, grey, yellow/green.
From 35 to 95mm.: black, light blue, yellow/green.
From 120 to 240mm.: black, yellow/green
Cveta: 10-25 mm2: xernyj, korixnevyj, goluboj, seryj, Ÿelto-zelenyj
35-95 mm2: xernyj, goluboj, Ÿelto-zelenyj
120-240 mm2: xernyj, Ÿelto-zelenyj

Marking: Embossed marking on insulation every 0.5 m: CEI 20-22 II SPEEDY FLAM PIRELLI (G) IEMMEQU
<YEAR> ECOLOGY LINE
Markirovka: CEI 20-22 II SPEEDY FLAM PIRELLI (G) IEMMEQU <YEAR> ECOLOGY LINE

INSTALLATION / PRIMENENIE

Minimum
installation Encased or in
Electric panels temperature Cabling surface conduit
V witah 5°C MontaŸ V kabel∫nyh
upravleniå Minimal∫naå kanalah
temperatura
montaŸa 5°C

13
LOW VOLTAGE (LV) INTERNAL WIRING AND CABLING
PROVODA DLÅ VNUTRENNEGO MONTA‚A
450/750 V
450/750 B

NO MA
RC
N07V-K >10 mm2

HIO
LIA
ITA

DI
QU
O
UT

AL
ITA
TIT

'
IS

L
NE
CA

I-U
VO

CE
CO

E
Ecology ®

RM
Line

NF
OR

NO
M
E
CEI 20-20

Nominal Conductor Insulation Max Max D.C. Max D.C. Current capacity (A) at Min. bending
size nominal average external resistance resistance ambient temperature of radius
diameter thickness diameter at 20°C at 20°C in in free
mm2 mm mm mm kg/km Ohm/km trench in air mm
Sexenie Diametr Srednåå Maks. Obwij Maks. Dopustimaå tokovaå Min. radius
Ÿily provodnika tolwina vneqnij ves soprotivlenie, nagruzka (A) izgiba
izolåcii diametr pri
postoånnom
toke, pri at 20°C
mm2 mm mm mm kg/km Ohm/km V trube Na otkrytom vozduhe mm
1 CONDUCTOR / ‚ILA (Table CEI-UNEL 35752)
10 3,9 1 7,6 100 1,91 57 50 30
16 5 1 8,8 160 1,21 76 68 35
25 6,5 1,2 11 260 0,780 101 89 45
35 7,6 1,2 12,5 350 0,554 125 110 50
50 9,3 1,4 14,5 490 0,386 151 134 60
70 11 1,4 17 670 0,272 192 171 70
95 12,5 1,6 19 890 0,206 232 207 80
120 15,4 1,6 21 1200 0,161 269 239 85
150 16,5 1,8 23,5 1400 0,129 309 275 95
185 18,3 2 26 1800 0,106 353 314 100
240 21,5 2,2 29,5 2400 0,0801 415 369 120

Notes: range has been calculated in the case of a duct made up of 3-4 cables with only 3 active conductors. For the sections superior to 6 mm 2, see the cable
NO7V-K RETOX.

14
MOBILE SERVICE LOW VOLTAGE (LV)

PODVI‚NOE PRIMENENIE
450/750-300/500 V
450/750-300/500 B

NO MA
RC
FROR

HIO
LIA
ITA

DI
QU
O
UT

AL
ITA
TIT

'
IS

L
NE
CA

I-U
VO

CE
CO

E
Ecology ®

RM
Line

NF
O

NO
RM
E
CEI 20-20
CHARACTERISTICS / TEHNIXESKIE HARAKTERISTIKI

70°C 160°C
SHORT CIRCUIT
OPERATING
TEMPERATURE UNLEADED OIL RESISTANT CICLES 60.000
TEMPERATURE CEI 20-35 CEI 20-22 III FLEXIBLE
RABOXAÅ
TEMPERATURA
IEC 332-1 IEC 332-3C
CEI 20-37/2 NE SODER‚IT
GIBKIJ MASKOSTOJKIJ 60.000 CIKLOV
PRI KOROTKOM SVINCA
TEMPERATURA
ZAMYKANII

Suitable for indoor installation in dry or wet environments and for outdoor intermittent or temporary uses. Recommended for mobile
service and suitable also for fixed installation (with proper precautions during installation). Recommended usage: civil buildings
wiring, industries, exhibition booths wiring, electrical panels.
Dlå ustanovki vnutri suhih i vlaŸnyh pomewenij, dlå periodixeskogo ispol∫zovaniå vne zdanij. Rekomendovan dlå
podviŸnogo primeneniå, odnako moŸet primenåt∫så dlå stacionarnogo montaŸa. Rekomendovan k primeneni¥ v Ÿilyh
stroeniåh, promyqlennyh sooruŸeniåh, witah upravleniå.

DESCRIPTION / STROENIE KABELÅ


CORE / ‚ILA :
Conductor : flexible untinned core conductor. / Provodnik : Gibkij, iz neluŸenoj medi.
INSULATION / IZOLÅCIÅ :
Special PVC type T12.
PVH, tip T12.
Colours of the cores / Cveta Ÿil :
light blue-brown / golubaå, korixnevaå
The cores of the cables are black, numbered and earth conductor is yellow/green
Bolee 3 Ÿil: xernye, numerovannye, odna Ÿila Ÿelto-zelenaå
SHEATH / OBOLOXKA :
Special PVC type TM1 and TM2, grey colour
Special∫nyh PVH plastikat tipa TM1 i TM2, serogo cveta.
Marking : Ink printed every 1 m: CEI 20-22 II IEMMEQU CEI 20-52 FROR 450/750 V
(or 300/500 V) FLEXI PIU' <n° for size >PIRELLI (G) <YEAR> ECOLOGY LINE.
Progressive metric marking.
Markirovka : CEI 20-22 II IEMMEQU CEI 20-52 FROR 450/750 V (or 300/500 V) FLEXI PIU'
<kol-vo Ÿil i sexenie>PIRELLI (G) <god vypuska> ECOLOGY LINE.

INSTALLATION / PRIMENENIE

Minimum
installation Incased Internal mobile
temperature or in surface service In free air Cabling
0°C conduit Vnutrennee Na otkrytom MontaŸ
Minimal∫naå V betone i podviŸnoe vozduhe
temperatura qtukaturke primenenie
montaŸa 0°C

15
LOW VOLTAGE (LV) MOBILE SERVICE
PODVI‚NOE PRIMENENIE
450/750-300/500 V
450/750-300/500 B

NO MA
RC
FROR

HIO
LIA
ITA

DI
QU
O
UT

AL
ITA
TIT

'
IS

L
NE
CA

I-U
VO

CE
CO

E
Ecology ®

RM
Line

NF
OR

NO
M
E
CEI 20-20
FROR 450/750 V
Nominal Conductor Insulation Max Nominal Max D.C. Current capacity at ambient Minimum bending
size nominal average external cable resistance temperature of 30°C in free air radius mm
diameter thickness diameter weigth at 20°C fix in duct mobile fix mobile
mm2 mm mm mm kg/km Ohm/km installation or trench service installation service

Sexenie Diametr Srednåå Maks. Obwij Maks. Dopustimaå tokovaå nagruzka (A) Min.
Ÿily provodnika tolwina vneqnij ves soprotivlenie radius izgiba
izolåcii diametr pri potstoånnom
toke, pri 20°C fiks. V trube PodviŸn. fik c. Pod viŸ
mm2 mm mm mm kg/km Ohm/km montaŸ or trench montaŸ montaŸ n. montaŸ

2 CONDUCTORS / ‚ILY (Proof Techn. Spec. IMQ-CPT-007)


1 1,3 0,7 8,8 88 19,50 15 13,5 12,5 35 90
1,5 1,5 0,7 9,3 105 13,30 22 16,5 17 40 95
2,5 1,9 0,8 11 155 7,98 30 23 22,5 45 110
4 2,4 0,8 12,5 205 4,95 40 30 30 50 130
6 3 0,9 14,5 285 3,30 51 38 40 60 140
3 COND y/g / ‚ILY V.T.X. ‚/3 (Proof Tech. Spec. IMQ-CPT-007)
1 1,3 0,7 9,4 100 19,50 15 13,5 12,5 40 95
1,5 1,5 0,7 9,8 120 13,30 22 16,5 17 40 100
2,5 1,9 0,8 12 185 7,98 30 23 22,5 50 120
4 2,4 0,8 13,5 245 4,95 40 30 30 55 140
6 3 0,9 15,5 345 3,30 51 38 40 65 160
4 COND y/g / ‚ILY s V.T.X. ‚/3 (Proof. Tech. Sp. IMQ-CPT-007)
1 1,3 0,7 10 120 19,50 13,6 12 11,5 40 100
1,5 1,5 0,7 11 150 13,30 18,5 15 15 45 110
2,5 1,9 0,8 13 220 7,98 25 20 21 55 130
4 2,4 0,8 14,5 300 4,95 34 27 28 60 150
6 3 0,9 17 420 3,30 43 34 36 70 170
5 COND y/g / ‚IL s V.T.X. ‚/3 (Proof. Tech. Sp. IMQ-CPT-007)
1 1,3 0,7 11 150 19,50 13,6 12 11,5 45 110
1,5 1,5 0,7 12 185 13,30 18,5 15 15 50 120
2,5 1,9 0,8 14 270 7,98 25 20 21 60 140
4 2,4 0,8 16,5 375 4,95 34 27 28 70 170
6 3 0,9 18,5 520 3,30 43 34 36 75 190

16
MOBILE SERVICE LOW VOLTAGE (LV)

PODVI‚NOE PRIMENENIE
450/750-300/500 V
450/750-300/500 B

NO MA
RC
FROR

HIO
LIA
ITA

DI
QU
O
UT

AL
ITA
TIT

'
IS

L
NE
CA

I-U
VO

CE
CO

E
Ecology ®

RM
Line

NF
O

NO
RM
E
CEI 20-20
FROR 300/500 V - Control and Signalling / Kontrol∫nyj i signal∫nyj
n° of Insulation Insulation Max Nominal Max D.C. Current capacity at ambient Minimum bending
conductor average average external weight resistance temperature of 30°C in free air radius mm
thickness thickness diameter at 20°C fix in duct mobile fix mobile
mm mm mm kg/km Ohm/km installation or trench service installation service

Kol-vo Diametr Srednåå Maks. Obwij Maks. Dopustimaå tokovaå nagruzka (A) Min. radius izgiba
Ÿil provodnika tolwina vneqnij ves soprotivlenie radius mm
izolåcii diametr pri potstoånnom
toke, pri 20°C fiks. V trube PodviŸn. fik c. Pod viŸ
mm2 mm mm mm kg/km Ohm/km montaŸ or trench montaŸ montaŸ n. montaŸ
SECTION 1 mm2 / SEXENIE 1 mm2 (Proof. Tech. Sp. IMQ-CPT-007)
7G 1,3 0,6 11 145 19,50 10 9 9 45 110
10 G 1,3 0,6 14 215 19,50 9,5 8,5 8 60 140
12 G 1,3 0,6 15 245 19,50 9 8 7,5 60 150
14 G 1,3 0,6 15,5 295 19,50 8,5 7,5 7 65 160
16 G 1,3 0,6 16,5 315 19,50 8 7 7 70 170
19 G 1,3 0,6 17,5 380 19,50 7,5 7 6,5 70 180
24 G 1,3 0,6 20,5 485 19,50 7 6,5 6 85 210
SECTION 1,5 mm2 / SEXENIE 1,5 mm2 (Proof. Tecn. Sp. IMQ-CPT-007)
7G 1,5 0,7 13 210 13,30 13 11,5 11 55 130
10 G 1,5 0,7 16,5 300 13,30 12 10,5 10 70 170
12 G 1,5 0,7 17,5 345 13,30 11 10 9,5 70 180
14 G 1,5 0,7 18,5 390 13,30 10,5 9,5 9 75 190
16 G 1,5 0,7 19,5 450 13,30 10 9 8,5 80 200
19 G 1,5 0,7 20,5 510 13,30 9,5 8,5 8 85 210
24 G 1,5 0,7 24 655 13,30 9 8 7,5 100 240

17
LOW VOLTAGE (LV) ENERGY AND SIGNALING
KABELÊ PITANIÅ I SIGNALÊNYJ
0,6/1 kV
0,6/1 kB

NO MA
RC
FG7(O)R

HIO
LIA
ITA

DI
QU
O
UT

AL
ITA
TIT

'
IS

L
NE
CA

I-U
VO

CE
CO

E
RM
Ecology ®

NF
Line

OR

NO
M
E
CEI 20-13
CHARACTERISTICS / TEHNIXESKIE HARAKTERISTIKI

90°C 250°C
SHORT CIRCUIT
OPERATING
TEMPERATURE UNLEADED
TEMPERATURE CEI 20-35 CEI 20-22 III FLEXIBLE
RABOXAÅ
TEMPERATURA
IEC 332-1 IEC 332-3C
CEI 20-37/2 NE SODER‚IT
GIBKIJ
PRI KOROTKOM SVINCA
TEMPERATURA
ZAMYKANII

Suitable for powering and transport of of commands and/or signals in industry/craftsmen and residential building.
Suitable for fixed pose both internal and exterior,on platforms,conduits.Can be directly buried.
Kabel∫ pitaniå i signal∫nyj. Ispol∫zuetså v promyqlennosti i Ÿilyh sooruŸemoåh. Dlå vnutrennego i naruŸnogo
stacionarnogo montaŸa. MoŸno grokladyvat∫ v zemle.

DESCRIPTION / STROENIE KABELÅ


CORE / ‚ILA :
Conductor : red flexible untinned round copper conductor. / Provodnik : Gibkij, iz neluŸenoj medi.
INSULATION / IZOLÅCIÅ :
High module HEPR rubber grants the cable outstanding electrical,mechanical and thermic
characteristics.(patent CEI 20-11 - CEI 20-34)
Rezina HEPR garantiruet velikolepnye ™lektrixeskie, mehanixeskie i termixeskie harakteristiki.
Colours of the cores / Colour of the core :
black / xernaå
light blue-brown / golubaå, korixnevaå
brown-black-grey-yellow/green-light blue-brown / golubaå, koruxnevaå, Ÿ/z
light blue-brown-black-grey-yellow/green-brown-blackgrey / golubaå, koruxnevaå, xernaå, Ÿ/z
yellow/green light blue-brown-black-grey / Ÿelto-zelenaå, golubaå, korixnevaå, xernaå, seraå
Signaling cable cores are black, numbered and earth conductor is yellow/green.
V signal∫nyh kabelåh Ÿily xernye, numerovannye, odna – Ÿelto-zelenaå
SHEATH / OBOLOXKA :
PVC special type Rz, grey. / PVH plastikat, serogo cveta.
Marking : Special ink printed each 1m : CEI 20-22 II IEMMEQU CEI 20-52<designation brand according to tables CEI
UNEL 35011> G-SETTE Piu<no. of conductor /sect.>PIRELLI (G) <year>ECOLOGY LINE. Mertical progressive
marking
Markirovka : CEI 20-22 II IEMMEQU CEI 20-52<designation brand according to tables CEI UNEL 35011> G-SET-
TE Piu<kol-vo Ÿil i sexenie>PIRELLI (G) <god vypuska>ECOLOGY LINE.

INSTALLATION / PRIMENENIE

Minimum
installation Incased Buried with
temperature or in surface In free air
Directly buried In duct protection
0°C conduit Na otkrytom
V zemle v trubah V zemle
Minimal∫naå V betone i vozduhe s zawitoj
temperatura qtukaturke
montaŸa 0°C

18
ENERGY AND SIGNALING LOW VOLTAGE (LV)

KABELÊ PITANIÅ I SIGNALÊNYJ


0,6/1 kV
0,6/1 kB

NO MA
RC
FG7(O)R

HIO
LIA
ITA

DI
QU
O
UT

AL
ITA
TIT

'
IS

L
NE
CA

I-U
VO

CE
CO

E
RM
Ecology ®

NF
Line

NO
RM
E
CEI 20-13

Nominal Conductor Insulation Max Nominal Max D.C. Current capacity (A) at ambient temperature of Min.
section nominal average external weight resistance 30°C 30°C 20°C 20°C bending
diameter thickness thickness at 20°C in free in duct buried in duct buried radius
mm2 mm mm mm kg/km Ohm/km air “ρ”=1 “ρ”=1,5 “ρ”=1 “ρ”=1,5 mm
Sexenie Diametr Srednåå Maks. Obwij Maks. Dopustimaå tokovaå nagruzka (A) pri ukazannoj temperature: Min.
Ÿil∫, provodnika, tolwina vneqnij ves, soprotivlenie 30°C 30°C 20°C b trube 20°C radius
izolåcii, diametr pri na v trube proloŸennoj v zemle izgiba,
potstoånnom otkrytom v zemle
toke, pri 20°C vozduhe
mm2 mm mm mm kg/km Om/km “ρ”=1 “ρ”=1,5 “ρ”=1 “ρ”=1,5 mm
1 CONDUCTOR / ‚ILA (Table CEI-UNEL 35375)
1,5 1,5 0,7 6,7 51 13,3 24 20 22 21 35 32 30
2,5 1,9 0,7 7,2 65 7,98 33 28 29 27 45 39 30
4 2,4 0,7 7,8 80 4,95 45 37 37 35 58 51 35
6 3 0,7 8,4 105 3,30 58 48 47 44 73 64 40
10 4,1 0,7 9,4 150 1,91 80 66 63 59 97 85 40
16 5,2 0,7 10,4 200 1,21 107 88 82 77 125 110 45
25 6,3 0,9 12,2 300 0,780 135 117 108 100 160 141 55
35 7,7 0,9 13,6 390 0,554 169 144 132 121 191 169 60
50 9,4 1 15,4 540 0,386 207 175 166 150 226 199 65
70 10,9 1,1 17,3 740 0,272 268 222 204 184 277 244 75
95 12,7 1,1 19,4 940 0,206 328 269 242 217 331 292 85
120 14,5 1,2 21,4 1200 0,161 383 312 274 251 377 332 90
150 15,6 1,4 23,8 1480 0,129 444 355 324 287 420 370 100
185 17,8 1,6 26,0 1830 0,106 510 417 364 323 476 419 110
240 20 1,7 29,2 2340 0,0801 607 490 427 379 550 484 120
300 23,1 1,8 32 2950 0,0641 703 — 484 429 620 546 140
400 26,7 2 36,5 3850 0,0486 823 — 564 500 700 616 150
2 CONDUCTORS / ‚ILY (Table CEI-UNEL 35375)
1,5 1,5 0,7 12 150 13,3 26 22 24 23 36 31 50
2,5 1,9 0,7 13 190 7,98 36 30 31 30 47 41 55
4 2,4 0,7 14,2 240 4,95 49 40 41 39 61 55 60
6 3 0,7 15,4 310 3,30 63 51 52 49 77 68 65
10 4,1 0,7 17,3 440 1,91 86 69 70 66 105 92 75
16 5,2 0,7 19,4 600 1,21 115 91 92 86 136 120 85
25 6,3 0,9 23 850 0,780 149 119 118 111 177 156 100
35 7,7 0,9 25,7 1130 0,554 185 145 145 136 212 185 110
50 9,4 1 29,3 1580 0,386 225 175 180 168 252 221 120

19
LOW VOLTAGE (LV) ENERGY AND SIGNALING
KABELÊ PITANIÅ I SIGNALÊNYJ
0,6/1 kV
0,6/1 kB

NO MA
RC
FG7(O)R

HIO
LIA
ITA

DI
QU
O
UT

AL
ITA
TIT

'
IS

L
NE
CA

I-U
VO

CE
CO

E
RM
Ecology ®

NF
Line

OR

NO
M
E
CEI 20-13

Nominal Conductor Insulation Max Nominal Max D.C. Current capacity (A) at ambient temperature of Min.
section nominal average external weight resistance 30°C 30°C 20°C 20°C bending
diameter thickness thickness at 20°C in free in duct buried in duct buried radius
mm2 mm mm mm kg/km Ohm/km air “ρ”=1 “ρ”=1,5 “ρ”=1 “ρ”=1,5 mm
Sexenie Diametr Srednåå Maks. Obwij Maks. Dopustimaå tokovaå nagruzka (A) pri ukazannoj temperature: Min.
Ÿil∫, provodnika, tolwina vneqnij ves, soprotivlenie 30°C 30°C 20°C b trube 20°C radius
izolåcii, diametr pri na v trube proloŸennoj v zemle izgiba,
potstoånnom otkrytom v zemle
toke, pri 20°C vozduhe
mm2 mm mm mm kg/km Om/km “ρ”=1 “ρ”=1,5 “ρ”=1 “ρ”=1,5 mm

3 CONDUCTORS / ‚ILY (Table CEI-UNEL 35375)


1,5 1,5 0,7 12,5 170 13,3 23 19,5 20 19 30 26 50
2,5 1,9 0,7 13,6 220 7,98 32 26 26 25 40 36 55
4 2,4 0,7 14,9 280 4,95 42 35 33 32 51 45 60
6 3 0,7 16,2 370 3,30 54 44 43 41 65 56 65
10 4,1 0,7 18,2 530 1,91 75 60 59 55 88 78 80
16 5,2 0,7 20,6 740 1,21 100 80 76 72 114 101 90
25 6,3 0,9 24,5 1060 0,780 127 105 100 93 148 130 100
35 7,7 0,9 27,3 1420 0,554 158 128 122 114 178 157 110
50 9,4 1 31,2 1960 0,386 192 154 152 141 211 185 130
70 10,9 1,1 35,6 2700 0,272 246 194 189 174 259 227 150
95 12,7 1,1 40 3430 0,206 298 233 226 206 311 274 170
120 14,5 1,2 44,4 4390 0,161 346 268 260 238 355 311 190
150 15,6 1,4 49,5 5400 0,129 399 300 299 272 394 345 200

Notes: The range of quadripolar cables has been calculated for three active conductors. The range of buried cables has been calculated for laying depth of 0,8 m.
Primexanie: Rasxety dlå xetyrehŸil∫nyh kabelej proizvedeny s uxetom togo, xto 3 provodnika faznye. Dannye dlå kabelej proloŸennyh v zemle rassxitany
dlå grubiny 0,8 m.

20
ENERGY AND SIGNALING LOW VOLTAGE (LV)

KABELÊ PITANIÅ I SIGNALÊNYJ


0,6/1 kV
0,6/1 kB

NO MA
RC
FG7(O)R 0,6/1kV

HIO
LIA
ITA

DI
QU
O
UT

AL
ITA
TIT

'
IS

L
NE
CA

I-U
VO

CE
CO

E
RM
Ecology ®

NF
Line

NO
RM
E
CEI 20-13

Nominal Conductor Insulation Max Nominal Max D.C. Current capacity (A) at ambient temperature of Min.
section nominal average external weight resistance 30°C 30°C 20°C 20°C bending
diameter thickness thickness at 20°C in free in duct buried in duct buried radius
mm2 mm mm mm kg/km Ohm/km air “ρ”=1 “ρ”=1,5 “ρ”=1 “ρ”=1,5 mm
Sexenie Diametr Srednåå Maks. Obwij Maks. Dopustimaå tokovaå nagruzka (A) pri ukazannoj temperature: Min.
Ÿil∫, provodnika, tolwina vneqnij ves, soprotivlenie 30°C 30°C 20°C b trube 20°C radius
izolåcii, diametr pri na v trube proloŸennoj v zemle izgiba,
potstoånnom otkrytom v zemle
toke, pri 20°C vozduhe
mm2 mm mm mm kg/km Om/km “ρ”=1 “ρ”=1,5 “ρ”=1 “ρ”=1,5 mm
3 COND. with yellow/green / ‚ILY (v. t.x. Ÿ/3) (Table CEI-UNEL 35375)
1,5 1,5 0,7 12,5 170 13,3 26 22 24 23 36 31 50
2,5 1,9 0,7 13,6 220 7,98 36 30 31 30 47 41 55
4 2,4 0,7 14,9 280 4,95 49 40 41 39 61 55 60
6 3 0,7 16,2 370 3,30 63 51 52 49 77 68 65
10 4,1 0,7 18,2 530 1,91 86 69 70 66 105 92 80
16 5,2 0,7 20,6 740 1,21 115 91 92 86 136 120 90
25 6,3 0,9 24,5 1060 0,780 149 119 118 111 177 156 100
35 7,7 0,9 27,3 1420 0,554 185 146 145 136 212 185 110
50 9,4 1 31,2 1960 0,386 225 175 180 168 252 221 130
70 10,9 1,1 35,6 2700 0,272 289 221 223 207 310 272 150
95 12,7 1,1 40 3430 0,206 352 265 265 245 371 325 170
120 14,5 1,2 44,4 4390 0,161 410 305 310 284 423 370 190
150 15,6 1,4 47,5 5400 0,129 473 334 356 324 472 414 200

4 COND. / ‚ILY (Table CEI-UNEL 35375)


1,5 1,5 0,7 13,4 200 13,3 23 19,5 20 19 30 26 55
2,5 1,9 0,7 14,6 260 7,98 32 26 26 25 40 36 60
4 2,4 0,7 16 330 4,95 42 35 33 32 51 45 65
6 3 0,7 17,5 430 3,30 54 44 43 41 65 56 70
10 4,1 0,7 19,8 640 1,91 75 60 59 55 88 78 85
16 5,2 0,7 22,4 900 1,21 100 80 76 72 114 101 95
25 6,3 0,9 26,8 1300 0,780 127 105 100 93 148 130 110
35+1X25 7,7 0,9 29,2 1650 0,554 158 128 122 114 178 157 120
50+1X25 9,4 1 32,4 2200 0,386 192 154 152 141 211 185 140
70+1X35 10,9 1,1 37 3000 0,272 246 194 189 174 259 227 160
95+1X50 12,7 1,1 42 3900 0,206 298 233 226 206 311 274 180
120+1X70 14,5 1,2 46,9 4700 0,161 346 268 260 238 355 311 200
150+1X95 15,6 1,4 52,5 6300 0,129 399 300 299 272 394 345 200

21
LOW VOLTAGE (LV) ENERGY AND SIGNALING
KABELÊ PITANIÅ I SIGNALÊNYJ
0,6/1 kV
0,6/1 kB

NO MA
RC
FG7(O)R

HIO
LIA
ITA

DI
QU
O
UT

AL
ITA
TIT

'
IS

L
NE
CA

I-U
VO

CE
CO

E
RM
Ecology ®

NF
Line

OR

NO
M
E
CEI 20-13

Nominal Conductor Insulation Max Nominal Max D.C. Current capacity (A) at ambient temperature of Min.
section nominal average external weight resistance 30°C 30°C 20°C 20°C bending
diameter thickness thickness at 20°C in free in duct buried in duct buried radius
mm2 mm mm mm kg/km Ohm/km air “ρ”=1 “ρ”=1,5 “ρ”=1 “ρ”=1,5 mm
Sexenie Diametr Srednåå Maks. Obwij Maks. Dopustimaå tokovaå nagruzka (A) pri ukazannoj temperature: Min.
Ÿil∫, provodnika, tolwina vneqnij ves, soprotivlenie 30°C 30°C 20°C b trube 20°C radius
izolåcii, diametr pri na v trube proloŸennoj v zemle izgiba,
potstoånnom otkrytom v zemle
toke, pri 20°C vozduhe
mm2 mm mm mm kg/km Om/km “ρ”=1 “ρ”=1,5 “ρ”=1 “ρ”=1,5 mm

4 COND. with yellow/green / ‚ILY (v. t.x. Ÿ/3) (Table CEI-UNEL 35375)
1,5 1,5 0,7 13,4 200 13,3 23 19,5 20 19 30 26 55
2,5 1,9 0,7 14,6 260 7,98 32 26 26 25 40 36 60
4 2,4 0,7 16 330 4,95 42 35 33 32 51 45 65
6 3 0,7 17,5 430 3,30 54 44 43 41 65 56 70
10 4,1 0,7 19,8 640 1,91 75 60 59 55 88 78 85
16 5,2 0,7 22,4 900 1,21 100 80 76 72 114 101 95
25 6,3 0,9 26,8 1300 0,780 127 105 100 93 148 130 110
35+1G25 7,7 0,9 29,2 1650 0,554 158 128 122 114 178 157 120
50+1G25 9,4 1 32,4 2200 0,386 192 154 152 141 211 185 140
70+1G35 10,9 1,1 37 3000 0,272 246 194 189 174 259 227 160
95+1G50 12,7 1,1 42 3900 0,206 298 233 226 206 311 274 180
120+1G70 14,5 1,2 46,9 4700 0,161 346 268 260 238 355 311 200
150+1G95 15,6 1,4 52,5 6300 0,129 399 300 299 272 394 345 200

5 COND. with yellow/green / ‚ILY (v. t.x. Ÿ/3) (Table CEI-UNEL 35375)
1,5 1,5 0,7 14,4 230 13,3 23 19,5 20 19 30 26 60
2,5 1,9 0,7 15,6 310 7,98 32 26 26 25 40 36 65
4 2,4 0,7 17,3 400 4,95 42 35 33 32 51 45 70
6 3 0,7 18,9 520 3,30 54 44 43 41 65 56 75
10 4,1 0,7 21,5 780 1,91 75 60 59 55 88 78 95
16 5,2 0,7 24,4 1120 1,21 100 80 76 72 114 101 100
25 6,3 0,9 29,3 1680 0,780 127 100 100 93 148 130 130
35 7,7 0,9 34,8 2150 0,554 158 128 122 114 178 157 140
50 9,4 1 38,2 3000 0,386 192 154 152 141 211 185 160

Notes: The range of quadripolar cables has been calculated for three active conductors. The range of buried cables has been calculated for laying depth of 0,8 m.
Primexanie: Rasxety dlå xetyrehŸil∫nyh kabelej proizvedeny s uxetom togo, xto 3 provodnika faznye. Dannye dlå kabelej proloŸennyh v zemle rassxitany
dlå grubiny 0,8 m.

22
ENERGY AND SIGNALING LOW VOLTAGE (LV)

KABELÊ PITANIÅ I SIGNALÊNYJ


0,6/1 kV
0,6/1 kB

NO MA
RC
FG7(O)R

HIO
LIA
ITA

DI
QU
O
UT

AL
ITA
TIT

'
IS

L
NE
CA

I-U
VO

CE
CO

E
RM
Ecology ®

NF
Line

NO
RM
E
CEI 20-13

Control and signalling / Kabel∫ upravleniå i signal∫nyj kabel∫


n° of Insulation Insulation Max Nominal Max D.C. Current capacity at ambient Minimum bending
conductor average average external weight resistance temperature of 30°C in free air radius mm
thickness thickness diameter at 20°C fix in duct mobile fix mobile
mm mm mm kg/km Ohm/km installation or trench service installation service

Kol-vo Diametr Srednåå Maks. Obwij Maks. Dopustimaå tokovaå nagruzka (A) Min. radius izgiba
Ÿil provodnika tolwina vneqnij ves soprotivlenie radius mm
izolåcii diametr pri potstoånnom
toke, pri 20°C fiks. V trube PodviŸn. fik c. Pod viŸ
mm2 mm mm mm kg/km Ohm/km montaŸ or trench montaŸ montaŸ n. montaŸ
SECTION 1,5 mm2 / SEXENIE 1 mm2 (Table CEI-UNEL 35377)
5G 1,5 0,7 14,4 230 13,3 16 14 26 23 90
7G 1,5 0,7 16,6 275 13,3 13 11,5 18,5 16 100
10 G 1,5 0,7 18,7 365 13,4 13 11,5 18,5 16 110
12 G 1,5 0,7 19,3 410 13,4 11 9,5 14,5 12,5 120
16 G 1,5 0,7 21,1 510 13,4 11 9,5 14,5 12,5 130
19 G 1,5 0,7 22,1 580 13,4 9 8 13 11,5 130
24 G 1,5 0,7 25,4 700 13,5 9 8 13 11,5 150
SECTION 2,5 mm2 / SEXENIE 2,5 mm2 (Table CEI-UNEL 35377)
7G 1,9 0,7 16,8 310 7,98 17,5 15,5 24 21 110
10 G 1,9 0,7 20,6 395 8,06 17,5 15,5 24 21 120
12 G 1,9 0,7 21,3 445 8,06 13,5 12 20 17,5 130
16 G 1,9 0,7 23,3 545 8,06 13,5 12 20 17,5 140
19 G 1,9 0,7 24,5 615 8,06 12 10,5 16 14 150
24 G 1,9 0,7 28,3 750 8,1 12 10,5 16 14 170

Notes: The range of quadripolar cables has been calculated for three active conductors. The range of buried cables has been calculated for laying depth of 0,8 m.
Primexanie: Rasxety dlå xetyrehŸil∫nyh kabelej proizvedeny s uxetom togo, xto 3 provodnika faznye. Dannye dlå kabelej proloŸennyh v zemle rassxitany
dlå grubiny 0,8 m.

23
LOW VOLTAGE (LV) LOW SMOKE ZERO HALOGEN
NIZKOE DYMO-I
GAZOVYDELENIEVYDELENIE, NE
0,6/1 kV SODER‚IT GALOGENOV
0,6/1 kB

NO MA
RC
FG7(0)M1

HIO
LIA
ITA

DI
QU
1000

O
UT

AL
ITA
TIT

'
IS

L
NE
CA

I-U
VO

CE
CO

E
RM
NF
OR

NO
M
E
CEI 20-13 / SOGLASNO CEI 20-12
CHARACTERISTICS / TEHNIXESKIE HARAKTERISTIKI
SHORT CIRCUIT
OPERATING
TEMPERATURE LEAD FREE
CEI 20-35
IEC 332-1 90°C TEMPERATURE
RABOXAÅ
TEMPERATURA
250°C TEMPERATURA
PRI KOROTKOM
CEI 20-22 III
IEC 332-3C
NE SODER‚IT
SVINCA
FLEXIBLE
GIBKIJ
CEI 20-37
CEI 20-38
ZAMYKANII

Single and multicore signalling cables with very low emission of smoke and toxic gases (according to CEI 20-38 tested in
compliance with CEI 20-37). Suitable for hazardous areas where best safety conditions are required and where it is important to
protect installed systems and installed devices from the attack of corrosive gases (schools, hospitals, hotels, shopping centres,
undergrounds, ecc.).
Suitable for fixed installation on walls and on metallic structures either for internal and external. (This product is protected by at
least one of the following patent applications -and foreign counterparts: EP-893,801; EP-983,802; WO 99/05688; WO 00/19452)
OdnoŸil∫nye i mnogoŸil∫nye ciglal∫nye kabeli s oxen∫ nizkim vydeleniem dyma i toksixnyh gazov (v sootvetstvii
s SEI 20-37). Pohodåt dlå ispol∫sovaniå v zonah, trebu¥wih vysqih standartov bezopasnosti, gde neobhodimo
zawitit∫ ustanovlennoe oborudovanie ot vydelå¥wihså, v sluxae vozgoraniå kabelå, raz√eda¥wih gazov (qkoly,
bol∫nicy, gostinicy, supermarkety, podzemnye sooruŸeniå).
VozmoŸna vneqnåå i naruŸnaå fiksirovannaå prokladka po stenam, metallixeskim konstrukciåm.

DESCRIPTION / STROENIE KABELÅ


CORE / ‚ILA :
Conductor : flexible untinned red copper conductor. / Provodnik : Gibkij, iz neluŸenoj medi.
INSULATION / IZOLÅCIÅ :
High module HEPR rubber grants the cable outstanding electrical, mechanical and thermic characteristics.
Rezina HEPR obespexivaet velikolepnye ™lektrixeskie, mehanixeskie i termixeskie harakteristiki.
Colour of the core / Colour of the core :
black / xernaå
light blue-brown / golubaå, korixnevaå
brown-black-grey-yellow/green-light blue-brown / golubaå, koruxnevaå, Ÿ/z
light blue-brown-black-grey-yellow/green-brown-black grey / golubaå, koruxnevaå, xernaå, Ÿ/z
yellow/green light blue-brown-black-grey / xerŸelto-zelenaå, golubaå, lroxnevaå, xernaå, seraånaå
Signalling cable cores are black, numbered and earth conductor is yellow/green.
V signal∫nyh kabelåh Ÿily xernye, numerovannye, odna – Ÿelto-zelenaå
SHEATH / OBOLOXKA :
Thermoplastic special quality type M1, green colour. / Termoplastikat osobogo kaxestva, tip M1, zelenogo cveta.
Marking : Special <FG7(O)M1> ink printed: CEI 20-22 III CAT. C IEMMEQ AFUMEX 1000(nr. conductors /section) PIREL-
LI(G) (YEAR) SAFETY LINE.progressive metric marking.
Markirovka : <FG7(O)M1> CEI 20-22 III CAT. C IEMMEQ AFUMEX 1000(kol-vo Ÿil i sexenie) PIRELLI(G)(god vypuska)

INSTALLATION / PRIMENENIE

Minimum
installation Incased Buried with
temperature or in surface In free air
In duct protection Directly buried
0°C conduit Na otkrytom
v trubah V zemle V zemle
Minimal∫naå V betone i vozduhe s zawitoj
temperatura qtukaturke
montaŸa 0°C

24
LOW SMOKE ZERO HALOGEN LOW VOLTAGE (LV)
NIZKOE DYMO-I
GAZOVYDELENIEVYDELENIE, NE
SODER‚IT GALOGENOV 0,6/1 kV
0,6/1 kB

NO MA
RC
FG7(0)M1

HIO
LIA
ITA

DI
QU
O
UT

AL
ITA
TIT
1000

'
IS

L
NE
CA

I-U
VO

CE
CO

E
RM
NF
O

NO
RM
E
CEI 20-13 / SOGLASNO CEI 20-12
Nominal Conductor Insulation Max Nominal Max D.C. Current capacity (A) at ambient temperature of Min.
section nominal average external weight resistance 30°C 30°C 20°C 20°C bending
diameter thickness thickness at 20°C in free in duct buried in duct buried radius
mm2 mm mm mm kg/km Ohm/km air “ρ”=1 “ρ”=1,5 “ρ”=1 “ρ”=1,5 mm
Sexenie Diametr Srednåå Maks. Obwij Maks. Dopustimaå tokovaå nagruzka (A) pri ukazannoj temperature: Min.
Ÿil∫, provodnika, tolwina vneqnij ves, soprotivlenie 30°C 30°C 20°C b trube 20°C radius
izolåcii, diametr pri na v trube proloŸennoj v zemle izgiba,
potstoånnom otkrytom v zemle
toke, pri 20°C vozduhe
mm2 mm mm mm kg/km Om/km “ρ”=1 “ρ”=1,5 “ρ”=1 “ρ”=1,5 mm

1 CONDUCTOR / ‚ILA
10 4,1 0,7 9,4 150 1,91 80 66 63 59 97 85 45
16 5,2 0,7 10,4 200 1,21 107 88 82 77 125 110 50
25 6,3 0,9 12,2 300 0,780 135 117 108 100 160 141 60
35 7,7 0,9 13,6 390 0,554 169 144 132 121 191 169 60
50 9,4 1 15,4 540 0,386 207 175 166 150 226 199 70
70 10,9 1,1 17,3 740 0,272 268 222 204 184 277 244 80
95 12,7 1,1 19,4 940 0,206 328 269 242 217 331 292 90
120 14,5 1,2 21,4 1200 0,161 383 312 274 251 377 332 95
150 15,6 1,4 23,8 1480 0,129 444 355 324 287 420 370 100
185 17,8 1,6 26 1830 0,106 510 417 364 323 476 419 110
240 20 1,7 29 2340 0,0801 607 490 427 379 550 484 130
300 23,1 1,8 32 2950 0,0641 703 - 484 429 620 546 140
2 CONDUCTORS / ‚ILY
1,5 1,5 0,7 12 150 13,3 26 22 24 23 36 31 55
2,5 1,9 0,7 13 190 7,98 36 30 31 30 47 41 60
4 2,4 0,7 14,2 240 4,95 49 40 41 39 61 55 65
6 3 0,7 15,4 310 3,30 63 51 52 49 77 68 70
10 4,1 0,7 17,3 440 1,91 86 69 70 66 105 92 80
16 5,2 0,7 19,4 600 1,21 115 91 92 86 136 120 90
25 6,3 0,9 23 850 0,780 149 119 118 111 177 156 100
35 7,7 0,9 25,7 1130 0,554 185 146 145 136 212 185 110
50 9,4 1 29,3 1580 0,386 225 175 180 168 252 221 120
3 CONDUCTORS / ‚ILY
1,5 1,5 0,7 12,5 170 13,3 23 19,5 20 19 30 26 55
2,5 1,9 0,7 13,6 220 7,98 32 26 26 25 40 36 60
4 2,4 0,7 14,9 280 4,95 42 35 33 32 51 45 65
6 3 0,7 16,2 370 3,30 54 44 43 41 65 56 70
10 4,1 0,7 18,2 530 1,91 75 60 59 55 88 78 85
16 5,2 0,7 20,6 740 1,21 100 80 76 72 114 101 90
25 6,3 0,9 24,5 1060 0,780 127 105 100 93 148 130 110
35 7,7 0,9 27,3 1420 0,554 158 128 122 114 178 157 120
50 9,4 1 31,2 1960 0,386 192 154 152 141 211 185 130
70 10,9 1,1 35,6 2700 0,272 246 194 189 174 259 227 150
95 12,7 1,1 40 3430 0,206 298 233 226 206 311 274 170
120 14,5 1,2 44,4 4390 0,161 346 268 260 238 355 311 190
150 15,6 1,4 49,5 5400 0,129 399 300 299 272 394 345 210
Notes: The range of quadripolar cables has been calculated for three active conductors. The range of buried cables has been calculated for laying depth of 0,8 m.
Primexanie: Rasxety dlå xetyrehŸil∫nyh kabelej proizvedeny s uxetom togo, xto 3 provodnika faznye. Dannye dlå kabelej proloŸennyh v zemle rassxitany
dlå grubiny 0,8 m.

25
LOW VOLTAGE (LV) LOW SMOKE ZERO HALOGEN
NIZKOE DYMO-I
GAZOVYDELENIEVYDELENIE, NE
0,6/1 kV SODER‚IT GALOGENOV
0,6/1 kB

NO MA
RC
FG7(0)M1

HIO
LIA
ITA

DI
QU
O
UT

AL
ITA
TIT
1000

'
IS

L
NE
CA

I-U
VO

CE
CO

E
RM
NF
OR

NO
M
E
CEI 20-13 / SOGLASNO CEI 20-12
Nominal Conductor Insulation Max Nominal Max D.C. Current capacity (A) at ambient temperature of Min.
section nominal average external weight resistance 30°C 30°C 20°C 20°C bending
diameter thickness thickness at 20°C in free in duct buried in duct buried radius
mm2 mm mm mm kg/km Ohm/km air “ρ”=1 “ρ”=1,5 “ρ”=1 “ρ”=1,5 mm
Sexenie Diametr Srednåå Maks. Obwij Maks. Dopustimaå tokovaå nagruzka (A) pri ukazannoj temperature: Min.
Ÿil∫, provodnika, tolwina vneqnij ves, soprotivlenie 30°C 30°C 20°C b trube 20°C radius
izolåcii, diametr pri na v trube proloŸennoj v zemle izgiba,
potstoånnom otkrytom v zemle
toke, pri 20°C vozduhe
mm2 mm mm mm kg/km Om/km “ρ”=1 “ρ”=1,5 “ρ”=1 “ρ”=1,5 mm

3 CONDUCTORS with yellow/green / ‚ILY (v. t.x. Ÿ/3)


1,5 1,5 0,7 12,5 170 13,3 26 22 24 23 36 31 55
2,5 1,9 0,7 13,6 220 7,98 36 30 31 30 47 41 60
4 2,4 0,7 14,9 280 4,95 49 40 41 39 61 55 65
6 3 0,7 16,2 370 3,30 63 51 52 49 77 68 70
10 4,1 0,7 18,2 530 1,91 86 69 70 66 105 92 85
16 5,2 0,7 20,6 740 1,21 115 91 92 86 136 120 90
25 6,3 0,9 24,5 1060 0,780 149 119 118 111 177 156 110
35 7,7 0,9 27,3 1420 0,554 185 146 145 136 212 185 120
50 9,4 1 31,2 1960 0,386 225 175 180 168 252 221 130
70 10,9 1,1 35,6 2700 0,272 289 221 223 207 310 272 150
95 12,7 1,1 40 3430 0,206 352 265 265 245 371 325 170
120 14,5 1,2 44,4 4390 0,161 410 305 310 284 423 370 190
150 15,6 1,4 49,5 5400 0,129 473 334 356 324 472 414 210

4 CONDUCTORS / ‚ILY
1,5 1,5 0,7 14,1 200 13,3 23 19,5 20 19 30 26 60
2,5 1,9 0,7 15,3 260 7,98 32 26 26 25 40 36 65
4 2,4 0,7 16,7 330 4,95 42 35 33 32 51 45 70
6 3 0,7 18,4 430 3,30 54 44 43 41 65 56 75
10 4,1 0,7 20,8 640 1,91 75 60 59 55 88 78 90
16 5,2 0,7 23,4 900 1,21 100 80 76 72 114 101 100
25 6,3 0,9 27,7 1300 0,780 127 105 100 93 148 130 120
35+1X25 7,7 0,9 30,4 1650 0,554 158 128 122 114 178 157 130
50+1X25 9,4 1 33,6 2200 0,386 192 154 152 141 211 185 140
70+1X35 10,9 1,1 38,2 3000 0,272 246 194 189 174 259 227 160
95+1X50 12,7 1,1 43,4 3900 0,206 298 233 226 206 311 274 180
120+1X70 14,5 1,2 48,3 4700 0,161 346 268 260 238 355 311 200
150 +1X95 15,6 1,4 53,9 6300 0,129 399 300 299 272 394 345 220

Notes: The range of quadripolar cables has been calculated for three active conductors. The range of buried cables has been calculated for laying depth of 0,8 m.
Primexanie: Rasxety dlå xetyrehŸil∫nyh kabelej proizvedeny s uxetom togo, xto 3 provodnika faznye. Dannye dlå kabelej proloŸennyh v zemle rassxitany
dlå grubiny 0,8 m.

26
LOW SMOKE ZERO HALOGEN LOW VOLTAGE (LV)
NIZKOE DYMO-I
GAZOVYDELENIEVYDELENIE, NE
SODER‚IT GALOGENOV 0,6/1 kV
0,6/1 kB

NO MA
RC
FG7(0)M1

HIO
LIA
ITA

DI
QU
O
UT

AL
ITA
TIT
1000

'
IS

L
NE
CA

I-U
VO

CE
CO

E
RM
NF
O

NO
RM
E
CEI 20-13 / SOGLASNO CEI 20-12
Nominal Conductor Insulation Max Nominal Max D.C. Current capacity (A) at ambient temperature of Min.
section nominal average external weight resistance 30°C 30°C 20°C 20°C bending
diameter thickness thickness at 20°C in free in duct buried in duct buried radius
mm2 mm mm mm kg/km Ohm/km air “ρ”=1 “ρ”=1,5 “ρ”=1 “ρ”=1,5 mm
Sexenie Diametr Srednåå Maks. Obwij Maks. Dopustimaå tokovaå nagruzka (A) pri ukazannoj temperature: Min.
Ÿil∫, provodnika, tolwina vneqnij ves, soprotivlenie 30°C 30°C 20°C b trube 20°C radius
izolåcii, diametr pri na v trube proloŸennoj v zemle izgiba,
potstoånnom otkrytom v zemle
toke, pri 20°C vozduhe
mm2 mm mm mm kg/km Om/km “ρ”=1 “ρ”=1,5 “ρ”=1 “ρ”=1,5 mm

4 CONDUCTORS with yellow/green / ‚ILY (v. t.x. Ÿ/3)


1,5 1,5 0,7 14,1 200 13,3 23 19,5 20 19 30 26 60
2,5 1,9 0,7 15,3 260 7,98 32 26 26 25 40 36 65
4 2,4 0,7 16,7 330 4,95 42 35 33 32 51 45 70
6 3 0,7 18,4 430 3,30 54 44 43 41 65 56 75
10 4,1 0,7 20,8 640 1,91 75 60 59 55 88 78 90
16 5,2 0,7 23,4 900 1,21 100 80 76 72 114 101 100
25 6,3 0,9 27,7 1300 0,780 127 105 100 93 148 130 120
35+1G25 7,7 0,9 30,4 1650 0,554 158 128 122 114 178 157 130
50+1G25 9,4 1 33,6 2200 0,386 192 154 152 141 211 185 140
70+1G35 10,9 1,1 38,2 3000 0,272 246 194 189 174 259 227 160
95+1G50 12,7 1,1 43,4 3900 0,206 298 233 226 206 311 274 180
120+1G70 14,5 1,2 48,3 4700 0,161 346 268 260 238 355 311 200
150+1G95 15,6 1,4 53,9 6300 0,129 399 300 299 272 394 345 220

5 CONDUCTORS with yellow/green / ‚IL (v. t.x. Ÿ/3)


1,5 1,5 0,7 15,1 230 13,3 23 19,5 20 19 30 26 65
2,5 1,9 0,7 16,4 310 7,98 32 26 26 25 40 36 70
4 2,4 0,7 18,2 400 4,95 42 35 33 32 51 45 75
6 3 0,7 19,8 520 3,30 54 44 43 41 65 56 80
10 4,1 0,7 23,4 780 1,91 75 60 59 55 88 78 95
16 5,2 0,7 25,4 1120 1,21 100 80 76 72 114 101 110
25 6,3 0,9 30,3 1680 0,780 127 105 100 93 148 130 130
35 7,7 0,9 34 2150 0,554 158 128 122 114 178 157 140
50 9,4 1 40,1 3000 0,386 192 154 152 141 211 185 160
Notes: The range of quadripolar cables has been calculated for three active conductors. The range of buried cables has been calculated for laying depth of 0,8 m.
Primexanie: Rasxety dlå xetyrehŸil∫nyh kabelej proizvedeny s uxetom togo, xto 3 provodnika faznye. Dannye dlå kabelej proloŸennyh v zemle rassxitany
dlå grubiny 0,8 m.

27
LOW VOLTAGE (LV) LOW SMOKE ZERO HALOGEN
NIZKOE DYMO-I
GAZOVYDELENIEVYDELENIE, NE
0,6/1 kV SODER‚IT GALOGENOV
0,6/1 kB

NO MA
RC
FG7(0)M1

HIO
LIA
ITA

DI
QU
O
UT

AL
ITA
TIT

'
IS

L
NE
CA

I-U
VO

CE
CO

E
RM
NF
OR

NO
M
E
CEI 20-13 / SOGLASNO CEI 20-12

Control and signalling / Kabel∫ upravleniå i signal∫nyj


Nr. of Conductor Insulation Max Nominal Max D.C. Current capacity (A) Min. bending
conductors nominal average external weight resistance at ambient temperature radius
diameter thickness thickness at 20°C 30°C 30°C 20°C buried
n. mm mm mm kg/km Ohm/km in free air in duct “ρ”=1 “ρ”=1,5 mm

Kolbo Diametr Srednåå Maks. Obwij Maks. Dopustimaå tokovaå nagruzka (A) pri Min. radius
Ÿil provodnika tolwina vneqnij ves soprotivlenie ukazannoj temperature: izgiba
izolåcii diametr pri
potstoånnom 30°C 30°C 20°C b trube
toŸe, pri 20°C na otkrytom v trube proloŸennoj v zemle
n. mm mm mm kg/km Ohm/km vozduhe “ρ”=1 “ρ”=1,5 mm

SECTION 1,5 mm / SEXENIE 1,5 mm2 2

5G 1,5 0,7 15,1 230 13,3 16 14 26 23 95


7G 1,5 0,7 16,1 275 13,3 13 11,5 18,5 16 110
10 G 1,5 0,7 19,7 365 13,4 13 11,5 18,5 16 120
12 G 1,5 0,7 20,2 410 13,4 11 9,5 14,5 12,5 120
16 G 1,5 0,7 22 510 13,4 11 9,5 14,5 12,5 130
19 G 1,5 0,7 23 580 13,4 9 8 13 11,5 140
24 G 1,5 0,7 26,4 700 13,5 9 8 13 11,5 160

SECTION 2,5 mm / SEXENIE 2,5 mm2 2

7G 1,9 0,7 17,8 310 7,98 17,5 15,5 24 21 120


10 G 1,9 0,7 21,6 395 8,06 17,5 15,5 24 21 130
12 G 1,9 0,7 22,2 445 8,06 13,5 12 20 17,5 130
16 G 1,9 0,7 24,3 545 8,06 13,5 12 20 17,5 150
19 G 1,9 0,7 25,4 615 8,06 12 10,5 16 14 150
24 G 1,9 0,7 29,3 750 8,1 12 10,5 16 14 180

Notes: The range of quadripolar cables has been calculated for three active conductors. The range of buried cables has been calculated for laying depth of 0,8 m.
Primexanie: Rasxety dlå xetyrehŸil∫nyh kabelej proizvedeny s uxetom togo, xto 3 provodnika faznye. Dannye dlå kabelej proloŸennyh v zemle rassxitany
dlå grubiny 0,8 m.

28
MOBILE SERVICE LOW VOLTAGE (LV)

PODVI‚NOE PRIMENENIE
450/750 V
450/750 B

H07RN-F USE
HAR
CEI 20-19 (CENELEC HD 22-4-S2)
CHARACTERISTICS / TEHNIXESKIE HARAKTERISTIKI

60°C 200°C
SHORT CIRCUIT
OPERATING OZONE
TEMPERATURE
TEMPERATURE CEI 20-35 RESISTANT OIL RESISTANT FLEXIBLE
RABOXAÅ
TEMPERATURA
IEC 332-1
AG4 STOJKIJ I AD8 MASLOSTOJKIJ GIBKIJ
PRI KOROTKOM
TEMPERATURA UF PUXAM
ZAMYKANII

Building characteristics of the cable grant high flexibility, an excellent seal to bad weather, oils and grease, to mechanical and
thermic pressure. These cables can be used for permanent dives up to 10 bar of pressure :Pireflex can be used up to 85 °C
(in a protected position), for fixed installations up to 1000V voltage.
Konstrukciå kabelå obespexivaet vysoku¥ gibkost∫, stojkost∫ k pogodnym usloviåm, maslam i smazoxnym
materialam, mehanixeskim i temperaturnym vozdejstviåm. Kabel∫ vyderŸivaet davlenie 10 atmosfer. Stoek k
temperature do 85°C. Dlå fiksirovannoj prokladki do 1000 V.

DESCRIPTION / STROENIE KABELÅ


CORE / ‚ILA :
Conductor : flexible untinned red copper conductor. / Provodnik : Gibkij, iz neluŸenoj medi.
INSULATION / IZOLÅCIÅ :
High quality E14 rubber grants the cable outstanding electrical, mechanical and thermic characteristics..
Rezina vysokogo kaxestva obespexivaet velikolepnye ™lektrixeskie, mehanixeskie i termixeskie
harakteristiki.
Colour of the core / Colour of the core :
black / xernaå
brown-light blue / golubaå, korixnevaå
yellow-green-brown-light blue / golubaå, koruxnevaå, Ÿ/z
yellow-green-black-grey-brown / golubaå, koruxnevaå, xernaå, Ÿ/z
yellow/green-grey-light blue-brown-black / Ÿelto-zrlenaå, golubaå, koruxnevaå, xernaå, Ÿ/z
Signalling cable cores are black, numbered and earth conductor is yellow/green.
V signal∫nyh kabelåh Ÿily xernye, numerovannye, odna – Ÿelto-zelenaå
SHEATH / OBOLOXKA :
Policloroprene module EM2 black coloured. / Polihloropren (neopren( xernogo cveta.
Marking : Special ink printed<PIREFLEX,USE HO7RN-F>
Markirovka : <PIREFLEX,USE HO7RN-F>

INSTALLATION / PRIMENENIE

Minimum
installation Internal mobile Mobile service External
temperature service In free air in yard mobile service
In water
0°C Vnutrennee Na otkrytom Gibkoe prime- Vneqnee
V vode
Minimal∫naå podviŸnoe vozduhe nenie na podviŸnoe
temperatura primenenie strojkah primenenie
montaŸa 0°C

29
LOW VOLTAGE (LV) MOBILE SERVICE
PODVI‚NOE PRIMENENIE
450/750 V
450/750 B

H07RN-F USE
HAR
CEI 20-19 (CENELEC HD 22-4-S2)

Nominal Conductor Insulation Max Nominal Max Current capacity (A) at Min. bending
size nominal average external weight resistance ambient temperature radius
diameter thickness diameter at 20°C of 30°C in free air fix mobile
mm2 mm mm mm kg/km Ohm/km mobile service installation service

Sexenie Diametr Srednåå Maks. Obwij Maks. Dopustimaå tokovaå Min. radius
Ÿil provodnik tokwina vneqnij ves soprotivlenie nagruzka (A) pri izgiba
a izolåcii diametr pri temperature 30°C na otkrytom fiks PodviŸ
postroånnom vozduhe, podviŸnoe primenenie montaŸ montaŸ
toke, pri 20°C
mm2 mm mm mm kg/km Ohm/km

1 CONDUCTOR / ‚ILA (Table CEI-UNEL 35364)


1,5 1,5 0,8 7,2 50 13,3 17,5 30 75
2,5 1,9 0,9 8 65 7,98 20 35 80
4 2,4 1 9 90 4,95 30 40 90
6 3 1 11 120 3,30 38 45 110
10 4,1 1,2 12,5 180 1,91 53 50 130
16 5,2 1,2 14,5 250 1,21 71 60 150
25 6,3 1,4 16,5 350 0,780 94 70 170
35 7,7 1,4 18,5 500 0,554 117 75 190
50 9,4 1,6 21 650 0,386 148 85 210
70 10,9 1,6 23,5 900 0,272 185 95 240
95 12,7 1,8 26 1200 0,206 222 100 260
120 14,5 1,8 28,5 1450 0,161 260 110 290
150 15,6 2 31,5 1800 0,129 300 130 320
185 17,8 2,2 34,5 2200 0,106 341 140 350
240 20 2,4 38 2800 0,0801 407 150 380
2 CONDUCTORS / ‚ILY (Table CEI-UNEL 35364)
1 1,3 0,8 10,5 95 19,50 16 45 110
1,5 1,5 0,8 11,5 120 13,30 19,5 50 120
2,5 1,9 0,9 13,5 170 7,98 25 55 140
4 2,4 1 15 230 4,95 34 60 150
6 3 1 18,5 300 3,30 43 75 190
10 4,1 1,2 24 540 1,91 60 100 240
16 5,2 1,2 27,5 720 1,21 79 110 280
25 6,3 1,4 31,5 1000 0,780 105 130 320

30
MOBILE SERVICE LOW VOLTAGE (LV)

PODVI‚NOE PRIMENENIE
450/750 V
450/750 B

H07RN-F USE
HAR
CEI 20-19 (CENELEC HD 22-4-S2)

Nominal Conductor Insulation Max Nominal Max Current capacity (A) at Min. bending
size nominal average external weight resistance ambient temperature radius
diameter thickness diameter at 20°C of 30°C in free air fix mobile
mm2 mm mm mm kg/km Ohm/km mobile service installation service

Sexenie Diametr Srednåå Maks. Obwij Maks. Dopustimaå tokovaå Min. radius
Ÿil provodnik tokwina vneqnij ves soprotivlenie nagruzka (A) pri izgiba
a izolåcii diametr pri temperature 30°C na otkrytom fiks PodviŸ
postroånnom vozduhe, podviŸnoe primenenie montaŸ montaŸ
toke, pri 20°C
mm2 mm mm mm kg/km Ohm/km

3 CONDUCTORS with yellow/green / ‚ILY (Table CEI-UNEL 35364)


1 1,3 0,8 11,5 110 19,50 16 50 120
1,5 1,5 0,8 12,5 140 13,30 19,5 50 130
2,5 1,9 0,9 14,5 210 7,98 25 60 150
4 2,4 1 16 280 4,95 35 65 160
6 3 1 20 370 3,30 44 80 200
10 4,1 1,2 25,5 670 1,91 62 100 260
16 5,2 1,2 29,5 900 1,21 82 120 300
25 6,3 1,4 34 1300 0,780 109 140 340
35 7,7 1,4 38 1750 0,554 135 150 380
50 9,4 1,6 44 2400 0,386 169 180 440
70 10,9 1,6 49,5 3200 0,272 211 200 500
95 12,7 1,8 54 4250 0,206 250 220 540
120 14,5 1,8 59 5200 0,161 292 240 590
150 15,6 2 66,5 6400 0,129 335 270 670
185 17,8 2,2 71,5 8350 0,106 378 290 720

4 CONDUCTORS with yellow/green / ‚ILY (Table CEI-UNEL 35364)


1 1,3 0,8 12,5 135 19,50 13,5 50 130
1,5 1,5 0,8 13,5 170 13,30 17,5 55 140
2,5 1,9 0,9 15,5 250 7,98 20 65 160
4 2,4 1 18 350 4,95 30 75 180
6 3 1 22 470 3,30 37 90 220
10 4,1 1,2 28 820 1,91 52 110 280
16 5,2 1,2 32 1100 1,21 69 130 320
25 6,3 1,4 37,5 1600 0,780 92 150 380
35 7,7 1,4 42 2200 0,554 114 170 420
50 9,4 1,6 48,5 3000 0,386 143 190 490
70 10,9 1,6 54,5 4100 0,272 178 220 550
95 12,7 1,8 60,5 5450 0,206 210 240 610
120 14,5 1,8 65,5 7100 0,161 246 260 660
150 15,6 2 74 8800 0,129 282 300 740

31
LOW VOLTAGE (LV) MOBILE SERVICE
PODVI‚NOE PRIMENENIE
450/750 V
450/750 B

H07RN-F USE
HAR
CEI 20-19 (CENELEC HD 22-4-S2)

Nominal Conductor Insulation Max Nominal Max Current capacity (A) at Min. bending
size nominal average external weight resistance ambient temperature radius
diameter thickness diameter at 20°C of 30°C in free air fix mobile
mm2 mm mm mm kg/km Ohm/km mobile service installation service

Sexenie Diametr Srednåå Maks. Obwij Maks. Dopustimaå tokovaå Min. radius
Ÿil provodnik tokwina vneqnij ves soprotivlenie nagruzka (A) pri izgiba
a izolåcii diametr pri temperature 30°C na otkrytom fiks PodviŸ
postroånnom vozduhe, podviŸnoe primenenie montaŸ montaŸ
toke, pri 20°C
mm2 mm mm mm kg/km Ohm/km

5 CONDUCTORS with yellow/green / ‚IL (Table CEI-UNEL 35364)


1 1,3 0,8 13,5 170 19,50 13,5 55 140
1,5 1,5 0,8 15 210 13,30 17,5 60 150
2,5 1,9 0,9 17 310 7,98 20 70 170
4 2,4 1 19,5 430 4,95 30 80 200
6 3 1 24,5 580 3,30 38 100 250
10 4,1 1,2 30,5 1000 1,91 54 120 310
16 5,2 1,2 35,5 1400 1,21 71 140 360
25 6,3 1,4 41,5 2000 0,780 94 170 420

Notes: The range of quadripolar cables has been calculated for three active conductors. The range of buried cables has been calculated for laying depth of 0,8 m.
Primexanie: Rasxety dlå xetyrehŸil∫nyh kabelej proizvedeny s uxetom togo, xto 3 provodnika faznye. Dannye dlå kabelej proloŸennyh v zemle rassxitany
dlå grubiny 0,8 m.

Control and signalling / Kabel∫ upravleniå i signal∫nyj kabel∫


Number Conductor Insulation Max esternal Nominal Max external Current capacity at Min. bending
conductor nominal average diameter weight diameter ambient temperature radius mm
dimeter thickness 20°C of 30°C in free air fixed mobile
mm2 mm mm mm kg/km Ohm/km mobile service install. service
Sexenie Diametr Srednåå Maks. Obwij Maks. Dopustimaå tokovaå Min. radius
Ÿil provodnik tokwina vneqnij ves soprotivlenie nagruzka (A) pri izgiba
a izolåcii diametr pri temperature 30°C na otkrytom fiks PodviŸ
postroånnom vozduhe, podviŸnoe primenenie montaŸ montaŸ
toke, pri 20°C
mm2 mm mm mm kg/km Ohm/km

SECTION 1,5 mm2 with yellow/green / SEXENIE 1,5 mm2 (s Ÿelto-zelenoj Ÿiloj)
7G 1,5 0,8 17 360 13,3 11 70 170
12 G 1,5 0,8 20,5 495 13,3 9 85 210
SECTION 2,5 mm with yellow/green / SEXENIE 2,5 mm (s Ÿelto-zelenoj Ÿiloj)
2 2

7G 2,5 0,9 19 530 7,98 15 80 190


12 G 2,5 0,9 24 760 7,98 12,5 100 240
Notes: The range of quadripolar cables has been calculated for three active conductors.
Primexanie: Rasxety dlå xetyrehŸil∫nyh kabelej proizvedeny s uxetom togo, xto 3 provodnika faznye.

32
XLPE INSULATED CABLE WITH STRANDED MEDIUM VOLTAGE (MV)
COMPACTED CONDUCTOR, AND PVC SHEATH
KABELÊ S IZOLÅCIEJ IZ SQITOGO
POLIÈTILENA, KOMPAKTNYJ PROVODNIK, 6-35 kV
PVH VNEQNÅÅ OBOLOXKA 6-35 kB

NA2XSY - N2XSY / A2XSY - 2XSY


DIN VDE 0276-620, MSZ IEC 502 / SOGLASNO DIN VDE 0276-620, MSZ IEC 502
CONSTRUCTION
stranded, compacted aluminium or copper conductor • semiconductive conductor screen • XLPE insula-
tion • semiconductive insulation screen • bedding • copper wire screen with copper counter helix • separa-
tor layer • PVC sheath

SAMPLE FOR MARKING :


NA2XSY 1 x 240 RM/25 6/10 kV

APPLICATION :
The cable can be used in 45-60 Hz networks.

STROENIE KABELÅ
Al¥minievyj ili mednyj provodnik • izolåciå iz sqitogo poli™tilena • ™kran poverh izolå-
cii • obmotka poluprovodåwej lentoj • mednyj ™kran (mednaå) provoloka i obmotka mednoj
lentoj • obmotka lentoj • PVH vneqnåå oboloxka

PRIMER OBOZNAXENIÅ :
NA2XSY 1 x 240 RM/25 6/10 kV

PRIMENENIE :
V setåh s xastotoj 45-60 Gc.

No. of Max. diameter Max. diameter Max. diameter Nominal Max. overall Metal Weight of Current carrying
cores & nom. over over over insulation thickness of diameter content completed capacity
cross-sect. conductor insulation screen jacket of cable (kg/km) cable In In the
earth air
(mm2) (mm) (mm) (mm) (mm) (mm) Al Cu (kg/km) (A) (A)

Kol-vo Maks. Maks. Maks. Tolwina Vneqnij Ves Obwij Dopustimaå


Ÿil i diametr diametr diametr izolåcii diametr metalla ves tokovaå
sexenie provodnika provodnika provodnika kabelå nagruzka
s izolåciej s izolåciej V Na
i ™krapanom Al Cu zemle vozduhe
(mm2) (mm) (mm) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

NA2XSY - 6/10 kV
1 x 50 RM/16 8,4 17,4 18,6 2,5 27,7 145 182 874 171 181
1 x 70 RM/16 9,9 18,9 20,1 2,5 29,2 203 182 974 209 226
1 x 95 RM/16 11,6 20,6 21,8 2,5 30,9 276 182 1094 249 275
1 x 120 RM/16 13,0 22,0 23,2 2,5 32,3 348 182 1200 283 317
1 x 150 RM/25 14,5 23,5 24,7 2,5 33,8 435 283 1407 316 359
1 x 185 RM/25 16,1 25,1 26,3 2,5 35,4 537 283 1549 358 412
1 x 240 RM/25 18,3 27,3 28,5 2,5 37,6 696 283 1762 416 489
1 x 300 RM/25 20,5 29,5 30,7 2,5 39,8 870 283 1762 469 559
1 x 400 RM/35 23,6 32,6 33,8 2,5 43,3 1160 394 2473 532 651
1 x 500 RM/35 26,3 35,3 36,5 2,5 46,0 1450 394 2825 599 744

33
MEDIUM VOLTAGE (MV) XLPE INSULATED CABLE WITH STRANDED
COMPACTED CONDUCTOR AND PVC SHEATH
KABELÊ S IZOLÅCIEJ IZ SQITOGO
6-35 kV POLIÈTILENA KOMPAKTNYJ PROVODNIK
6-35 kB PVH VNEQNÅÅ OBOLOXKA

NA2XSY - N2XSY / A2XSY - 2XSY


No. of Max. diameter Max. diameter Max. diameter Nominal Max. overall Metal Weight of Current carrying
cores & nom. over over over insulation thickness of diameter content completed capacity
cross-sect. conductor insulation screen jacket of cable (kg/km) cable In In the
earth air
(mm2) (mm) (mm) (mm) (mm) (mm) Al Cu (kg/km) (A) (A)

Kol-vo Maks. Maks. Maks. Tolwina Vneqnij Ves Obwij Dopustimaå


Ÿil i diametr diametr diametr izolåcii diametr metalla ves tokovaå
sexenie provodnika provodnika provodnika kabelå nagruzka
s izolåciej s izolåciej V Na
i ™krapanom Al Cu zemle vozduhe
(mm2) (mm) (mm) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

N2XSY - 6/10 kV
1 x 50 RM/16 8,4 17,4 18,6 2,5 27,7 – 662 1187 220 234
1 x 70 RM/16 9,9 18,9 20,1 2,5 29,2 – 854 1413 269 292
1 x 95 RM/16 11,6 20,6 21,8 2,5 30,9 – 1094 1689 321 354
1 x 120 RM/16 13,0 22,0 23,2 2,5 32,3 – 1334 1952 364 407
1 x 150 RM/25 14,5 23,5 24,7 2,5 33,8 – 1723 2346 405 460
1 x 185 RM/25 16,1 25,1 26,3 2,5 35,4 – 2059 2707 457 527
1 x 240 RM/25 18,3 27,3 28,5 2,5 37,6 – 2587 3265 528 621
1 x 300 RM/25 20,5 29,5 30,7 2,5 39,8 – 3163 3870 593 709
1 x 400 RM/35 23,6 32,6 33,8 2,5 43,3 – 4234 4977 665 815
1 x 500 RM/35 26,3 35,3 36,5 2,5 46,0 – 5194 5956 739 921

NA2XSY - 12/20 kV
1 x 50 RM/16 8,4 21,6 22,8 2,5 31,9 145 182 1058 173 184
1 x 70 RM/16 9,9 23,1 24,3 2,5 33,4 203 182 1167 211 229
1 x 95 RM/16 11,6 24,8 26,0 2,5 35,1 276 182 1298 252 278
1 x 120 RM/16 13,0 26,2 27,4 2,5 36,5 348 182 1414 287 320
1 x 150 RM/25 14,5 27,7 28,9 2,5 38,0 435 283 1629 320 363
1 x 185 RM/25 16,1 29,3 30,5 2,5 39,6 537 283 1781 362 415
1 x 240 RM/25 18,3 31,5 32,7 2,5 41,8 696 283 2007 421 493
1 x 300 RM/25 20,5 33,7 34,9 2,5 44,0 870 283 2250 474 563
1 x 400 RM/35 23,6 36,8 38,0 2,5 47,5 1160 394 2751 538 652
1 x 500 RM/35 26,3 39,5 40,7 2,5 50,2 1450 394 3120 606 746

N2XSY - 12/20 kV
1 x 50 RM/16 8,4 21,6 22,8 2,5 31,9 – 662 1371 223 238
1 x 70 RM/16 9,9 23,1 24,3 2,5 33,4 – 854 1606 273 296
1 x 95 RM/16 11,6 24,8 26,0 2,5 35,1 – 1094 1893 325 358
1 x 120 RM/16 13,0 26,2 27,4 2,5 36,5 – 1334 2166 368 412
1 x 150 RM/25 14,5 27,7 28,9 2,5 38,0 – 1723 2566 410 466
1 x 185 RM/25 16,1 29,3 30,5 2,5 39,6 – 2059 2939 463 532
1 x 240 RM/25 18,3 31,5 32,7 2,5 41,8 – 2587 3510 534 627
1 x 300 RM/25 20,5 33,7 34,9 2,5 44,0 – 3163 4128 601 715
1 x 400 RM/35 23,6 36,8 38,0 2,5 47,5 – 4234 5255 674 816
1 x 500 RM/35 26,3 39,5 40,7 2,5 50,2 – 5194 6251 750 927

34
XLPE INSULATED CABLE WITH STRANDED MEDIUM VOLTAGE (MV)
COMPACTED CONDUCTOR AND PVC SHEATH
KABELÊ S IZOLÅCIEJ IZ SQITOGO
POLIÈTILENA KOMPAKTNYJ PROVODNIK 6-35 kV
PVH VNEQNÅÅ OBOLOXKA 6-35 kB

NA2XSY - N2XSY / A2XSY - 2XSY


No. of Max. diameter Max. diameter Max. diameter Nominal Max. overall Metal Weight of Current carrying
cores & nom. over over over insulation thickness of diameter content completed capacity
cross-sect. conductor insulation screen jacket of cable (kg/km) cable In In the
earth air
(mm2) (mm) (mm) (mm) (mm) (mm) Al Cu (kg/km) (A) (A)

Kol-vo Maks. Maks. Maks. Tolwina Vneqnij Ves Obwij Dopustimaå


Ÿil i diametr diametr diametr izolåcii diametr metalla ves tokovaå
sexenie provodnika provodnika provodnika kabelå nagruzka
s izolåciej s izolåciej V Na
i ™krapanom Al Cu zemle vozduhe
(mm2) (mm) (mm) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

NA2XSY - 18/30 kV
1 x 50 RM/16 8,4 26,6 27,8 2,5 36,9 145 182 1312 175 187
1 x 70 RM/16 9,9 28,1 29,3 2,5 38,4 203 182 1432 214 232
1 x 95 RM/16 11,6 29,8 31,8 2,5 40,1 276 182 1575 256 281
1 x 120 RM/16 13,0 31,2 32,4 2,5 41,5 348 182 1699 290 323
1 x 150 RM/25 14,5 32,7 33,9 2,5 43,0 435 283 1926 324 365
1 x 185 RM/25 16,1 34,3 35,5 2,5 44,6 537 283 2090 366 418
1 x 240 RM/25 18,3 36,5 37,7 2,5 46,8 696 283 2331 426 494
1 x 300 RM/25 20,5 38,7 39,9 2,5 49,0 870 283 2591 479 564
1 x 400 RM/35 23,6 41,8 43,0 2,5 52,7 1160 394 3138 545 654
1 x 500 RM/35 26,3 44,5 45,7 2,6 55,4 1450 394 3529 614 747

N2XSY - 18/30 kV
1 x 50 RM/16 8,4 26,6 27,8 2,5 36,9 – 662 1625 226 241
1 x 70 RM/16 9,9 28,1 29,3 2,5 38,4 – 854 1871 276 299
1 x 95 RM/16 11,6 29,8 31,8 2,5 40,1 – 1094 2170 329 362
1 x 120 RM/16 13,0 31,2 32,4 2,5 41,5 – 1334 2451 373 416
1 x 150 RM/25 14,5 32,7 33,9 2,5 43,0 – 1723 2865 415 469
1 x 185 RM/25 16,1 34,3 35,5 2,5 44,6 – 2059 3248 468 536
1 x 240 RM/25 18,3 36,5 37,7 2,5 46,8 – 2587 3834 541 630
1 x 300 RM/25 20,5 38,7 39,9 2,5 49,0 – 3163 4469 608 717
1 x 400 RM/35 23,6 41,8 43,0 2,5 52,7 – 4234 5618 684 823
1 x 500 RM/35 26,3 44,5 45,7 2,5 55,4 – 5194 6660 762 929

A2XSY - 20/35 kV
1 x 50 RM/16 8,4 28,2 29,4 2,5 38,5 145 182 1401 175 187
1 x 70 RM/16 9,9 29,7 30,9 2,5 40,0 203 182 1524 214 232
1 x 95 RM/16 11,6 31,4 32,6 2,5 41,7 276 182 1672 256 281
1 x 120 RM/16 13,0 32,8 34,0 2,5 43,1 348 182 1798 290 323
1 x 150 RM/25 14,5 34,3 35,5 2,5 44,6 435 283 2028 324 365
1 x 185 RM/25 16,1 35,9 37,1 2,5 46,2 537 283 2197 366 418
1 x 240 RM/25 18,3 38,1 39,3 2,5 48,4 696 283 2444 426 494
1 x 300 RM/25 20,5 40,3 41,5 2,5 50,6 870 283 2707 479 564
1 x 400 RM/35 23,6 43,4 44,6 2,6 54,3 1160 394 3263 545 654
1 x 500 RM/35 26,3 46,1 47,3 2,7 57,2 1450 394 3686 614 747

35
MEDIUM VOLTAGE (MV) XLPE INSULATED CABLE WITH STRANDED
COMPACTED CONDUCTOR AND PVC SHEATH
KABELÊ S IZOLÅCIEJ IZ SQITOGO
6-35 kV POLIÈTILENA KOMPAKTNYJ PROVODNIK
6-35 kB PVH VNEQNÅÅ OBOLOXKA

NA2XSY - N2XSY / A2XSY - 2XSY


No. of Max. diameter Max. diameter Max. diameter Nominal Max. overall Metal Weight of Current carrying
cores & nom. over over over insulation thickness of diameter content completed capacity
cross-sect. conductor insulation screen jacket of cable (kg/km) cable In In the
earth air
(mm2) (mm) (mm) (mm) (mm) (mm) Al Cu (kg/km) (A) (A)

Kol-vo Maks. Maks. Maks. Tolwina Vneqnij Ves Obwij Dopustimaå


Ÿil i diametr diametr diametr izolåcii diametr metalla ves tokovaå
sexenie provodnika provodnika provodnika kabelå nagruzka
s izolåciej s izolåciej V Na
i ™krapanom Al Cu zemle vozduhe
(mm2) (mm) (mm) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

2XSY - 20/35 KV
1 x 50 RM/16 8,4 28,2 29,4 2,5 38,5 - 662 1714 226 241
1 x 70 RM/16 9,9 29,7 30,9 2,5 40,0 - 854 1963 276 299
1 x 95 RM/16 11,6 31,4 32,6 2,5 41,7 - 1094 2267 329 362
1 x 120 RM/16 13,0 32,8 34,0 2,5 43,1 - 1334 2550 373 416
1 x 150 RM/25 14,5 34,3 35,5 2,5 44,6 - 1723 2967 415 469
1 x 185 RM/25 16,1 35,9 37,1 2,5 46,2 - 2059 3355 468 536
1 x 240 RM/25 18,3 38,1 39,3 2,5 48,4 - 2587 3947 541 630
1 x 300 RM/25 20,5 40,3 41,5 2,5 50,6 - 3163 4585 608 717
1 x 400 RM/35 23,6 43,4 44,6 2,6 54,3 - 4234 5767 684 823
1 x 500 RM/35 26,3 46,1 47,3 2,7 57,2 - 5194 6817 762 929

36
XLPE INSULATED CABLE WITH STRANDED MEDIUM VOLTAGE (MV)
COMPACTED CONDUCTOR AND PE SHEATH
KABELÊ S IZOLÅCIEJ IZ SQITOGO
POLIÈTILENA KOMPAKTNYJ PROVODNIK 6-35 kV
PÈ VNEQNÅÅ OBOLOXKA 6-35 kB

NA2XS2Y - N2XS2Y / A2XS2Y - 2XS2Y


DIN VDE 0273, MSZ IEC 502 / SOGLASNO DIN VDE 0273, MSZ IEC 502
CONSTRUCTION
Stranded, compacted aluminium or copper conductor • semiconductive conductor screen • XLPE insula-
tion • semiconductive insulation screen • bedding • copper wire screen with copper counter helix • separa-
tion layer • PE sheath

SAMPLE FOR MARKING :


NA2XS2Y 1 x 240RM/25 6/10 kV

APPLICATION :
The cable is applicable in 45-60 Hz networks.

STROENIE KABELÅ
Al¥minievyj ili mednyj provodnik • ™kran provodnika • izolåciå iz sqitogo poli™tilena •
™kran poverh izolåcii • obmotka lentoj • mednyj ™kran (mednaå) provoloka i obmotka mednoj
lentoj • obmotka lentoj • PÈ vneqnåå oboloxka

PRIMER OBOZNAXENIÅ :
NA2XS2Y 1 x 240RM/25 6/10 kV

PRIMENENIE :
V setåh s xastotoj 45-60 Gc.

No. of Max. diameter Max. diameter Max. diameter Nominal Max. overall Metal Weight of Current carrying
cores & nom. over over over insulation thickness of diameter content completed capacity
cross-sect. conductor insulation screen jacket of cable (kg/km) cable In In the
earth air
(mm2) (mm) (mm) (mm) (mm) (mm) Al Cu (kg/km) (A) (A)

Kol-vo Maks. Maks. Maks. Tolwina Vneqnij Ves Obwij Dopustimaå


Ÿil i diametr diametr diametr izolåcii diametr metalla ves tokovaå
sexenie provodnika provodnika provodnika kabelå nagruzka
s izolåciej s izolåciej V Na
i ™krapanom Al Cu zemle vozduhe
(mm2) (mm) (mm) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

NA2XS2Y - 6/10 kV
1 x 50 RM/16 8,4 17,4 18,6 2,5 27,7 145 182 765 171 181
1 x 70 RM/16 9,9 18,9 20,1 2,5 29,2 203 182 589 209 226
1 x 95 RM/16 11,6 20,6 21,8 2,5 30,9 276 182 971 249 275
1 x 120 RM/16 13,0 22,0 23,2 2,5 32,3 348 182 1071 283 317
1 x 150 RM/25 14,5 23,5 24,7 2,5 33,8 435 283 1272 316 359
1 x 185 RM/25 16,1 25,1 26,3 2,5 35,4 537 283 1407 358 412
1 x 240 RM/25 18,3 27,3 28,5 2,5 37,6 696 283 1610 416 489
1 x 300 RM/25 20,5 29,5 30,7 2,5 39,8 870 283 1830 469 559
1 x 400 RM/35 23,6 32,6 33,8 2,5 43,3 1160 394 2297 532 651
1 x 500 RM/35 26,3 35,3 36,5 2,5 46,0 1450 394 2637 599 744

37
MEDIUM VOLTAGE (MV) XLPE INSULATED CABLE WITH STRANDED
COMPACTED CONDUCTOR AND PE SHEATH
KABELÊ S IZOLÅCIEJ IZ SQITOGO
6-35 kV POLIÈTILENA KOMPAKTNYJ PROVODNIK
6-35 kB PÈ VNEQNÅÅ OBOLOXKA

NA2XSY - N2XSY / A2XSY - 2XSY


No. of Max. diameter Max. diameter Max. diameter Nominal Max. overall Metal Weight of Current carrying
cores & nom. over over over insulation thickness of diameter content completed capacity
cross-sect. conductor insulation screen jacket of cable (kg/km) cable In In the
earth air
(mm2) (mm) (mm) (mm) (mm) (mm) Al Cu (kg/km) (A) (A)

Kol-vo Maks. Maks. Maks. Tolwina Vneqnij Ves Obwij Dopustimaå


Ÿil i diametr diametr diametr izolåcii diametr metalla ves tokovaå
sexenie provodnika provodnika provodnika kabelå nagruzka
s izolåciej s izolåciej V Na
i ™krapanom Al Cu zemle vozduhe
(mm2) (mm) (mm) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

N2XS2Y - 6/10 kV
1 x 50 RM/16 8,4 17,4 18,6 2,5 27,7 - 662 1078 220 234
1 x 70 RM/16 9,9 18,9 20,1 2,5 29,2 - 854 1298 269 292
1 x 95 RM/16 11,6 20,6 21,8 2,5 30,9 - 1094 1566 321 354
1 x 120 RM/16 13,0 22,0 23,2 2,5 32,3 - 1334 1823 364 407
1 x 150 RM/25 14,5 23,5 24,7 2,5 33,8 - 1723 2211 405 460
1 x 185 RM/25 16,1 25,1 26,3 2,5 35,4 - 2059 2565 457 527
1 x 240 RM/25 18,3 27,3 28,5 2,5 37,6 - 2587 3113 528 621
1 x 300 RM/25 20,5 29,5 30,7 2,5 39,8 - 3163 3708 593 709
1 x 400 RM/35 23,6 32,6 33,8 2,5 43,3 - 4234 4801 665 815
1 x 500 RM/35 26,3 35,3 36,5 2,5 46,0 - 5194 5768 739 921

NA2XS2Y - 12/20 kV
1 x 50 RM/16 8,4 21,6 22,8 2,5 31,9 145 182 931 173 184
1 x 70 RM/16 9,9 23,1 24,3 2,5 33,4 203 182 1034 211 229
1 x 95 RM/16 11,6 24,8 26,0 2,5 35,1 276 182 1158 252 278
1 x 120 RM/16 13,0 26,2 27,4 2,5 36,5 348 182 1267 287 320
1 x 150 RM/25 14,5 27,7 28,9 2,5 38,0 435 283 1457 320 363
1 x 185 RM/25 16,1 29,3 30,5 2,5 39,6 537 283 1621 362 415
1 x 240 RM/25 18,3 31,5 32,7 2,5 41,8 696 283 1837 421 493
1 x 300 RM/25 20,5 33,7 34,9 2,5 44,0 870 283 2070 474 563
1 x 400 RM/35 23,6 36,8 38,0 2,5 47,5 1160 394 2555 538 652
1 x 500 RM/35 26,3 39,5 40,7 2,5 50,2 1450 394 2913 606 746

N2XS2Y - 12/20 kV
1 x 50 RM/16 8,4 21,6 22,8 2,5 31,9 - 662 1244 223 238
1 x 70 RM/16 9,9 23,1 24,3 2,5 33,4 - 854 1473 373 296
1 x 95 RM/16 11,6 24,8 26,0 2,5 35,1 - 1094 1753 325 358
1 x 120 RM/16 13,0 26,2 27,4 2,5 36,5 - 1334 2019 368 412
1 x 150 RM/25 14,5 27,7 28,9 2,5 38,0 - 1723 2414 410 466
1 x 185 RM/25 16,1 29,3 30,5 2,5 39,6 - 2059 2779 463 532
1 x 240 RM/25 18,3 31,5 32,7 2,5 41,8 - 2587 3340 534 627
1 x 300 RM/25 20,5 33,7 34,9 2,5 44,0 - 3163 3948 601 715
1 x 400 RM/35 23,6 36,8 38,0 2,5 47,5 - 4234 5059 674 816
1 x 500 RM/35 26,3 39,5 40,7 2,5 50,2 - 5194 6044 750 927

38
XLPE INSULATED CABLE WITH STRANDED MEDIUM VOLTAGE (MV)
COMPACTED CONDUCTOR AND PE SHEATH
KABELÊ S IZOLÅCIEJ IZ SQITOGO
POLIÈTILENA KOMPAKTNYJ PROVODNIK 6-35 kV
PÈ VNEQNÅÅ OBOLOXKA 6-35 kB

NA2XSY - N2XSY / A2XSY - 2XSY


No. of Max. diameter Max. diameter Max. diameter Nominal Max. overall Metal Weight of Current carrying
cores & nom. over over over insulation thickness of diameter content completed capacity
cross-sect. conductor insulation screen jacket of cable (kg/km) cable In In the
earth air
(mm2) (mm) (mm) (mm) (mm) (mm) Al Cu (kg/km) (A) (A)

Kol-vo Maks. Maks. Maks. Tolwina Vneqnij Ves Obwij Dopustimaå


Ÿil i diametr diametr diametr izolåcii diametr metalla ves tokovaå
sexenie provodnika provodnika provodnika kabelå nagruzka
s izolåciej s izolåciej V Na
i ™krapanom Al Cu zemle vozduhe
(mm2) (mm) (mm) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

NA2XS2Y - 18/30 kV
1 x 50 RM/16 8,4 26,6 27,8 2,5 36,9 145 182 1163 175 187
1 x 70 RM/16 9,9 28,1 29,3 2,5 38,4 203 182 1276 214 232
1 x 95 RM/16 11,6 29,8 31,0 2,5 40,1 276 182 1413 256 281
1 x 120 RM/16 13,0 31,2 32,4 2,5 41,5 348 182 1530 290 323
1 x 150 RM/25 14,5 32,7 33,9 2,5 43,0 435 283 1750 324 365
1 x 185 RM/25 16,1 34,3 35,5 2,5 44,6 537 283 1908 366 418
1 x 240 RM/25 18,3 36,5 37,7 2,5 46,8 696 283 2139 426 494
1 x 300 RM/25 20,5 38,7 39,9 2,5 49,0 870 283 2390 479 564
1 x 400 RM/35 23,6 41,8 43,0 2,5 52,7 1160 394 2897 545 654
1 x 500 RM/35 26,3 44,5 45,7 2,6 55,4 1450 394 3293 614 747

N2XS2Y - 18/30 kV
1 x 50 RM/16 8,4 26,6 27,8 2,5 36,9 - 662 1476 226 241
1 x 70 RM/16 9,9 28,1 29,3 2,5 38,4 - 854 1715 276 299
1 x 95 RM/16 11,6 29,8 31,0 2,5 40,1 - 1094 2008 329 362
1 x 120 RM/16 13,0 31,2 32,4 2,5 41,5 - 1334 2282 373 416
1 x 150 RM/25 14,5 32,7 33,9 2,5 43,0 - 1723 2689 415 469
1 x 185 RM/25 16,1 34,3 35,5 2,5 44,6 - 2059 3066 468 536
1 x 240 RM/25 18,3 36,5 37,7 2,5 46,8 - 2587 3642 541 630
1 x 300 RM/25 20,5 38,7 39,9 2,5 49,0 - 3163 4268 608 717
1 x 400 RM/35 23,6 41,8 43,0 2,5 52,7 - 4234 5401 684 823
1 x 500 RM/35 26,3 44,5 45,7 2,6 55,4 - 5194 6529 762 929

A2XS2Y - 20/35 kV
1 x 50 RM/16 8,4 28,2 29,4 2,5 38,5 145 182 1245 175 187
1 x 70 RM/16 9,9 29,7 30,9 2,5 40,0 203 182 1362 214 232
1 x 95 RM/16 11,6 31,4 32,6 2,5 41,7 276 182 1502 256 281
1 x 120 RM/16 13,0 32,8 34,0 2,5 43,1 348 182 1622 290 323
1 x 150 RM/25 14,5 34,3 35,5 2,5 44,6 435 283 1846 324 365
1 x 185 RM/25 16,1 35,9 37,1 2,5 46,2 537 283 2008 366 418
1 x 240 RM/25 18,3 38,1 39,3 2,5 48,4 696 283 2245 426 494
1 x 300 RM/25 20,5 40,3 41,5 2,5 50,6 870 283 2498 479 564
1 x 400 RM/35 23,6 43,4 44,6 2,6 54,3 1160 394 3031 545 654
1 x 500 RM/35 26,3 46,1 47,3 2,7 57,2 1450 394 3432 614 747

39
MEDIUM VOLTAGE (MV) XLPE INSULATED CABLE WITH STRANDED
COMPACTED CONDUCTOR AND PE SHEATH
KABELÊ S IZOLÅCIEJ IZ SQITOGO
6-35 kV POLIÈTILENA KOMPAKTNYJ PROVODNIK
6-35 kB PÈ VNEQNÅÅ OBOLOXKA

NA2XSY - N2XSY / A2XSY - 2XSY


No. of Max. diameter Max. diameter Max. diameter Nominal Max. overall Metal Weight of Current carrying
cores & nom. over over over insulation thickness of diameter content completed capacity
cross-sect. conductor insulation screen jacket of cable (kg/km) cable In In the
earth air
(mm2) (mm) (mm) (mm) (mm) (mm) Al Cu (kg/km) (A) (A)

Kol-vo Maks. Maks. Maks. Tolwina Vneqnij Ves Obwij Dopustimaå


Ÿil i diametr diametr diametr izolåcii diametr metalla ves tokovaå
sexenie provodnika provodnika provodnika kabelå nagruzka
s izolåciej s izolåciej V Na
i ™krapanom Al Cu zemle vozduhe
(mm2) (mm) (mm) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

2XSY - 20/35 KV
1 x 50 RM/16 8,4 28,2 29,4 2,5 38,5 - 662 1558 226 241
1 x 70 RM/16 9,9 29,7 30,9 2,5 40,0 - 854 1801 276 299
1 x 95 RM/16 11,6 31,4 32,6 2,5 41,7 - 1094 2097 329 362
1 x 120 RM/16 13,0 32,8 34,0 2,5 43,1 - 1334 2374 373 416
1 x 150 RM/25 14,5 34,3 35,5 2,5 44,6 - 1723 2785 415 469
1 x 185 RM/25 16,1 35,9 37,1 2,5 46,2 - 2059 3166 468 536
1 x 240 RM/25 18,3 38,1 39,3 2,5 48,4 - 2587 3748 541 630
1 x 300 RM/25 20,5 40,3 41,5 2,5 50,6 - 3163 4376 608 717
1 x 400 RM/35 23,6 43,4 44,6 2,6 54,3 - 4234 5551 684 823
1 x 500 RM/35 26,3 46,1 47,3 2,7 57,2 - 5194 6563 762 929

40
XLPE INSULATED LONGITUDINALLY WATERTIGHT CABLE MEDIUM VOLTAGE (MV)
WITH STRANDED COMPACTED CONDUCTOR
AND WITH PE SHEATH
KABELÊ S IZOLÅCIEJ IZ SQITOGO POLIÈTILENA 6-35 kV
VODONEPRONICAEMYJ S KOMPAKTNYM 6-35 kB
PROVODNIKOM PÈ VNEQNEJ OBOLOXKOJ

NA2XS(F)2Y - N2XS(F)2Y / A2XS(F)2Y - 2XS(F)2Y


DIN VDE 0276-620, MSZ IEC 502 / SOGLASNO DIN VDE 0276-620, MSZ IEC 502
CONSTRUCTION
Stranded, compacted aluminium or copper conductor • semiconductive conductor screen • XLPE insula-
tion • semiconductive insulation screen • bedding • copper wire screen with copper counter helix • separa-
tion layer • PE sheath

SAMPLE FOR MARKING :


NA2XS(F)2Y 1 x 240RM/25 6/10 kV

APPLICATION :
The cable is applicable in 45-60 Hz frequency networks.

STROENIE KABELÅ
Al¥minievyj ili mednyj provodnik • ™kran provodnika • izolåciå iz sqitogo poli™tilena •
™kran poverh izolåcii • obmotka vodonepronicaemoj lentoj • mednyj ™kran (mednaå) provo-
loka i obmotka mednoj lentoj • obmotka vodonepronicaemoj lentoj • PÈ vneqnåå oboloxka

PRIMER OBOZNAXENIÅ :
NA2XS(F)2Y 1 x 240RM/25 6/10 kV

PRIMENENIE :
V setåh s xastotoj 45-60 Gc.

No. of Max. diameter Max. diameter Max. diameter Nominal Max. overall Metal Weight of Current carrying
cores & nom. over over over insulation thickness of diameter content completed capacity
cross-sect. conductor insulation screen jacket of cable (kg/km) cable In In the
earth air
(mm2) (mm) (mm) (mm) (mm) (mm) Al Cu (kg/km) (A) (A)

Kol-vo Maks. Maks. Maks. Tolwina Vneqnij Ves Obwij Dopustimaå


Ÿil i diametr diametr diametr izolåcii diametr metalla ves tokovaå
sexenie provodnika provodnika provodnika kabelå nagruzka
s izolåciej s izolåciej V Na
i ™krapanom Al Cu zemle vozduhe
(mm2) (mm) (mm) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

NA2XS(F)2Y - 6/10 kV
1 x 50 RM/16 8,4 17,4 18,6 2,5 28,6 145 182 772 171 181
1 x 70 RM/16 9,9 18,9 20,1 2,5 30,1 203 182 866 209 226
1 x 95 RM/16 11,6 20,6 21,8 2,5 31,8 276 182 978 249 275
1 x 120 RM/16 13,0 22,0 23,2 2,5 33,2 348 182 1078 283 317
1 x 150 RM/25 14,5 23,5 24,7 2,5 34,7 435 283 1278 316 359
1 x 185 RM/25 16,1 25,1 26,3 2,5 36,3 537 283 1415 358 412
1 x 240 RM/25 18,3 27,3 28,5 2,5 38,5 696 283 1617 416 489
1 x 300 RM/25 20,5 29,5 30,7 2,5 40,7 870 283 1838 469 559
1 x 400 RM/35 23,6 32,6 33,8 2,5 44,2 1160 394 2303 532 651
1 x 500 RM/35 26,3 35,3 36,5 2,5 46,9 1450 394 2644 599 744

41
MEDIUM VOLTAGE (MV) XLPE INSULATED LONGITUDINALLY WATERTIGHT CABLE
WITH STRANDED COMPACTED CONDUCTOR
AND WITH PE SHEATH
6-35 kV KABELÊ S IZOLÅCIEJ IZ SQITOGO POLIÈTILENA
6-35 kB VODONEPRONICAEMYJ S KOMPAKTNYM
PROVODNIKOM PÈ VNEQNEJ OBOLOXKOJ

NA2XS(F)2Y - N2XS(F)2Y / A2XS(F)2Y - 2XS(F)2Y


No. of Max. diameter Max. diameter Max. diameter Nominal Max. overall Metal Weight of Current carrying
cores & nom. over over over insulation thickness of diameter content completed capacity
cross-sect. conductor insulation screen jacket of cable (kg/km) cable In In the
earth air
(mm2) (mm) (mm) (mm) (mm) (mm) Al Cu (kg/km) (A) (A)

Kol-vo Maks. Maks. Maks. Tolwina Vneqnij Ves Obwij Dopustimaå


Ÿil i diametr diametr diametr izolåcii diametr metalla ves tokovaå
sexenie provodnika provodnika provodnika kabelå nagruzka
s izolåciej s izolåciej V Na
i ™krapanom Al Cu zemle vozduhe
(mm2) (mm) (mm) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

N2XS(F)2Y - 6/10 KV
1 x 50 RM/16 8,4 17,4 18,6 2,5 28,6 - 662 1085 220 234
1 x 70 RM/16 9,9 18,9 20,1 2,5 30,1 - 854 1305 269 292
1 x 95 RM/16 11,6 20,6 21,8 2,5 31,8 - 1094 1573 321 354
1 x 120 RM/16 13,0 22,0 23,2 2,5 33,2 - 1334 1830 364 407
1 x 150 RM/25 14,5 23,5 24,7 2,5 34,7 - 1723 2217 405 460
1 x 185 RM/25 16,1 25,1 26,3 2,5 36,3 - 2059 2573 457 527
1 x 240 RM/25 18,3 27,3 28,5 2,5 38,5 - 2587 3120 528 621
1 x 300 RM/25 20,5 29,5 30,7 2,5 40,7 - 3163 3716 593 709
1 x 400 RM/35 23,6 32,6 33,8 2,5 44,2 - 4234 4807 665 815
1 x 500 RM/35 26,3 35,3 36,5 2,5 46,9 - 5194 5775 739 921

NA2XS(F)2Y - 12/20 KV
1 x 50 RM/16 8,4 21,6 22,8 2,5 32,8 145 182 939 173 184
1 x 70 RM/16 9,9 23,1 24,3 2,5 34,3 203 182 1041 211 229
1 x 95 RM/16 11,6 24,8 26,0 2,5 36,0 276 182 1166 252 278
1 x 120 RM/16 13,0 26,2 27,4 2,5 37,4 348 182 1272 287 320
1 x 150 RM/25 14,5 27,7 28,9 2,5 38,9 435 283 1482 320 363
1 x 185 RM/25 16,1 29,3 30,5 2,5 40,5 537 283 1628 362 415
1 x 240 RM/25 18,3 31,5 32,7 2,5 42,7 696 283 1843 421 493
1 x 300 RM/25 20,5 33,7 34,9 2,5 44,9 870 283 2077 474 563
1 x 400 RM/35 23,6 36,8 38,0 2,5 48,4 1160 394 2562 538 652
1 x 500 RM/35 26,3 39,5 40,7 2,5 51,1 1450 394 2920 606 746

N2XS(F)2Y - 12/20 KV
1 x 50 RM/16 8,4 21,6 22,8 2,5 32,8 - 662 1252 223 238
1 x 70 RM/16 9,9 23,1 24,3 2,5 34,3 - 854 1480 373 296
1 x 95 RM/16 11,6 24,8 26,0 2,5 36,0 - 1094 1761 325 358
1 x 120 RM/16 13,0 26,2 27,4 2,5 37,4 - 1334 2024 368 412
1 x 150 RM/25 14,5 27,7 28,9 2,5 38,9 - 1723 2421 410 466
1 x 185 RM/25 16,1 29,3 30,5 2,5 40,5 - 2059 2786 463 532
1 x 240 RM/25 18,3 31,5 32,7 2,5 42,7 - 2587 3346 534 627
1 x 300 RM/25 20,5 33,7 34,9 2,5 44,9 - 3163 3955 601 715
1 x 400 RM/35 23,6 36,8 38,0 2,5 48,4 - 4234 5066 674 816
1 x 500 RM/35 26,3 39,5 40,7 2,5 51,1 - 5194 6051 750 927

42
XLPE INSULATED LONGITUDINALLY WATERTIGHT CABLE MEDIUM VOLTAGE (MV)
WITH STRANDED COMPACTED CONDUCTOR
AND WITH PE SHEATH
KABELÊ S IZOLÅCIEJ IZ SQITOGO POLIÈTILENA 6-35 kV
VODONEPRONICAEMYJ S KOMPAKTNYM 6-35 kB
PROVODNIKOM PÈ VNEQNEJ OBOLOXKOJ

NA2XS(F)2Y - N2XS(F)2Y / A2XS(F)2Y - 2XS(F)2Y


No. of Max. diameter Max. diameter Max. diameter Nominal Max. overall Metal Weight of Current carrying
cores & nom. over over over insulation thickness of diameter content completed capacity
cross-sect. conductor insulation screen jacket of cable (kg/km) cable In In the
earth air
(mm2) (mm) (mm) (mm) (mm) (mm) Al Cu (kg/km) (A) (A)

Kol-vo Maks. Maks. Maks. Tolwina Vneqnij Ves Obwij Dopustimaå


Ÿil i diametr diametr diametr izolåcii diametr metalla ves tokovaå
sexenie provodnika provodnika provodnika kabelå nagruzka
s izolåciej s izolåciej V Na
i ™krapanom Al Cu zemle vozduhe
(mm2) (mm) (mm) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

NA2XS(F)2Y - 18/30 KV
1 x 50 RM/16 8,4 26,6 27,8 2,5 37,8 145 182 1169 175 187
1 x 70 RM/16 9,9 28,1 29,3 2,5 39,3 203 182 1283 214 232
1 x 95 RM/16 11,6 29,8 31,0 2,5 41,0 276 182 1419 256 281
1 x 120 RM/16 13,0 31,2 32,4 2,5 42,4 348 182 1536 290 323
1 x 150 RM/25 14,5 32,7 33,9 2,5 43,9 435 283 1757 324 365
1 x 185 RM/25 16,1 34,3 35,5 2,5 45,5 537 283 1915 366 418
1 x 240 RM/25 18,3 36,5 37,7 2,5 47,7 696 283 2146 426 494
1 x 300 RM/25 20,5 38,7 39,9 2,5 49,9 870 283 2396 479 564
1 x 400 RM/35 23,6 41,8 43,0 2,5 53,4 1160 394 2903 545 654
1 x 500 RM/35 26,3 44,5 45,7 2,6 56,3 1450 394 3298 614 747

N2XS(F)2Y - 18/30 KV
1 x 50 RM/16 8,4 26,6 27,8 2,5 37,8 - 662 1482 226 241
1 x 70 RM/16 9,9 28,1 29,3 2,5 39,3 - 854 1722 276 299
1 x 95 RM/16 11,6 29,8 31,0 2,5 41,0 - 1094 2014 329 362
1 x 120 RM/16 13,0 31,2 32,4 2,5 42,4 - 1334 2288 373 416
1 x 150 RM/25 14,5 32,7 33,9 2,5 43,9 - 1723 2696 415 469
1 x 185 RM/25 16,1 34,3 35,5 2,5 45,5 - 2059 3073 468 536
1 x 240 RM/25 18,3 36,5 37,7 2,5 47,7 - 2587 3649 541 630
1 x 300 RM/25 20,5 38,7 39,9 2,5 49,9 - 3163 4274 608 717
1 x 400 RM/35 23,6 41,8 43,0 2,5 53,4 - 4234 5407 684 823
1 x 500 RM/35 26,3 44,5 45,7 2,6 56,3 - 5194 6429 762 929

A2XS(F)2Y - 20/35 KV
1 x 50 RM/16 8,4 28,2 29,4 2,5 39,4 145 182 1251 175 187
1 x 70 RM/16 9,9 29,7 30,9 2,5 40,9 203 182 1368 214 232
1 x 95 RM/16 11,6 31,4 32,6 2,5 42,6 276 182 1508 256 281
1 x 120 RM/16 13,0 32,8 34,0 2,5 44,0 348 182 1629 290 323
1 x 150 RM/25 14,5 34,3 35,5 2,5 45,5 435 283 1853 324 365
1 x 185 RM/25 16,1 35,9 37,1 2,5 47,1 537 283 2015 366 418
1 x 240 RM/25 18,3 38,1 39,3 2,5 49,3 696 283 2251 426 494
1 x 300 RM/25 20,5 40,3 41,5 2,5 51,5 870 283 2505 479 564
1 x 400 RM/35 23,6 43,4 44,6 2,6 55,2 1160 394 3036 545 654
1 x 500 RM/35 26,3 46,1 47,3 2,7 58,1 1450 394 3438 614 747

43
MEDIUM VOLTAGE (MV) XLPE INSULATED, LONGITUDINALLY WATERTIGHT CABLE
WITH STRANDED COMPACTED CONDUCTOR
AND WITH PE SHEATH
6-35 kV KABELÊ S IZOLÅCIEJ IZ SQITOGO POLIÈTILENA
6-35 kB VODONEPRONICAEMYJ S KOMPAKTNYM
PROVODNIKOM PÈ VNEQNEJ OBOLOXKOJ

NA2XS(F)2Y - N2XS(F)2Y / A2XS(F)2Y - 2XS(F)2Y


No. of Max. diameter Max. diameter Max. diameter Nominal Max. overall Metal Weight of Current carrying
cores & nom. over over over insulation thickness of diameter content completed capacity
cross-sect. conductor insulation screen jacket of cable (kg/km) cable In In the
earth air
(mm2) (mm) (mm) (mm) (mm) (mm) Al Cu (kg/km) (A) (A)

Kol-vo Maks. Maks. Maks. Tolwina Vneqnij Ves Obwij Dopustimaå


Ÿil i diametr diametr diametr izolåcii diametr metalla ves tokovaå
sexenie provodnika provodnika provodnika kabelå nagruzka
s izolåciej s izolåciej V Na
i ™krapanom Al Cu zemle vozduhe
(mm2) (mm) (mm) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

2XS(F)2Y - 20/35 KV
1 x 50 RM/16 8,4 28,2 29,4 2,5 39,4 - 662 1564 226 241
1 x 70 RM/16 9,9 29,7 30,9 2,5 40,9 - 854 1807 276 299
1 x 95 RM/16 11,6 31,4 32,6 2,5 42,6 - 1094 2103 329 362
1 x 120 RM/16 13,0 32,8 34,0 2,5 44,0 - 1334 2381 373 416
1 x 150 RM/25 14,5 34,3 35,5 2,5 45,5 - 1723 2792 415 469
1 x 185 RM/25 16,1 35,9 37,1 2,5 47,1 - 2059 3173 468 536
1 x 240 RM/25 18,3 38,1 39,3 2,5 49,3 - 2587 3754 541 630
1 x 300 RM/25 20,5 40,3 41,5 2,5 51,5 - 3163 4383 608 717
1 x 400 RM/35 23,6 43,4 44,6 2,6 55,2 - 4234 5540 684 823
1 x 500 RM/35 26,3 46,1 47,3 2,7 58,1 - 5194 6569 762 929

44
STRANDED OF THREE SINGLE CORES CABLES MEDIUM VOLTAGE (MV)

TREH‚ILÊNYJ KABELÊ S IZOLÅCIEJ IZ SQITOGO


POLIÈTILENA PÈ VNEQNÅÅ OBOLOXKA
6-35 kV
6-35 kB

NA2XS(F)2Y
DIN VDE 0276-620, MSZ IEC 502 / SOGLASNO DIN VDE 0276-620, MSZ IEC 502
CONSTRUCTION
Stranded, compacted aluminium conductor • semiconductive conductor screen • XLPE insulation • semi-
conductive insulation screen • swellable bedding • copper wire screen with copper counter helix • swella-
ble tape • PE sheath • three single cores stranded

SAMPLE FOR MARKING :


NA2XS(F)2Y 3 x 1 x 240 RM/25 6/10 kV

APPLICATION :
The cable is applicable in 45-60 Hz networks.

STROENIE KABELÅ
Al¥minievyj ili mednyj provodnik • ™kran provodnika • izolåciå iz sqitogo poli™tilena •
™kran poverh izolåcii • obmotka vodonepronicaemoj lentoj • mednyj ™kran (mednaå) provo-
loka i obmotka mednoj lentoj • obmotka vodonepronicaemoj lentoj • PÈ vneqnåå oboloxka

PRIMER OBOZNAXENIÅ :
NA2XS(F)2Y 3 x 1 x 240 RM/25 6/10 kV

PRIMENENIE :
V setåh s xastotoj 45-60 Gc.

No. of Max. diameter Max. diameter Max. diameter Nominal Max. overall Metal Weight of Current carrying
cores & nom. over over over insulation thickness of diameter content completed capacity
cross-sect. conductor insulation screen jacket of cable (kg/km) cable In In the
earth air
(mm2) (mm) (mm) (mm) (mm) (mm) Al Cu (kg/km) (A) (A)

Kol-vo Maks. Maks. Maks. Tolwina Vneqnij Ves Obwij Dopustimaå


Ÿil i diametr diametr diametr izolåcii diametr metalla ves tokovaå
sexenie provodnika provodnika provodnika kabelå nagruzka
s izolåciej s izolåciej V Na
i ™krapanom Al Cu zemle vozduhe
(mm2) (mm) (mm) (mm) (mm) (mm) (kg/km) (kg/km) (A) (A)

NA2XS(F)2Y - 6/10 kV
3x1x95 RM/16 11,6 20,6 21,8 2,5 31,8 828 546 2964 249 275
3x1x120RM/16 13,0 22,0 23,2 2,5 33,2 1044 546 3267 283 317
3x1x150RM/25 14,5 23,5 24,7 2,5 34,7 1305 849 3873 316 359
3x1x185RM/25 16,1 25,1 26,3 2,5 36,3 1611 849 4288 358 412
3x1x240RM/25 18,3 27,3 28,5 2,5 38,5 2088 849 4900 416 489
3x1x300RM/25 20,5 29,5 30,7 2,5 40,7 2610 849 5570 469 559

NA2XS(F)2Y - 12/20 kV
3x1x95 RM/16 11,6 24,8 26,0 2,5 36,0 828 546 3555 252 278
3x1x120RM/16 13,0 26,2 27,4 2,5 37,4 1044 546 3855 287 320
3x1x150RM/25 14,5 27,7 28,9 2,5 38,9 1305 849 4491 320 363
3x1x185RM/25 16,1 29,3 30,5 2,5 40,5 1611 849 4933 362 415
3x1x240RM/25 18,3 31,5 32,7 2,5 42,7 2088 849 5585 421 493

45
LOW VOLTAGE (LV) I N S U L AT E D O V E R H E A D C O N D U C T O R S
PODVESNYE IZOLIROVANNYE PROVODA
NA NAPRłENIE
0,6/1 kV
0,6/1 kB

There are two main groups of product: 1. Self supporting conductors 2. Conductors with messenger
Suwestvuet 2 osnovnyh tipa produkcii: 1. Samonesuwie provoda 2. Provoda s nesuwej Ÿiloj

1. Construction of the self-supported type: 2. Construction with messenger:


1.1 Material of conductor: Al-99, 5-E Aluminium 2.1 Material of conductor: Al-99, 5-E Aluminium
1.2 Conductor: stranded, compacted, round 2.2 Conductor: stranded, compacted , round
1.3 Insulation: UV proof cross linked PE (XLPE) 2.3 Insulation: UV proof cross linked PE (XLPE)
1.4 Cable bundles: insulated cores are stranded together with 2.4 Messenger cable:
a lay ratio of 20-30 D (D=Bundle Diameter) Material: AlMgSI-E Aldrey
Generally, the insulated cores have the same cross-section, Execution: stranded, compacted , round
however as per request lighting core could be used.
Insulation: UV proof cross linked PE (XLPE)
The cores are clamped and stringed independently at installa-
tion. 2.5 Cable bundles: insulated cores are stranded around to the
messenger cable with a lay ratio of 20-30 D (D=Bundle
Diameter)
Generally, core for lighting included.
The messenger cable is gripped at installation, bearing the
mechanical load and acting as “0” conductor at the same time.

1. Konstrukciå samonesuwih provodov: 2. Konstrukciå provodov s nesuwej Ÿiloj:


1.1 Material provodnika: Al-99, Al¥minij 5-E 2.1 Material provodnika: Al-99, Al¥minij 5-E
1.2 Provodnik: vitoj, kompaktnyj, kruglyj 2.2 Provodnik: vitoj, kompaktnyj, kruglyj
1.3 Izolåciå: Sqityj poli™tilen, stokjkij k k UF iz- 2.3 Izolåciå: Sqityj poli™tilen, stokjkij k k UF iz-
luxeni¥ luxeni¥
1.4 Kabel∫nye puxki: Izolirovannye Ÿily skruxeny v 2.4 Nesuwaå Ÿila:
puxk, radius izgiba - 20-30 diamerov puxka. Izolåciå: Sqityj poli™tilen, stojkij k k UF iz-
Obyxno, vse Ÿily ime¥t odinakovoe sexenie, odnako, po luxeni¥
zaprosu vozmoŸno izgotovlenie odnoj Ÿily menyqego 2.5 Kabel∫nye puxki: Isolirovannye Ÿily skryxeny v
sexeniå. puxki vokrug nesuwej Ÿily, radius izgiba - 20-30
‚ily pri montaŸe obŸima¥tså otdel∫no. diametrov puxka.
Posle obŸima nesuwaå Ÿila prinimaet na sebå meha-
nixesku¥ nagruzku, odnovremenno igraå rol∫ nulevoj.

Compact C. Al
Al
Compact Compact
Al Al Compact
Compact Aldrey
Al

Compact Compact
Al Al C. Al
Compact
Al

46
I N S U L AT E D O V E R H E A D C O N D U C T O R S LOW VOLTAGE (LV)

PODVESNYE IZOLIROVANNYE PROVODA


NA NAPRłENIE
0,6/1 kV
0,6/1 kB

Example for denomination and marking:


MKM BALASSAGYARMAT-PIRELLI 2005 NFA2X 4x70 0,6/1 kV
MKM BALASSAGYARMAT-PIRELLI 2005 NFA2X 3x70+71,5+2_16 0,6/1 kV
Cores are marked with longitudinal ribs as the figures demonstrate:
Phase conductors: 1, 2, 3, rib;
“0” conductor: without rib

Application:
Conductors are resistant to the ambient effects (cold, sunshine),
Connecting (outdoor) building, etc
Connecting to the distribution network

Primery oboznaxeniå:
MKM BALASSAGYARMAT-PIRELLI 2005 NFA2X 4x70 0,6/1 kV
MKM BALASSAGYARMAT-PIRELLI 2005 NFA2X 3x70+71,5+2_16 0,6/1 kV
‚ily markirovany prodol∫nymi nasexkami, kotorye oboznaxa¥t:
Faza: 1,2,3 nasexki
Nulevaå: bez nasexki

Primenenie:
Provoda ustojxivy k vozdejstviåm okruŸa¥wej sredy (holod, Ÿara)
Podkl¥xenie zdanij,
Podkl¥xenie k raspredelitel∫noj seti.

NFA2X NOMINAL DATA OF INSULATED CORES / Texnixeskie harakteristiki kabelå NFA2X


Conductors Messenger
Provodnik Nesuwaå Ÿila

Cross-section, mm2
16* 25 35 50 70 95 71,5
Secenie, mm2
Construction 7x1.80 7x2.20 7x2.74 7x2.20 + 7x2.40 + 7x2.74 + 7x3,73
Stroenie Ÿily 12x19.2 12x2.15 12x2.50

Diameter of conductor (mm)


4.8 5.9 6.8 8.8 9.8 11.5 10.5
Tolwina izolåvcii (mm)
Outer diameter (mm)
7.2 8.5 9.4 11.0 12.8 14.9 13.5
Vneqnik diametr (mm)

Mass (kg/km)
65 100 125 170 230 315 260
Ves (mm)
Current carrying capacity (A)
Dopustimaå tokovaå nagruzka (A) 90 107 132 165 205 240 --

Modulus of elasticity (kN/mm2)


60 60 60 58 58 58 60
Modul∫ uprugosti ( kN/mm2)
DC resistance at 20°C
Soprotivlenie pri postoånnom toke, pri 20°C 1.910 1.200 0.868 0.641 0.443 0.320 0.470

Calculated breaking load (kN)


2.84 4.17 5.78 8.45 11.32 15.68 15.20
Razrivnaå nagruzka (kN)
Standard for wires: DIN 48200 T5, T6
‚ily v sootvetstvii s DIN 48200 T5, T6

47
LOW VOLTAGE (LV) I N S U L AT E D O V E R H E A D C O N D U C T O R S
PODVESNYE IZOLIROVANNYE PROVODA
NA NAPRłENIE
0,6/1 kV
0,6/1 kB

NFA2X SIZES / Tiporazmery kabelå NFA2X


Cross-section of Denomination Mass NFA2X covering circle
insulated conductors (n. x mm2) (kg/Km) diameter (mm2)

Kol-vo Ÿil i secenie (n. x mm2) Oboznaxenie Ves (kg/km) Obqij diametr (mm2)
2x16* NAF2X 2x16 130 14
2x25* NAF2X 2x25 200 17
4x16* NAF2X 4x16 260 17
5x16* NAF2X 5x16 325 20
4x25* NAF2X 4x25 400 21
5x35* NAF2X 4x35 500 23
4x50* NAF2X 4x50 680 27
4x70* NAF2X 4x70 920 31
4x95* NAF2X 4x95 1260 36
* additional cross-section to DIN VDE D276-626 standard

NFA2X SIZES WITH 71,5 mm2 MESSENGER CABLE / Tiporazmery kabelå NFA2X s nesuwim provodnikom 71,5 mm2
Cross-section of Denomination Mass NFA2X covering circle
insulated conductors (n. x mm2) (kg/Km) diameter (mm2)

Kol-vo Ÿil i secenie (n. x mm2) Oboznaxenie Ves (kg/km) Obqij diametr (mm2)
3x35 + 71,5 NAF2X 3x35 + 71,5 670 28
3x35 + 2x16 + 71,5* NAF2X 3x35 + 2x16 + 71,5* 800 28
3x50 + 71,5 NAF2X 3x50 + 71,5 775 32
3x50 + 2x16 + 71,5* NAF2X 3x50 + 2x16 + 71,5* 905 32
3x70 + 71,5* NAF2X 3x70 + 71,5* 1000 37
3x70 + 2x16 + 71,5* NAF2X 3x70 + 2x16 + 71,5* 1130 37
* additional cross-section to DIN VDE D276-626 standard

48