Busbar 8hort Circuit Force and 8upport Calculation. Busbar 8hort Circuit Force and 8upport Calculation.
Busbar 8hort Circuit Force and 8upport Calculation. Busbar 8hort Circuit Force and 8upport Calculation.
Applicable for Applicable for Applicable for Applicable for MCC A/C Nalco Water MCC A/C Nalco Water MCC A/C Nalco Water MCC A/C Nalco Water- -- -8M8 ndia 8M8 ndia 8M8 ndia 8M8 ndia
System Supply : 415 Volts, 3 Phase, 4 Wire 50 Hz.
Incomer Rating : 32A MCCB with SC & OC release.
Busbar Enclosure Size as per Drg. 450mm.(Width) x 400mm.(Height) x 300mm(Depth)
Busbar Size : For 50 KA Fault Level for 1 Sec, required Busbar Size is 0.75 [Link] to keep
the final temp. of Al Busbar within 180
0
C.
HENCE, 50mm x 10mm(approx [Link]) for each Phase is adequate to withstand thermal
stress due to 1sec 50KA Short-circuit Fault condition.
Selected Busbar Size:1no. each of 50mm. x 10mm. Al for Phases (RYB) & 25mm x 10mm for
Neutral Busbar.
Maximum Short Ckt. Force between Busbars.
W = 3 x 5.4 x I
2
x 10
-7
S 1bs / ft.
1 = Short Ckt. Current in Amp. = [Link] 1Sec.
FOR VERTICAL BUSBURS
S = Distance between phases in inch. = 100mm. or 3.93 3.34 inch.
W = 3 x 5.4 x 50 x 50 10
6
x 10
-7
= 1031 1bs / ft. or 15.13 Kg. / cm.
3.34
Load on support = 1.25 x W x L
L= Distance between 2 supports along the length of Busbar.
= 250 mm. Or 25cm.
Now load on supports = 1.25 x 15.13 x 25
= 483 Kg.
Tensile strength of FRP Busbar support : 1200 Kg. / Cm
2
.
Factor of safety = 2
So, allowable tensile strength = 1200 = 600 Kg / Cm
2
2
Hence minimum required cross section of support at weakest
Point under maximum stress = Maxm. Load on Support
Allowable Tensile Strength
483 Kg.
= = 0.8 [Link].
600 Kg.
30mm dia FRP Post type Hexagonal Support with 8mm dia threaded Brush Insert has been
provided for Vertical Busbars with a Cental gap of 100mm. Effective 28mm(min)x12mm area
(3..[Link]) of FRP support shall be under dynamic Stress .
So Cross Sectional area of FRP support under maximum Stress : 3.36 Cm
2
.
Remarks :Required area of Max. Stress at 50KA : 0.8 Cm
2
.
area provided by support for maximum Stress : 3.36 Cm
2
.
FACTOR OF SAFETY: 3.36/0.8 = 4.2
Hence support design is absolutely safe. FOR VERTICAL BUSBARS
Bus-Bar Calculation
is not accurate.
Please find below
the short ckt
calculation.
Kindly recheck your
Bus-Bar Calculation
for 50 kA for 1 sec.
Busbar sizing Busbar sizing Busbar sizing Busbar sizing for Busbar for Busbar for Busbar for Busbar Design using NDAL Make Design using NDAL Make Design using NDAL Make Design using NDAL Make
D508WP Grade Aluminium Busbar D508WP Grade Aluminium Busbar D508WP Grade Aluminium Busbar D508WP Grade Aluminium Busbar/Euivant from Hindalco /Euivant from Hindalco /Euivant from Hindalco /Euivant from Hindalco
Incomer Rating : 32Amps TP MCCB with SC&OC release.
Busbar Size : For 50 KA Fault Level for 1 Sec, required Busbar Size is 0.75 [Link] to keep
the final temp. of Al Busbar within 180
0
C.
HENCE, 50mm x 10mm(approx 1 [Link]) for each Phase is adequate to withstand thermal stress
due to 1sec 50KA Short-circuit Fault condition.
However, from Table 2 of HANDBOOK (INDAL ALUMINIUM BUSBARS)
50.8 mm x 9.53mm [Link] is rated for 830A @1.714 A/[Link]
76.2mm x 12.7 mm do 1863A @ 1.92A/[Link]
So, selected 50mm x 10mm Al Busbar is rated for 1.714 x 50 x 10 = 870A--------Line-A
Busbar enclosure : 450mm. (Width)
300mm. (Depth)
A. Derating Factor for Temp. Rise
considering 35
0
C ambient and 40
0
C Temp. Rise = 0.88%
and considering 50
0
C ambient and 35
0
C [Link] = 0.8%
B. Cross section of Alu Busbar : 3.5 x 50mm. x 10mm.
Volume of Busbar Chamber Compared to Volume of Busbar
= 50 x 10 x 3.5 = 1.3%
450mm x 300mm.
So,as per condition 2(Indoors where enclosure itself in a well-ventilated room)
Derating Factor 75% as per Table 5 (enclosed)
Hence, overall Derating Factor = 0.8 x 0.75 = 0.6
As per table 2 of INDAL (Enclosed) & as indicated above(Line-A)
Derated Current = 870A x 0.6 = 522 Amps.
Hence the Busbar Size 50mm. x 10mm. of Aluminium suits the requirement.
for SWITCHING CIRCUITS
DATED : 24/07/2014
(D.K. BASAK)