Water Penetration Test in Concrete

The Bautechnische Versuchsanstalt testing laboratory conducted tests on concrete samples with HIT V-R M12x150 anchor rods installed using HIT-RE 500 adhesive. Five concrete cubes were cast with a C25/30 mix and anchors were installed. The samples were subjected to 500 kPa of water pressure for 72 hours. Test results showed no water penetration past the anchors. Plain concrete samples were also tested under pressure, showing a maximum penetration of 34 mm. Compressive strength tests yielded a mean strength of 45.3 MPa, meeting the specified C25/30 class.

Uploaded by

Asmir Softic
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
321 views9 pages

Water Penetration Test in Concrete

The Bautechnische Versuchsanstalt testing laboratory conducted tests on concrete samples with HIT V-R M12x150 anchor rods installed using HIT-RE 500 adhesive. Five concrete cubes were cast with a C25/30 mix and anchors were installed. The samples were subjected to 500 kPa of water pressure for 72 hours. Test results showed no water penetration past the anchors. Plain concrete samples were also tested under pressure, showing a maximum penetration of 34 mm. Compressive strength tests yielded a mean strength of 45.3 MPa, meeting the specified C25/30 class.

Uploaded by

Asmir Softic
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

BAUTECHNISCHE VERSUCHSANSTALT

NEGRELLISTRASSE 50

A-6830 RANKWEIL

an der HTL RANKWEIL


Akkreditierte Prf- und Inspektionsstelle

FACHBEREICH FR BAUSTOFFE UND BAUELEMENTE

TEL
FAX
E-MAIL

+43 5522 44004


+43 5522 44004 416
vab@[Link]

PENETRATION OF WATER UNDER PRESSURE


IN HARDENED CONCRETE C25/30
SAMPLES WITH ANCHOR ROD HIT V-R M12x150
INSTALLED WITH HIT-RE 500
EN 12390-[Link] Testing hardened concrete Part 8: Depth of penetration of water under pressure
description of order

Ordering party

Hilti Entwicklungsgesellschaft mbH


Product Care Chemical Anchors
Development Chemical Anchors

Address of ordering party

Hiltistr. 6
86916 KAUFERING
GERMANY

Date of order
Order No.

March 25, 2009


4505965763

Test material

HIT-RE 500 Injection Adhesive


ANCHOR ROD HIT V-R M12x150

Receipt of test material

April 21, 2009

Test Report No.

176/09a

Date of issue

June 23, 2009

This report consists of:

Text
Appendix 1
Appendix 2

6 pages
1 page
2 pages

The reported test results relate only to the tested items.


If this test report is transcribed or copied, the wording and layout may not be changed, nothing may be omitted and no additions may
be made. Extracts may only be copied or published with the written permission of the testing station.
The Testing Laboratory at the HTL Rankweil (Bautechnische Versuchsanstalt) is attached to the HTBLuVA Rankweil. The Testing
Laboratory is accredited by BMWFJ-92.714/0231-I/12/2009, dated April 14, 2009 and OIB ZL-OIB-180-001/02-034 dated October 24,
2006 as Testing Laboratory/Inspecting body ([Link]. 115).

TESTING LABORATORY
at the HTL Rankweil
Department for construction materials and elements

Test Report No 176/09a


Page 2 of 6

MISCELLANEOUS
The Hilti Entwicklungsgesellschaft mbH contracted the Testing Laboratory at the HTL Rankweil
(Bautechnische Versuchsanstalt an der HTL Rankweil) to conduct tests to determine the depth of
penetration of water under pressure in hardened concrete, when anchor rods HIT V-R M12x150
are installed with the adhesive mortar HIT-RE 500.
Following test procedure was agreed upon between the ordering party and the Testing Laboratory:
-

casting of 5 concrete samples using C25/30 Dmax 22, cubes with 200 mm edge-length;

installation of the anchor rod HIT V-R M12x150 with HIT-RE 500 according to the
instructions given by the ordering party;

testing the samples according to EN 12390-8:2009 respectively to ISO 1920-5:2004 by


applying a water presser of (500 50) kPa for the duration of (72 2) hours.

It was agreed upon, that the specimens in which the anchors were installed are not water-cured for
the whole period between demolding and testing.
In addition to the above described test procedure a series of 3 samples concrete cubes were
fabricated and their compressive strength was determined according to the Austrian Standard
NORM B 3303 respectively to NORM EN 12390-3.
To get informations on the penetration of water under pressure in to the plain concrete, concrete
samples with the dimension 200x200x120 mm were casted with the same mix design, water-cured
till the age of 28 days and then tested according to EN 12390-8.
Tested adhesive anchor:

HIT-RE 500 and HIT V-R M12x150

ONCRETE MIX DESIGN - CASTING OF CONCRETE SAMPLES


2.1

CONCRETE MIX DESIGN


Cement:
Water:
W/C - ratio:

345 kg/m CEM II/A-LL 32,5 R, Heidelberger Cement


drinking water 189 kg/m
0,55

Aggregate - natural rounded gravel


0/4:
4/8:
8/16:
16/32:

831 kg/m
269 kg/m
461 kg/m
346 kg/m

Zech-Kies GmbH
Zech-Kies GmbH
Zech-Kies GmbH
Zech-Kies GmbH

TESTING LABORATORY
at the HTL Rankweil
Department for construction materials and elements

Test Report No 176/09a


Page 3 of 6

Grading of the aggregates:


100

Dmax 22 mm

91

90

PERCENTAGE PASSING IN M%

80

90

78
73

70

67

65
60

59
53

50

51
45

40

40
30

28

20

9
5

0,063

0,125

16

6,5
0

0,25

28

26

17

16
10

38

0,5

11,2 16

22,4 31,5

SIEVE SIZE IN MM

2.2

CASTING OF CONCRETE SPECIMENS


The concrete components were mixed with a laboratory compulsory mixer. After adding the water
the concrete was mixed for 2 minutes. Subsequent to the mixing the concrete flow and the density
of fresh concrete were tested.
Properties of the fresh concrete
date of casting
concrete flow
density of fresh concrete
temperature of fresh concrete
fabricated specimens

20.03.2009

27.03.2009

440 mm

465 mm

2466 kg/m

2479 kg/m

18,7 C

20,7 C

09.04801 - 09.04806

09.04832 - 09.04836

The moulds were filled and the concrete was compacted with a vibrating table at 7500 R/min during
30 sec.
Storing and curing the specimens:
All samples were stored 24 hours within the mould at room temperature (20 2) C and the
concrete surface was covered with plastic foil.
After remoulding the specimen were stored as follows:
cubes for compressive-strength test (150 mm edge-length) to the age of 7 days under water at a
temperature of (20 2) C;
subsequently till testing at room temperature (20 2) C.
slabs for the water-penetration test (200x200x120 mm)
till the start of testing under water at a temperature of (20 2) C.
cubes to test water-penetration of concrete with installed adhesive anchors
till the age of 7 days under water at a temperature of (20 2) C;
subsequently till installing the anchors and testing the water penetration at room
temperature (20 2) C.

TESTING LABORATORY
at the HTL Rankweil
Department for construction materials and elements

Test Report No 176/09a


Page 4 of 6

TEST PROCEDURE AND TEST RESULTS

3.1

COMPRESSIVE STRENGTH
Test procedure: NORM EN 12390-2 and NORM B 3303, chapter 7.2
Details of the test results

mm

ultimate
load
kN

bulk
density 1)
kg/m

compressive
strength
MPa

149,5

149,5

1002

2428

44,7

149,9

149,6

149,5

1038

2439

46,3

150,5

150,0

149,9

1015

2423

45,0

2430

45,3

mass

length

width

height

kg

mm

mm

09.04801

8,144

150,1

09.04802

8,176

09.04803

8,198

Specimen No

date of testing:
17 April, 2009
1)

age of concrete:
28 days

mean value:

calculated from measured values determined on specimens without preparation or conditioning.

surface conditions of samples: air-dry


preparation of loading areas: none
3.2

PENETRATION OF WATER UNDER PRESSURE - PLAIN CONCRETE


Test procedure: EN 12390-8:2009, section 6
ISO 1920-5:2004, section 5.4
Details of test:
date of start of the test:

17.04.2009

age of concrete at start of test:

28 days

direction of application of water pressure:

on bottom of the specimen perpendicular


to the direction of casting

applied water pressure:

(500 50) kPa during (72 2) h

concrete area exposed to the water pressure:

according to a circle with 100 mm diameter

specimens:

prismatic slabs with dimensions of


200x200x120 mm

specimen no
maximum depth of penetration

09.04804
16 mm

17 mm

09.04805
28 mm

34 mm

09.04806
25 mm

27 mm

deviation of the water penetration


from the acceptable one

none

none

none

leakage

none

none

none

penetration front curve

see appendix 1 page 1

TESTING LABORATORY
at the HTL Rankweil
Department for construction materials and elements

3.3

Test Report No 176/09a


Page 5 of 6

SETTING THE ADHESIVE ANCHORS


USED ANCHORING SYSTEM
Adhesive Mortar:
HIT-RE 500
A: 3006224
B: 3106048
article no: 305074
Anchor rod:

SETTING DETAILS
Drill bit:

HIT V-R M12x150


article no: 387081

TE-C3X 14

Cutting diameter of
used drill bit:

dcut = 14,28 mm

Depth of bore hole:

h = 110 mm

Rotary hammer drill:

TE 25

Bore hole cleaning:

brushing 3 times - dust removal with vacuum cleaner,


brushing 3 times - dust removal with vacuum cleaner.

SETTING PROCEDURE
The hole was drilled vertically downwards in the centre of a casted surface perpendicular to the
direction of casting. The bore hole was cleaned and diameter and depth were measured. Then
the adhesive was injected using the dispenser MD 2000 and the anchor rod was inserted.
Five samples were prepared and setting was done an 21.04.2009 at 09:55. After setting the
anchors, the adhesive was allowed to cure for > 24 hours at room temperature (20 2) C.

Specimen with installed anchor


bore hole
diameter
mm

bore hole
depth
mm

depth of
embedment
mm

09.04832

13,6

111

111

09.04833

13,5

114

114

09.04834

13,6

111

111

09.04835

13,6

112

112

09.04836

13,6

113

113

specimen no

BAUTECHNISCHE VERSUCHSANSTALT
an der HTL Rankweil
Departement for construction materials and elements

PENETRATION FRONT CURVE - PLAIN CONCRETE

e176_09a-[Link]

Test Report No 176/09a


Appendix 1
Page 1 of 1

BAUTECHNISCHE VERSUCHSANSTALT
an der HTL Rankweil
Departement for construction materials and elements

PENETRATION FRONT CURVE


Samples with adhesive mortar HIT-RE 500

e176_09a-[Link]

Test Report No 176/09a


Appendix 2
Page 1 of 2

BAUTECHNISCHE VERSUCHSANSTALT
an der HTL Rankweil
Departement for construction materials and elements

PENETRATION FRONT CURVE


Samples with adhesive mortar HIT-RE 500

e176_09a-[Link]

Test Report No 176/09a


Appendix 2
Page 2 of 2