16_Sec (161-180).
qxd
07/28/03
03:38 PM
Page 16/165
SIMATIC S7 - 200 Micro PLC
General
CPU 221, 222, 224, 226, 226 XM
CPU selection chart
(Use this quick selection guide to help choose the proper CPU for your application).
Feature
Physical size of unit memory
CPU 221
CPU 222
CPU 224
90 mm x 80 mm x 62 mm
90 mm x 80 mm x 62 mm
120.5 mm x 80 mm x 62 mm 190 mm x 80 mm x 62 mm
CPU 226 (XM)
Program
2048 words
2048 words
4096 words
User data
1024 words
1024 words
2560 words
4096 words (8192)
2560 words (5120)
User program storage type
EEPROM
EEPROM
EEPROM
EEPROM
Data backup (super capacitor)
(optional battery)
50 hours typical
200 days typical
50 hours typical
200 days typical
190 hours typical
200 days typical
190 hours typical
200 days typical
Local I/O
6 In/4 Out
8 In/6 Out
14 In/10 Out
24 In/16 Out
Number of expansion modules
none
2 modules
7 modules
7 modules
Digital I/O image size
256
(128 In/128 Out)
256
(128 In/128 Out)
256
(128 In/128 Out)
256
(128 In/128 Out)
Analog I/O image size
none
16 In/16 Out
32 In/32 Out
32 In/32 Out
Local I/O
Total I/O
Actual I/O count that can be realized with each CPU may be limited by image register size, module count, 5V power, and the physical number of I/O points on
each product. Refer to the User Manual for detailed information.
Instructions
Boolean execution speed
0.37s/ instruction
0.37 s/ instruction
0.37 s/ instruction
I/O Image Register
128 I and 128 Q
128 I and 128 Q
128 I and 128 Q
0.37 s/ instruction
128 I and 128 Q
Internal relays
256
256
256
256
Counters/Timers
256/256
256/256
256/256
256/256
Word In / Word Out
None
16/16
32/32
32/32
Sequential control relays
256
256
256
256
For/Next loops
Yes
Yes
Yes
Yes
Integer math (+ - * /)
Yes
Yes
Yes
Yes
Real math (+ - * /)
Yes
Yes
Yes
Yes
Enhanced features
Built-in high-speed counter
4 H/W (20 KHz)
4 H/W (20 KHz)
6 H/W (20 KHz)
6 H/W (20 KHz)
Analog adjustments
Pulse outputs
2 (20 KHz, DC only)
2 (20 KHz, DC only)
2 (20 KHz, DC only)
2 (20 KHz, DC only)
Communication interrupts
1 transmit/
2 receive
1 transmit/
2 receive
1 transmit/
2 receive
2 transmit/
4 receive
Timed interrupts
2
(1 ms to 255 ms)
2
(1 ms to 255 ms)
2
(1 ms to 255 ms)
2
(1 ms to 255 ms)
Hardware input interrupts
4, input filter
4, input filter
4, input filter
4, input filter
Real-time clock
Yes (cartridge)
Yes (cartridge)
Yes (built-in)
Yes (built-in)
Password protection
Yes
Yes
Yes
Yes
Number of comm ports:
PPI, DP/T Baud rate
Freeport Baud rate
1 (RS485)
up to 187.5Kbaud
up to 38.4Kbaud
1 (RS485)
up to 187.5Kbaud
up to 38.4Kbaud
1 (RS485)
up to 187.5Kbaud
up to 38.4Kbaud
2 (RS485)
up to 187.5Kbaud
up to 38.4Kbaud
Protocols supported
Port 0:
Port 1:
PPI, DP/T, Freeport
N/A
PPI, DP/T, Freeport
N/A
PPI, DP/T, Freeport
N/A
PPI, DP/T, Freeport
PPI, DP/T, Freeport
Peer-to-peer
Yes, NETR/NETW
Yes, NETR/NETW
Yes, NETR/NETW
Yes, NETR/NETW
Communications
Siemens Energy & Automation, Inc.
Industrial Controls Catalog
16/165
16_Sec (161-180).qxd
07/28/03
03:38 PM
Page 16/166
SIMATIC S7 - 200 Micro PLC
General
CPU 221, 222, 224, 226, 226 XM
CPU technical specification
DC input features
Environmental conditions
Storage environment
-40 to +70C, 25 to 55C 95% humidity
Ambient operating
Environment
0 to 55 C horizontal mounting
0 to 45 C vertical mounting
95% non-condensing humidity, no corrosive gas
Mechanical shock
15 G, 11 ms pulse, 6 shocks in each of 3 axis
Sinusoidal vibration
0.30 mm peak-to-peak 10 to 57 Hz; 2 G panel
mount, 1 G DIN rail mount, 57 Hz to 150 Hz; 10
sweeps each axis, 1 octave/minute
Mechanical protection
IP 20
Agency approvals
UL, CSA, FM, CE
Input power supply 24V DC power
115/230V AC power
Line voltage-permissi- 20.4 - 28.8 VDC
ble range
Input current CPU only/ 80/900 mA at 24 VDC
max load
10 ms at 24 VDC
85 - 264 VAC, 47 - 63
Hz
15/60 mA at 240
VAC30/120 mA at 120
VAC
20 A at 264 VAC
1500 VAC
80 ms at 240 VAC,
20 ms at 120 VAC
2 A, 250 V, slow blow
2 A, 250 V, slow blow
In rush current (max)
Isolation (input power
to logic)
Hold up time (after
power loss)
Internal fuse, not
replaceable
10 A at 28.8 VDC
Not isolated
24 VDC sensor power output
Voltage range
Maximum current
Ripple noise
Current limit
Isolation (sensor power
to logic)
15.4 - 28.8 VDC
180 mA
Same as input line
600 mA
20.4 - 28.8 VDC
180 mA
Less than 1 V p-p max.
600 mA
Non-isolated
Non-isolated
Installation dimensions
Input type
Input Voltage
Maximum continuous
Surge
Rated value
Logic 1 signal (minimum)
Logic 0 signal (maximum)
Isolation (field side to logic)
Optical isolation (galvanic)
Input delay & HSC rate
Filtered inputs and interrupts
Single phase HSC
Logic 1 level = 15 to 30 VDC
Logic 1 level = 15 to 26 VDCQuadrature HSC
Logic 1 level = 15 to 30 VDC
Logic 1 level = 15 to 26 VDC
2-Wire prox. leakage
Sink/source (IEC type 1 sink)
30 VDC
35 VDC for 0.5 s
24 VDC at 4 mA, nominal
15 VDC at 2.5 mA, minimum
5 VDC at 1 mA, maximum
500 VAC for 1 minute
0.2 to 12.8 ms, user-selectable
20 kHz
30 kHz
10 kHz
20 kHz
1 mA, maximum
Output specifications
DC output
Relay output
General
Output type
Permissible range
Rated value
Logic 1 signal at max. current
Logic 0 signal with 10 K W load
Solid State-MOSFET
20.4 to 28.8 VDC
24 VDC
20 VDC, minimum
0.1 VDC, maximum
Relay, dry contact
0.75 A
2.00 A
3.0 A
4.5A
3.75A
6.0 A
5.0 W
0.3
10 A, maximum
8 A for 100 ms, max.
No
6.0 A
6.0 A
8.0 A
10.0 A
30 W DC/200 W AC
0.2 , max. when new
7 A w/ contacts closed
No
500 VAC for 1 min.
-
100 M , min. when new
1500 VAC for 1 min.
750 VAC for 1 min.
Output Current
Logic 1 signal
Max. current per common/group
CPU221
CPU222
CPU224
CPU226
Lamp load
ON state resistance (contact)
Leakage current per point
Surge current
Overload protection
Isolation
Optical isolation (galvanic)
Isolation resistance
Isolation coil to contact
Isolation between open contacts
Inductive Load Clamping
Repetitive Energy dissipation
1 W, all channels
0.5 LI2 x switch. rate
Clamp voltage limits
L+ minus 48 V
Product
CPU221) t) 90 mm
(3.54 in)
CPU222) t) 90 mm
(3.54 in)
CPU224) t) 120.5 mm
(4.74 in)
CPU22626 196 mm
(XM)
(7.84 in)
8pt t) )
46 mm
(1.81 in)
8/8pt) t) ) 71.2 mm
(2.80 in)
16/16pt) t) 137.3 mm
(5.41 in)
16/166
Product
82 mm
(3.23 in)
82 mm
(3.23 in)
112.5 mm
(4.43 in)
188 mm
(7.52 in)
38 mm
(1.5 in)
63.2 mm
(2.49 in)
129.3 mm
(5.09 in)
71.2 mm
(2.80 in)
46 mm
(1.81 in)
Ethernet,
71.2 mm
Modem
(2.80 in)
RTD, TC,
71.2 mm
Profibus, AS-I (2.80 in)
Analog
71.2 mm
In., Combo
(2.80 in)
Analog
46 mm
output
(1.81 in)
Position,
71.2 mm
IT
(2.80 in)
16pt
4pt, 4/4pt
B
63.2 mm
(2.49 in)
63.2 mm
(2.49 in)
63.2 mm
(2.49 in)
63.2 mm
(2.49 in)
63.2 mm
(2.49 in)
38 mm
(1.5 in)
63.2 mm
(2.49 in)
5-30VDC or 5-250VAC
-
Output Delay & Frequency
Off to On (Q0.0 & Q0.1)
On to Off (Q0.0 & Q0.1)
Off to On (Q0.2 & Q0.3)
On to Off (Q0.2 & Q0.3)
Pulse Train Output (Q0.0 & Q0.1)
2 s, maximum
10 s, maximum
15 s, maximum
100 s, maximum
20 kHz, maximum
1 Hz, maximum
Relay Life
Switching delay
Lifetime mechanical (no load)
Lifetime contacts at rated Load
10 ms, maximum
10,000,000 open/
close
100,.000 open/close
Siemens Energy & Automation, Inc.
Industrial Controls Catalog
16_Sec (161-180).qxd
07/28/03
03:38 PM
Page 16/167
SIMATIC S7 - 200 Micro PLC
General
CPU configurations
CPU 221, 222, 224, 226, 226 XM
Expansion I/O modules
The S7-200 Micro PLC system
can be expanded to cover
applications up to 256 I/O
points by adding I/O expansion modules. There are several types of expansion modules:
Discrete Input / Output
Discrete Input / Output
Combination
Analog Input / Output
Ethernet
Maximum Configurations
Internet
As shown in the CPU selection guide, there is a maximum number of expansion
modules that can be connected to any given CPU. Another
item to consider is the available power budget. Each expansion module consumes
+5V DC power from the CPU
I/O bus, so this can determine
the maximum I/O configuration as well. The tables show
the power budget and maximum I/O configurations for the
S7-200 Micro PLC system.
Modem
Positioning
Modules can be added directly next to the CPU, or in an
extended arrangement with a
0.8m Expansion Cable, either
with panel mounting or standard DIN rail mounting.
Analog Input / Output combination
RTD / Thermocouple input
CPU 22x
5 VDC
Current
CPU 222 340 EM 221 DOI8 x DC24V
50
CPU 226 1000 EM 222 DO8 x Rly
40
EM 222 DI4/DO4 x DC24V
AS-Interface master
CPU 221
5V ma
Digital
Inputs
No expansion possible
Digital
Outputs
30
CPU 224 660 EM 222 DO8 x DC24V
PROFIBUS-DP slave
Module
Expansion module
5 VDC Current
Consumption - ma
40
EM 223 DI4/DO4 x DC24V/Rly
40
EM 223 DI8/DO8 x DC24V
80
EM 223 DI8/DO8 x DC24V/Rly
80
EM 223 DOI6/DO16 x DC24V
160
EM 223 DI16/DO16 x DC24V/Rly
150
EM 231 AI4 x 12 Bit
20
EM 231 AI4 x Thermocouple
60
EM 231 AI4 x RTD
60
EM 232 AQ2 x 12 Bit
20
EM 235 AI4I/AQ1 x 12 Bit
30
EM 277 PROFIBUS-DP
150
Analog
Inputs
Analog
Outputs
8
8
2
2
0
0
4
4
28
28
7
7
0
0
14
14
CPU 222
Max Digital In / Out
CPU
2 x EM 223 DI16 / DO16 x DC24V
or
2 x EM 223 DI16 / DO16 x DC24V / Rly
Max Analog In
CPU
2 x EM 235 AI4 / AQ1
Max Analog Out
CPU
2 x EM 232 AQ2
+340
-320
or
-300
Total = >0
8
32
6
32
40
38
+340
-60
Total = >0
+340
-40
Total = >0
+660
-600
-60
Total = =0
14
64
16
94
10
64
+660
-640
Total = >0
14
64
78
10
64
74
+660
-600
-40
Total = >0
14
64
78
10
64
8
82
+1000
-900
-80
Total = >0
24
96
8
128
16
96
8
120
+1000
-960
-30
Total = >0
24
96
8
128
16
96
>660
-210
Total = >0
14 (24)
10 (16)
14 (24)
10 (16)
>660
-140
Total = >0
14 (24)
10 (16)
14 (24)
10 (16)
CPU 224
Max Digital In / Rly Out
CPU
4 x EM 223 DI16 / DO16 x DC24V / Rly
2 x EM 221 DI8 x DC24V
Max Digital In / DC Out
CPU
4 x EM 223 DI16 / DO16 x DC24V
Digital In / Max Rly Out
CPU
4 x EM 223 DI16 / DO16 x DC24V/Rly
1 x EM 222 DO8 x Rly
74
CPU 226 (XM)
Max Digital In / Rly Out
CPU
6 x EM 223 DI16 / DO16 x DC24V / Rly
1 x EM 223 DI8 / DO8 x DC24V / Rly
Max Digital In / DC Out
CPU
6 x EM 223 DI16 / DO16 x DC24V
1 x EM 221 DI8 x DC24V
112
CPU 224 or CPU 226 (XM)
Max Analog In
CPU
7 x EM 235 AI4 / AQ1
Max Analog Out
CPU
7 EM 232 AQ2
Siemens Energy & Automation, Inc.
Industrial Controls Catalog
16/167