AN708 Se ri es Int e l li ge nt Adj ust or
AN708 Series Intelligent Temperature Controller/ Adjustor
Users Manual
Measuring Accuracy:0.3%F.S
KKAN708E01-A/1-1
[Link] Illustration
AN708
Input and communication0:One loop input without communication
8:One loop input with RS485 communication (Please indicate when order)
Alarm3: Two alarm output 2:One alarm output 1:Without alarm output
One more alarm will be added when not using Heating or cooling control
Output functionR:Relay output C:420mA current output Q:Logic output
Dimension (mm)4:48W48H 6:48W96H 7:72W72H 8:96W48H 9:96W96H
16:80W160H 80:160W80H
AN708 Series intelligent temperature controller /adjustor
[Link] Illurstration
AN708-4 series product can be ordered for 4--20mA input
Code
AN708 - 4- R20
AN708- 4- C20
Size 48*48
AN708- 4- Q20
AN708- 4- R18
Other size
OUT 1 or OUT 2
Alarm output
Alarm
RS485
Relay output
without
Relay output
without
SSR output
Relay output
without
Relay output
Relay output
without
RS485
Relay output
4-20mA current output
AN708- 4- C18
4-20mA current output
Relay output
without
RS485
AN708- 4- Q18
SSR output
Relay output
without
RS485
AN708 - - R30
Relay output
Relay output
without
AN708- - C30
4-20mA current output
Relay output
without
AN708- - Q30
SSR output
Relay output
without
AN708- - R38
Relay output
Relay output
RS485
AN708- - C38
4-20mA current output
Relay output
RS485
AN708- - Q38
SSR output
Relay output
RS485
5
Can be worked just under heating-cooling control(OT=3); under other control,
worked as alarm 3 (size:48*48 worked as alarm 2)
5
1
Alarm output: Relay output capacity: 1A/250Vac
3. Main Technical Parameters
3. 1 Whole controller parameters
RTU
KKAN708E01-A/1-2
3.2. Input signal table
Symbol
0
-501300
100K
-501200
100K
-501000
100K
-50400
100K
6001800
100K
-101700
100K
-101600
100K
-501200
100K
-199.9850.0
0.1
0.2mA)
10
-199.9500.0
0.1
0.2mA)
11
-50.0150.0
0.1
0.2mA)
12
-50.0150.0
0.1
0.2mA)
13
050mV
0.01%FS
100K
14
420mA
0.01%FS
15
010V
0.01%FS
100K
16
0400
0.01%FS
0.2mA
110
4. Panel Indication
SET function key
OUT1 Indication Lamp
OUT2 Indication Lamp
OUT1
AL1 Indication Lamp
AL2 Indication Lamp
AL3 Indication Lamp
AT:Auto-tuning Indication Lamp
AL1
SET
Shift function key
OUT2
Increase Key
AL2
AL3
Decrease key
AT
PV Value
SV set value Display measured value or parameter code
Display setted value or parameter code
[Link] Key Operation
KKAN708E01-A/1-3
Temperature unit switch
OUT1 control cycle: when current output ,the cycle is 0; SSR output,
it is 1; Relay output it is more than 4
(it is more than 4 )
KKAN708E01-A/1-4
-50
60
0: unit of celsius 1unit of fahrenheit
0/1
Formula
0
HY
High limit absolute value alarm
AL
1
Low limit absolute value alarm
Alarm:PV<AL
Cancel:PVAL-HY
HY
AL
Temperature drops down
HY
SV+AL
High limit deviation value alarm
SV
3
Temperature rises
Low limit deviation value alarm
Temperature drops down
Alarm:PV>AL
Cancel:PVAL-HY
Temperature rises
HY
SV-AL
Alarm:PV>AL +SV
Cancel:PVSV+AL-HY
Alarm:PV<SV-AL
Cancel:PVSV-AL+HY
SV
8.
A
G +0.5
-0
C
E
J +0.5
-0
B
Code
H(Minimun)
K(Minimun)
48
101
10
91
45
45.5
25
45.5
25
48
96
100
94
91
45.5
25
91.5
25
72
72
100
10
90
67.5
68
25
68
25
25
4:(48*48)
48
6:(96*48)
7:(72*72)
8:(48*96)
96
48
100
94
45
91.5
25
45.5
9:(96*96)
96
96
101
10
91
90.5
91
25
91
25
10
92
76
154
30
76.5
30
10
92
153.5
76.5
30
154
30
80:(80*160)
160
16:(160*80)
80
Note
80
102
160
102
unit(mm) tolerance+0.5%
9
Series
AN708 series
CodeAN708-7
Accuracy0.3%FS3digits 25
Temperature excursion:0.01%FS/
KKAN708E01-A/1-5
AN708 series temperature controller
CodeAN708-9
Accuracy0.3%FS3digits 25
Temperature excursion:0.01%FS/
AN708 series temperature controller
CodeAN708-16/80
Accuracy0.3%FS3digits 25
series temperature controller:0.01%FS/
AN708 series temperature controller
CodeAN708-6 / AN708-8
Accuracy0.3%FS3digits 25
series temperature controller:0.01%FS/
Note:Please subject to the connecting drawing on the actual product if any changes.
10. Simple Problem Shooting
Dispaly Message
Reasons & Solving Methods
Display HHHH
Input disconnect or over upper limit. Please check input signal, FH value and ambient working temperature.
Display LLLL
Input disconnect or under lower limit. Please check input signal, FH value and ambient working temperature.
[Link]
AN708 series adjustor follow Modbus RTU communication protocol, and it can run RS485 half-duplex [Link]
function code is 0x03, write function code is 0x10, 16-bit CRC checking is applied. The meter can not return error message.
Data frame format
Start bit
Data bit
Stop bit
Check bit
None
11.1. Read Multiple Registers
For example: The host computer read the float number AL1 (The value of Alarm 1 is 14.5).The address code of AL1 is 0x0000,
for AL1 is float number (4bits), it will occupy 2 data register. Reference IEEE-574 standard the hexadecimal 16 result of the
decimal float number is 0x41766666.
Request from the master unit (Read Multiple Registers)
Meter address
Function code
High bit of
start address
0x01
0x03
0x00
4
Low bit of
start address
0x02
High bit of
data
Low bit of
data
0x00
0x04
Low bit of CRC code High bit of CRC code
0xE5
0xC9
KKAN708E01-A/1-6
Correct answer from slave unit (Read Multiple Registers)
Meter address
Function code
0x01
0x03
Data byte length
0x04
Data 1
high byte
Data 1
low bit
Data 2
high bit
Data 2
low bit
0x41
0x76
0x66
0x66
9
High bit of
CRC code
Low bit of
CRC code
0xE2
0xF4
11.2. Write Multiple Registers
For example: The host computer read the float number (setting value 600) ,
The address code for SV is 0x0000, for SV is float number (4bits), it will occupy 2 data register. Referring to IEEE-574
standard the hexadecimal 16 result of the decimal float number is 0x44160000.
Request from the master unit (Write Multiple Registers)
2
Function High bit of Low bit of High bit of Low bit of Data
Unit
data
start
data
start
Length
address Code
length
address
0x01
0x00
0x10
address
length
0x00
0x00
0x02
10
11
High bit Low bit High bit Low bit
of data 1 of data 1 of data 2 of data 2
0x04
0x44
0x00
0x16
0x00
12
13
Low bit High bit
of CRC of CRC
0xFD
0xFC
Correct answer from slave unit (Write Multiple Registers)
1
Meter
address
Function
Code
Start address
of high 8 bit
Start address
of low 8 bit
Data length
high bit
0x10
0x00
0x00
0x00
0x01
Data length
low bit
0x02
Low bit
of CRC
High bit
of CRC
0x41
0xC8
AN708 Series table reference address
Code
Reference
address
0x0000
Setting Value SV
R/W
0x0002
Alarm value AL1
R/W
0x0004
Alarm value AL2
R/W
0x0006
Alarm value AL3
R/W
0x0008
Correct value PS
R/W
0x000A
Proportion rate P
R/W
0x000C
Integral time I
R/W
0x000E
Differentia lD
R/W
0x0010
ON/OFF Control Hysteresis HY
R/W
0x0012
Heating & cooling dead district DB
R/W
10
0x0014
Alarm 1 Hysteresis HY1
R/W
11
0x0016
Alarm 2 Hysteresis HY2
R/W
12
0x0018
Alarm 2 Hysteresis HY3
R/W
13
0x001A
Control output Lo OLL
R/W
14
0x001C
Control output Hi OLH
R/W
15
0x001E
Display Low limit FL
R/W
16
0x0020
Display High limit FH
R/W
17
0x0022
Low limit value of analog
R/W
18
0x0024
High limit value of analog
R/W
19
0x0026
Measuring value
Number of Variable
Data
Length
Read & Write
allow
Remark
KKAN708E01-A/1-7
Code
Reference
address
Number of Variable
Data
Length
20
0x0028
Manualswitch MAN
21
0x002A
Lock LCK
22
0x002C
Control output OT
R/W
23
0x002E
Heating control Turn CT
R/W
24
0x0030
Cooling proportion C_P
R/W
25
0x0032
Cooling control Turn C_CT
R/W
26
0x0034
Alarm 1 mode AD1
R/W
Note1
27
0x0036
Alarm 2 mode AD2
R/W
Note1
28
0x0038
Alarm 2 mode AD2
R/W
Note1
29
0x003A
Input signal select INP
R/W
Note2
30
0x003C
Decimal DP
31
0x003E
Filter FT
32
0x0040
Baud rate BAD
33
0x0042
Address ADD
Read & Write
allow
Remark
Note3
RRead only R/WRead/Write
For Parameter Setting Range , please refer to users manual
Note 1Please refer to alarm parameter form
Note 2Please refer to input Parameter form
Note 3Please refer to below table
Baud rate BAD
4.8K
9.6K
Data value
16 digit CRC verify program
unsigned int Get_CRC(uchar *pBuf, uchar num)
{
unsigned i,j;
unsigned int wCrc = 0xFFFF;
for(i=0; i<num; i++)
{
wCrc ^= (unsigned int)(pBuf[i]);
for(j=0; j<8; j++)
{
if(wCrc & 1){wCrc >>= 1; wCrc ^= 0xA001; }
else
wCrc >>= 1;
}
}
return wCrc;
}
KKAN708E01-A/1-8