york airside products
Delivering precision air conditioning
for critical applications
Serie
R410A
Close control
air conditioners
2011 Johnson Controls, Inc.
www.johnsoncontrols.com
Johnson Controls Inc, Building Efficiency, De Kleetlaan 3, Diegem Zuid - Pegasus Park, Brussels, Belgium B-1831
Johnson Controls reserve the right, in line with continuing research and development, to amend or change specifications without notice.
PUBL-5484
Air Conditioners for Close Control
and Data Centers
High energy efciency and
minimum environmental
impact
laboratories,
P Series air conditioners for close control are
thermal loads and crowding is negligible.
special machines with design and operating features
Their application is also ideal in widely varied
which clearly differentiate them from standard air
industrial sectors: optics, electronics, electro-
conditioning units.
medical
The total cooling capacity coverage of the models
production,
with direct expansion - OPA with up-ow air
etc. In these applications an integrated system of
discharge and UPA with down-ow - ranges from 7
treatment of the external air may be requested.
TV
recording
studios,
musical
instrument storage areas, museums, control rooms
for electricity power stations and railway junctions
and other areas where there are prevalent sensible
equipment,
musical
electronic
equipment
instrument
production
up to 90 kW.
The same machines are available in chilled water
versions - OPU and UPU - with capacities of up to
approximately 200kW.
The P Series air conditioners offer very high energy
efciency values in all operating conditions which
translates into less CO2 emissions and particularly
low running costs.Though optimised for use in data
centers and telephone exchanges, they are equally
valid in special applications such as measurement
GOST certification
ISO 9001
Cert. n 273
Optimal efciency
reduce as the speed diminishes;
- extensive thermo-acoustic insulation of the
Johnson Controls P Series design offers the
cabinet shell.
highest sensible cooling capacity with the minimum
footprint possible, which translates into optimal
Available versions
ratio levels of cooling capacity to footprint
area. This is an important feature in reducing the
The P Series air conditioners are produced in
space needed by machinery, allowing more room
two main construction versions which enable all
in the space for IT equipment. This advantage is
application requirements to be met, in both data
especially important given the progressive increases
centres and in other specialised locations:
in capacity required by data centers and other
- direct expansion units, commonly used in
computer applications which, over time, need the
buildings of medium/ small dimensions, with
addition of extra air conditioners. Clean efciency
required capacity not exceeding 400kW;
is also ensured by the use of the R-410A refrigerant,
respectful to the ozone layer.
- chilled
The design of the machine has not not neglected
the search for low sound operation, thanks in
particular to:
- the selection of quiet scroll compressors;
- the application of EC plug fans featuring low sound
levels at project conditions which appreciably
units,
with
dedicated
cooling groups generally used above 400kW
capacity.
Silent functioning
water
Different versions
for different needs
with high crowd levels and appreciable external
airow. They are appropriate for commercial and
service industry areas such as ofces, shopping
Also considering their adequacy from an aeraulic
centres, restaurants, libraries and museums.
and performance level angle, the P Series direct
expansion air conditioners are assembled with
various combinations of compressors/airows, thus
determining different machine SHR (sensible heat
ratio). Models with SHR between 0.9 and 1 are to
be chosen for the air conditioning of areas where
sensible thermal loads are prevalent and which do
not require (if not minimally) the treatment of latent
loads by dehumidication, such as data centers,
highly computerised ofces, telephone exchanges
and more generally special close control uses.
Machines with SHR of less than 0.9 are characterised
by having (at equal refrigerant circuit) a lower airow
and therefore greater dehumidication. This makes
them well suited to civil or special applications also
Main features
- better functionality;
- improved energy efciency;
Plug fans with EC motors
- lower sound level;
- absence of vibration in operation and soft start
Plug fans, made up by one or more backward
(lower absorbed current on starting).
curved, free running impeller, radial fans, offer
several advantages:
Regulation Options
- particularly silent operation;
Johnson
- extremely high performance;
alternatives for the regulation of the airow of
- easy cleaning of the blades.
the EC fans depending on the requirements of the
Plug fans factory tted with EC (electronically
installation:
Controls
provides
four
different
commutated) constant current brushless motors
with external rotors are the latest innovation in
energy saving when it comes to the fan sector. They
are about 25-30% more efcient than traditional
asynchronous alternating current motors. They also
allow continuous speed variation depending on the
external sensor signal on the microprocessor control
of the machine, without the need for an inverter or
1. Constant fan rotation speed. The available
high static pressure is ideal for most applications.
The effective air ow depends on the real
pressure drop of the aeraulic system of the
installation,
however
it
can
be
calculated
through Johnson Controls computerised selection
program.
other electronic devices.
2. Constant airow independent of the pressure
At equal operating conditions, the combination of
drop of the lters. In order to maintain a constant
EC motors and plug fans therefore offers several
airow, an internal sensor guides the microprocessor
advantages:
management system to vary the airow handled
by the fan, depending on the degree of clogging
pressure. In particular, in very large areas subdivided
of the lters. This ensures that insufcient cooling
into multiple local zones with partition dampers
does not occur due to reduced airow arising from
driven by individual thermostats, constant regulation
dirty lters. This type of regulation is recommended
of the pressure is necessary to avoid imbalances in
when F7 lters are used, in order to increase their
the distribution of the air. In fact, without correct
working life.
fan speed regulation, the closure of one or more of
3. Variable airow depending on the cooling
capacity required by the installation. This is the
classic VAV (Variable Air Volume) plant arrangement
which responds to increased demand by a
proportionate increase in airow and vice versa. This
type of plant offers interesting energy advantages at
the dampers could cause an excessive increase in
the airow through the dampers remaining open.
A pressure sensor is included to be installed in a
representative under-oor point to guide the Survey
which, in turn, regulates the fan speed in order to
maintain the designed pressure values.
partial loads, which occur extensively throughout
the year, especially at night. The VAV system, which
is recommended only for chilled water machines,
requires that modulating regulation of the cooling
capacity is provided.
4. Airow as a function of pressure in the raised
oor. This regulation alternative is envisaged for
plants with raised oors where the air is distributed
under
the
oor
itself.
The
microprocessor
management system maintains constant under-oor
Plug fans with AC motors
Microprocessor
Standard fans with AC motors have two operating
The P Series air conditioners are equipped
speeds and therefore two different airows and
with an on board controller which has been
static pressures, which can be selected through their
especially designed to manage the performance
terminal strip cabling.
of the machines in both data centers and civil
applications. The intelligent controller keeps control
of the fundamental functions of the air conditioning:
cooling with or without dehumidication, heating,
humidication, regulation of the air ow based
on the condition of the lters and/or other design
requirements. These features mean that the
Controller operates the machine at a high energy
efciency level in all working conditions. This ensures
continuity of service, even in emergency situations,
for example if the machines are equipped with two
supplied from reputable global manufacturers.
compressors or the plant has multiple machines.
Also offers a wide range of auto-diagnosis functions,
and the capability to fully manage all the alarms.
Scroll compressors
Single or double refrigerant
circuit
Models with 1 as the last digit of the numerical part
of an identication code have a single circuit and a
Extremely quiet, energy efcient scroll compressors
single compressor. Those with 2 as the last digit on
have been installed in the direct expansion
the other hand have two completely independent
units. Offering a signicant energy consumption
refrigerant circuits and two compressors.
reduction, they allow a very limited impact on the
The installation designer can therefore choose to
environment. Compared to alternative ones, at
use a single compressor machine or one with two
equal yield capacity scroll compressors give higher
compressors which offers 50% redundancy. The
volumetric performance. In addition, the absence
circuits are tted with all the safety and regulation
of valves eliminates the pressure drop which is
devices necessary for efcient and reliable operation.
typical of the traditional ones, allowing an increase
The evaporator coil can be single or double circuit
in energy efciency in equal conditions. The P
depending on the number of compressors.
Series air conditioners utilise the most efcient
and reliable available scroll compressors models
Electronic expansion valve
Electronic expansion valves are one of the most
recent pieces of equipment that enable to improve
the energy efciency at partial loads of direct
expansion machines. These valves are installed at the
inlet of the evaporator, substituting the traditional
thermostatic expansion ones: this allows much
more precise control of the quantity of refrigerant
entering the evaporator, depending on the effective
requirement of the load. This guarantees good
capacity regulation, typically between 100% and
50%. Electronic expansion valves also enable to
control the amount of overheated gas at the outlet of
the evaporator, thus allowing a signicant reduction
of the condensation pressure during winter or nighttime operation whilst maintaining the evaporation
pressure unchanged. Adoption of the electronic
expansion valve (optional) guarantees a signicant
increase of the EER values.
High efciency heat exchanger
coil
The surface treatment reduces the heat exchange
and requires coils with more rows, therefore making
it totally unfruitful.
The copper-aluminum coils tted to direct
expansion machines with downward air discharge
can have an optional hydrophilic surface treatment
to the ns in order to prevent any downward
condensate drag.
This treatment, penalising the heat exchange of the
ns, makes it necessary to increase the coils size
and is required whenever the environment has to be
dehumidied. It therefore has to be specied when
many operators are present or when there are large
The aluminum ns have specialisation of the TURBO/
COIL prole, perfected in the LU-VE SpA research
labs. They produce a predetermined turbulence
of the crossing air which therefore increases the
coefcient of heat exchange.
The copper tubes have the special TURBO/FIN
internal helical grooves which centrifuge the liquid
refrigerant ow thus optimising the capacity of heat
exchange between air and refrigerant.
volumes of fresh air.
In machines with chilled water coils, the hydrophilic
treatment is not envisaged. Dehumidication is in
fact non-existent, due to several factors:
- supply water temperatures are always higher
to exploit the free cooling effect (up to 20C in
data centers with hot pool air distribution);
- operators absence;
- absence of any kind of humidity.
Refrigerant and oil charge
OPA e UPA mono-block air conditioners with
incorporated water condenser (accessory) are
supplied complete with refrigerant and oil charge.
OPA e UPA air conditioners for connecting to
remote condensers are supplied only with nitrogen
pressurized charge and the standard oil charge of
the compressor(s). The refrigerant charge and any
topping-up of the oil level has to be done by the
installer during the installation process.
centres, telephone exchanges etc;
- 7/12 C, mainly for wellness applications in the
civil sector.
In both cases, the standard oating regulation allows
the progressive modulation of the cooling capacity
based on the demand for cooling the environment,
without any sudden variations which could cause
discomfort. Nevertheless, a modulating valve is
available as an accessory, installed in place of the
oating one when very precise regulation of the
cooling capacity is required. It is also very suitable
for those cases which involve high rates of fresh air.
Hydraulic circuit and regulation
valves
The chilled water units are tted with a n-pack
type heat exchanger coil with several rows,
copper tubes and aluminum ns. The coils have
as standard a motorised three-way valve for the
oating regulation of the water ow. The coils are
designed to give maximum performance in the two
regimes typical of chilled water temperatures:
- 15/20 C, or higher, as required by most data
10
If the plant is equipped with variable ow pumps,
two-way valves with modulating regulation can be
tted instead of three-way ones.
Local network and remote
management
PSeries air conditioners are capable of standalone
operation, local private network with multiple units
(up to 12) or fully integrated with Metasys Building
Management System from Johnson Controls.
units can be equipped with an RS485 card working
with BacNET MS/TP protocol.
Further Gateways are available for interfacing more
units (up to 12 units to 1 gateway) to other important
Serial Communication Protocols:
- Lonworks FTT10;
- Bacnet MS/TP or TCP/IP;
In local network applications, one machine is
the master, and the remaining slaves follow the
same algorithm. The slave units, which come into
- TCP/IP Ethernet;
- TCP/IP
Ethernet
with
an
integrated
GSM
modem.
operation in emergency situations or when peak
demand exceeds the design values, are rotated at
predetermined intervals (for example every 12 or 24
hours) and switch to the master role to balance the
number of working hours of the compressors.
In remote applications, the machines can be
controlled from remote positions interfacing with
common Building Management Protocols such as
BacNET, LON and Modbus. Either via GSM Modem or
TCP/IP Internet Protocol.
For total integration with to Johnson Control
Metasys Building Management Systems (BMS) the
11
Safety features
Air ltration requirements
The P Series air conditioners comply with the main
Adequate air ltration is an especially important
European and international safety regulations.
requirement in data centers, where air-dispersed
This also thanks to:
particles can also carry corrosive substances
- electrical boards that feature a main switch with
damaging the equipment. But it is also in civil
shutter-block function, in addition to magneto-
applications, where IAQ (indoor air quality) control
thermal switches and contactors;
is a topic of ever-growing importance.
- On/Off terminals for switching the machine
To satisfy this demand, Johnson Controls equips
by remote control, and other free terminals
its P Series air conditioners, as standard, with re-
for the remote indication of a cumulative
generable self-extinguishing class G4 lters, which
alarm;
can be substituted with high efciency F7 air lters if
- standard
machines
a more rigorous IAQ control is required. The lters are
with compressors that protect the compressors
installed, upstream of the cooling coil, in an inclined
from any damage, should the machine start
position. Their large surface allows lower air crossing
up in the opposite direction from normal;
speeds and therefore lower energy consumption.
- remote
phase
condenser
(accessory).
12
sequencers
fan
on
speed
regulators
Modern design
user: the standard version has the suction grille on
The P Series air conditioners feature a modern,
functional design suitable not only for data centers
but also for civil areas.
- anthracite grey colour that blends in perfectly with
most ofce and laboratory furnishings
- metal frame and aluminium machine proles,
with closing panels and access doors in sheet
the front, while the special version has a blind front
panel and takes air in from the bottom of the unit.
For downow (UP) units, air is taken from the top
of the machine and discharged through the bottom
panel or, as an alternative, through grilles in the
lower part of the front panel so that the air ows
out above the oor.
steel;
- thermo-acoustically
insulated
doors
and
panels: the inside is covered by a layer of
polyurethane protected by a plastic lm for a
total thickness of 25mm;
- anthracite PVC lm external surface treatment
for doors and panels.
The recirculation air intake for upow (OP) units
can be situated in two positions, at the choice of the
13
Renewable energy
Free cooling air-water
desired conditions. This situation implies as well
good energy savings.
Mechanical cooling only. This situation arises when
This system (accessory) uses external air instead of
(or in addition to), mechanical cooling. Envisaged for
the OPA/FC - UPA/FC air conditioners, it consists of a
cold water coil integrated with the direct expansion
one with a three way modulating valve controlled by
microprocessor.
Three different operating regimes are therefore
possible:
Free cooling only. This occurs when the external
air temperature is sufciently low to bring the
water circulating in the coil to a value which fulls
the requirements of cooling in the area to be
acclimatised. This is the maximum energy saving
scenario as the compressors are always out of
service.
Free cooling + mechanical cooling. If the external
air temperature is higher than what necessary
to maintain the water cooling at the desired
temperature, one or more compressors are switched
on for the length of time necessary to reach the
14
the temperature of the external air is too high to
produce sufcient cooling. In this case compressors
function as normal. This operation exploits to the
full the high energy efciency of the refrigerant
circuits thanks to the larger size of the coils n pack.
So even using only mechanical cooling helps to
keep energy consumption down compared to other
systems.
Accessory water cooled condensers of the refrigerant
circuit are provided with a pressure-switch system to
regulate the condensing pressure.
FREE COOLING SYSTEM
working mode
SPRING - AUTUMN
(Direct Expansion + H2o).
FREE COOLING SYSTEM
working mode
SUMMER
(Direct Expansion)
FREE COOLING SYSTEM
working mode
WINTER
(chilled water)
15
Two sources system:
maximum safety, zero waste
exibility that the two sources typology enables:
the second source can be both by direct expansion
or chilled water and the priority of operation can
Instead of using a free cooling circuit, this system
(accessory) uses any available excess energy from the
air conditioning plant of the building. In other words,
when there is enough cooling energy available from
the central air conditioning plant, the unit stops its
own compressors and uses the cooled water thus
made available, passing it through the same water
coil installed in the free cooling air conditioners. So
excess energy consumption typical of a centralised
installation is avoided.
One advantage of this system is the maximum
safety of continuity of operation that it provides,
for example, in emergency situations: if a dedicated
cooling group breaks down, it will maintain a
continuity of service thanks to the cooled water from
the central plant. Another advantage resides in the
16
be chosen depending on the requirements of the
installation.
TWO SOURCES SYSTEM
working mode
DIRECT EXPANSION
TWO SOURCES SYSTEM
working mode
CHILLED WATER
17
Accessories
Numerous accessories and options are available
for the P Series air conditioners to personalise
the installation depending on the requirements of
the plant and its design. Divided by function, they
include:
Free cooling or two sources
Additional Free cooling circuit.
Additional Two sources circuit.
Alarms
Water alarm (supplied loose).
Out-of-range air discharge temperature
alarm.
Smoke/fire alarm terminals.
Water cooled condensers and pressostatic valves
Welded stainless steel water cooled plate
condenser.
2 way pressostatic valve (only if the water
condenser is selected).
18
Sound proong devices
Sound damped duct for air suction or
discharge (h=550 mm). Allows a reduction
of approx 4 dB(A) of the SPL of the unit.
Double layer sound damping panels.
Reduces SPL by approx 2 dB(A) in upflow
units (OP series), and approx.4 dB(A) in
downflow units ((UP series).
Double-layer
sandwich
thermo-acoustic
insulation panels.
Panels and base
Blind front panel (OP) and open base for
bottom air intake.
Front panel with grille in the lower part (UP)
and closed base.
Plenum
Plenum (h=550 mm) for air discharge or
intake with front grille.
Plenum (h=550 mm) for air discharge or
intake with front and side grilles.
Direct expansion unit cooling capacity regulation
Electronic expansion valve.
Electronic hot-gas injection system for the
regulation of cooling capacity (100-10%).
Heating, reheating and humidication
Single-step or double-step low thermalinertia electrical heating/reheating coil.
Immersed-electrode modulating humidifier
and dehumidification control.
Humidity sensor for the single control of
dehumidification.
Boards and sensors
Humidity sensor and board for external
humidification control not supplied by
Johnson Controls.
RS 485 communication board.
Dampers
Gravity-operated overpressure dampers on
the air outlet (OP series).
Motorised overpressure dampers on the air
intake (UP series).
Under bases
Adjustable
under
base
(OP
only).
(Precise height to be specified with order).
Adjustable under base with air deflector
(UP only). (Precise height to be specified with
order).
Fans and lters
Electronic EC fans with incorporated inverter
for constant rotation speed regulation.
Electronic EC fans with incorporated inverter
for the regulation of air flow in relation to the
required cooling capacity.
Electronic EC fans with incorporated inverter
for the regulation of constant pressure in the
raised floor.
Electronic two-speed AC fans.
F7 filter to be installed on the air intake as
substitute for the standard G4.
Monophase condenser-fan rotation speed
variator (winter control), maximum power 8
Ampere.
19
Performance at JOHNSON CONTROLS test conditions
YC-OPA: direct expansion air conditioners with air cooled or water condensers
and up-ow air supply
Models
71
111
141
211
251
301
361
461
Tot. cooling cap. kW:
7,0
11,4
15,3
21,6
25,6
31,1
38,9
48,1
Sens cooling cap. kW:
6,8
11,1
12,7
20,8
22,6
28,7
36,3
43,9
2200
3200
3200
7000
7000
8700
14.500
14.500
ACC 11
ACC 16
ACC 21
ACC 32
ACC 42
ACC 50
ACC 55
ACC 74
3,01
3,11
3,47
3,29
3,13
3,28
3,50
3,52
49
49
49
56
56
58
63
63
750
750
750
860
860
1.410
1.750
1.750
Performance
Airflow m3/h:
Condenser Model
EER
SPL:dB(A)
Dimensions & weight
Lenght mm.
Depth mm.
630
630
630
880
880
880
880
880
Height mm.
1990
1990
1990
1.990
1.990
1990
1.990
1.990
Net weight kg.
170
170
170
210
270
270
330
400
YC-UPA: direct expansion air conditioners with air cooled or water condensers
and down-ow air supply
Models
71
111
141
211
251
301
361
461
Tot. cooling cap. kW:
7,0
11,4
15,3
21,6
25,6
31,1
38,9
48,1
Sens cooling cap. kW:
6,8
11,1
12,7
20,8
22,6
28,7
36,3
43,9
Performance
Airflow
m3/h:
2200
3200
3200
7000
7000
8700
14.500
14.500
ACC 11
ACC 16
ACC 21
ACC 32
ACC 42
ACC 50
ACC 55
ACC 74
3,07
3,43
3,58
3,74
3,26
3,39
3,74
3,67
49
49
49
56
56
58
63
63
Lenght mm.
750
750
750
860
860
1410
1.750
1.750
Depth mm.
630
630
630
880
880
880
880
880
Height mm.
1990
1990
1990
1.990
1.990
1990
1.990
1.990
Net weight kg.
170
170
170
210
255
270
330
400
Condenser Model
EER
SPL:dB(A)
Dimensions & weight
20
Performance at JOHNSON CONTROLS test conditions
YC-OPU: with chilled water coil and up-ow air supply
Models
10
20
30
50
80
110
160
220
Tot. cooling cap. kW:
11,3
19,6
31,7
39,8
70,9
89,3
152,8
178,8
Sens cooling cap. kW:
9,6
15,9
28,4
34,4
61,2
74,1
122,0
148,7
2200
3400
7800
8.300
16000
17.000
26.400
34800
47
49
57
56
59
61
64
82
Lenght mm.
750
750
860
860
1750
1.750
2.640
3496
Depth mm.
630
630
880
880
880
880
880
880
Height mm.
1990
1990
1990
1990
1990
1.990
1.990
1990
Net weight kg.
155
155
180
250
450
450
650
900
Performance
Airflow m3/h:
SPL:dB(A)
Dimensions & weight
YC-UPU: with chilled water coil and down-ow air supply
Models
10
20
30
50
80
110
160
220
Tot. cooling cap. kW:
11,3
19,6
31,7
39,8
70,9
89,3
152,8
178,8
Sens cooling cap. kW:
9,6
15,9
28,4
34,4
61,2
74,1
122,0
148,7
2200
3400
7800
8.300
16000
17.000
26.400
34800
47
49
57
56
59
61
64
82
Lenght mm.
750
750
860
860
1750
1.750
2.640
3496
Depth mm.
630
630
880
880
880
880
880
880
Height mm.
1990
1990
1990
1990
1990
1.990
1.990
1990
Net weight kg.
155
155
180
250
450
450
650
900
Performance
Airflow
m3/h:
SPL:dB(A)
Dimensions & weight
Notes:
The performances are referred to: refrigerant R410; condensing temperature: 45C; inlet air: 24C - 45% RH; for chilled water: 7/12C;
The SPL is referred to 2 m distance, 1,5 m height, free eld and sound damped discharge mouth. Available static pressure: 30 Pa.
EER = Electro Efciency Ratio = Total cooling capacity / Compressors + fans + condensers fans power input.
The above performances dont consider the heat generated by the fans which must be added to the thermal load of the system.
21
Air cooled condensers to be matched
with Johnson Controls P series air conditioners
Galvanised steel casing with Epoxy-Polyester powder coating for a maximum resistence to the corrosion Painted in
white colour RAL 9003.
High efciency condensing coil.
High efciency single phase directly driven axial fans for continuos external operation.
Life lubricated and thermally protected motors. Each fan section is separated from the others.
Safety protection grilles on air discharge.
Main switch tted in a weatherproof box.
Fans speed regulation (winter control) is available as accessory in the indoor unit. The models ACC 74 and ACC 83 are
standard equipped with fans speed regulation.
Models
ACC
11
16
19
21
25
29
Performance
Nominal capacity (1)
Air quantity
kW
8,3
10,8
16,5
19,9
21,5
24,8
29,8
m3/h
2.600
2.200
5.200
4.800
4.400
7.800
7.200
Fans number
n.
Fans diameter
mm
350
350
350
350
350
350
350
180
180
360
360
360
540
540
Absorbed current
Amps
0,85
0,85
1,7
1,7
1,7
1,7
2,5
Sound pressure level (2)
dB(A)
40
40
43
43
43
45
45
Internal circuit volume
dm3
2,0
3,0
3,0
4,0
5,0
4,0
6,0
Lenght (H - V installation)
mm
743
743
1.298
1.298
1.298
1.853
1.853
Depth (H installation)
mm
610
610
610
610
610
610
610
Depth (V installation)
mm
510
510
510
510
510
510
510
Height (H installation )
mm
906
906
906
906
906
906
906
Height (V installation )
mm
578
578
578
578
578
578
578
Weight
kg
20
29
29
33
37
42
48
Models
ACC
32
42
50
55
61
74
83
Motor power input
DIMENSIONS AND WEIGHT
Performance
Nominal capacity (1)
Air quantity
kW
32,3
43,1
50,3
56,1
62,0
75,4
84,0
m3/h
6.600
8.800
13.600
12.700
14.900
20.400
19.000
Fans number
n.
Fans diameter
mm
350
350
500
500
500
500
500
540
720
1.250
1.250
1.160
1.880
1.880
Absorbed current
Amps
2,5
3,4
5,5
5,5
5,5
8,3
8,3
Sound pressure level (2)
dB(A)
45
46
50
50
51
51
51
Internal circuit volume
dm3
6,0
10,0
9,0
12,0
14,0
13,0
17,0
Lenght (H - V installation)
mm
1.853
2.408
1.895
1.895
2.393
2.705
2.705
Depth (H installation)
mm
610
610
905
905
1.110
905
905
Depth (V installation)
mm
510
510
470
470
705
470
470
Height (H instllation )
mm
906
906
1.070
1.070
1.230
1.070
1.070
Height (V installation )
mm
578
578
830
830
1.040
830
830
kg
54
71
94
102
177
132
144
Motor power input
DIMENSIONS AND WEIGHT
Weight
(1) Nominal capacity at 35C ambient and 50C condensing temperature; R410A
(2) Sound pressure level in free eld at 10 meters from the unit.
The ACC air cooled condensers are available in the following versions:
ACC/H horizontal installation and vertical air discharge;
ACC/V vertical installation and horizontal air discharge;
ACC/LT for very low temperature; vertical installation and horizontal air discharge.
22
Available accessories:
ALUPAINT: for better protection of the aluminium ns (suggested in salt atmospheres);
EC FANS: for energy saving (available on models with fan diameter 500 mm).
york airside products
Delivering precision air conditioning
for critical applications
Serie
R410A
Close control
air conditioners
2011 Johnson Controls, Inc.
www.johnsoncontrols.com
Johnson Controls Inc, Building Efficiency, De Kleetlaan 3, Diegem Zuid - Pegasus Park, Brussels, Belgium B-1831
Johnson Controls reserve the right, in line with continuing research and development, to amend or change specifications without notice.
PUBL-5484