DPS- 1
DATA POINT SUMMARY FOR BUILDING AUTOMATION SYSTEM
Sr. No.
Description
AI
DI
AO
DO
Schedule
Trend
Alarm
Grahics
Bacnet / Modbus Interface
License
Chiller (3 Nos.)
Chillers - ON / OFF
Chiller run status
Chiller Auto / Manual switch
Chillers Trip / Fault
CHW supply / return temp.
Common Header CHW supply / return temp.
Ambient Temperature & Humidity
Chiller
isolation
Mortised
command & status.
valves
BMS
BMS
BMS
Immersion temperature sensor
Immersion temperature sensor
12
Ambient temp/Humidity sensor
ON/OFF
3
#
Differential pressure sensor and transmitter across
chilled water header
10
Chilled Water Flow Status
Primary Chilled Water Pumps
Pump ON / OFF
Pump run status
Pump Auto / Manual switch status
CHW pump trip status.
Condenser Water Pumps
Condenser Water pump ON / OFF Command.
Condenser Water pump ON / OFF status.
Condenser Water pump Auto / Manual status.
Condenser Water pump trip status.
Cooling Tower
Cooling Tower sump outlet temperature.
Cooling Tower fan ON/OFF command.
Cooling Tower fan trip status.
Cooling Tower fan Auto/ Manual status.
Sump level monitoring low
Make up water tank
CHW Motorised Valve
CHW Motorised Valve Open/ Close Command
CHW Motorised Valve Open/ Close Status
#
3
#
3
3
24
49
#
#
#
0
AHU ON/OFF
AHU blower status
25
AHU Auto / Manual status
25
AHU filter status
25
Return Air Temperature
25
#
25
Potential Free Contact from BMS
to Pump Starter panel
Differential pressure switch across
the CHW pumps for ON/OFF
status.
Signal from A/M switch.
potential
Potential Free Contact to BMS Potential Free Contact in Chiller
from Chiller MCC panel
Panel
Potential Free Contact to BMS Potential Free Contact in Chiller
from Chiller MCC panel
Panel
Differential Switch across Fans
Duct Temperature Sensor
Suitable Insertion Provision in AHU
0-10 V DC Signal
2 / 3 Way Control Valve by
HVAC, with acceptance of 0-10
V DC Signal
Fan Air Flow status
Differential Switch across Fans
Fan Auto / Manual status
Potential
Free
Contact
Auto/Manual Switch
Ventillation/ Exhuast Fans
Fan ON/OFF
Data Point Summary
Suitable Insertion Provision in AHU
Potential
Free
Contact
at Potential Free Contact in AHU
Auto/Manual Switch
Panel
Differential Pressure Switch across
Suitable Insertion Provision in AHU
filter
Fan ON/OFF
in
#
#
#
4
4
#
#
#
#
4
7
14
Provision
4
4
4
12
Suitable Insertion
Water Line
Imm type temp sensor.
Potential Free Contact from BMS Acceptance of Potential Free
to CT Starter panel
Output in CT Panel
Signal
from
potential
free Potential Free Contact in CT
contact.
Panel
Signal
from
potential
free Potential Free Contact in CT
contact.
Panel
Suitable Insertion Provision in
Signal from level switch
Cooling Tower
Suitable Insertion Provision in
Signal from level switch
Cooling Tower
Sub Total (K)
Acceptance of Potential Free
Output in Pump Panel
25
4
4
4
4
12
in
Potential Free Contact in Pump
Panel
free Potential Free Contact in Pump
Panel
25
Provision
Potential Free Contact from BMS Acceptance of Potential Free
to Pump Starter panel
Output in Pump Panel
Suitable Insertion Provision in
Differential Switch across Pumps
Water Line
Potential
Free
Contact
at Potential Free Contact in Pump
Auto/Manual Switch
Panel
Signal
from
potential
free Potential Free Contact in Pump
contact.
Panel
Sub Total (F)
Plant Roof Ventilation
Fan ON/OFF Command
Fan ON/OFF Status
Fan Trip
Fan Auto/ Manual Status
Sub Total (I)
TFA Units
Fan ON/OFF Command
Fan ON/OFF Status
Fan Trip
Fan Auto/ Manual Status
Sub Total (J)
Pressurization Fans
75
in
Potential Free Contact from BMS Acceptance of Potential Free
to fan Starter panel
Output in AHU Panel
25
25
Provision
18
Air Handling Units - (25 Nos.)
Motorised Valve Cooling
Potential Free Contact from BMS Butterfly Valves
to motorised butter fly valve with
limit switch for position status.
Suitable Insertion
Differential Pressure Sensor
Water Line
Suitable Insertion
Suitable insertion provision
Water Line
Signal
from
contact.
BMS
Sub Total (A+B+C+D+E)
Potential Free Contact from
to Chiller MCC panel
Potential Free Contact to
from Chiller MCC panel
Potential Free Contact to
from Chiller MCC panel
Potential Free Contact to
from Chiller MCC panel
HVAC Vendor to provide RS 485
MODBUS / Bacnet interface in
each chiller. HVAC Vendor to
show the parameters on the
MODSCAN /Bacstack/Cimetrics
software before integrating to
IBMS. All mapping details & the
Master/slave ID setting in the
Chillers to be done by the HVAC
Contractor
Acceptance of Potential Free
Output in Chiller Panel
Potential Free Contact in Chiller
Panel
Potential Free Contact in Chiller
Panel
Potential Free Contact in Chiller
Panel
Suitable Insertion Provision in
Water Line
Suitable Insertion Provision in
Water Line
Potential Free Contact from BMS Acceptance of Potential Free
to fan Starter panel
Output in AHU Panel
Suitable Insertion Provision in AHU
at Potential Free Contact in AHU
Panel
39
Potential Free Contact from BMS Acceptance of Potential Free
to fan Starter panel
Output in AHU Panel
DPS- 2
DATA POINT SUMMARY FOR BUILDING AUTOMATION SYSTEM
Sr. No.
Description
AI
DI
AO
DO
Schedule
Trend
Alarm
Grahics
Fan Air Flow status
39
Differential Switch across Fans
Fan Auto / Manual status
39
Potential
Free
Contact
Auto/Manual Switch
CO Level Monitoring in Parking Areas
CO Sensors
Sub Total (L)
Fire Fighting System
Hydrant pressure monitroing
Pressure Sensor
Sprinkler pressure monitroing
Pressure Sensor
1
2
3
4
5
6
7
#
78
Jockey Pump run status
Sprinkler Pump run status
Fire Pump Run Status (Electrically driven)
Sprinkler / Hydrant header flow status
Suitable insertion provision
Potential Free Contact water DP
switch
Suitable Insertion
Water Line
Suitable Insertion
Water Line
Suitable Insertion
Water Line
Suitable Insertion
Water Line
Suitable Insertion
Water Line
Suitable Insertion
Water Line
Suitable Insertion
Water Line
#
#
#
1
4
at Potential Free Contact in AHU
Panel
39
Fire Pump Run Status (Diesel driven)
Sub Total (M)
Suitable Insertion Provision in AHU
Potential Free Contact water DP
switch
Potential Free Contact water DP
switch
Potential Free Contact water DP
switch
Provision
in
Provision
in
Provision
in
Provision
in
Provision
in
Provision
in
Provision
in
Water Supply System
Fire Water Tank High / Low Level
Level Switch
Suitable Insertion Provision
Raw Water Tank High / Low Level
Level Switch
Suitable Insertion Provision
Treated Water Tank High / Low Level
Level Switch
Suitable Insertion Provision
Soft Water Tank High / Low Level
Level Switch
Suitable Insertion Provision
Fire Pump Auto/Manual Status
Fire Pump run status
Raw Water Pump Auto/Manual Status
Raw Water Pump run status
Soft Water Pump Auto/Manual Status
10
Soft Water Pump run status
Potential Free Contact to BMS
from fan Starter panel
Differential pressure switch across
the pumps
Potential Free Contact to BMS
from fan Starter panel
Differential pressure switch across
the pumps
Potential Free Contact to BMS
from fan Starter panel
Differential pressure switch across
the pumps
Potential Free Contact in Pump
Panel
Suitable Insertion Provision in
Water Line
Potential Free Contact in Pump
Panel
Suitable Insertion Provision in
Water Line
Potential Free Contact in Pump
Panel
Suitable Insertion Provision in
Water Line
Sub Total (N)
28
Electrical System - HT Panels , LT Panels
HT / LT Panel Phase Voltage Monitoring
HT / LT Panel Phase Current Monitoring
HT / LT Panel Frequency Monitoring
HT / LT Panel KW Monitoring
HT / LT Panel KWH Monitoring
6
7
8
HT / LT Breaker On/Off status
Bus Coupler On/Off Status
HT / LT Panel Trip Status
Sub Total (O)
Through Modbus Output of Multi data
meters
#
#
#
10
10
10
0
30
Diesel Generator
DG Start/Stop Stauts
DG AMF Breaker Status
3
4
Bulk Storage Tank level Monitoring
DG Oil Day Tank Level
Sub Total (P)
Lifts / Escalators
UPS Nos on Modbus RTU / Bacnet
Fire Alarm System
VFD
Grand Total (A to T)
Data Point Summary
#
4
310
25
of suitable rating CT in
of suitable rating CT/PT
of suitable rating CT/PT
of suitable rating CT/PT
Free Contact in Panel
Free Contact in Panel
Free Contact in Panel
#
#
DG Panel vendor to provide RS
485 MODBUS RTU. The electrical
vendor to show the parameters
on the MODSCAN software
Integration
through
Modbus
before integrating to IBMS. All
Protocol
mapping
details
&
the
Master/slave ID setting in the
meter to be done by the DG
vendor
Potential Free Contact from BMS
to DG Starter panel
Potential Free Contact from BMS
to DG Starter panel
Flame Proof Level Transmitter
Flame Proof Level Transmitter
0
Integration of Lifts through
Modbus Protocol.
Integration of UPS through
Modbus Protocol / Bacnet
Integration of FAS through
Modbus/Bacnet/OPC Protocols of
all devices/detectors
Integration of VFD through
Modbus/Bacnet protocol
62
of suitable rating PT in
2
2
4
Provision
Panel
Provision
Panel
Provision
in Panel
Provision
in Panel
Provision
in Panel
Potential
Potential
Potential
97