Product data sheet
Characteristics
RM35TF30
multifunction phase control relay RM35-T range 194..528 V AC
Product availability: Stock - Normally stocked in distribution facility
Commercial Status
Commercialised
Range of product
Zelio Control
Product or component
type
Modular measurement and control relays
Relay type
Multifunction control relay
Product specific
application
For 3-phase supply
Relay name
RM35TF
Relay monitored
parameters
Asymmetry
Phase failure detection
Phase sequence
Undervoltage and overvoltage in window mode
Time delay
Adjustable 0.1...10 s, 10 %
Switching capacity in
VA
1250 VA
Measurement range
194...528 V AC
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Main
Complementary
Reset time
<= 1500 ms for at 480 V
Maximum switching voltage
250 V DC
250 V AC
Minimum switching current
10 mA at 5 V DC
Maximum switching current
5 A DC
5 A AC
[Us] rated supply voltage
220...480 V AC
Supply voltage limits
194...528 V AC 3 phases
Control circuit voltage limits
- 12 %, + 10 % Un
Power consumption in VA
<= 22 VA 400 V AC 50 Hz
Voltage detection threshold
< 194 V
Control circuit frequency
50...60 Hz +/- 10 %
Output contacts
2 C/O
Nominal output current
5A
Hysteresis
2%
Run-up delay at power-up
<= 650 ms
Measuring cycle
<= 140 ms measurement cycle as true rms value
Threshold adjustment voltage
+2...+10 % in the range 480 V AC
+2...+20 % in the range 220...440 V AC
-12...-2 % in the range 220 V AC
2...20 % of Un selected
-20...-2 % in the range 380...480 V AC
Voltage range
480 V phase to phase
440 V phase to phase
415 V phase to phase
400 V phase to phase
380 V phase to phase
220 V phase to phase
Adjustment of asymmetry threshold
5...15 % of Un selected
Measurement accuracy
+/- 10 % of the full scale value
Repeat accuracy
0.5 % for input and measurement circuit
0.3 % for time delay
Measurement error
0.05 %/C with temperature variation
< 1 % over the whole range with voltage variation
Response time
< 200 ms in the event of a fault
Feb 9, 2016
Marking
CE : 73/23/EEC
CE : EMC 89/336/EEC
Overvoltage category
III conforming to IEC 60664-1
Insulation resistance
> 500 MOhm at 500 V DC conforming to IEC 60664-1
> 500 MOhm at 500 V DC conforming to IEC 60255-5
[Ui] rated insulation voltage
400 V conforming to IEC 60664-1
Supply frequency
50/60 Hz +/- 10 %
Operating position
Any position without
Connections - terminals
Screw terminals 2 x 0.2...2 x 1.5 mm - AWG 24...AWG 16, flexible cable with
cable end
Screw terminals 1 x 0.2...1 x 2.5 mm - AWG 24...AWG 12, flexible cable with
cable end
Screw terminals 2 x 0.5...2 x 2.5 mm - AWG 20...AWG 14, solid cable without
cable end
Screw terminals 1 x 0.5...1 x 4 mm - AWG 20...AWG 11, solid cable without
cable end
Tightening torque
5.31...8.85 lbf.in (0.6...1 N.m) conforming to IEC 60947-1
Housing material
Self-extinguishing plastic
Status LED
1 LED yellow for relay ON
1 LED yellow for fault
1 LED green for power ON
Mounting support
35 mm symmetrical DIN rail conforming to EN/IEC 60715
Electrical durability
100000 cycles
Mechanical durability
<= 30000000 cycles
Operating rate
<= 360 operations/hour under full load
Utilisation category
DC-13 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-12 conforming to IEC 60947-5-1
Width
1.38 in (35 mm)
Product weight
0.29 lb(US) (0.13 kg)
Environment
Electromagnetic compatibility
Immunity for industrial environments conforming to EN/IEC 61000-6-2
Emission standard for residential, commercial and light-industrial environments
conforming to EN/IEC 61000-6-3
Emission standard for industrial environments conforming to EN/IEC 61000-6-4
Standards
EN/IEC 60255-1
Product certifications
CSA
C-Tick
GL
GOST
UL
Ambient air temperature for storage
-40...158 F (-40...70 C)
Ambient air temperature for operation
-4...122 F (-20...50 C)
Relative humidity
95 % at 131 F (55 C) conforming to IEC 60068-2-30
Vibration resistance
1 gn (f = 57.6...150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
0.35 mm (f = 5...57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
Shock resistance
15 gn for 11 ms conforming to IEC 60255-21-1
IP degree of protection
IP30 (casing) conforming to IEC 60529
IP20(Terminals) conforming to IEC 60529
Pollution degree
3 conforming to IEC 60664-1
Dielectric test voltage
2 kV 1 min AC 50 Hz
Non-dissipating shock wave
4 kV
Ordering and shipping details
Category
22380 - RELAYS-MEASUREMENT (RM17-RM35)
Discount Schedule
CP2
GTIN
00785901596745
Nbr. of units in pkg.
Package weight(Lbs)
0.28
Product availability
Stock - Normally stocked in distribution facility
Returnability
Country of origin
ID
Contractual warranty
Period
18 months