Design of The Pole

This document provides design calculations for the foundation of an 11 meter high pole that is part of a 33kV substation project for NTPC Lara. It calculates the wind load on the pole based on IS 802 standards and determines that a concrete foundation with dimensions of 0.7 x 0.7 x 1.95 meters would provide a factor of safety of 2.24, greater than the required 2, to stabilize the pole against overturning from wind loads. All foundations for poles are to be this size and located at least 500mm below ground level.

Uploaded by

Irshad Khan
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
75% found this document useful (4 votes)
5K views5 pages

Design of The Pole

This document provides design calculations for the foundation of an 11 meter high pole that is part of a 33kV substation project for NTPC Lara. It calculates the wind load on the pole based on IS 802 standards and determines that a concrete foundation with dimensions of 0.7 x 0.7 x 1.95 meters would provide a factor of safety of 2.24, greater than the required 2, to stabilize the pole against overturning from wind loads. All foundations for poles are to be this size and located at least 500mm below ground level.

Uploaded by

Irshad Khan
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd

PROJECT:

Construction of 33kV Substation at NTPC Lara

CUSTOMER:

NTPC , LARA
C & ELECTRIC LTD

CONTRACTOR

Client PO PROJECT: Consultant: M/s. Alif Engineers & Planners, Mumbai

Construction Power Package NTPC, Lara


DRN.
PRPD CHKD APPD

NAME
A.K. S.A S.A

SIGN

DATE
25.06.13 25.06.13 25.06.13

TITLE 11KV POLE - DESIGN CALCULATIONS DOC. NO. C&S/LARA/AEP/C/101 REV. NO. 0

DESIGN OF THE FOUNDATION FOR THE POLE INPUT DETAILS OF POLE HT h1 2.7 h2 2.7 h3 5.6 Tot Ht 11 m Self wt of the Pole

DIA OF POLE 140 163 194

241 kg = = 0.7 x 1/6 x 0.7 x 11 = 1.95 1.83 m (150mm above ground)

Minium depth of embedment Prvide Pedestal of size

1.0 WIND LOAD CALCULATION Calculation of design wind pressure Basic wind speed Reference Wind Speed VR Risk Co-efficient Terrain category Design wind Speed Design Wind Pressure Vb = = Vb/Ko k1 = (category-1 and class-A) k2 = Vd = Vb * k1 * k2 = 34.24 Pd = 0.6 Vz2 703 =

(As per IS:802 ) 44 = 1.07 1 m/s N/m2 = 70.34 kg/m2 m/s 44 / 1.375 (Reliability level -1 ) (Category -1) Wind Zone = = 32.00 m/s 3

Overturning Moment due to the wind on the pole : M = 70.34 x 70.34 x 70.34 x ( ( ( 2.7 x 2.7 x 5.6 x 0.1 ) 0.2 ) 0.2 ) x x x 9.7 x 7x 2.8 x 0.6 + 0.6 + 0.6 +

410.1 kg.mtr 241 + 0.35 = 0.7 x 0.7 x 1.95 x 2500 = 2629.75 Kg

Total weight of pole + foundation = Stabilizing Moment = 2630 x

920.4125 Kgm

Factor of Safety

2.24

>

2 Hence safe

Provide a block of 0.7 x 0.7 x 1.95 m for all pole foundation in 1:3:6 grade Concrete All foundations shall be minm 500mm below natural grund level.