High-Tech Range
IRI1- Overcurrent, Short-circuit and Earth Fault Relay
C&S Protection & Control Ltd.
Contents
1.
Introduction
2.
Applications
3.
Characteristics and features
4.
Versions
5.
Design
6.
7.
5.1
Connection
5.1.1
Analog input
5.1.2
Output contacts for Relay IRI1-31-EO
5.2
Front panel IRI-3I-EO
5.2.1
LEDs
5.2.2
DIP-switches
5.2.3
Reset-push button
7.2.9
Setting of tripping time for tripping time
(tIE>>) of earth fault high set stage
7.2.10 Setting of nominal freequency
Working principle
7.3
Indication of faults
7.4
Reset
7.4.1
Reset by pressing pushbutton <RESET>
7.4.2
Reset by each new energization
7.5
Calculation of the setting values
7.5.1
Phase over-current stage (I>)
7.5.2
Fast tripping short circuit protection (I>>)
7.5.3
Dependent over-current time protection
7.5.4
Phase over-current stage (I>)
7.5.5
Time multiple setting
7.5.6
Fast tripping short circuit protection (I>>)
7.5.7
Setting only for IRI1-3I-EI
6.1
Analog Circuits
6.2
Digital Circuits
6.3
Power supply
8.1
Flush mounting
6.4
Demands imposed on the main current
transformers
8.2
Rack mounting
8.3
Terminal
8.
Operations and settings
7.1
Layout of the operating elements
7.2
Setting of parameters by DIP-Switches
7.2.1
Setting of tripping characteristics for
phase over-current and earth fault stage
7.2.2
9.
Housing
Test and maintenance
10. Technical Data
10.1
Measuring input
Setting of response value (I>) for phase
over-current
10.2
Auxiliary voltage
10.3
General data
7.2.3
Setting of tripping time (ti>) for phase
over-current
10.4
Setting ranges and steps
7.2.4
Setting of response value (I>>) for phase
short circuit
10.5
Tripping Characteristics
10.6
Output Relays
7.2.5
Setting of tripping time (ti>>) for tripping
of phase short circuit protection
10.7
System data
10.8
Mechanical test
7.2.6
Setting of response value IE> for earth
fault stage
10.9
Dimensional Drawing
7.2.7
Setting of tripping time (tIE>) for tripping
of earth fault stage
7.2.8
Setting of response value (IE>>) for earth
fault high set stage
11. Order form
1.
Introduction
3.
Digital processing of the sampled measuring values
The application of powerful microprocessors opens a
new chapter for power protection systems. Because of
their capabilities to process the measuring values
digitally and to perform arithmetical and logical
operations, the digital protective relays are superior to
the traditional analogue devices. In addition, the digital
protective relays offer some additional advantages such
as very low power consumption, adaptability,
possibilities for selfsupervision, flexible construction,
selection of relay characteristics etc.
Digital filtering of the measured values by using
discrete Fourier analysis to suppress the high
frequency harmonics and transient d.c.
components during short circuit
Selectable protective functions between : definite
time over-current relay and inverse time overcurrent relay
Selectable inverse time characteristics according
to BS 142 and IEC 255-4 :
The development of microprocessor-based protective
relays and their introduction into the market are
stimulated by the trend nowadays to replace analogue
with digital protective equipment.
normal inverse
very inverse
extremely inverse
The superiority of digital protective relays to the
traditional systems is enchanced by the MR relay family
which has the following characteristics :
Independent stage for the fast tripping of short
circuit (protection)
Two-stage over-current time protection for phase
current
Integration of multiple protective functions into one
compact housing
High measuring accuracy due to digital processing
of measuring values
Digital relay setting with very wide setting ranges
and the fine setting steps
User-friendly setting procedure by means of DIPswitches
Operation reliability due to continuous selfsupervision
The digital time relay IRI1 was designed as a universal
over-current relay for application to medium voltage
networks.
A similar protection relay with extended functions, the
MRI1
MRI1-digital multifunctional relay is also available. It
additionally provides an alpha-numeric display for the
indication of measuring values and faults. Furthermore,
the MRI1 allows data exchange via serial interface and
directional determination of the fault.
2.
Application
The digital over-current time relay IRI1 is a universal
protection device for low and medium voltage
networks. It is used in radial networks and combines the
following functions in one unit :
Independent (Definite) time over-current relay
Inverse definte minimum time over-current relay
with following selectable characteristics :
Normal inverse
Very inverse
Extremely inverse
Integrated independent and dependent overcurrent time protection for the earth fault
detection.
Furthermore, the device, providing the above
functions,can be employed as back-up protection for
differential and distance protection relays.
Characteristic and features
One-stage over-current time protection for
earthfault current
Extremely wide setting ranges and fine steps for
current and time settings
Continuous self-supervision of software and
hardware
Wide operating ranges of the supply voltage (AC/
DC)
Plug-in technology with self-shorting c.t. circuits
4.
Versions
3 Phase over current with high set and 1 earth fault
with highset.
IRI1-20-EO
2phase over current and 1 phase
earth fault without high set
IRI1-EO
Earth fault relay with high set
IRI1-3I-EI
(N1 MODEL)
3 Phase overcurrent with high set and
1 E/F with high set.
5.
Design
5.1 Connection
In the following the IRI1 functional description always
refers to the version IRI-3I-EO
IRI-3I-EO. With a few exceptions
(no earth-fault detection for the IRI-3O & IRI1-3I
IRI1-3I) all
functions are valid for the other units.
5.1.1
Analog input
L+/L L-/N
C9
E9 D9
L1 L2
The analog input signal of the conductor currents IL1
(B3-B4), IL2 (B5-B6), IL3 (B7-B8) and the total current
IE (B1-B2) are fed to the protective device via separate
input transformers.
L3
~
=
Power
Supply
The continuously measured current values are
galvanically isolated, analog filtered and finally fed to
the analog/digital converter.
D1
C1
E1
D2
C2
E2
AUX. SUPPLY
L+/L L-/N
E9
C9
D3
D9
C3
E3
~
-
L1
L2
L3
D4
SUPPLY
P1
S1
B1
P2
S2
B2
C4
E4
P1
S1
P2
S2
P1
S1
P2
S2
P1
S1
P2
S2
S1 B3
L1.1
S2 B4
L1.2
S1 B5
L2.1
S2 B6
L2.2
S1 B7
L3.1
S2 B8
S2 B2
L3.2
S1 B1
N1
I1
I2
D1
C1
E1
I>
D2
I3
C2
E2
IE
D5
N2
Circuit Diagram IRI1-EO for CBCT Application
C5
E5
IE
D6
C6
E6
L+/L L-/N
L1
L2
L3
C9 E9 D9
P1
S1
P2
S2
POWER SUPPLY
D1
C1
Circuit Diagram IRI1-2O-EO
P1
E1
D2
B1
S1
C2
E2
P2
L1 L2 L3
D3
S2
IE
L+/L L-/N
P1
A6A8 A7
S1
C3
E3
B2
P2
S2
D4
C4
E4
P1
S1
P2
S2
P1
S1
S1 B3
L1.1
S2 B4
L1.2
S1 B5
L2.1
I1
I2
P2
S2 B6
L2.2
S1 B7
L3.1
S2 B8
L3.2
S1 B2
N2
S2 B1
N1
A2 (COM1)
IRI-EO in Holmgreen Circuit
A3 NO1
5.2.1
A4 (COM2)
S2
P1
S1
A5 NO2
I3
P2
S2
LEDs
On the front panel there are 8 LEDs (9 LEDs in case of
3I-EI). Their functions are indicated by the appropriate
inscriptions above them. LED ON indicates the
readiness for service, the other 7 LEDs are used for the
fault display and indicate the type of fault and the
repective phases.
IE
Circuit Diagram IRI1-3I-EI (N1 MODEL)
5.2.2
DIP - switches
The 7 sets of DIP - switches on the front plate serve to
adjust the tripping values, times, characteristics and
mains frequency.
5.2.3
RESET - pushbutton
Push - button RESET is used for acknowledgment and
reset after fault clearance.
L1
L3
l>
ON IE
0.1
0
0
lE 0
t IE
IE>
0.2
0.2
0.4
0.8
x10
x100
0.1
0.2
0.4
0.8
x1
x1
0
0
0
0
RESET
IE>> ON
0.5
0
0
0
0
0.55
0.1
0.2
0.4
0.8
x1
x1
0
0
0
0
x.10
x100
0.1
0.2
0.4
0.8
I>
RESET
0.1
0
0
0
IE>>
IE>
x.10
x100
0.1
0.2
0.4
0.8
x1
x1
0
0
0
0
t IE>>
NINV
VINV
EINV
60HZ
DEFT
DEFT
DEFT
50HZ
0.05
0.1
0.2
0.4
0.8
0
0
0
0
0
tIE>
tI>
1
1
2
4
8
0.5
0
0
0
0
0.2
0.2
0.4
0.8
IRI1 -2O-EO
NINV
VINV
EINV
60HZ
DEFT
DEFT
DEFT
50HZ
IRI1 -EO
Front plate IRI1-2O-EO
6.
6.1 Analog circuits
Front plate IRI1-EO
L1 L2 L3 E ON
l>
l>> IE>
IE>>
0.1
0
0
0
IE>
0
0
0
0
0
t IE>
0.2
0.2
0.4
0.8
FINE
0.1
0.2
0.4
0.8
RESET
0.5
0
0
0
0
0.55
0.1
0.2
0.4
0.8
I>
NINV1.3
tI>
0
0
0
0
0.5
0
0
0
0
1
1
2
4
8
2.0
0
0
0
0
2.6
1.2
2.4
4.8
9.6
IE>>
NINV3
0.1
0.2
0.4
0.8
l>>
t IE> 0
6086
tI>
Front plate IRI1-3I-EI
Working Principles
0
0
0.01
0.02
0.04
0.08
IRI1 -3I-EI
The incoming currents from the main current
transformers on the protected objects are converted to
voltage signals in proportion to the currents via the
input transducers and shunt resistors. The noise signals
caused by inductive and capacitive coupling are
suppressed by an analog R-C filter circuit. The analog
voltage signals are fed to the A/D-converter of the
microprocessor and transformed to digital signals
through Sample and Hold circuits. All the processing is
carried out on these digitized values. The measuring
values are detected with a sampling frequency of 800
Hz, a sampling rate of 1.25 ms for each measurement
(at 50 Hz).
6.2 Digital circuits
The protective device is equipped with an efficient
microprocessor which is the main processing unit. It
digitally carries out all of the operations, from the
digitization of the measuring values to the protective
tripping.
The relay program is located in an EPROM (ReadOnly-Memory). With this program the microprocessor
processes the voltages at the analog inputs and
calculates the fundamental components of the current.
For the calculation of the current value an efficient
digital filter based on the Fourier Transformation (DEFTDiscrete Fast Fourier Transformation) is applied to
suppress high frequency harmonics and d.c.
components during a short circuit.
The calculated actual current values are continuously
compared with the set value which is adjusted using the
DIP - switches. When activated, the over-current tripping
time is determined according to the selected
characteristic curve. When the calculated time delay has
elapsed, a tripping command is given.
a)
Independent tripping curve : DEFT (definite)
adjusted :
b)
dependent tripping curve :
NINV (normal inverse)
VINV (very inverse)
6.3 Power supply
EINV (extremely inverse)
For the 24 V (nominal voltage) unit it is possible to select
an auxiliary voltage range from 16 V to 90 V and for the
110 V (nominal voltage) unit an auxiliary voltage from
80 V to 250 V (a.c./d.c.).
6.4 Demands imposed on the main
current transformers
The current transformers have to be rated in such a way,
that a saturation should not occur within the following
operating current ranges : Independent time overcurrent function K1 = 2
Inverse time over-current function K1 = 20
High-set function K1 = 1.2 - 1.5
K1 = Current factor related to set value with the current
transformer not yet operating in the saturation range.
Moreover, the current transformers have to be rated
according to the maximum expected short circuit
currents of the network or the object to be protected.
The lower consumption of the IRI1
IRI1, i.e. 0.2 VA, has a
positive effect on the rating of the current transformers.
It implies that, if an electromechanical relay is replaced
by IRI1, a high accuracy limit factor is automatically
obtained by using the same current transformer.
7.
Operation and Settings
7.1 Layout of operating elements
All DIP-switches required for the setting of parameters
are located on the front panel (see fig. front panel).
7.2 Setting of parameters by DIPswitches
For a better comprehension of the different DIP-switch
positions, it was agreed that
1.
DIP-switch is turned off (Off possition)
DIP-switch is turned on (On position)
2. Contrary to the DIP-switches on the IRI1 front panel
the examples given here are numbered. Position On is
equally marked.
DEFT
NINV
DEFT
VINV
DEFT
EINV
50 Hz
60 Hz
For characteristic selection in IRI-3I-EI refer 7.5.5.
By setting DIP-switch (not 50/60 Hz) to the On position
it is possible to select one of the three dependent
tripping curves. If an independent over-current tripping
is required, all three of the DIP-switches must be set to
position DEFT. In case of an invalid setting of the DIPswitches, for example if several switches are
simultaneously set to On position, an independent
tripping characteristic with the smallest possible tripping
values and times is automatically selected. This ensures
that the object to be protected cannot be overloaded
under any circumstances. Setting ranges and
characteristics are detailed in chapter 10.
Please Note :
The IRI1-2O-EO unit type provides identical
dependent tripping characteristics for phase
overcurrent and earth overcurrent stages i.e. if
NINV characteristics is selected it is applicable
for both O/C + E/F
E/F..
7.2.2
Setting of response value I> for
phase-over-current
With the aid of DIP-switch set I> it is possible to adjust
the respons value for phase-over-current tripping in the
range 0.5 - 2.5 x I N. The tripping value is calculated
from the sum of the individual settings of all the DIPswitches.
Example :
A tripping value of 1.0 X IN is required.
Therefore switches 2 and 4 are switched on.
0.5
0.55
Setting of the tripping
characteristic for phase overcurrent and earth fault stage
0.1
0.2
0.4
The following tripping characteristics can be adjusted :
0.8
Reserve
7.2.1
t> = 0.5 + 0.1 + 0.4 = 1.0 x I N
7.2.3
Setting of tripping time (t I>) for
phase-over-current
With the aid of DIP-switch set tI> it is possible to select
the tripping time for the phase-over-current in the range
-0.1 -150 s. There are four switches available to adjust
the set value switch (3, 4, 5 & 6) and two switches
(switch 1 & 2) to select the multiplication factor.
7.2.9
Setting of the tripping time
(tIE>>) for earth-fault high set
stage
See setting procedure as described in paragraph
7.2.3.
7.2.10
Setting of normal frequency
The set value is calculated from the sum of the individual
factors (switch 3-6) multiplied by the set multiplication
factor (switch 1 or 2). 1, 10 and 100 are possible as
multiplication factors. If the switches 1 and 2 are both set
On, the setting is invalid and gives an automatic
multiplication factor of 1. If all the switches 3 - 6 are set
to the Off position, the tripping time is equal to the relay
operating time (approx. 30 ms).
The nominal frequency can be adjusted to 50 or 60 Hz
by means of DIP-switches on the front panel.
LED L1
: fault in phase L1
Note: The multiplication factor (switch 1 and 2)
must be set to 1 for dependent tripping
characteristics.
LED L2
: fault in phase L2
LED L3
: fault in phase L3
7.2.4
LED E
: earth-fault
LED I>
: serves to indicate tripping from a phase
over-current
Setting of response value (I>>)
for phase-short-circuit
With the aid of DIP-switch set I>> it is possible to adjust
the response value for the fast tripping of phase-shortcircuit in the range from 2.0-33.5 x IN .
The tripping value is calculated as described in 7.2.2.
7.2.5
Setting of the tripping time (t I>>)
for tripping of phase-short
circuit protection
With the aid of DIP-switch ti>> it is possible to adjust the
tripping period ti>> for the fast tripping of phase -short
circuit protection in the range from 0.05 - 1.55 s. The
setting time is calculated from the sum of the individual
factors of all the DIP - switches switched on. If all the
switches are in the Off position, the tripping time is equal
to the relay operating time (approx. 30 ms).
Please Note :
If switch is set, the fast tripping of shortcircuit
protection
is
inhibited,
independent of other switch settings.
7.3
Indication of faults
For the fault indication the IRI1front panel provides 8/
9 LEDs with the following functions :
LED I>> : serves to indicate tripping from a phaseshort-current
LED IE
: serves to indicate tripping from a earth
fault
LED IE>> : serves to indicate tripping from earth
fault high set stage
ON
: power ON indication.
7.4
Reset
7.4.1
Reset by pressing push-button
<RESET>
When the push-button <RESET> is pressed, the device
immediately reset and the LEDs extinguish.
7.4.2
Reset by each new energization
At each new energization, the unit returns to its initial
position and the LEDs indicate the fault now present.
Independent of the selected tripping characteristic of the
over-current stage I>>, the tripping period for the fast
tripping short-circuit stage I> is always definite.
7.5
Calculation of the setting values
7.5.1
Phase-over-current stage (I>)
7.2.6
The main criterion for the setting of the over-current
response value is the normal maximum operating
current which is therefore adjusted to about 20% for
power line, about 50 % for transformers and motors,
above the maximum expected load currents. The delay
of the trip signal is selected according to the selectivity
and time grading, and the system overload capacity of
the protected object.
Setting of response value (I E) for
earth-fault stage
See setting procedure as described in paragraph 7.2.2.
7.2.7
Setting of the tripping time (tIE>)
for earth-fault stage
See setting procedure as described in paragraph 7.2.3.
7.2.8
Setting of response value (I E>>)
for earth-fault high set stage
See setting procedure as described in paragraph 7.2.2.
7.5.2
Fast tripping short circuit
protection (I>>)
The fast tripping short-circuit protection is normally set
to act for near-by faults. The time delay for I>> is
always independent of the fault current.
8.
The IRI1 can be supplied in an individual housing for
flush-mounting or as a plug-in module for installation
in a 19 mounting rack according to DIN 41494. Both
versions have plug-in connections.
8.1
7.5.3
Dependent over-current time
protection
Apart from the selection of the tripping characteristics,
the response value for the phase-current is also
adjustable.
7.5.4
Phase-over-current stage (I>)
The starting current is determined according to the
maximum expected load current. For example :
Current transformer ratio : 400/5 A
Maximum expected load current : 300 A
Overload coefficient : 1.2 (assumed)
Starting current setting : IS = (300 / 400) x 1.2 = 0.9
x IN
7.5.5
Time multiplier setting
The time multiplier setting for inverse time over-current
is a scale factor for the selected characteristics. The
characteristics for two adjacent relays should have a
time interval of about 0.3 - 0.4 s.
7.5.6
Fast tripping short circuit
protection (I>>)
Housing
Flush mounting
The individual housing of the IRI1 is constructed for
flush-mounting. The dimensions of the mounting frame
correspond to the requirements of DIN 43700 (76 x
142 mm). The cut-out for panel mounting is 68.7 x
136.5 mm.
The front panel of the IRI1 is covered with a
transparent, sealable flap (IP54).
For case dimensions and cut-out refer to technical
data. The individual housing is fixed with the supplied
clasps from the rear of the panel.
8.2
Rack mounting
The IRI1 is in general suitable for installation in a
modular carrier according to DIN 41494. The
installation dimensions are : 12 TE; 3 HE. According
to requirements, The IRI1
IRI1-devices can be delivered
mounted in 19 racks.
8.3
Terminal
The IRI1
IRI1-plug-in module has a very compact plug-and
socket connector. This connector consists of up to 27
terminals of 5 A and 15 terminals of 20 A.
The current terminals are equipped with self-closing
contacts. Thus, the IRI1-module can be unplugged
even with current flowing, without endangering the
current transformers connected.
The measuring circuits of IRI1 (terminal connector
series A and B) are connected through spade terminals
with dimensions of 6.3 mm x 0.8 mm, for cables,
max. 6 mm 2. By using 2.8 mm x 0.8 mm spade
terminals, a bridge connection between different poles
is possible.
The following figure shows the terminals back of IRI1
The high-set current setting is set as a multiplier of the
nominal current. The time delay is always independent
to the fault current.
A
7.5.7
IRI1-3I-EI
E
1
Short Circuit Protection : The Current setting range is
from 2 x In to 20.6 x In.
2
3
4
5
6
7
8
9
F
9.
Test and Maintenance
The measuring input circuits are of completely static
design and the relay functions are entirely digital, so
that the IRI1 has no requirement for maintenance.
10.
10.1
Technical Data
Measuring input
Rated data
Rated current IN
Rated frequency FN
Power consumption in current
circuit
at IN = 1 A 0.2 VA
at IN = 5 A 0.1 VA
Thermal withstand capability
in current circuit
dynamic current withstand (half-wave)
for 1 s
for 10 s
continuously
Rated auxiliary voltage UH
Power consumption
24 V
110 V
at 24 V
at 110 V
10.2
10.3
1 A or 5 A
50/60 Hz adjustable (IRI1-3I-EI) is available
only in 50 Hz version)
250 x IN
100 x IN
30 x IN
4 x IN
Auxiliary voltage
working range
working range
quiescent approx. 3 W
quiescent approx. 3 W
16-90 V AC/DC
80-250 V AC/DC
operating approx. 6 W
operating approx. 6 W
General data
Dropout ratio
Returning time
Time lag error class index E
Minimum operating time
Transient overreach at
instantaneous operation
:
:
:
:
>97%
30 ms
+ 10 ms
30 ms
5 %
10.4
Setting ranges and steps
10.4.1
Independent time over-current, earth fault and short circuit protection
I>
Is
ti>
I>>
I
ti>>
Is
tIE
IE
IE>>
IRI1 - EO only
IE>>
tIE>
Setting Range
0.5 - 2.05 x I N
x 1 : 0.1 - 1.5s
x 10 : 1.0 - 1.5s
x 100 : 10 - 150s
2.0 - 33.5 x I N
0.05 - 1.55 s
0.1 - 1.6 x I N
x 1 : 0.1 - 1.5 s
x 10 : 1.0 - 15 s
x100 : 10 -150 s
0.5 - 16 x IN
0.05 - 1.55 s
Step
0.05 x I N
0.1 s
1.0 s
10 s
0.5XIN
0.05 s
0.1 x I N
0.1 s
1.0 s
10 s
0.5 x I N
0.05 s
Tolerances
5% from set value
3% or 10 ms
3% or 10 ms
3% or 10 ms
5% from set value
3% or 10 ms
5% from set value
3% or 10 ms
3% or 10 ms
3% or 10 ms
5% of set value
3% or 10 ms
For short circuit protection setting range of IRI1-3I-EI please refer 10.4.3.
10.4.2
Dependent time over-current, earth fault and short circuit protection
Tripping characteristics according to IEC 255-4 or BS 142
0.14
Normal Inverse
t
=
tI> [s]
(I/Is)0.02-1
Very Inverse
Extremely Inverse t
Where
13.5
(I/Is)-1
80
(I/Is)2-1
= tripping time
= fault current
tI> [s]
tI> [s]
tI>
= time multiplier
Is
= setting value of the current
I>
Is
tI>
Setting Range
0.5 - 2.05 x IN
0.1 - 1.5
I>>
I
tI>>
Is
tIE
2.0 - 33.5 x IN
0.05 - 1.55 s
0.1 - 1.6 x IN
0.1 - 1.5
0.5 X I N
0.05 s
0.1 x I N
0.1
IE>>
tIE>
0.5 - 16 x IN
0.05 - 1.55 s
0.5 x I N
0.05 s
Tolerances
5% from set value
5% for NINV and VINV
7.5% for EINV at 10 xls
5% from set value
3% or 10 ms
5% from set value
5% for NINV and VINV
7.5% for EINV at 10 xls
5% of set value
3% or 10 ms
Step
0.6 x In
Tolerances
5% from set value
0.5 x In
5% from set value
IE
IE>>
IRI1 - EO only
10.4.3
Setting only for IRI1-3I-EI(N1 MODEL)
I>>
I>>
Setting Range
2.0 - 20.6 x In
IE>>
IE>>
0.5 - 16.0 x In
10.5
Step
0.05 x I N
0.1
Tripping characteristics
100
100
tI>=
10
tI>=
10
t[s]
t[s]
1.5
1.3
1.0
0.8
1.5
1.3
1.0
0.8
0.6
0.5
0.4
0.3
0.6
0.5
0.4
0.3
0.2
0.2
0.1
0.1
0.1
1
Normal inverse
I/IS
6 7
8 9 10
20
Very inverse
7 8 9 10
20
I/IS
10
100
100
0.5
I>
2.05
10
10
t[s]
150
t[s]
tI >
tI>=
1
1
0.1
2.0
1.5
1.3
1.0
0.8
0.6
0.5
0.4
0.3
0.1
I>>
33.5
1.55
t l >>
0.1
0.05
0.2
0.1
1
7 8 9 10
20
0.01
1
I/IS
10
I/IN
Extremely inverse
10.6
Definite time overcurrent relay
Output Relays
Number of relays
Contacts
Max. breaking capacity
Max. breaking voltage
Max. continuous current
Max. making current (16 ms)
:
:
:
2 in IRI1-2O-EO and IRI1-EO
1 in IRI1-3I-EI
2 change-over contacts each for trip relay I> and I>>
2 change-over contacts for I E
2 change-over contacts for IE>>
1250 VA/150 W resistive
500 VA/90 W inductive
400 V AC, 125 V DC
5 A
20 A
VDE 04335, part 303, IEC 255-4, BS 142
:
:
-400C to + 850C
-200C to + 700C
Relative humidity 95 % at 400C for 56 days
2.5 kV (eff.) / 50 Hz, 1 min.
2.5 kV (eff.) / 50 Hz, 1 min.
2.5 kV / 1 MHz
4 kV / 2.5 kHz, 15 ms
Limit value class B
8 kV
10.7
System data
Design standard
Specified ambient service
Temperature range
for storage
for operation
Environmental protection class F as per
DIN 40040 and per DIN IEC 68, part 2.3
Isolation test voltage, inputs and outputs
between themselves and to the relay
frame as per VDE 0435, part 303
Impulse test voltage, inputs and outputs
between themselves and to the relay
frame as per VDE IEC 0435, part 303
High frequency interference test
voltage, inputs and outputs between
themselves and to the relay frame
as per DIN IEC 255, part 22-1
Electrical fast transient (Burst)
test as per DIN VDE 0843, part 4
Radio interference suppression
test as per DIN VDE 57 871
Electostatic discharge (ESD)
test as per DIN VDE 0843 part 2
Radiated electromagnetic field
test as per VDE 0843 part 2
10 V/m
11
10.8
Mechanical tests
Shock
Vibration
Protection-front panel
Protection-rear panel
Weight
10.9
:
:
:
:
:
As per DIN IEC 41 B (CO) 38 : class 1
As per DIN IEC 41 B (CO) 35 : class 1
IP 54
IP 00
Approx. 1.5 kg
Dimensional Drawing
260
230
76
68.7
16
142
136.5
142
36
76
Cut Out Dimensions
Installation Depth : 275mm
All dimensions in : mm
11.
Order form
Microprocessor Over-current + Earth Fault Protection Relay
3 O/C with high Set and 1 E/F with high Set
2 O/C without high Set and 1 E/F
1 E/F without high Set
Rated current (O/C Element)
Rated current (E/F Element)
Auxiliary voltage (AC/DC)
24 V (16 to 90 V)
110 V (80 to 250 V)
Housing Flush
19 rack
3I-EI
2O-EO
EO
IRI1
N1
1
5
1
5
L
H
D
A
HR/IRI1/06.07.01/140307
* Data subject to change without notice