PROJECT:
Construction of 33kV Substation at NTPC Lara
CUSTOMER:
NTPC , LARA
C & ELECTRIC LTD
CONTRACTOR
Client PO PROJECT: Consultant: M/s. Alif Engineers & Planners, Mumbai
Construction Power Package NTPC, Lara
DRN.
PRPD CHKD APPD
NAME
A.K. S.A S.A
SIGN
DATE
25.06.13 25.06.13 25.06.13
TITLE 11KV POLE - DESIGN CALCULATIONS DOC. NO. C&S/LARA/AEP/C/101 REV. NO. 0
DESIGN OF THE FOUNDATION FOR THE POLE INPUT DETAILS OF POLE HT h1 2.7 h2 2.7 h3 5.6 Tot Ht 11 m Self wt of the Pole
DIA OF POLE 140 163 194
241 kg = = 0.7 x 1/6 x 0.7 x 11 = 1.95 1.83 m (150mm above ground)
Minium depth of embedment Prvide Pedestal of size
1.0 WIND LOAD CALCULATION Calculation of design wind pressure Basic wind speed Reference Wind Speed VR Risk Co-efficient Terrain category Design wind Speed Design Wind Pressure Vb = = Vb/Ko k1 = (category-1 and class-A) k2 = Vd = Vb * k1 * k2 = 34.24 Pd = 0.6 Vz2 703 =
(As per IS:802 ) 44 = 1.07 1 m/s N/m2 = 70.34 kg/m2 m/s 44 / 1.375 (Reliability level -1 ) (Category -1) Wind Zone = = 32.00 m/s 3
Overturning Moment due to the wind on the pole : M = 70.34 x 70.34 x 70.34 x ( ( ( 2.7 x 2.7 x 5.6 x 0.1 ) 0.2 ) 0.2 ) x x x 9.7 x 7x 2.8 x 0.6 + 0.6 + 0.6 +
410.1 kg.mtr 241 + 0.35 = 0.7 x 0.7 x 1.95 x 2500 = 2629.75 Kg
Total weight of pole + foundation = Stabilizing Moment = 2630 x
920.4125 Kgm
Factor of Safety
2.24
>
2 Hence safe
Provide a block of 0.7 x 0.7 x 1.95 m for all pole foundation in 1:3:6 grade Concrete All foundations shall be minm 500mm below natural grund level.