P R O D U C T C A T A L O G U E 08
The
Group
www.detectomat.com
contents / contact
Page
1.
Fire Control Panels detect 3004 .....................................................................................................................................3-5
2.
Fire Control Panels detect 3016 .....................................................................................................................................6-8
3.
3.1
3.2
3.3
Accessories
Accessories detect 3004/3016 ........................................................................................................................................9-10
Network Components....................................................................................................................................................11-14
Programming Tools and Software ..................................................................................................................................15-17
4.
4.1
4.2
4.3
Fire Detectors
loop 3000 Addressable Fire Detectors ...........................................................................................................................18-23
Accessories..................................................................................................................................................................23-24
Addressable Call Points ................................................................................................................................................25-26
5.
loop 3000 Modules .....................................................................................................................................................27-28
6.
Signalling Devices ......................................................................................................................................................29-30
7.
Wireless Detect...........................................................................................................................................................31-37
8.
Conventional System ..................................................................................................................................................38-42
9.
Residential Detectors .................................................................................................................................................43-44
10.
Information ......................................................................................................................................................................45
History
Quality
detectomat was founded in 1977 and became one of the most
qualified smoke detector manufacturers in Germany. In 1999,
detectomat was acquired by the JOB Group, the world leading
manufacturer of thermal glass bulbs for sprinklers. 2003, the
JOB Group also integrated their qualified supplier of control
panels. detectomat has become an integrated system seller
carrying the highly touted VdS mark with a complete smoke
detection system out of one hand at competitive prices.
detectomat is certificated to all new quality standards of the
DIN EN ISO 9001. Extensive verify and test modalities as
well as automated production flow assure a high quality
standard of all products. A complete documentation of the
quality of every product is guarantied by the in the product
integrated model identification. The settlements of the high
claim of quality for all user of the system detect 3000 is
guaranteed by our service and technical support center.
The management, the improved supplier and customer relations
as well as research, competence and experience achieved a
high level of worldwide appreciation: "The German detectomat
smoke detector alarming system and the fire-fighting system is
more sensitive, more accurate and more intelligent."
features detectors system PL 3000:
126 devices per loop and a maximum length of 3,000m
automatic or manual addressing of all loop 3000 elements
recognition of short circuit and broken wire diagnostic
software I-Check
high relaibility via different measurement procedures
(O,T,OT,OTi,OTi Fusion, COBT)
freely programmable detector sensivities
adjustable sensivity for occupied and unoccupied periods
T-branch and isolator function in every PL 330X element
addressable radio loop extension
variance in design
contact
detectomat GmbH
An der Strusbek 5
22926 Ahrensburg
Fon: +49 (0) 4102 2114 60
Fax: +49 (0) 4102 2114 670
editing status Dezember 2007
www.detectomat.com
[email protected]
updates you will find at www.detectomat.com
www.detectomat.com
detectomat loop 3000contents
system
PC
visual detect
PC
www
Server
DRCP
TCP/IP
USB
PCI
LCD Tableau
BaCnet
Modbus
detect 3004
detect 3004
detect 3004
PL 3300 O
LS 3300 VLC
PL 3300
PBDH ABS
detect 3016-19"
LS 33000 R
I-Check 3000
PL 3200 O
PL 3300
OTi Fusion
PL 3300 MCP Kit
WL 3200 O
PL 3200 O
PL 3300 OTi
detect 3016
detect 3004
WL 3200 O
WGW 3300
DPT 3000
PL 3300 O
PL 3300 PA
WL 3200 O
LS 33000 VCL Kit
UBW 3311
OMS 3311
PL 3200 O
PL 3300 COBT
PL 3200 O
AMD 3311
IOM 3311
PL 3200 O
VTG 32 SB r
1
www.detectomat.com
detectomat loop 3000 system
detectomat loop 3000 system features
wide range of applications
modular microprocessor controlled fire control panels
high level of system integration and customised functionality
various language kits for international operations
up to 16 x 126 loop devices
max. loop length of 3000 m
a range of different housings
interfaces for LAN (Local Area Networks) connections or
superior systems (ESPA 4.44)
2
www.detectomat.com
graphic displays of the bus structure with powerful
I-check software
extensive event-memory for system diagnostics
alarm-management
easiest system expansion
interface for graphic displays and remote maintenance
control and link time-switched operations
international approvals and certifications
1. Fire Control Panels detect 3004
No. 31973
Fire control panel up to 4 loops
detect 3004
No. 31972
Fire control panel shallow up to 4 loops
detect 3004-shallow
Microprocessor controlled modular fire control panel for use with
the loop 3000 fire detection system components:
display- and control panel according EN 54 part 2
4 alphanumeric lines LC-display with backlight
2 slots for detector interface boards (max. to equip 4 loops
or 16 conventional fire zones)
128 programmable detector zones
3 potential-free relay outputs (250 V/5 A)
9 open collector outputs (30 V/90 mA)
monitored signal transmitter (400 mA)
2 x RS-232 interfaces for personal computer, printer, modem,
building management system
network compatible
operation and event memory for 500 messages
possibility via mounting panel to integrate a protocolprinter
and LED indicator modules for zone alarm and zone fault
indication
power supply 72 W integrated
Technical data
detect 3004
input voltage
frequency
operation voltage
power supply
230 V AC (-15 %/+10 %)
50/60 Hz
21,0 up to 29,2 V DC
72 Watt
emergency power
detect 3004
detect 3004- shallow
max. 2 x 12 V/26 Ah
max. 2 x 12 V/12 Ah
quiescent current
alarm current
interfaces
detect 3004-shallow
display
output sounder
output external user
output relay
output open collector
operation temperature
humidity
protection class
colour housing
colour front
material
86 mA
146 mA
2 x RS-232, RS-422 (optional),
bitbus (optional)
LCD 4 x 20 characters
24 V DC/400 mA monitored
24 V DC/800 mA
3 change over 250 V/5 A
9 open collector 30 V DC/90 mA
-5C up to +40C
max. 95 %
IP 30
light grey, RAL 7035
tele grey, RAL 7046
sheet steel
dimension (H x W x D)
detect 3004
detect 3004 shallow
490 mm x 420 mm x 210 mm
490 mm x 420 mm x 150 mm
EN
approvals
weight
54-2
VdS S295054, LPCB, GOST
further on request
12,5 kg
3
www.detectomat.com
1. Fire Control Panels detect 3004
No. 31975
Language kit english
Language kit integrates English software, English
description, English labelling.
No. 30088
LED indicator module
LK 3004 GB
Additional languages available on request.
CP ZM 8
To plug into the detect 3004 fire control panel for zone alarm and
zone fault indication:
8 red and yellow LEDs for 8 zones
up to 6 units connectable in the front
3 mA alarm current per zone
No. 32098
Loop interface active 2 loops
DLI 3240P X1
No. 32254
Loop interface active 1 loop
DLI 3240P X1 1L
To plug into the detect 3004 fire control panel DLI 3240P X1 1L
for one or DLI 3240P X1 for two loops with up to 126 loop 3000
components:
two-wire loop
8 freely programmable open collector outputs
2 open collector outputs 30 V DC/90 mA for alarm and fault
loop voltage 32 V DC, loop current 140 mA per loop
RS-232 interface for additional data monitoring
slot for optional redundant processor
Technical data
operation voltage
quiescent current
20 up to 28 V DC
40 mA
alarm current
DLI 3240P x11L
DLI 3240P x1
max. 1 x 140 mA
max. 2 x 140 mA
interfaces
DLI 3240P x11L
DLI 3240P x1
1 x RS-232
1 x RS-232
output open collector
4
www.detectomat.com
10 open collector output 30 V
DC/90 mA
1. Fire Control Panels detect 3004
No. 30210
Conventional interface for 8 fire zones
CP CLI X1
To plug into the detect 3004 fire control panel for max. 8
conventional fire zones:
maximum 25 automatic/10 non-automatic conventional
detectors per fire zone connectable
8 freely programmable open collector outputs (30 V DC/90 mA)
3 open collector outputs (30 V DC/90 mA)
slot for optional redundant processor
Technical data
operation voltage
output open collector
quiescent current
alarm current
No. 30386
Adapter board for LED indicator module
20 up to 28 V DC
11 open collector 30 V DC/90 mA
60 mA
85 mA + 50 mA per zone output
CP ADB 48
To plug into the fire control panel detect 3004 more than 4 LED
indicator modules No. 30088:
max. 6 alarm indicator zones available
after 16 zones is required the adapter plate no. 30836
Technical data
dimension (H x W)
switch off
No. 31946
Mounting plate
55 mm x 108 mm
zones 17-48
CP MP 3004
Expansion mounting plate to plug into the fire control panel detect
3004 including front foil for 48 detector zones.
mounting plate for maximum 6 LED indicator modules (CP ZM 8)
provides facility for protocol printer (PIP 2)
optional: protocol printer
Technical data
operation temperature
switch off
-5C up to +40C
228 mm x 365 mm
5
www.detectomat.com
2. Fire Control Panels detect 3016
No. 31989
Fire control panel up to 16 loops
detect 3016
No. 31990
Fire control panel 19" up to 16 loops
detect 3016-19"
9 open collector outputs (30 V/90 mA)
monitored signal transmitter (400 mA)
2 additional external outputs (24 V/800 mA)
2 x RS-232 interfaces for personal computer, printer, modem,
building management system
network compatible
operation and event memory for 500 messages
possibility via mounting panel to integrate a protocolprinter
and LED indicator modules for zone alarm and zone fault
indication
power supply 192 W integrated
Technical data
input voltage
frequency
operation voltage
power supply
230 V AC (-15 %/+10 %)
50/60 Hz
21,0 up to 29,2 V DC
192 Watt
emergency power
detect 3016
detect 3016-19"
max. 2 x 12 V/45 Ah
max. 2 x 12 V/65 Ah
quiescent current
alarm current
interfaces
detect 3016
Microprocessor controlled modular fire control panel for use with
the loop 3000 fire detection system components:
display- and control panel according EN 54 part 2
4 alphanumeric lines LC-display with backlight
max. to equip up to 16 loops or 64 conventional zones
192 programmable detector zones
3 potential-free relay outputs (250 V/5 A)
No. 31992
Language kit english
Language kit integrates English software, English
description, English labelling.
display
output sounder
output external user
output relay
output open collector
operation temperature
humidity
protection class
colour housing
colour front
material
86 mA
146 mA
2 x RS-232, RS-422 (optional),
bitbus (optional)
LCD 4 x 20 characters
24 V DC/400 mA monitored
24 V DC/800 mA
3 change over 250 V/5 A
9 open collector 30 V DC/90 mA
-5C up to +40C
max. 95 %
IP 30
light grey, RAL 7035
tele grey, RAL 7046
sheet steel
dimension (H x W x D)
detect 3016
detect 3016-19"
750 mm x 600 mm x 240 mm
19" 6HE
EN
approvals
weigh detect 3016
54-2
VdS S295054, LPCB, NF,
GOST, CCC
30 kg
LK 3016 GB
Additional languages available on request.
6
www.detectomat.com
2. Fire Control Panels detect 3016
No. 32099
Loop interface active redundant 2 loop
DLI 3240P X2-R
To plug into the detect 3016 fire control panel for max. two loops
with up to 126 loop 3000 components:
two-wire loop
8 freely programmable open collector outputs
2 open collector outputs 30 V DC/90 mA for alarm and fault
loop voltage 32 V DC, loop current 140 mA per loop
RS-232 interface for additional data monitoring
redundant board processor unit to duplicate the functions
Technical data
operation voltage
quiescent current
alarm current
interfaces
output open collector
No. 30096
Conventional interface redundant 8 fire zones
20 up to 28 V DC
40 mA
max. 2 x 140 mA
1 x RS-232
11 open collector output 30 V
DC/90mA
CP LI X2-R
To plug into the fire control panle detect 3016 for max. 8
conventional fire control panel:
maximum 25 automatic/10 non-automatic conventional
detectors per fire zone connectable
8 freely programmable open collector outputs (30 V DC/90 mA)
3 open collector outputs (30 V DC/90 mA)
redundant board processor unit to duplicate the functions
Technical data
operation voltage
quiescent current
alarm current
output open collector
No. 30098
LED indicator module
20 up to 28 V DC
60 mA
85mA+50mA per zone output
11 open collector output 30 V
DC/90mA
CP ZM 32
To plug into the detect 3016 fire control panel for zone alarm and
zone fault indication:
32 fire zones on one module
1 red and 1 yellow LED per fire zone
Technical data
alarm current
operation temperature
dimension (H x W)
3 mA per zone
-5C up to +40C
108 mm x 193 mm
7
www.detectomat.com
2. Fire Control Panels detect 3016
No. 30927
Ground circuit module
CP EM
To plug into the detect 3016 fire control panel for monitoring of the
galvanic separation between ground potential and all secondaryvoltages, e.g. loop 3000, fire zones, monitoring outputs.
Technical data
operation voltage
quiescent current
alarm current
interfaces
output open collector
No. 30097
Extension module
18 up to 30 V DC
approx. 7 mA
max. 2 x 140 mA
2 x RS-232
fault output voltage: max. 29 V
fault output current: max. 0,1A
CP ECB
To plug into the fire control panel detect 3016 up to 16 loops:
No. 31947
Mounting plate
3 slots for plugging in 2 additional loop-/conventional
interfaces and 1 alarm module
max. 2 extension modules in one detect 3016 installable
CP MP 3016
To plug into the fire control panel detect 3016 front for up to 192
detector zones and protocol printer, including front foil:
mounting plate for maximum 6 LED indicator modules
for mounting protocol printer PIP 2
zones can be identified by labelling
Technical data
operation temperature
material
dimension (H x W)
-5C up to +40C
sheet steel
400 mm x 483 mm
Remarks: for installing a printer, a LED indicator module with
max. 160 LED's possible
No. 30164
19"-Mounting plate
To plug into the fire control panel detect 3016 front for up to 192
detector zones and protocol printer, including front foil:
mounting plate for maximum 6 LED indicator modules
for mounting protocol printer PIP 2
zones can be identified by labelling
MP-1 19"
Technical data
operation temperature
material
dimension (H x W)
8
www.detectomat.com
-5C up to +40C
sheet steel
878 mm x 485 mm
3. Accessories
3.1 Accessories detect 3004 / detect 3016
No. 32066
Monitored module for 4 outputs
SC 4
To add to the fire control panels of the system detect 3000:
externally powered via the fire control panel
maximum 600 mA per output
4 jumpers acoustics on/off option to control the noise of
the outputs
4 output channels with 24 V for all kind of signalling devices
1 general alarm input to activate all outputs
housing for plugging in on DIN rails
Technical data
operation voltage
quiescent current
alarm current
dimension (H x W x D)
No. 30118
Monitored module for 8 outputs
21 up to 37 V DC
90 mA
0,5 up to 2,6 A
125 mm x 130 mm x 70 mm
SC 8
To add to the fire control panels of the system detect 3000:
8 monitored alarm outputs (24 V DC/400 mA) for signalling
devices (separately fused)
8 open collector outputs for LED indicators
8 alarm inputs to activate the selected output
8 manually switched inputs
1 general alarm input to activate all outputs
externally powered 24 V DC/max. 3,2 A
Technical data
operation voltage
quiescent current
open collector output
alarm current
dimension (H x W x D)
No. 30077
Relay board 8 change over
21 up to 28 V DC
58 mA
12 outputs 24 V DC/90 mA
0,5 up to 2,6 A
125 mm x 130 mm x 70 mm
RB 8
To add to the fire control panels of the system detect 3000:
8 potential-free output relays, change over contact
8 inputs controlled by the fire control panel
8 LEDs to display the current operation status
mountable on C-rails 35 mm in the panel
housing for plugging in on DIN rails
Technical data
operation voltage
quiescent current
alarm current
relay output
dimension (H x W x D)
21 up to 28 V DC
5 mA
30 mA per relay
8 x change over 250 V/5A
125 mm x 110 mm x 60 mm
9
www.detectomat.com
3. Accessories
3.1 Accessories detect 3004 / detect 3016
No. 30115
Control module
With 32 open collector
outputs for installation in
the fire control panels of
the system detect 3000:
CP AM 32
32 open collector outputs (24 V DC/90 mA) for detector zones
all outputs are freely programmable
up to 6 boards usable in FCP detect 3016
up to 24 outputs usable in FCP detect 3004
Technical data
operation voltage
quiescent current
open collector output
alarm current
No. 30116
Connection board for alarm module
21 up to 28 V DC
30 mA
32 outputs 24 V DC/90 mA
0,5 up to 2,6 A
CP AM AP
Connecting printed circuit board (PCB) for alarm module CP AM 32
(No. 30115) for use outside the fire control panel:
No. 30106
Mount in printer
housing for plugging in on DIN rails
connectable via housing on DIN rails 35 mm
dimensions (H x W x D): 88 mm x 175 mm x 70 mm
PIP 2
thermo printer with 24 characters
58 mm paper width
integrated printer memory of 8 RAM
directly connectable via fire control panels interface RS-232
powered via fire control panel
Technical data
To expand the front of the fire control panel (detect 3004/ detect 3016)
with a printer:
No. 32312
Independent control unit
operation voltage
quiescent current
alarm current
operation temperature
protection class
dimension (H x W x D)
21 up to 28 V DC
12 mA
100 mA
-5C up to +40C
IP 30
115 mm x 115 mm x 80 mm
AB 320 english
AB 320 control display transmit information though DT-Loop and
detectomat fire control panel, information display,
keyboard input, fire alarm, breakdown, linkage display, acoustics
indicate, information print, ect.:
through RS-232 link computer forming CRT display an link net
through bitbus system
information could be shared by other control panels, many
displays could be on one control panel
rated voltage 24 V
dimension of display screen: 5.7 inch (320 mm x 240 mm)
dimension of overall (W x H): 482,6 mm x 178 mm (standard H)
10
www.detectomat.com
3. Accessories
3.2 Network Components
No. 32311
Interface control unit
DT Loop Card
Intelligent Interface for use in between DLI 3240 (P) and AB 320:
monitored alarm and fault information of DLI 3240 CAN
two bus protocols for connection (Interface: VAN BUS and I2C)
internal memory 512k EEPROM up to 2048 loop components
could be programmed
Technical data
operation voltage
quiescent current
alarm current
operation temperature
dimension (H x W x D)
20 up to 30 V DC
20 mA
100 mA
0C up to +40C
220 mm x 150 mm x 2 mm
Remarks: one DT Loop Card connect of DLI 3240 CAN with 16 loops
No. 32118
Display remote and control panel
RDCP
No. 32119
Display remote and control panel 19"
RDCP 19"
Technical data
operation voltage
power supply
emergency power
quiescent current
alarm current
interfaces
To expand the detect 3000 fire detection network, basic version,
wall mount housing or 19 version without power supply:
incl. bitbus interface for interlink connection
128 programmable detector zones
3 potential-free relay outputs (250 V / 5 A)
9 open collector outputs (30 V/90 mA)
monitored signal transmitter (400 mA)
2 x RS-232 interfaces for personal computer and printer
externally powered via fire control panel or power supply
it is essential to have a separate master display and control
panel ABF in the bitbus network
control panel and power supply consist of detect 3004 shallow
and language kit master or slave
No. 32040
Master language kit english
To equip a display- and control panel with software and language:
integrates English software, description and labelling
display
output sounder
output external user
output relay
output open collector
operation temperature
humidity
protection class
colour housing
colour front
material
21,0 up to 29,2 V DC
72 Watt
max. 2 x 12 V/12 Ah
132 mA
192 mA
2 x RS-232, RS-422 (optional),
bitbus (optional)
LCD 4 x 20 characters
24 V DC/400 mA monitored
24 V DC/800 mA
3 change over 250 V/5 A
9 open collector 30 V DC/90 mA
-5C up to +40C
max. 95 %
IP 30
light grey, RAL 7035
tele grey, RAL 7046
sheet steel
dimension (H x W x D)
RDCP
RDCP 19"
262 mm x 420 mm x 83 mm
6HE x 19 x 83 mm
DIN-EN
weigh
54-2
6 kg
LK RDCP M GB
Additional languages available on request.
11
www.detectomat.com
3. Accessories
3.2 Network Components
No. 32296
Slave language kit english
Upgrade of a fire control panel of the system detect 3000 as
display- and control panel in the network:
integrates English software, description and labelling
No. 30087
Bitbus interface
LK RDCP S GB
Additional languages available on request.
CP BBI
To expand the fire control panel to interlink several fire control
panels, control- and display panels:
No. 32257
Bitbus interface PCI
to build up a fire control panel network up to 63 bitbus components
via 4-wired interface distances up to 1.200 m (3,900 feet) possible
data rate maximal 62,5/375 kBd
IPC BIT900-PCI
To connect one computer to the fire control system detect 3000
network:
connection of the visualisation system visual detect
PCI slot plug-in card with isolated bitbus-interface
for the Windows-operating system 2000 and XP Vista projected)
supports repeater functions
bitbus rate: 62,5 and 375 kBit
Technical data
operation voltage
interfaces
No. 32258
Bitbus interface USB
5 V DC via PCI Bus and computer
PCI, bitbus DB9M and DB9F
USB BIT
To connect one computer to the fire control system detect 3000
network:
connection gateway for the visualisation system visual detect
compact USB-box with isolated bitbus interface
for the Windows-operating system 2000 und XP (Vista projected)
supports no repeater functions
bitbus rate: 62,5 and 375 kBit
incl. USB 2.0 cable with connector A & B
Technical data
operation voltage
interfaces
dimension (H x W x D)
12
www.detectomat.com
5 V DC/500 mA via USB Bus
PCI, bitbus DB9M and DB9F
USB, bitbus DB9F
115 mm x 57 mm x 20 mm
3. Accessories
3.2 Network Components
No. 32259
Bitbus ethernet gateway
ETH BIT/R
To connect one computer to the fire control system detect 3000
network, mounting on top snap rail:
connection gateway for the visualisation system visual detect
mounting-rate module with bitbus interface
for the Windows-operating system 2000 und XP (Vista projected)
supports no repeater functions
bitbus-clock rate: 62,5 and 375 kBit
Technical data
operation voltage
interfaces
dimension (H x W x D)
No. 32260
Bitbus ethernet gateway
24 V DC (from FCP)
10/100 MBit, bitbus DB9F
140 mm x 118 mm x 45 mm
ETH BIT
To connect the computer to the fire control system detect 3000
network, wall-mounting:
connection of the visualisation system visual detect
on-wall socket 9 x 13 with bitbus-interface
for the Windows-operating system 2000 und XP (Vista projected)
supports no repeater functions
bitbus-clock rate: 62,5 and 375 kBit
connection bitbus-terming for operation at the start and at
the end of the circuit is possible
Technical data
operation voltage
interfaces
dimension (H x W x D)
No. 32269
Bitbus-repeater bidirectional
24 V DC (from FCP)
10/100 MBit Ethernet LSA,
bitbus spring-clamp-detector
140 mm x 118 mm x 45 mm
BBR
extension of the maximum cable length of 1200 m
connection of branch lines
built-in ferrule resistors for the slave-segment
operation status via LEDs (power supply, green/sending from
slave-segment: RTS, yellow)
three DB9-connectors, two for the master-segment and one for
the slave-segment
3-pole plug-in screw clamp for 24 V-power supply and earth
respectively
Technical data
Bidirectional repeater for the bitbus RS-485-Repeater for
application in the following cases:
operation voltage
current consumption
interfaces
dimension (H x W x D)
24 V DC
100 mA
3 x bitbus
151 mm x 64 mm x 48 mm
13
www.detectomat.com
3. Accessories
3.2 Network Components
No. 30119
Bitbus CPU
BB-CPU
Separate intelligent unit to control outputs in the bitbus network
without using fire control panels:
up to 8 extensions art.-no. 30120/30122 connectable
maximum 61 units in one bitbus network usable
housing for plugging in on DIN rails
outputs freely programmable
externally powered (24 V DC)
Technical data
operation voltage
quiescent current
alarm current
interfaces
dimension (H x W x D)
No. 30120
Extension for bitbus OC
21 up to 28 V DC
175 mA
150 mA
bitbus/RS 232
125 mm x 133 mm x 58 mm
BB-32
Module to extend the bitbus CPU:
with 32 open collector outputs (24 V DC/90 mA)
housing for plugging in on DIN rails
up to 8 units on one bitbus CPU usable
connection cable art. 55126 is necessary for each unit
Technical data
operation voltage
quiescent current
alarm current
output open collector
dimension (H x W x D)
No. 30122
Extension for bitbus relay
21 up to 28 V DC
17 mA
max. 320 mA
32 (24 V DC/90 mA)
125 mm x 163 mm x 60 mm
BB-16
Module to extend the bitbus CPU:
housing for snap on DIN rails
up to 8 units on one bitbus CPU usable
3 relais 30V/2A
connection cable No. 55126 is necessary for each unit
Technical data
operation voltage
quiescent current
alarm current
output relay
dimension (H x W x D)
14
www.detectomat.com
21 up to 28 V DC
16 mA
max. 320 mA
with 16 relay outputs
(30 V DC/2 A)
125 mm x 163 mm x 60 mm
3. Accessories
3.3 Programming Tools and Software
No. 30501
I-Check software
I-Check 3000
Loop configuration and test software:
No. 30136
detectomat programming tool
loop diagnostics and the location of failures are automatically
displayed in a graphic of the loop 3000 devices
graphical representation of the loop structure via software
the loop devices are constantly analysed and the analogue
values are displayed
graphical display of the analogue values of smoke,
contamination, temperature, loop-voltage and
temperature-compensation
display of detector-type, serial-number, detector-zone with
number, free customer text
all data can be exported in Excel or Word files
extensive print functions of graphics and charts
configuration for all loop devices (algorithms, sensitivities, etc.)
Windows based user interface
software runs on required Windows 98, 2000 or XP
supported by loop tester LT 3000
data medium CD-ROM
DPT 3000
Configuration software for fire control panels of the system detect
3000, the remote control panel and the bitbus CPU network:
No. 31482
Easy Check
programming of the fire control panel
network-configuration
supported by remote maintenance
software-expansion-dongle No. 30137
Windows user interface
software runs on required Windows 98, 2000 or XP
data medium CD-ROM
EC 3000
Manual addressing and programming tool for all loop 3000 devices:
battery-operated stand-alone unit
bilingual German/English
4 rows with backlight LC-display
keypad
integrated detector base
separate connection for loop modules and manual call points
read-out and changing of the addresses and grades of
sensitivity of all loop 3000 elements
copy-function for device replacement
automatic switch-off if not in use to save batteries
automatic lighting
low battery warning
acoustic confirmation in case of keystroke and waring
acoustic confirmation can be switched off
15
www.detectomat.com
3. Accessories
3.3 Programming tools and software
No. 31625
Loop-Tester
LT 3000
Loop testing tool for all loop 3000 installations, independently
usable without panel installation:
No. 30143
Visual detect basic software
test and programming tool for one loop
direct connection to the personal computer
loop diagnostics and the location of failures are automatically
graphical representation of the loop structure via software
the loop devices are constantly analysed and the analogue
values are displayed
graphical display of the analogue values of smoke, contamination,
temperature, loop-voltage and temperature compensation
display of detector type, serial number, detector zone with number,
free customer text
all data can be exported in Excel or Word files
extensive print-functions of graphics and charts
configuration for all loop devices (algorithms, sensitivities, etc.)
Windows based user interface
the software runs on Windows 98, 2000 or XP
VD Basic 11
Basic visualization software kit for detectomat fire control systems,
basis software for one fire control panel and one workstation:
runs under Windows 2000/XP
network compatible (server-client-principle)
modular structure of the software
full graphic visualization
simulation tool (to test the detectors and the programmed
system connections)
freely definable alarm management, procedure-plans
option for automatic execution of procedure-plans
German/English/Russian/Spanish multilingual
print function (e.g. print of fire brigade routing card, unit
location plans)
system consists of a development and runtime interface
help function for development and runtime interface
password can be modified in the log-on window
data-codification between server and clients
detector data can be generated and read-in via the
dpt-programming tool
full functionality within the system in one host without an active
connection to a bitbus network
all simulated messages and their execution are recorded and
can be analysed and retrieved with a filter
own projects are programmable, incl. scanning of unit location
plans, routing cards, places of addressed detectors and creation
of procedure-briefings
comprehensive operator and rights management
different user hierarchies can be created within the software by
assigning individual rights
connection via bitbus (USB module, PCI card)
location-independent system (TCP/IP protocol)
16
www.detectomat.com
3. Accessories
3.3 Programming tools and software
No. 32668
Visual detect basis SW kit
VD smart
Fire control visualisation kit for detectomat fire control systems,
basis software VD Basic 11 for a fire control panel and one
workstation, incl. bitbus-interface USB-BIT (No. 32258):
No. 30144
Visual detect user expansion
For the expansion of detectomat fire control systems
(1 more workstation/user each):
No. 30145
Visual detect expansion panel
For the expansion of detectomat fire control systems
(1 more workstation/user each):
No. 30146
Visual detect operation expansion
included in delivery CD single licence VD Basic 11, VD
operation expansion VD CE 1, bitbus interface USB-BIT,
CD and licence dongle
no licence extension possible
VD UE 1
possibility to work in the network
messages notification and "send messages"
operator specific classified messages and rights possible
VD PE 1
a maximum of 20 units can be managed
operator specific classified messages and rights possible
VD CE 1
License kit for the remote control function expansion via
visualisation software.
No. 32310
Universal programming set
The cable is a RS-232 serial cable where the transmit and receive
lines are crosslinked. This 6ft cable has a DB9 female connector on
each end. A direct electronic data interchange between fire control
panel and PC interfaces is possible. Including gender changer.
UPC
Technical data
connection
colour cable
cable length
No. 32313
Hardlock FCP
9pol. D-SUB-female jack <>
9pol. D-SUB-male jack
grey
1800 mm
HL
Hardlock protects the FCP of unautorised programming in
conjunction with the detectomat programming tool.
17
www.detectomat.com
4. Fire Detectors
System 3000 Detectors
Early and reliable fire detection of high performance
Innovative technologies and highest functionality with a wide range of features
loop length of 3.000 m
126 devices per loop
automatic addressing
easy soft addressing
high reliability measurement system
automatic threshold adjusting
programmable sensitivity levels
multichamber and algorithm analyzing FUSION and HUMITEC
fastest detection without false alarm
T-branch and open collector output (OC)
international approvals and certifications
18
www.detectomat.com
4. Fire Detectors
4.1 loop 3000 Addressable Fire Detectors
No. 32149
Multisensor optical/thermal
PL 3300 OTi Fusion
Intelligent optical and thermal detector for loop 3000, for earliest
fire detection in environments with difficult ambient conditions,
according to EN 54-5/7:
highly functional detection system for loop 3000
highest operational reliability thanks to intelligent connection of
thermal and optical sensor signals via algorithms
integrated measuring system and algorithm for bedewing
identification/-compensation (Humitec)
display of the fire control panel temperature profile
alarm output for triggering a detector indication
detector sensitivities automatical adjustable as well as
freely programmable
optical measurement according to the Tyndall principle
detection of smallest smoke particles and early-stagefires by
using the wide banded white light in the wave length of 380 nm
e of 380 nm up to 750 nm (Fusion-technology)
exact detection and compensation of contamination by an
independent second measuring channel
No. 30301
Detector base standard
intelligent analysis and suppression mode for cigarette smoke
(disturbance variables)
intermittent implementation of an authentic sensor test
programmable attendance and absence via individually
selectable sensitivity
last maintenance event storage
automatic and manual addressing on the loop 3000
failure monitoring of the measurement signal chamber and
loop 3000 electronics
mode for adapting to environmental conditions
integrated isolator and t-branch (spur) facility
multicolour LED for alarm (red) and fault (yellow)
Technical data
operating voltage
quiescent current
alarm current
sensitivity
operation temperature
output open collector
humidity
protection class
colour housing
material
DIN-EN
further approvals
dimensions (H x )
air speed
approval
15 up to 30 V loop powered
250 A
5 mA
5 levels adjustable
-10C up to +60C
max. 10 mA for LED
indicators or piezo base
max. 95% RH/40C
IP 30
white, similar to RAL 9003
ABS
54-7, 54-5
BMA 06/0625-A, 2006277-SW
52 mm x 100 mm
max. 20 m/s
submitted
SDB 3000 white
Standard base for all detectors of the series loop 3000:
including LED indicator connection
space for additional modules
Remarks: Accessories for smoke detectors chapter 4.1 Accessories.
No. 31959
Detector base standard bridged
Standard detector base for all detectomat detectors of the series
loop 3000 with integrated bridge for loop:
including LED indicator connection
in the absence of the detector the function of the loops operated
minus contacts are bridged in non-operative condition
SDBB 3000 white
Technical data
operation temperature
material
dimensions (H x )
-10C up to +60C
ABS
20 mm x 95 mm
19
www.detectomat.com
4. Fire Detectors
4.1 loop 3000 Addressable Fire Detectors
No. 32150
Multisensor optical/thermal, isolator
PL 3300 OTi
integrated measuring system and algorithm for bedewing
identification/-compensation (Humitec)
alarm output for triggering a detector indication
detector-sensitivity is freely programmable
different sensitivities are programmable for day and
night periods
la log of a last maintenance event is stored
integrated isolator and t-branch (spur) facility
multicolour LED for alarm (red) and fault (yellow)
Technical data
Intelligent optical and thermal detector for loop 3000, for earliest
fire detection in environments with difficult ambient conditions,
according to EN 54-5/7:
highly functional detection system for loop 3000
highest operational reliability with intelligent connection of
thermal and optical sensor signals via algorithms
No. 30079
CO gas and heat detector, isolator
quiescent current
alarm current
operating voltage
sensitivity
operation temperature
Humidity
protection class
DIN-EN
further approvals
dimensions (H x )
air speed
approval
250 A
5 mA
15 up to 30 V loop powered
5 levels adjustable
-10C up to +60C
max. 95% RH/40C
IP 30
54-7, 54-5
BMA 06/0625-A,
2006277-SW
52 mm x 100 mm
max. 20 m/s
submitted
PL 3300 COBT
superior operational reliability from intelligent analysis of
the sensor signals
fault monitoring for sensor signal and thermal sensor
alarm analysis wit professional carbon monoxide sensors
independent carbon monoxide measurement
maximum and rate of rise analysis with thermal
sensor technology
a log of the last maintenance date is stored
alarm output for triggering a detector indication
multicolour-LED for alarm (red) and fault (yellow)
integrated buzzer for CO-alarm
Technical data
Intelligent multisensor detector for loop 3000, for carbon
monoxide gas, 2 thermal sensors and bidirectional isolator,
according to EN 54-5:
quiescent current
alarm current
operating voltage
operation temperature
humidity
protection class
DIN-EN
dimensions (H x )
air speed
addressable spur connection via T-branch
temperature measurement via highly sensitive sensors
20
www.detectomat.com
600 A
5 mA
15 up to 30 V loop powered
-10C up to +60C
max. 95% RH/40C
IP 30
54-5
58 mm x 100 mm
max. 20 m/s
4. Fire Detectors
4.1 loop 3000 Addressable Fire Detectors
No. 30007
Optical smoke and heat detector
PL 3200 OT
VdS G205052
No. 30021
Optical smoke and heat detector, isolator
PL 3300 OT
VdS G205051
detector-sensitivity is freely programmable
different sensitivities are programmable for day and
night periods
a log of the last maintenance date is stored
outputs for the alarm and fault condition indication
at the detector
automatic fault monitoring of the measuring chamber electronics
multicolour-LED for alarm (red) and fault (yellow)
integrated isolator and t-branch (spur) facility
PL 3300 OT with integrated short circuit isolator
Technical data
Intelligent addressable detector for loop 3000, 2 optical and 2
thermal sensors, according to EN 54-5/7:
superior operational reliability from intelligent analysis of
the thermo sensors
temperature measurement via highly sensitive sensors
maximum and rate of rise analysis with thermal
sensor technology
two independent optical measuring channels
quiescent current
alarm current
Operation voltage
operation temperature
humidity
protection class
DIN-EN
dimensions (H x )
air speed
approvals
250 A
5 mA
15 up to 30 loop powered
-10C up to +60C
max. 95% RH/40C
IP 30
54-7, 54-5
52 mm x 100 mm
max. 20 m/s
further on request
No. 30009
Optical smoke detector
PL 3200 O
VdS G202003
No. 30011
Optical smoke detector, isolator
PL 3300 O
VdS G202002
detector-sensitivity is freely programmable
different sensitivities are programmable for day and
night periods
a log of the last maintenance date is stored
outputs for the alarm and fault condition indication
at the detector
multicolour-LED for alarm (red) and fault (yellow)
integrated isolator and t-branch (spur) facility
PL 3300 O with integrated short circuit isolator
Technical data
Intelligent addressable detector for loop 3000, 2 optical sensors,
according to EN 54-7:
superior operational reliability from intelligent analysis of
the measuring chamber signal
a second independent optical measuring channel
quiescent current
alarm current
Operating voltage
operation temperature
humidity
protection class
DIN-EN
dimensions (H x )
weight
approvals
250 A
5 mA
15 up to 30 V loop powered
-10C up to +60C
max. 95% RH/40C
IP 30
54-7
44 mm x 100 mm
0,11 kg
further on request
21
www.detectomat.com
4. Fire Detectors
4.1 loop 3000 Addressable Fire Detectors
No. 30008
Heat detector
PL 3200 T
VdS G203038
No. 30010
Heat detector, isolator
PL 3300 T
VdS G203037
detector-sensitivity is freely programmable
different sensitivities are programmable for day and
night periods
a log of the last maintenance date is stored
outputs for the alarm and fault condition indication
at the detector
multicolour-LED for alarm (red) and fault (yellow)
integrated isolator and t-branch (spur) facility
PL 3300 T with integrated short circuit isolator
Technical data
Intelligent addressable detector for loop 3000, 2 thermal sensors,
according to EN 54-5:
superior operational reliability from intelligent analysis of
the thermo sensors
temperature measurement via highly sensitive sensors
quiescent current
alarm current
operating voltage
operation temperature
humidity
protection class
DIN-EN
further approvals
dimensions (H x )
air speed
approvals
250 A
5 mA
15 up to 30 V loop powered
-10C up to +60C
max. 95% RH/40C
IP 30
54-7
VdS G 202003 (G 202002)
44 mm x 100 mm
max. 20 m/s
further on request
No. 30567
Optical smoke detector
PL 3305 O white
VdS G204089
No. 30568
Optical smoke detector
PL 3305 O silver
VdS G204089
a second independent optical measuring channel
detector-sensitivity is freely programmable
different sensitivities are programmable for day and
night periods
a log of the last maintenance date is stored
outputs for the alarm and fault condition indication
at the detector
multicolour-LED for alarm (red) and fault (yellow)
integrated isolator and t-branch (spur) facility
PL 3300 O with integrated short circuit isolator
Technical data
Intelligent addressable detector for loop 3000, 2 optical sensors,
according to DIN EN 54-7:
superior operational reliability from intelligent analysis of
the measuring chamber signal
quiescent current
alarm current
Operation voltage
operation temperature
humidity
protection class
DIN-EN
dimensions (H x )
air speed
approvals
22
www.detectomat.com
250 A
5 mA
15 up to 30 V loop powered
-10C up to +60C
max. 95% RH/40C
IP 30
54-7
44 mm x 100 mm
max. 20 m/s
further on request
4. Fire Detectors
4.1 loop 3000 Addressable Fire Detectors
No. 30956
Optical smoke detector
PL 3301 O white
VdS G205046
No. 30488
Optical smoke detector
PL 3301 O silver
VdS G205046
No. 30525
Optical smoke detector
PL 3301 O black
VdS G205046
different sensitivities are programmable for day and night periods
a log of the last maintenance date is stored
outputs for the alarm and fault condition indication
at the detector
multicolour-LED for alarm (red) and fault (yellow)
integrated isolator and t-branch (spur) facility
PL 3300 O with integrated short circuit isolator
Technical data
Intelligent addressable detector for loop 3000, 2 optical sensors,
according to DIN EN 54-7:
superior operational reliability from intelligent analysis of
the measuring chamber signal
a second independent optical measuring channel
detector-sensitivity is freely programmable
quiescent current
alarm current
operation voltage
operation temperature
humidity
protection class
DIN-EN
dimensions (H x )
approvals
250 A
5 mA
15 up to 30 V loop powered
-10C up to +60C
max. 95% RH/40C
IP 30
54-7
44 mm x 100 mm
further on request
4. Fire Detectors
4.2 Accessories
No. 30301
Detector base standard
SDB 3000 white
No. 30926
Detector base standard
SDB 3000 silver
No. 30523
Detector base standard
SDB 3000 black
Standard base for all detectors
of the series loop 3000 and CT:
including LED indicator connection
space for additional modules
operation temperature
material
dimensions (H x )
No. 31959
Detector base standard with bridge
SDBB 3000 white
No. 32084
Detector base standard with bridge
SDBB 3000 silver
No. 32083
Detector base standard with bridge
SDBB 3000 black
Standard detector base for all detectomat detectors of the series
loop 3000 with integrated bridge for loop:
Technical data
including LED indicator connection
in the absence of the detector the function of the loops operated
minus contacts are bridged in non-operative condition
-10C up to +60C
ABS
20 mm x 95 mm
Technical data
operation temperature
material
dimensions (H x )
-10C up to +60C
ABS
20 mm x 95 mm
23
www.detectomat.com
4. Fire Detectors
4.2 Accessories
No. 30479
Detector labelling clip
MBC
Usable for all detector bases SDB and SDBB of the series loop
3000 and CT:
No. 32091
Piezo buzzer for loop 3000 detectors
fixing via plug in
selling-packages include 30 pieces each
PB
activated by open collector output
powered by the detector
Technical data
Additional buzzer for detectors of the series loop 3000 and CT:
No. 31698
Wall mount base adapter
operation voltage
sound volume
operation temperature
dimensions (H x W x D)
15 up to 33 V DC
85 dB/0,3 m distance
-10C up to +60C
8 mm x 45mm x35 mm
APS
Usable as wall mount kit for detector base standard SDB 3000, for
on wall wire installations:
four wire entries at the side
internal space for additional modules
Technical data
operation temperature
material
dimensions (H x )
-10C up to +60C
ABS
28 mm x 110 mm
Remarks: It is essential to specifying the right base separately. The
base is not incl.
No. 32070
Flush-mounting adapter
DR45 white
No. 31684
Flush-mounting adapter
DR45 silver
flush mounting base kit for smoke detectors
ceiling hole diameter 120 mm
Technical data
operation temperature
material
Dimensions (H x )
Usable as mount-in kit for semi-recess detectors of the series
loop 3000 and CT 3000 in lowered ceilings:
-10C up to +60C
steel
35 mm x 165 mm
Remarks: The flush-mounting adapter is only suitable for ceilings in
rooms without pressure difference. Overpressure and/or negative
pressure, like in air-conditioned ambiance, produce a permanent
airflow that influences the plotting unit.
24
www.detectomat.com
4. Fire Detectors
4.3 Addressable Call Points
No. 32065
Manual call point, isolator
PL 3300 MCP-kit
Intelligent push button detector for loop 3000 with bidirectional
isolator, label symbol "Burning House":
loop 3000 is a highly functional detection-system
automatic addressing (soft-addressing)
manual addressing (Easy Check)
output for alarm at the detector
Technical data
quiescent current
alarm current
operation temperature
humidity
protection class
colour housing
material
DIN-EN
dimensions (H x W x D)
No. 31669
Manual call point
PL 3300 PBDH-ABS-R
370 A
5 mA
-10C up to +55C
max. 95% RH/40C
IP 24 D
red, RAL 3000
ABS
54-11
88 mm x 88 x 54 mm
VdS G 2030211
Intelligent manual call point for loop 3000, with bidirectional
isolator, labelled symbol "Burning House":
highly functional detection-system for loop 3000
alarm output for triggering a detector indication
addressable spur connection via T-branch
a log of the last maintenance date is stored
intelligent function monitoring of push button mechanism
automatic addressing (soft-addressing)
manual addressing (Easy Check)
suitable for installation in fire extinguishing cabinets
LED for alarm (red)
Technical data
operation voltage
quiescent current
alarm current
operation temperature
protection class
color housing
material
DIN-EN
dimensions (H x W x D)
15 up to 30 V loop powered
250 A
5 mA
-10C up tol +60C
IP 42
red, RAL 3000
ABS
54-11, Typ B
135 mm x 135 mm x 33 mm
25
www.detectomat.com
4. Fire Detectors
4.3 Addressable Call Points
No. 31668
Manual call point
PL 3300 PBDH-ALU-R
VdS G 203021
Intelligent manual call point for loop 3000, with bidirectional
isolator, labelled symbol "Burning House":
highly functional detection-system for loop 3000
alarm output for triggering a detector indication
addressable spur connection via T-branch
a log of the last maintenance date is stored
intelligent function monitoring of push button mechanism
automatic addressing (soft-addressing)
manual addressing (Easy Check)
suitable for installation in fire extinguishing cabinets
LED for alarm (red)
Technical data
operation voltage
quiescent current
alarm current
operation temperature
protection class
colour housing
material
DIN-EN
dimensions (H x W x D)
No. 31091
Weatherproof housing
15 up to 30 V loop powered
250 A
5 mA
-10C up tol +60C
IP 42
red, RAL 3000
aluminium
54-11, Typ B
125 mm x 125 mm x 34 mm
WH-R
Weatherproof housing in red for aluminium manual call points
PL 3300 PBDH-ALU-R:
usable to reach protection level IP 54
including fitting kit
Technical data
protection class
color housing
material
dimensions (H x W x D)
26
www.detectomat.com
IP 54
red, RAL 3000
aluminium
145 mm x 131 mm x 55 mm
5. loop 3000 modules
No. 30200
In-/Output module
IOM 3311
VdS G 205029
1 monitored input to connect external devices to the loop 3000
1 potential-free output to control external devices
in- and output freely programmable
multicolour-LED for alarm (red) and fault (yellow)
Technical data
Intelligent in-/output module for loop 3000, with bidirectional
isolator, in a housing:
highly functional detection-system for loop 3000
addressable spur connection via T-branch
No. 30211
Output module
operation voltage
quiescent current
alarm current
output relay
operation temperature
protection class
colour housing
material
DIN-EN
dimensions (H x W x D)
OMS 3301
15 up to 30 V loop powered
500 A
5 mA
change over 30 V DC/1 A
-10C up to +60C
IP 54
grey, similar to RAL 7035
ABS
54
93 mm x 93 mm x 55 mm
VdS G 205030
1 potential-free output to control external devices
the relay can be reset at the fire control panel via
"external sounder on/off"
output is freely programmable
Technical data
Intelligent sounder control module for loop 3000 including
bidirectional isolator, in a housing:
output module with highest functionality for loop 3000
addressable spur connection via T-branch
No. 32073
Extension module for IOM 3311/OMS 3301
operation voltage
quiescent current
alarm current
output relay
operation temperature
protection class
colour housing
material
DIN-EN
dimensions (H x W x D)
UBW 3311
Extension module for the
realisation of monitored
outputs via IOM 3311
or OMS 3301:
operation voltage
quiescent current
alarm current
operation temperature
protection class
colour housing
material
DIN-EN
dimensions (H x W x D)
to be easily built into
the housing of I
OM 3311/OMS 3301
1 monitored output with
broken wire- and short
circuit monitoring
max. current 1 A
externally powered 24 V/11 mA quiescent current
15 up to 30 V loop powered
500 A
5 mA
change over 30 V DC/1 A
-10C up to +60C
IP 54
grey, similar to RAL 7035
ABS
54
93 mm x 93 mm x 55 mm
convenient for the monitored connection of signalling devices
delivery including 1 x connecting cable and 1 x 10 K-Ohm-resistor
Technical data
24 V/11 mA
11 mA
max. 1 mA
-10C up to +60C
IP 54
grey, similar to RAL 7035
ABS
54-18
20 mm x 38 mm x 55 mm
27
www.detectomat.com
5. loop 3000 Modules
No. 30205
Conventional zone module
TCM 3300
VdS G 206048
external power supply of 12/24V
automatic addressing (soft-addressing)
manual addressing (Easy Check)
multicolour-LED for alarm- (red) and fault-display (yellow)
Technical data at the conventional line: voltage 12/24 V, current
consumption 10 mA plus conventional detector, max. current 65 mA
Technical data
Intelligent connecting module for one zone of conventional detectors
to loop 3000, including bidirectional isolator:
detector zone interface with high functionality for loop 3000
addressable spur connection via T-branch
variable adjustable of short circuit-, break wire-, pre-alarm and
alarm threshold
operation voltage
quiescent current
alarm current
output external user
operation temperature
protection class
colour housing
material
DIN-EN
dimensions (H x W x D)
No. 30513
In-/output module mini
AMD 3311 mini
No. 31640
Output module mini
OMS 3301 mini
15 up to 30 V loop powered
560 A
5 mA per zone
12/24 V
-10C up to +60C
IP 54
grey, similar to RAL 7035
ABS
54
93 mm x 93 mm x 55 mm
VdS G 206047
Technical data
Intelligent mini casted input/output module for loop 3000:
AMD 3311: 1 monitored input to connect external devices
to the loop 3000
OMS 3301: 1 open collector output to control external devices
in- and output are freely programmable
No. 32074
Output module mini
operation voltage
quiescent current
alarm current
output open collector
operation temperature
protection class
colour housing
DIN-EN
dimensions (H x W x D)
15 up to 30 V loop powered
370 A
5 mA
1 x OC 500 mA
-10C up to +60C
IP 54
blue
54
27 mm x 73 x 15 mm
AOM 3301
1 monitored output to control external devices (sounder, LED-flashlight)
output is freely programmable
circuit board version, with grey housing
Technical data
Intelligent mini-output-module for loop 3000, monitored, including
bidirectional isolator to control active devices (sounder, beacons):
quiescent current
alarm current
operating voltage
output external user
operation temperature
protection class
colour housing
material
DIN-EN
dimensions (H x W x D)
28
www.detectomat.com
400 A
5 mA
15 up to 30 V loop powered
5 mA monitored
-10C up to +60C
IP 54
grey, similar to RAL 7035
ABS
54
400 mm x 112 mm x 38 mm
6. Signalling Devices
No. 31836
Loop sounder red
LS 3300 R
No. 32012
Loop sounder white
LS 3300 W
directly addressable via loop 3000
2 different tones adjustable (including DIN tone)
automatic addressing (soft-addressing)
manual addressing (Easy Check)
audibility adjustable via potentiometer
Technical data
Low current multiple tone sounder directly powered by loop 3000,
with bidirectional short circuit isolator:
No. 32060
Loop sounder shallow
operation voltage
alarm current
volume
operation temperature
protection class
colour housing
material
dimensions (H x )
15 up to 30 V loop powered
5 mA
max. 97 dB
-10C up to +60C
IP 43
red/white
ABS
100 mm x 101 mm
LS 3300 VLC
automatic addressing (soft-addressing)
manual addressing (Easy Check)
figure: LS 3300 VLC incl. AOM 3301 excl. base No. 32241
Technical data
Low current multiple tone sounder, with 4 different tones, directly
powered by loop 3000 via control module:
4 different tones adjustable via DIP button
tones in the frequency-band of 440 Hz up to 2900 Hz
3 sound levels adjustable
operation voltage
frequency
current alarm
quiescent current
volume
operation temperature
protection class
colour housing
material
DIN-EN
dimensions (H x )
E. g. Loop-sounder
E. g. Loop-sounder shallow
Figure 1:
1 x 32060 LS 3300 VLC
1 x 32241 SDB
1 x 30011 PL 3300 O
Figure 2:
1 x 32060 LS 3300 VLC
1 x 32067 CP red or
32067 CP white
No. 32067
Cover for sounder flat red
CP r
No. 32068
Cover for sounder flat white
CP w
24 up to 32 V loop powered
440 up to 2900 Hz
6 mA
280 A
max. 85 dB/3 m
-10C up to +60C
IP 43
white
ABS
54
27 mm x 117 mm
29
www.detectomat.com
6. Signalling Devices
No. 32090
Loop beacon amber
LB 3300 VBX O
No. 32058
Loop beacon red
LB 3300 VBX R
Low current LED beacon
for the system loop 3000:
housing white with an
amber or red calotte
flash rate: 1Hz
current consumption:
at 5 mA 0,7 watt and
at 3 mA 0,4 watt
directly powered by
loop 3000 via integrated
control module
No. 32282
LED indicator
Intelligent LED-indicator
for loop 3000 with
bidirectional isolator:
highly functional LED
indicator with integrated
addressing module
automatic addressing
(soft-addressing)
manual addressing
(Easy Check)
Technical data
operation voltage
current alarm
frequency
operation temperature
protection class
colour housing
material
DIN-EN
dimensions (H x )
24 up to 35 V loop powered
3 up to 5 mA
1 Hz
-20C up to +70C
IP 43
White
ABS
54
60 mm x 95 mm
PL 3300 PA
Technical data
operation voltage
operation temperature
alarm current
quiescent current
humidity
protection class
DIN-EN
material
dim ensions (H x W x D)
No. 30204
Sound unit red
SDM 3300 R
No. 30527
Sound unit white
SDM 3300 W
15 up to 30 V DC loop powered
-15C up to +50C
5 mA
280 A
max. 95 %
IP 30
54-18
ABS
84 mm x 84 mm x 35 mm
integrated automatic addressing-unit
integrated bidirectional short circuit isolator
addressable spur connection via T-branch
external voltage supply (24V) necessary
internal sound levels adjustable
26 different tones programmable
Technical data
Multiple-tone sounder to be used in loop 3000, with soundmodule,
addressable connections with external voltage according to DIN 33404:
frequency
operation voltage
quiescent current
current alarm
volume
operation temperature
protection class
colour housing
material
DIN-EN
dimensions (H x )
30
www.detectomat.com
500 Hz up to 2850 Hz
15 up to 30 V DC loop powered
250 A
9 up to 29 mA
111 dB
-10C up to +60C
IP 54
red
ABS
54
93 mm x 93 mm
7. Wireless Detect
Wireless Detection System
with unique detectors for smaller applications
RCP6 B
HD 3000 detectors
wireless fire control panel
microprocessor controlled
433 MHz
6 zones
up to 100 radio addressable devices linkable
4 potential-free outputs
emergency batteries
LCD display
optical and thermal smoke detectors for an early
smoke verification
programmable sensitivity levels
up to 40 fire detectors interlinked
interface interlinking via radio module (433 MHz or 868 MHz)
automatic fault monitoring of measuring chamber
acoustic alert
wide range of design variants
certified DIN 14604
international approvals and certifications
31
www.detectomat.com
7. Wireless Detect
No. 32130
Wireless fire control panel
RCP 6B
4 potential-free relay outputs
emergency power (batteries 8 x 1,5 V type Mignon LR 6)
for max. 77h without alarm/with continuous alarm min. 15h
optic and acoustic signal of alarm and fault
identifying and monitoring devices for battery capacity, sensor
malfunction, availability (wireless path) and signs of life
analysis of the life signs after 24 h
integrated back-up batteries 8 x 1,5 V
integrated power supply
per FCP unit 3 repeater applicable
Technical data
Microprocessor controlled wireless radio panel, bidirectional, with
backup alarm function to connect up to 100 wireless detectors of
the series HD:
operating range in the frequency band 433 MHz
6 alarm zones/detector zones
No. 32294
Connecting cable for RCP 6B
system voltage
operating voltage
quiescent current
alarm current
frequency
emergency power
operation temperature
output relay
display
protection class
humidity
colour housing
material
dimensions (H x D x W)
230 V AV
12 V DC
max. 30 mA
160 mA
433. 42 MHz
8 x 15 V/max. 77 h
0C up to +60C
4 relais 50 V/0,5 A
LCD display
IP 20
max. 70 %
grey
ABS
170 mm x 170 mm x 55 mm
F.BZ
Cable 24 V with SUB-D-plug connector for easy connection to the
potential-free relay contacts of the RCP 6B.
No. 32131
Wireless repeater
F.RP RCP 6B
indication of the signal strength while programming
transmission of signals (alarm, fault and status) to the panel
life signs are sent regularly in order to keep up the control function
emergency power supply 1 x Alkaline battery type IEC 6LR61, ca. 8 h
appropriate for use in dry, heated locations
wall mounting
Technical data
Radio repeater to extend radio distances between wireless fire
control panel RCP 6B and wireless detectors:
10 sensors each wireless repeater RCP 6B programmable
system voltage
operating voltage
quiescent current
alarm current
frequency
emergency power
operation temperature
colour housing
material
dimensions (H x D x W)
32
www.detectomat.com
230 V AV
12 V DC
35 mA
70 mA
433. 42 MHz
1 x 9 V/8 h
0C up to +60C
grey
ABS
158 mm x 95 mm x 45 mm
7. Wireless Detect
No. 30458
Smoke alarm
HDv 3000 O
VdS G202042
up to 40 fire detectors interlinked
the acoustic alert is made by an integrated piezo
alarmsounder (> 85 dB)
a visual and acoustic siganl at low battery condition for 30 days
the optional plug-in radio module interface offers radio
interlinking for reporting fault and alarm conditions via 433 MHz
the average life span with a 9 V alkaline battery is
approximately 2 years (without interlinking or alarms at 20C
ambient temperature)
delivery including detector base, battery, screws and anchors
Technical data
Battery powered optical smoke alarm detector according to EN 14604:
automatic fault monitoring of the measuring chamber as well as
the battery voltage
operating voltage
responsivity
quiescent current
frequency
operation temperature
colour housing
material
dimensions (H x )
approvals
9 V DC
< 0,15 dB/m
< 16 A
433. 42 MHz
-10C up to +60C
white
ABS
51 mm x incl. base 100 mm
further on request
No. 32004
Smoke alarm
HD 3005 O silver
VdS G204091
No. 32015
Smoke alarm
HD 3005 O white
VdS G204091
Battery powered smoke alarm detector EN 14604:
automatic fault monitoring of the measuring chamber as
well as the battery voltage
up to 40 fire detectors interlinked
the acoustic alert is made by an integrated piezo
alarmsounder (> 85 dB)
a visual and acoustic siganl at low battery condition for 30 days
the optional plug-in radio module interface offers radio
interlinking for reporting fault and alarm conditions via 433 MHz
the average life span with a 9 V alkaline battery is
approximately 2 years (without interlinking or alarms
at 20C ambient temperature)
delivery including detector base, battery, screws and anchors
Technical data
operating voltage
responsivity
quiescent current
frequency
operation temperature
colour housing
protection class
material
dimensions (H x )
approvals
9 V DC
< 0,15 dB/m
< 16 A
433. 42 MHz
-10C up to +60C
white/silver
IP 30
ABS
55 mm x 113 mm incl. base
further on request
33
www.detectomat.com
7. Wireless Detect
No. 30023
Smoke alarm
HD 3001 O white
VdS G202054
No. 30024
Smoke alarm
HD 3001 O silver
VdS G202054
No. 30123
Smoke alarm
HD 3001 O black
VdS G202054
automatic fault monitoring of the measuring chamber as well as
the battery voltage
the acoustic alert is made by an integrated piezo
alarmsounder (> 85 dB)
a visual and acoustic siganl at low battery condition for 30 days
the optional plug-in radio module interface offers radio
interlinking for reporting fault and alarm conditions via 433 MHz
the average life span with a 9 V alkaline battery is
approximately 2 years (without interlinking or alarms at
20C ambient temperature)
delivery including detector base, battery, screws and anchors
Technical data
Battery powered smoke alarm detector EN 14604:
No. 32132
Wireless module
operating voltage
responsivity
quiescent current
alarm current
frequency
operation temperature
colour housing
protection class
material
dimensions (H x )
approvals
9 V DC
< 0,15 dB/m
< 16 A
20 mA
433. 42 MHz
-10C up to +60C
white/silver
IP 30
ABS
50 mm x 95 mm incl. base
further on request
F.M RCP 6B
Wireless module for smoke detector HDv 3000 O (No. 30458)
for wireless transmission of alarms and fault messages to the
wireless fire control panel RCP 6B:
backup alarm function via the panel by means of bidirectional
data exchange
signs of life are sent regularly in order to keep up the
control function
indication of the signal strength while programming
after plausibility check transmission of signals
(fault, battery capacity) to the panel
acoustic warning individually adjustable
nominal current 36 A
power consumption sending: typ. 35 mA
power consumption receiving: typ. 18 mA
Technical data
operating voltage
responsivity
quiescent current
alarm current
frequency
operation temperature
34
www.detectomat.com
9 V DC
< 0,15 dB/m
36 A
35 mA./18 mA
433. 42 MHz
-10C up to +55C
7. Wireless Detect
No. 30528
Battery
Lithium
Block-Battery 9V/1.2Ah with aluminium cladding
No. 31957
Thermal home detector
TM
up to 40 detectors connectable via networking clamp
connection possibility for wireless networking module
(433 MHz resp. 868 MHz) via integrated wireless interface
the average life span with a 9 V alkaline battery is approximately
2 years (without interlinking or alarms at 20C ambient temperature)
delivery including detector base, battery, screws and anchors
on-wall mounting
Technical data
Battery powered thermal smoke detector with integrated wireless
interface for alarming in domestic applications:
trigger temperature: 60C
acoustical alarm via piezo sounder with audible tone (85 dB)
optical alarm: red LED
signalising of sensor faults and low battery warning for 30 days
No. 32189
Wireless module for thermal detectors
operating voltage
responsivity
quiescent current
alarm current
frequency
operation temperature
output relay
humidity
sound volume
protection class
colour housing
material
dimensions (H x )
9 V DC
60C
max. 16 A
max. 20 mA
433. 42 MHz
-10C up to +65C
4 relais 50 V/0,5 A
max. 80 %
85 dB/1 m
IP 20
white
plastics
70 mm x 80 mm
F.M T RCP 6B
Update module to equip thermal home detector TM (No. 31957)
with, for wireless transmission of alarms and fault messages to
the wireless fire control panel RCP 6B:
backup alarm function via the panel by means of
bidirectional data exchange
signs of life are sent regularly in order to keep up the
control function
indication of the signal strength while programming
after plausibility check transmission of signals
(fault, battery capacity) to the panel
acoustic warning individually adjustable
nominal current 36 A
power consumption sending: typ. 35 mA
power consumption receiving: typ. 18 mA
Technical data
operating voltage
responsivity
quiescent current
alarm current
frequency
operation temperature
9 V DC
< 0,15 dB/m
36 A
35 mA./18 mA
433. 42 MHz
-10C up to +55C
35
www.detectomat.com
7. Wireless Detect
No. 32190
Wireless manual call point
F.MCP RCP 6B
Wireless spring-button detector with integrated wireless module
for manual triggering of fire alarm at the Fire Control Panel RCP 6B:
alarm or battery change signals are transmitted to Fire
Control Panel RCP 6B via the integrated wireless module
life signs are sent regularly in order to keep up the
control function
nominal current: typ. 7,5 A
power consumption alarm: 40 mA
power supply: 1 x 9 V Alkaline block battery IEC 6LR 61,
average, lifetime approx. 1 year
Technical data
operating voltage
quiescent current
alarm current
frequency
operation temperature
protection class
colour housing
material
dimensions (H x W x D)
No. 32133
Wireless manual call point
9 V DC
7,5 A
40 mA
433. 42 MHz
-10C up to +55C
IP 24 D
red
plastics
93 mm x 89 mm x 59 mm
F.DKM RCP 6B
integrated sounder for the acoustic signalising of alarm
and fault
backup alarm function via the panel by means of
bidirectional data exchange
acoustic signalising of received alarms and faults of other
detectors (function of the push-button detector can be
switched on/off optionally)
signalling alarm: LED red, sounder (continuous tone)/signalling
fault: LED yellow, sounder (interval tone every 45 sec.)
nominal current: typ. 45 A
power consumption alarm: typ. 50 mA
acoustic low battery warning for 30 days
life signs are sent regularly in order to keep up the control
function of the radio distance
Technical data
Wireless push-button detector with integrated wireless module for
manual triggering of fire alarm at the fire control panel RCP 6B:
operating voltage
responsivity
quiescent current
alarm current
frequency
operation temperature
colour housing
material
dimensions (H x W x D)
36
www.detectomat.com
6 V DC
60C
45 A
50 mA
433. 42 MHz
-10C up to +55C
blue
plastics
120 mm x 120 mm x 31 mm
7. Wireless Detect
No. 32135
Wireless input module
Universal wireless input module for
wired connection of (e.g.) a manual
call point or a spring-button detector
to wireless fire control panel
RCP 6B:
possibility of connecting a
potential-free contact
indication of the signal
strength while programming
transmission of low battery
warning (Alkaline battery
type IEC 6LR61) to the panel
life signs are sent regularly in
order to keep up the control function
nominal current 15 A
No. 32134
Wireless sounder/beacon
Wireless sounder for direct triggering
via wireless fire control panel RCP 6B
in case of fire alarms:
F.IB RCP 6B
power consumption sending: typ. 35 mA/ receiving: typ. 25 mA
Technical data
operating voltage
responsivity
quiescent current
alarm current
frequency
operation temperature
output relay
humidity
sound volume
protection class
colour housing
material
dimensions (H x )
9 V DC
60C
max. 16 A
max. 20 mA
433. 42 MHz
-10C up to +65C
4 relais 50 V/0,5 A
max. 80 %
85 dB/1 m
IP 20
white
plastics
70 mm x 80 mm
F.ABM RCP 6B
life signs are sent regularly in order to keep up the control
function of the radio distance
Technical data
after plausibility check transmission
of signals (fault, battery capacity) to
the panel
acoustic alarm: approx. 101 dB/1 m
distance, tone changeover from 2400
to 2850 Hz/visual alarm: Xenon
beacon, flash energy 0,7 joule/battery
loss signal: approx. every 45 sec. a
short flash
No. 30964
Radio analyser
operating voltage
quiescent current
alarm current
frequency
operation temperature
sound volume
Protection class
colour housing
material
dimensions (H x )
6 V DC
48 A
150 mA
433. 42 MHz
-10C up to +55C
101 dB
IP 65
red/white
plastics
93 mm x 121 mm
RCP 6B F.RA
Field Analyser for projection and object analysis including
wireless test module for smoke detectors of the series HD
37
www.detectomat.com
8. Conventional System
No. 32143
Fire control panel
FCP 4
No. 30941
Fire control panel
FCP 6
Conventional fire control panel with 4 or 6 detector zones:
2 monitored outputs for signalling devices (250 mA)
max. 30 automatic detectors each zone
6 quiescent current monitored detector zones
6 relay outputs for alarm and fault
space for battery (1 x 12 V/7 Ah)
Technical data
Conventional fire control panel with (FCP 4) 4 detector zones:
2 monitored outputs for signalling devices (300 mA)
1 programmable output for telephone operators
4 quiescent current monitored detector zones
max. 30 automatic detectors each zone
4 relay outputs for alarm and fault
space for battery (1 x 12 V/7 Ah)
No. 30015
Optical smoke detector
system voltage
operating voltage
quiescent current
alarm current
frequency
emergency power
operation temperature
output relay
sounder output
display
humidity
protection class
colour housing
material
220 up to 240 V AC
24 V DC
190 mA
160 mA
50/60 Hz
12 V/7 Ah
0C up to +60C
1 relay per zone
2 x 24 V/300 mA monitored
LCD display
max. 95 %
IP 20
grey
ABS
EN:
FCP
54-2, 54-4
dimensions (H x D x W)
weight
240 mm x 325 mm x 80 mm
2 kg without battery
CT 3000 O
VdS G203036
Conventional optical smoke detector according to EN 54-7:
highly functional detection-system
intelligent analysis of the measuring chamber signal
Technical data
operating voltage
quiescent current
alarm current
open collector output
sensitivity
operation temperature
humidity
protection class
colour housing
material
DIN EN
dimensions (H x )
approvals
38
www.detectomat.com
9 up to 33 V DC
40 mA
20 mA
15 mA for LED indicators
< 0,15 dB/m
-10C up to +60C
max. 95 %/RH/40C
IP 30
white
ABS
54-7
44 mm x 100 mm
further on request
8. Conventional System
No. 30022
Multisensor detector optical/thermal
CT 3000 OT
intelligent analysis of the thermal sensor
intelligent analysis of the measuring chamber signal
Technical data
Conventional multisensor detector optical/thermal according to EN 54-7:
No. 30014
Heat detector
operating voltage
quiescent current
alarm current
open collector output
sensitivity
operation temperature
humidity
protection class
colour housing
material
EN
approvals
9 up to 33 V DC
100 A
20 mA
15 mA for LED indicators
< 0,15 dB/m 60C rate of rise
-10C up to +60C
max. 95 %/RH/40C
IP 30
white
ABS
54-7
further on request
CT 3000 T
highly functional detection-system
intelligent analysis of the thermal sensor
Technical data
Conventional heat detector according to EN 54-7:
No. 30301
Detector base standard
operating voltage
quiescent current
alarm current
open collector output
sensitivity
operation temperature
humidity
protection class
colour housing
material
EN
approvals
9 up to 33 V DC
80 A
20 mA
15 mA for LED indicators
60C rate of rise
-10C up to +60C
max. 95 %/RH/40C
IP 30
white
ABS
54-7
further on request
SDB 3000 white
Standard base for all conventional:
including LED indicator connection
space for additional modules
Technical data
operation temperature
material
colour
dimensions (H x )
-10C up to +60C
ABS
white
20 mm x 95 mm
39
www.detectomat.com
8. Conventional System
No. 30551
Optical smoke detector
CT 3005 O white
No. 30552
Optical smoke detector
CT 3005 O silver
Conventional optical smoke detector according to EN 54-7:
highly functional detection-system
intelligent analysis of the measuring chamber signal
Technical data
operating voltage
quiescent current
alarm current
open collector output
sensitivity
operation temperature
protection class
humidity
colour housing
material
DIN EN
approvals
No. 31929
Optical smoke detector
CT 3001 O white
No. 31589
Optical smoke detector
CT 3001 O silver
No. 31926
Optical smoke detector
CT 3001 O black
9 up to 33 V DC
40 mA
20 mA
15 mA for LED indicators
< 0,15 dB/m
-10C up to +60C
IP 30
max. 95 %/RH/40C
white
ABS
54-7
further on request
Conventional optical smoke detector according to EN 54-7:
highly functional detection-system
intelligent analysis of the measuring chamber signal
Technical data
operating voltage
quiescent current
alarm current
open collector output
sensitivity
operation temperature
protection class
humidity
colour housing
material
DIN EN
dimensions (H x )
approvals
40
www.detectomat.com
9 up to 33 V DC
40 mA
20 mA
15 mA for LED indicators
< 0,15 dB/m
-10C up to +60C
IP 30
max. 95 %/RH/40C
white
ABS
54-7
42 mm x 95 mm
further on request
8. Conventional System
No. 32051
Multiple tone sounder red
VTG 32 SB R
VdS G205137
No. 32053
Multiple tone sounder white
VTG 32 SB W
VdS G205137
Conventional multiple tone sounder
with 32 different tones:
32 different tones adjustable
via DIP button
tones in the frequency-band of
440 Hz up to 2900 Hz,
synchronizable
3 sound levels adjustable
flat base for lateral and rear
cable entry
operating voltage
quiescent current
alarm current
frequency
operation temperature
Sound volume
sound volume
protection class
DIN-EN
material
further approvals
dimensions (H x )
15 up to35 V DC
48 A
9 up to 36 mA
440 up to 2900 Hz
-20C up to +70C
max. 106 dB
101 dB
IP 33 C
54-3
ABS
further on request
85 mm x 94 mm
No. 32052
Multiple tone sounder red
VTG 32 DB R
VdS G205137
No. 32054
Multiple tone sounder white
VTG 32 DB W
VdS G205137
Conventional multiple tone sounder
with 32 different tones:
Technical data
32 different tones adjustable
via DIP button
tones in the frequency-band of
440 Hz up to 2900 Hz,
synchronizable
3 sound levels adjustable
hollow base for lateral and rear
cable entry
No. 32055
Base sounder
Technical data
operating voltage
quiescent current
alarm current
frequency
operation temperature
sound volume
sound volume
protection class
DIN-EN
material
further approvals
dimensions (H x )
15 up to35 V DC
48 A
9 up to 36 mA
440 up to 2900 Hz
-20C up to +70C
max. 106 dB
101 dB
IP 65
54-3
ABS
further on request
102 mm x 94 mm
Verso 32
LPCB 546a/04
flat base for lateral and rear cable entry
Technical data
Conventional multiple tone sounder with 32 different tones:
32 different tones adjustable via DIP button
tones in the frequency-band of 440 Hz up to 2900 Hz,
synchronizable
3 sound levels adjustable
operation voltage
frequency
current alarm
volume
operation temperature
protection class
colour housing
material
DIN-EN
dimensions (H x )
15 up to 35 V DC
440 up to 2900 Hz
9 up to 36 mA
max. 93 dB/m
-20C up to +70C
IP 42
white
ABS
54-3
27 mm x 117 mm
Remarks: Cover plate for sound in white No. 32068 in red No. 32067
41
www.detectomat.com
8. Conventional System
No. 31193
LED indicator
PA
3 separate entries
connection to the detector base
on-wall mounting
Technical data
Conventional LED indicator:
operation voltage
operation temperature
alarm current
material
Protection class
colour
dim ensions (H x W x D)
No. 32056
Beacon, red
VXB 1 SB WB RL
No. 32142
Beacon, amber
VXB 1 SB WB AL
7 up to 35 V DC
-15C up to +50C
4 mA
ABS
IP 30
white/red
84 mm x 84 mm x 35 mm
flash rate: 1 Hz
current consumption: at 5 mA 0,7 watt and at 3 mA 0,4 watt
flat base for cable insertion from the side and the back
Technical data
Conventional beacon:
white housing with amber or red calotte
No. 32063
Sounder beacon combination
operation voltage
operation temperature
alarm current
protection class
frequency
material
colour
dimensions (H x )
20 up to 35 V DC
-20C up to +70C
3 up to 5 mA
IP 43
1 Hz
ABS
white/red/amber
60 mm x 95 mm
VTB 32 DB W
ones in the frequency-band of 440 Hz up to 2900 Hz
are synchronizable
red LED-flashlight, 3 sound levels adjustable
flash rate: 1 Hz
current consumption: at 5 mA 0,7 watt and at 3 mA 0,4 watt
hollow base for cable insertion from the side and the back
Technical data
Conventional multiple tone sounder:
operation voltage
operation temperature
alarm current
protection class
sound volume
frequency
material
colour
dimensions (H x )
32 different tones adjustable via DIP button
42
www.detectomat.com
18 up to 35 V DC
-20C up to +70C
37 mA/24 VDC
IP 65
max. 109 dB
440 up to 2900 Hz
ABS
white/red
107 mm x 94 mm
9. Residential Detection
No. 30458
Smoke alarm
HDv 3000 O
VdS G 202042
up to 40 fire detectors interlinked
a visual and acoustic siganl at low battery condition for 30 days
monitoring area = 60 m2/< 6 m height
the optional plug-in radio module interface offers radio
interlinking for reporting fault and alarm conditions via
433 MHz or 868 MHz
suitable for the installation in habitable leisure vehicles
the average life span with a 9 V alkaline battery is
approximately 2 years (without interlinking or alarms at
20C ambient temperature)
delivery including
Technical data
Battery powered optical home detector for detection and alarming
in domestic applications according to DIN EN 14604:
automatic fault monitoring of the measuring chamber as
well as the battery voltage
the acoustic alert is made by an integrated piezo
alarmsounder (> 85 dB)
operating voltage
responsivity
quiescent current
frequency
operation temperature
colour housing
protection class
material
dimensions (H x )
approvals
9 V DC
< 0,15 dB/m
< 16 A
433. 42 MHz
-10C up to +60C
white
IP 30
ABS
51 mm x incl. base 100 mm
further on request
No. 30023
Smoke alarm
HD 3001 O white
VdS G 202054
No. 30024
Smoke alarm
HD 3001 O silver
VdS G 202054
No. 30123
Smoke alarm
HD 3001 O black
VdS G 202054
a visual and acoustic siganl at low battery condition for 30 days
monitoring area = 60 m2/< 6 m height
the optional plug-in radio module interface offers radio
interlinking for reporting fault and alarm conditions via
433 MHz or 868 MHz
suitable for the installation in habitable leisure vehicles
the average life span with a 9 V alkaline battery is
approximately 2 years (without interlinking or alarms at
20C ambient temperature)
delivery including detector base, battery, screws and anchors
Technical data
Battery powered optical home smoke detector for detection and
alarming in domestic applications, similar to HDv 3000 O, design 1:
automatic fault monitoring of the measuring chamber as
well as the battery voltage
the acoustic alert is made by an integrated piezo
alarmsounder (> 85 dB)
operating voltage
sensitivity
alarm current
quiescent current
humidity
operation temperature
air speed
Protection class
colour housing
material
dimensions (H x )
approvals
9 V DC
< 0,15 dB/m
< 16 A
10 A
95%/RH/40C
-10C up to +60C
max. 20 m/s
IP 30
white/silver/black
ABS
42 mm incl. base x 95 mm
further on request
43
www.detectomat.com
9. Residential Detection
No. 32015
Smoke alarm
HD 3005 O white
VdS G 204091
No. 32004
Smoke alarm
HD 3005 O silver
VdS G 204091
Battery powered optical home detector for smoke detection and
alarm during initial stages of fire, similar to HDv 3000 O, design 5:
a visual and acoustic siganl at low battery condition for 30 days
monitoring area = 60 m2/< 6 m height
up to 40 fire detectors interlinked
the optional plug-in radio module interface offers radio
interlinking for reporting fault and alarm conditions via
433 MHz or 868 MHz
suitable for the installation in habitable leisure vehicles
the average life span with a 9 V alkaline battery is
approximately 2 years (without interlinking or alarms at
20C ambient temperature)
delivery including
Technical data
operating voltage
sensitivity
alarm current
quiescent current
humidity
operation temperature
air speed
protection class
colour housing
material
dimensions (H x )
approvals
No. 30933
Wireless link module
9 V DC
< 0,15 dB/m
20 mA
< 16 A
95%/RH/40C
-10C up to +60C
max. 20 m/s
IP 30
white/silver
ABS
35 mm x 113 mm incl. base
further on request
FM 868
Bidirectional wireless module to interlink home detectors in
cascaded networks in the transmitting frequency of 868 MHz:
bidirectional control function in alarm events, in case of
alarm alerting of all connected detectors
with the module the detectors can be interlinked cascadely
without a panel
automatic boost of the radio signal via integrated
repeater functions
connection via interface (inside of HD-detector)
Technical data
operation temperature
Interface
humidity
alarm current
frequency
operation temperature
44
www.detectomat.com
-10C up to +60C
interface for home detector
95 % RH/40C
37 mA.
868 MHz
-10C up to +60C
10. Information
Technical modification
Due ton continuous development of our products, together with altering manufacturing methods,
the description and data provided are for information only and subject to changes without notice.
Information give the catalogue
We accept no responsibility for the accurancy of the information given in the catalogue.
(Our prices are exclusive of applicable value added tax (VAT). Applicable cale added tax
will be included separately in the invoice on the billing day.
Updates and terms of delivery you will find at www.detectomat.com
detectomat GmbH
An der Strusbek 5, 22926 Ahrensburg, Germany
Registered: Amtsgericht Lbeck, HR B 4645 AH
Geschftsfhrer:
Dipl.-Ing. Eduard J. Job
Dipl.-Ing. Bodo Mller
www.detectomat.com
detectomat GmbH
An der Strusbek 5
22926 Ahrensburg
Germany
Fon: +49 (0) 4102 2114 60
Fax: +49 (0) 4102 2114 670
email: [email protected]
web: www.detectomat.com
The
Group
www.detectomat.com