Form 090.
040-SPC01 (FEB 2012)
SPECIFICATIONS
File:
Replaces:
Dist:
EQUIPMENT MANUAL - Section 90
NOTHING (New Information)
1, 1a, 1b, 1c, 4a, 4b, 4c
QUANTUM HD
CONTROL PANEL
The most technologically advanced screw
compressor control center in the world.
Hardware
The Quantum HD Control Panel incorporates hardware
features & technology proven in millions of applications.
The high-speed, PC-based processor provides speed and
processing capability far surpassing competitive microprocessor offerings. The High Definition Touch Display offers a
high contrast, crisp clear display of compressor information
and status with a superior viewing angle.
Additional Input/Output can be easily installed in the field.
This provides flexibility for future engine room upgrades and
changes. No longer will you be constrained by the manufacturers limited I/O capability.
Three field-selectable serial communication ports allow you
to choose from a combination of RS422, RS485, or RS232
port configurations for external communications. Ethernet
port allows Ethernet and Internet communications.
Additional Features
Circuit Breaker Protection for Main Power.
UL, cUL, and ISO 9001 Certifications
Flexible Analog Inputs Setup is easily changed in the field
to accept 0-5 volt, 1-5 volt, 4-20 mA or ICTD sensors and
transmitters.
Long-Life, Easily Replaceable, Lithium Coin Cell Battery
for power backup to the time/date clock only.
Communication Activity and Diagnostic Lamps simplify
troubleshooting and provide visual indication of proper component operation. Code readouts also appear on the display
if an internal component problem is detected.
FLASH Setpoint Memory All setpoints are stored in FLASH
memory which requires no battery backup. Setpoints can be
field programmed within Johnson Controls defined limits. A
notice is displayed if setpoints are entered outside of the
defined ranges.
Replaceable Input and Output Modules with individual,
replaceable fuses, on-board tester, and spare fuse.
Software
Intuitive Operator Interface All of the Quantum HD control panel screens are user friendly, menu driven and easy
to use and understand. The straight-forward menu design
keeps you on track.
Software Diagnostics Numerous diagnostic features have
been incorporated to ease troubleshooting and identify
component malfunctions. Diagnostic features include: sensor
short/open, setpoint input out of sensing range, DC and AC
power monitoring, and memory error sensing.
Multiple Capacity Controllers provide application flexibility
for auto setback control and control reset for changes in
modes of operation.
Override Controls All safety and controller functions can
be programmed to unload the compressor within maximum
safety and control parameters.
On-screen Calibrations for sensors, motor current, slide
valve and slide stop with easy to understand graphics.
Potentiometer tuning has been eliminated.
Shutdown Notification Display backlight flashes on shutdown to attract attention in noisy engine rooms.
Selectable Pressure and Temperature Units
Programmed Compressor Sequencing
Condenser Control
Industry Standard Communication Protocols
Real-Time and Historical x-y trending Selected data and
selected time periods can be viewed in either an xy trending
chart or a tabular chart.
Ability to add analog inputs Can add any 05Vdc, 15Vdc,
or 420mA sensor. A name and unit description can be
entered to identify the input. The inputs have high and low
alarm and shutdown setpoints.
Ability to add digital inputs A name can be entered to
identify the input. Either an alarm or shutdown can be selected to occur when the input is de-energized. A selection
can be made whether to monitor the input continuously or
only when the compressor is running.
090.040-SPC01 (FEB 2012)
Page 2
FRICK QUANTUM HD CONTROL PANEL
SPECIFICATIONS
CONTROL PANEL SPECIFICATIONS
PANEL
Size
22 (55.88 cm) W x 24 (60.96 cm) H x 10 (25.40) D
Weight
78 lb (35.38 kg) (with all options installed)
Design
NEMA 4 (Type 4)
Material
Painted steel
Finish
Frick sea blue epoxy paint
ENVIRONMENTAL
Operating
Ambient Temperature
Storage
-40F to 122F*
-13F to 140F
-40C to 50C*
-25C to 60C
Humidity (noncondensing)
0% to 90%
0% to 90%
Vibration
15 gs (14.7 m/s )
RFI field strength immunity
10v/m (20 MHz to 1ghz)
EMI
complies with CE EMC directive
15 gs (14.7 m/s)
*Ambient temperatures down to -40F (-40C) require heater(s).
CERTIFICATIONS
UL / cUL 508A
ISO9001
POWER
USA voltage
100 to 125 volts AC 47-63 Hz
International voltage*
185 to 254 volts AC 47-63 Hz
Power loss
16 millisecond maximum (1 cycle)
* Requires change-out of plug-in relays and AC input modules to 230 volts AC type.
DISPLAY
Format
1024 x 768 pixels XGA
Type
Color active matrix TFT (Thin Film Transistor) LCD (Liquid Crystal Display)
Colors
256 simultaneous colors from 256,000 color palette
Size
15 (38.10 cm) diagonal display area
Luminance
60 minimum, 70 typical cd/m2
Backlight
LED 50,000 hour on time.
KEYPAD
Material
Poly Carbonate
Switches
24.69 oz (700 gram) trip force stainless steel snap domes
Misc.
RFI protected, UV protected, Scratch resistant
INPUT/OUTPUT MODULES
Input
USA voltage
IACM-5
Input
International voltage
IACM-5A
180 to 280 volts AC
90 to 140 volts AC
Output
USA & International voltage
OACM-5
24 to 280 volts AC
FRICK QUANTUM HD CONTROL PANEL
SPECIFICATIONS
ANALOG INPUT CHANNELS
Channel
Input
0-5 volt DC
Channels 1 through 13
1-5 volt DC
4-20 ma.
ICTD (Integrated Circuit Temperature Device) AD590
0-5 volt DC
1-5 volt DC
Channels 14 & 15
4-20 ma.
ICTD (Integrated Circuit Temperature Device) AD590
0 to 1,000 ohm potentiometer
0-5 volt DC
1-5 volt DC
Channel 16
4-20 ma.
ICTD (Integrated Circuit Temperature Device) AD590
0-50 ma. AC or DC
ANALOG OUTPUT CHANNELS
Channel
Output
Channels 1 through 8 4-20 ma., 0-20 ma.
TEMPERATURE SENSOR (ICTD)
Device
AD590J
Range
-67F to 302F (-55C to 150C)
Output
1 uA / Kelvin
Excitation Voltage
4 to 30 volts DC
Accuracy
+/- 5.0C over specified temperature range.
PRESSURE SENSOR
Device
Signal-conditioned silicon strain gauge
Material
100% stainless steel welded parts.
2X over pressure (200 PSI device)
Physical
1.5X over pressure (500 PSI device)
10X burst pressure (200 PSI device)
5X burst pressure (500 PSI device)
Suction pressure
200 PSIA range: 29.9" hg to 185.7 PSI
Discharge pressure
Oil pressure
500 PSIA range: 29.9" hg to 485.7 PSI
Oil filter pressure
Output (all)
1-5 volt DC
Compensated temperature range
30 F to 185F (-1C to 85C)
Operating temperature range
-40F to 185F (-40C to 85C)
Excitation voltage
9 to 30 volts DC
Accuracy
+/- 0.8% FS
090.040-SPC01 (FEB 2012)
Page 3
090.040-SPC01 (FEB 2012)
Page 4
FRICK QUANTUM HD CONTROL PANEL
SPECIFICATIONS
POWER SUPPLY
Input power
90 to 125 volts AC
47-63 Hz
(Auto detect)
185 to 264 volts AC
47-63 Hz
Output power
75 watts continuous, 110 watts peak
+5 volt DC
DC Supplies
5 amp max.
(V1)
25 Watts
+12 volt DC
4 amp max.
(V4)
48 Watts
+24 volt DC
2.1 amp max.
(V2)
48 Watts
Other
AC line quality monitoring and reporting.
Type
Switching
POWER SUPPLY SETTINGS:
Minimum setting
Recommended Setting
Maximum setting
+5 volts DC (V1) adjustable
Supply
5.00 volts DC
5.20 volts DC
5.25 volts DC
+12 volts DC (V4) adjustable
11.76 volts DC
12.12 Volts DC
12.24 volts DC
+24 volts DC (V2) adjustable
22.80 volts DC
24.50 volts DC
26.40 volts DC
COMMUNICATIONS INTERFACE
Port
Type
Protocol / Usage
Com-1 *
RS-485
Frick #, $ Allen-Bradley DF1
Com-2 *
RS-422
MODBUS ASCII
Com-3 *
RS-232
MODBUS RTU Status Communication
Ethernet
RJ-45
MODBUS TCP, HTTP, E-mail, Compressor Sequencing
*May require additional hardware.
SUPPORTED WEB BROWSERS
Google Chrome (current version)
Firefox (current version)
Internet Explorer (current version)
Safari (current version)
MISCELLANEOUS
Relay
Plug-in type; 120 volt AC; 3-pole; 10 amp contacts
FIELD WIRING
AC wiring
All AC wiring must enter on the right hand side and bottom of the enclosure or bottom right side.
(40 volts and above)
Top entry is not permitted. Predrilled conduit holes are provided.
DC wiring
All DC wiring must enter on the left hand side and bottom of the enclosure or bottom left side.
(40 volts and below)
Top entry is not permitted. Predrilled conduit holes are provided.
Form 090.040-SPC01 2012-02
Supersedes: NOTHING (New Information)
Subject to change without notice
Published in USA GUI 0212 2k
2012 Johnson Controls Inc. - ALL RIGHTS RESERVED
Johnson Controls
100 CV Avenue
Waynesboro, PA USA 17268-1206
Phone: 717-762-2121 FAX: 717-762-8624
[Link]/frick