<<Contents>> <<Index>>
General
Specications
Digital I/O Modules
(for ProSafe-RS)
GS 32S06K40-01E
GENERAL
This GS provides the hardware specications of the digital I/O modules that can be installed in the Safety Node Unit
(SNB10D) and Safety Control Units (SSC10S and SSC10D).
STANDARD SPECIFICATIONS
Input Module
Input modules accept a contact signal from the eld. SDV144 input modules can be dual-redundant.
Item
Specications
Model
SDV144
Number of inputs
16, collective isolation
Input signal
No-voltage contact
ON: 1 k maximum
OFF: 100 k minimum
Input current
6 mA 20%
(External power supply, 24 V DC at 0 input)
Contact rating
24 V 5%, 10 mA or greater
External power supply
24 V 5%
Current capacity: 200 mA
Instantaneous maximum permissible
input voltage
30.0 V DC
Input response time
40 ms maximum
Withstand voltage
2 kV AC between input signal and system, 16-input line collectively connected
Current consumption
290 mA maximum (5 V DC)
140 mA maximum (24 V DC)
Weight
0.31 kg (with no option codes)
External connection
Pressure clamp terminal
MIL cable
Dedicated cable
Note: When dedicated cables are used, the module withstand voltage shall be 500 V AC (between input signal lines and system).
If MIL connector cables are used, the withstand voltage depends on their cables electrical specications.
If SDV144 eld wiring diagnostic functions are used, the following diagnostic elements should be installed for individual channels in the vicinity of the eld equipment:
SCB100 (for defective open circuit detection while accepting off signals) (*1)
SCB110 (for defective short-circuit detection while accepting on signals) (*2)
*1:
*2:
Input signals are normally off while in normal operation.
Input signals are normally on while in normal operation.
Yokogawa Electric Corporation
2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan
Tel.: 81-422-52-5816 Fax.: 81-422-52-0571
GS 32S06K40-01E
Copyright Feb. 2005
2nd Edition Nov.07,2005
<<Contents>> <<Index>>
When the input signals are normally off while in normal operation, connect the SCB100 in parallel with the contact
output of the eld equipment as given below.
SCB100
SDV144
DCn
INn
: Field equipment switch
[Link]
When the input signals are normally on while in normal operation, connect the SCB110 in series with the contact output of the eld equipment (take care about the polarity taking note of the polarity).
SCB110
SDV144
DCn
Red
Blue
INn
[Link]
When checking for both defective short and open circuits, connect the SCB100 and SCB110 in parallel and series with
the contact outputs of the eld equipment respectively, as given below.
SDV144
DCn
SCB100
Red
SCB110
Blue
INn
[Link]
All Rights Reserved. Copyright 2005, Yokogawa Electric Corporation
GS 32S06K40-01E
Feb.01,2005-00
<<Contents>> <<Index>>
Output Module
Output modules output 24 V DC on/off status signals to eld equipment.
SDV531 output modules can be dual-redundant. The output modules incorporate eld wiring diagnostic features, so
they require no wiring diagnosis elements.
Item
Specications
Model
SDV531
Number of outputs
Eight, collective isolation
Output voltage
24 V DC
External power supply rating
24 V DC, 5 A minimum
External power supply
24 V DC 5%
Current capacity, 5 A
Output voltage drop
1 V maximum
Maximum leak current at output off
status
1.6 mA
Output format
Current source
Maximum load current
0.6 A/output line (4.8 A in total output line)
Output response time
30 ms maximum
Withstand voltage
Current consumption
2 kV AC (between input signal lines and system), eight input lines collectively
connected (negative lines) (*1)
280 mA maximum (5 V DC)
140 mA maximum (24 V DC)
Weight
0.28 kg (with no option codes)
External connection
Pressure clamp terminal
MIL cable
Dedicated cable
*1:
When dedicated cables are used, the modules withstand voltage shall be 500 V AC (between input signal lines and system). If MIL connector cables are used, the withstand voltage depends on their cables electrical specications.
All Rights Reserved. Copyright 2005, Yokogawa Electric Corporation
GS 32S06K40-01E
Nov.07,2005-00
<<Contents>> <<Index>>
EXTERNAL DIMENSIONS
SDV144 Digital Input Module
Unit: mm
107.5
32.8
130
[Link]
SDV531 Digital Output Module
Unit: mm
107.5
32.8
130
[Link]
SBC100 and SBC110 Wiring Diagnosis Elements
25010
83
655
113
[Link]
All Rights Reserved. Copyright 2005, Yokogawa Electric Corporation
GS 32S06K40-01E
Feb.01,2005-00
<<Contents>> <<Index>>
MODEL AND SUFFIX CODES
Digital Input Module
Description
Model
Sufx codes
SDV144
Digital input module (16 input channels, collective isolation)
-S
Basic type
Always 1
3
Option codes
*1:
G3-compatible and temperature-adaptive
/D4A00
With signal cable interface adapter
[Part name: STD4A-00]
/B4S00
With pressure clamp terminal block for digital input (without surge absorber)
[Part name: STB4S-00]
/B4S10
With pressure clamp terminal block for digital input (with surge absorber)
[Part name: STB4S-10]
/B4D00
Dual-redundant pressure clamp terminal block for digital input (without surge absorber) (*1)
[Part name: STB4D-00]
/B4D10
Dual-redundant pressure clamp terminal block for digital input (with surge absorber) (*1)
[Part name: STB4D-10]
/CCC01
With connector cover for MIL cable (ribbon cable)
[Part name: SCCC01]
/CCC02
With connector cover for MIL cable (separated cable)
[Part name: SCCC02]
When this module is used in dual-redundancy, one more module with the same specication is needed, but no option code
is required in its module.
Digital Output Module
Description
Model
Sufx codes
SDV531
Digital output module (eight outputs, collective isolation)
-S
Basic type
Always 2
3
Option codes
*1:
G3-compatible and temperature-adaptive
/D4A00
With signal cable interface adapter
[Part name: STD4A-00]
/B4S00
With pressure clamp terminal block for digital output (without surge absorber)
[Part name: STB4S-00]
/B4S10
With pressure clamp terminal block for digital output (with surge absorber)
[Part name: STB4S-10]
/B4D00
Dual-redundant pressure clamp terminal block for digital output (without surge absorber) (*1)
[Part name: STB4D-00]
/B4D10
Dual-redundant pressure clamp terminal block for digital output (with surge absorber) (*1)
[Part name: STB4D-10]
/CCC01
With connector cover for MIL cable (ribbon cable)
[Part name: SCCC01]
/CCC02
With connector cover for MIL cable (separated cable)
[Part name: SCCC02]
When this module is used in dual-redundancy, one more module with the same specication is needed, but no option code
is required in its module.
All Rights Reserved. Copyright 2005, Yokogawa Electric Corporation
GS 32S06K40-01E
Nov.07,2005-00
<<Contents>> <<Index>>
Wiring Diagnosis Elements
Description
Model
Sufx codes
*1:
SCB100
Wiring Check Adapter for Digital input (for defective open circuit detection while accepting off
signals) (*1)
-S
Basic type
Always 1 (G3-compatible)
Eight wires/set
Description
Model
Sufx codes
*1:
SCB110
Wiring check adapter for Digital input (for defective short-circuited detection while accepting on
signals) (*1)
-S
Basic type
Always 1 (G3-compatible)
Eight wires/set
ORDERING INFORMATION
Specify the model and sufx codes when ordering.
TRADEMARKS
ProSafe is a registered trademark of Yokogawa Electric Corporation.
Other company and product names appearing in this document are trademarks or registered trademarks of their
respective holders.
All Rights Reserved. Copyright 2005, Yokogawa Electric Corporation
Subject to change without notice.
GS 32S06K40-01E
Feb.01,2005-00