Calculation Size of Neutral Earthing Transformer (NET)
Generator Details:
Generator Voltage (VL) (L-L)
11
KV
14.3
50
KV
Hz
Transformer Primary Voltage
33
KV
Transformer Secondary Voltage
11
KV
Maximum Over Voltage
Frequency
Generator Transformer Details:
Capacitance Per Phase:
Generator Winding Capacitance / Phase
0.22
Farad
Generator Connection Capacitance / Phase
Generator Transformer Capacitance / Phase
0.001
0.006
Farad
Farad
Generator Transformer Connection Capacitance / Phase
Transformer Cabale Capacitance / Phase
0
0.0003
Farad
Surge Arrestor Capacitance / Phase
0.25
Other Capacitance / Phase
Total Zero Sequence Capacitance (C):
Total Zero Sequence Capacitance Reactance to Ground (Xc):
0.47730
6672.35
Farad
Farad
Farad
Farad
/Phase
Neutral Earthing Transformer Size:
Primary Voltage of the Grounding Transformer (Vp)
11
KV
Secondary Voltage of the Grounding Transformer (Vs)
240
Volt
Turns Ratio of the Grounding Transformer (N)
Neutral Earthing Transformer % Reactance (X%)
Neutral Earthing Transformer Reactance in PU (Xpu)
Neutral Earthing Transformer Base KV (Bv)
45.83
4%
0.04
0.24
0.04
PU
KV
[Link], [Link], jiguparmar@[Link]
al Earthing Transformer (NET)
:Calculate Size of Neutral Earthing Transformer:
Phase to Neutral Voltage (Vp1)
6.35
KV
VL/1.732
% of Force field condition for Neutral Earthing Transformer
Phase to Neutral Voltage under Force Field Condition (Vf)
30%
8.26
1.3
KV
Vf=Vp1x 1.3
Capacitive charging current/phase (Ic)
1.24
Amp
Ic=Vf / Xc
Total Capacitive charging current (It)
3.71
Amp
It=3xIc
Rating of Neutral Earthing Transformer (Pr)
40.83
KVA
Pr=VpxIt
Neutral Earthing Transformer overloading factor
2.6
KVA
P=Pr/ 2.6
Residual Capacitive reactance (Xct)
Required Resistance value at secondary side (Rsec)
2224.12
1.059
Xct=Xc / 3
Rsec=Xct / (NxN)
Required Grounding Resistor value at primary side (Rp)
Neutral Earthing Transformer Secondary Current
2224.12
65.44
Amp
Rp=Xct
Neutral Earthing Transformer Secondary Resistor Current (for 30 Seconds)
221.18
Amp
Size of Neutral Earthing Transformer (P)
16
Neutral Earthing Transformer Reactance Base(Base X):
Neutral Earthing Transformer Reactance (X)
Neutral Earthing Transformer X/R Ratio
3.67
0.15
0.14
X=Xpu x Base X
Fault current through Neutral (single line to ground fault) (If)
2.86
Amp
If=Vp1/Rp
:Results:
Rating of Neutral Earthing Transformer (P)
16
KVA
Short time Rating of Neutral Earthing Transformer
Ratio of Neutral Earthing Transformer
Neutral Earthing Transformer Secondary Current
Required Grounding Resistor value at primary side (Rp)
41
11000 /240
65.44
2224.12
KVA
Volt
Amp
Required Resistance at secondary side (Rsec)
1.06
Neutral Earthing Transformer Secondary Resistor Current (for 30 Seconds)
221.18
Amp