12TransformerFactoryTestsBrieflyExplained
12 Transformer Factory Tests Briefly Explained (on photo: 400 kV power transformer, rated power 350 MVA produced
by KOLEKTOR ETRA in new production facility which is specialised in production of 400 kV has successfuly passed
factory acceptance tests and will be dispatched to customer in Slovakia)
Factorytests
[Link]
connectionsandformulasofsomeofthelistedtestsarealreadydescribedinseparatlypublished
articles,andfortherestyouaredirectedtoANSI/IEEEStandardC57.12.90forthesedetails.
Thislistisnotcomplete,therearefewtestsmissing,notmentionedhere,likeTurnratiotest
orMeasurementofvoltageratioandcheckofphasedisplacement,butyoucanfindthemalso
separatlypublishedatEEP(useSearch).
1. NoLoadLosses
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
NoLoadExcitationCurrent
LoadLossesandImpedanceVoltage
DielectricTests
SwitchingImpulseTest
LightningImpulseTest
PartialDischargeTest
InsulationPowerFactor
InsulationResistance
NoiseMeasurement
TemperatureRise(HeatRun)
ShortCircuitTest
[Link]
Thetestsmeasuresthenoloadlossesatspecifiedexcitationvoltageandaspecifiedfrequency.
Sinewavevoltagesareusedunlessadifferentwaveformisinherentintheoperationofthe
transformer.
Therecommendedmethodistheaveragevoltagevoltmetermethod,employingtwo
[Link]
calibratedvoltmeterandtheothervoltmeterisatrueRMSrespondingvoltmeter.
Thetestvoltageisadjustedtothespecifiedvalueasreadbytheaverageresponding
[Link]
basis.
READTHISTESTINDETAILS
Connection diagram for measuring noload losses
GobacktoTests
[Link]
Thiscurrentismeasuredinthewindingusedtoexcitethetransformerwiththeotherwindings
[Link]
excitationcurrentisnotsinusoidalandcontains,aswehaveseen,oddharmonics(predominantly
thirdharmoniccurrent).
TheammeterusedtorecordthenoloadexcitationcurrentisanRMSmeterwhichreadsthe
squarerootofthesumofthesquaresoftheharmoniccurrents.
GobacktoTests
[Link]
Thetransformermustbeinaspecificstatebeforetheloadlossesandimpedancevoltageare
[Link]
thetopandbottomoiltemperaturesshallbelessthan5C.
Thewindingtemperaturesmustbemeasured(usingaresistancemethod)beforeand
[Link]
windingtemperaturebeforeandafterthetestmustnotexceed5C.
Thetwotestmethodsformeasuringloadlossesandimpedancevoltageare:
1. Wattmetervoltmeterammetermethodand
2. Impedancebridgemethod.
Circuit for the impedance and loadloss measurement
Thesetestsgenerallyapplyareducedvoltagetoonesetofwindingswiththeothersetof
[Link],thesetestsarerepeatedforeach
combinationofwindingstakentwoatatime.
READTHISTESTINDETAILS
GobacktoTests
[Link]
Thesetestsconsistofappliedvoltagetestsandinducedvoltagetests.
Appliedvoltagetestsapplyahighvoltagetoallbushingsofawinding,onewindingatatime,
withtheotherwindingsgrounded.A60Hzvoltageisincreasedgraduallyover15sandheldfor
40sandreducedtozeroover5s.
Inducedvoltagetestsapplyahighvoltageacrossawindingwiththeotherwindingsopen
[Link]
saturationatthehigherexcitationvoltage,thefrequencyoftheinducedvoltagetestisincreased
(typicallyaround120Hz).Theinducedvoltageisappliedfor7200cyclesor60s,whicheveris
shorter.
READTHISTESTINDETAILS
GobacktoTests
[Link]
Theswitchingimpulsetestappliesaswitchingimpulsewavebetweeneachhighvoltageline
terminalandground.
Thetestseriesconsistsofonereducedvoltagewave(50%70%ofspecifiedtestlevel)followed
[Link],orboth,maybeused.A
[Link]
[Link]
saturation.
READTHISTESTINDETAILS
Switching onoff impulse test connection diagram
GobacktoTests
[Link]
Thetestsequenceconsistsofonereducedfullwave,twochoppedwaves,andtwofull
[Link]
[Link]
eachwave.
Thegeneraltechniqueforinterpretingtheresultsistolookfordifferencesintheshapesofthe
reducedfullwaveandthetwofullwaves,whichindicateturntoturninsulationfailure.
READTHISTESTINDETAILS
Transformer impulse testing and fault detection connections
[Link]
highestlikelihoodfailuresamongallofthefactoryteststhataretypicallyperformed.
GobacktoTests
[Link]
Thistestdetectsradiofrequency(0.851.15MHz)noisegeneratedfrompartialdischargeswithin
[Link]
occur,[Link]
stops,whichistheextinctionvoltage.
Theextinctionvoltagemustbelessthantheoperatingvoltageofthetransformerotherwise,once
partialdischargestartsinthefield(duetosomevoltagetransient),itwouldcontinueindefinitely
andpossiblycausedamageorfailure.
READTHISTESTINDETAILS
Partial discharge measuring connection circuit
GobacktoTests
[Link]
Insulationpowerfactoristheratioofthepowerdissipatedintheinsulationinwattstothe
apparentpower(voltamperes)underasinusoidalvoltage.Theapplied60Hzvoltageofthistest
[Link]
specificallytocarryoutthistest.
Portableversionsareusedtomeasuretheinsulationpowerfactoroftransformersinthefield.
[Link]
toareferencetemperatureof20C.
GobacktoTests
[Link]
ThistestappliesahighvoltageDCvoltagetoonewindingatatimewiththeotherwindings
[Link]
Ohmslaw.
AInsulationresistancetestsetisdesignedspecificallytocarryoutthistest,andits
[Link]
Meggeraswellasothermanufacturershasaportableinstrumentthatcaneasily
carriedaroundinthefield.
READTHISTESTINDETAILS
GobacktoTests
[Link]
Thenoisemeasurementtestiscarriedoutwhilethetransformerisenergizedatratedvoltage
[Link],
[Link],ifsucha
chamberisnotavailable,noacousticallyreflectingsurfacemaybewithin3mofthemeasuring
microphoneotherthanthefloororground.
Therecordingmicrophonesarepositionedin1mintervalsaroundtheperimeterofthe
transformer,withnofewerthanfour(4)microphonepositionsforsmalltransformers..
Noise measurement zone and layout of measuring points of Power
transformer 242 kV / 15.65 kV, 112 MVA (credit: Aleksandra
Petrovic, Ljubomir Lukic, Milan Kolarevic and Dusica Lukic at
University of Kragujevac)
[Link]
areconvertedintodecibels(dB).
READMOREABOUTNOISE
GobacktoTests
[Link](HeatRun)
[Link]
areconnectedtoaloadingtransformerthatsimultaneouslycirculatesratedcurrentsthroughallof
thewindingsinordertodeveloploadlosses.
Naturally,theexcitationvoltageandtheappliedcirculatingcurrentsareelectrically90apartto
[Link],alargepowertransformercan
consumeupto1MWoftotallossesandtheheatruntestisanexpensivetesttoperform.
Therefore,inordertoreducethetotalexpense,heatruntestsarenormallyperformed
ononlyonetransformeronapurchaseorderformultipletransformers,unlessthe
customerchoosestopayfortestingadditionalunits.
GobacktoTests
[Link]
Theshortcircuittestisgenerallyreservedforasampletransformertoverifythedesignofa
coreandcoilassemblyunlessthecustomerspecifiesthatashortcircuittestbeperformedon
transformersthatarepurchased.
Thecustomershouldbecognizantoftheeverpresentriskofdamagingthe
transformerduringshortcircuittests.
Alowvoltageimpulse(LVI)currentwaveformisappliedtothetransformerbeforeandafterthe
[Link]
comparedforsignificantchangesinwaveshapethatcouldindicatemechanicaldamagetothe
windings.
GobacktoTests
Reference//[Link],Jr.