Product data sheet
Characteristics
RM17TE00
multifunction control relay RM17-TE - range
183..528 V AC
Range of product
Zelio Control
Product or component
type
Modular measurement and control relays
Relay type
Multifunction control relay
Product specific
application
For 3-phase supply
Relay name
RM17TE
Relay monitored
parameters
Asymmetry
Phase failure detection
Phase sequence
Undervoltage and overvoltage in window mode
Time delay
Adjustable 0.1...10 s, 10 %
Switching capacity in
VA
1250 VA
Measurement range
183...528 V AC
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Main
Complementary
Reset time
1500 ms for time delay
Maximum switching voltage
250 V AC
250 V DC
Minimum switching current
10 mA at 5 V DC
Maximum switching current
5 A AC
5 A DC
[Us] rated supply voltage
208...480 V AC 3 phases
Supply voltage limits
183...528 V AC
Control circuit voltage limits
- 12 %, + 10 % Un
Power consumption
<= 1.8 VA AC
Control circuit frequency
50...60 Hz +/- 10 %
Output contacts
1 C/O
Nominal output current
5A
Hysteresis
2%
Run up delay at power up
0.5 s time delay
Measuring cycle
<= 150 ms measurement cycle as true rms value
Threshold adjustment voltage
+2...+17 % in the range 480 V AC
-2...-12 % in the range 208 V AC
-2...-17 % in the range 220 V AC
2...20 % of Un selected
Voltage range
208 V phase to phase
220 V phase to phase
380 V phase to phase
400 V phase to phase
415 V phase to phase
440 V phase to phase
480 V phase to phase
Adjustment of asymmetry threshold
5...15 % of Un selected
Measurement accuracy
+/- 10 % of the full scale value
Repeat accuracy
0.5 % for input and measurement circuit
3 % for time delay
Measurement error
< 0.05 %/C with temperature variation
< 1 % over the whole range with voltage variation
Phase failure sensitivity
0.7 Un
Response time
< 200 ms in the event of a fault
7/9/2011
Marking
CE : 73/23/EEC
CE : EMC 89/336/EEC
Overvoltage category
III conforming to IEC 60664-1
Insulation resistance
> 500 MOhm at 500 V DC conforming to IEC 60255-5
> 500 MOhm at 500 V DC conforming to IEC 60664-1
[Ui] rated insulation voltage
400 V conforming to IEC 60664-1
Supply frequency
50/60 Hz +/- 10 %
Operating position
Any position without
Electrical connection
1 conductor cable 0.2...2.5 mm AWG24...AWG12 flexible with cable end
conforming to IEC 60947-1
1 conductor cable 0.5...4 mm AWG20...AWG11 solid without cable end
conforming to IEC 60947-1
2 conductors cable 0.2...1.5 mm AWG24...AWG16 flexible with cable end
conforming to IEC 60947-1
2 conductors cable 0.5...2.5 mm AWG20...AWG14 solid without cable end
conforming to IEC 60947-1
Tightening torque
0.6...1 N.m conforming to IEC 60947-1
Housing material
Self-extinguishing plastic
Status LED
1 LED green for power ON
1 LED yellow for relay ON
Mounting support
35 mm symmetrical DIN rail conforming to EN/IEC 60715
Electrical durability
100000 cycles
Mechanical durability
30000000 cycles
Operating rate
<= 360 operations/hour under full load
Utilisation category
AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
Width
17.5 mm
Product weight
0.13 kg
Environment
Immunity to microbreaks
10 ms
Electromagnetic compatibility
Emission standard for industrial environments conforming to EN/IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments
conforming to EN/IEC 61000-6-3
Immunity for industrial environments conforming to EN/IEC 61000-6-2
Standards
EN/IEC 60255-6
Product certifications
CSA
C-Tick
GL
GOST
UL
Ambient air temperature for storage
-40...70 C
Ambient air temperature for operation
-20...50 C
Relative humidity
95 % at 55 C conforming to IEC 60068-2-30
Vibration resistance
0.35 mm (f = 5...57.6 Hz conforming to IEC 60068-2-6/IEC 60255-21-1
1 gn (f = 57.6...150 Hz conforming to IEC 60068-2-6/IEC 60255-21-1
Shock resistance
15 gn for 11 ms conforming to IEC 60255-21-1
IP degree of protection
IP20 (terminals) conforming to IEC 60529
IP30 (casing) conforming to IEC 60529
Pollution degree
3 conforming to IEC 60664-1
Dielectric test voltage
2 kV 1 min AC 50 Hz conforming to IEC 60255-5
2 kV 1 min AC 50 Hz conforming to IEC 60664-1
Non-dissipating shock wave
4 kV conforming to IEC 60255-5
4 kV conforming to IEC 60664-1
4 kV conforming to IEC 61000-4-5
RoHS EUR status
Compliant
RoHS EUR conformity date
0701
Product data sheet
Dimensions Drawings
RM17TE00
Multifunction 3-Phase Supply Control Relays
Dimensions and Mounting
Product data sheet
Connections and Schema
Multifunction 3-Phase Supply Control Relays
Wiring Diagram
RM17TE00
Product data sheet
Technical Description
RM17TE00
Function Diagrams
Phase Sequence Control, Phase Failure Detection (U measured < 0.7 x nominal supply voltage) and Asymmetry
Detection
Tt
Time delay after crossing of threshold (adjustable on front panel)
L1, Phases of the supply voltage monitored
L2,
L3
A
Asymmetry threshold (adjustable from 5...15% of the nominal supply voltage)
H
Hysteresis
11-12,Output relay connections (refer to Connections and Schema)
11-14
Relay status: black color = energized.
Control of Overvoltage and Undervoltage in Window Mode
Tt
Time delay after crossing of threshold (adjustable on front panel)
H
Hysteresis
U> Overvoltage threshold
U< Undervoltage threshold
L1, Phases of the supply voltage monitored
L2,
L3
11-12,Output relay connections (refer to Connections and Schema)
11-14
Relay status: black color = energized.
The overvoltage and undervoltage threshold in window mode is adjustable from 220% of Un:
Un
208V
220V
380, 400, 415,
440V
480V
Voltage threshold (%)
<
- 12- 2
- 17- 2
- 20- 2
>
+ 2+
20
+ 2+ 20
+ 2+ 20
+ 2+ 10
- 20- 2