1000 A MCC BUSBAR SIZING CALCULATION
PROJECT
CLIENT
CONSULTANT
EPC
CONTRACTOR
Document ID
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
Revision : 01
M/s. K.P.R. SUGAR MILL LTD
Date : 24-05-2012
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
No. of Sheet - 4
ISGEC HEAVY ENGINEERING LIMITED
KR11-10302-CLC-001
Input Data
1.1
Type of Panel
Cubical Type
1.2
System
3PH ,3 Wire / 4 Wire
1.3
Rated Voltage
415V
1.4
degree of Protection
50 Hz.
1.5
Panel Max. Current Rating in Amp (Design)
1000
1.6
Fault Current & Duration (KA RMS Symmetrical for
1 Sec.)
50
1.7
Ambient Temperature (Deg. C.)
50
1.8
Maximum Bus bar Temperature (Deg. C.)
85
1.9
Maximum Enclosure Temperature (Deg. C.)
70
1.10
Degree of Protection
IP: 52 & IP: 42 for ACB Incomer
Bus bar Size for Phase
Bus bar Size for Neutral
No. of Runs
:
:
:
1 x 1 x 125 x 10 MM
1 x 125 x 06 MM
1
No. of times Interleaved
:
:
1.12
Width of Bus Bar in mm
Thickness of Bus Bar in mm
Bus bar cross section for Neutral in [Link]
125
10
750
1.13
Cross section of Bus bar Selected in Sq. mm
1250
1.14
Type of Insulator
SMC support with ribbed construction
1.15
Basic Insulation Level:
:
2.5KV RMS
a. Enclosure Interior & Exterior
Epoxy paint RAL-7032, Siemens Grey
b. Bus bar
Heat Shrinkable Sleeved.
Minimum Clearance:
a. Phase to Phase
25 mm
b. Phase to Earth
20 mm
IS: 8623 Construction
IS : 5082 Bus bar
1.11
a
1.16
1.17
1.18
One Minute Power Frequency voltage
Painting:
Applicable Standard
1.19
Degree of Protection
IP: 54 for Indoor & IP: 55 for Outdoor
1.20
Span Between 2 support
0.5mtr. (500mm)
Page 1 of 4
1000 A MCC BUSBAR SIZING CALCULATION
PROJECT
CLIENT
CONSULTANT
EPC
CONTRACTOR
Document ID
2
2.1
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
Revision : 01
M/s. K.P.R. SUGAR MILL LTD
Date : 24-05-2012
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
No. of Sheet - 4
ISGEC HEAVY ENGINEERING LIMITED
KR11-10302-CLC-001
Bus duct Sizing Calculation for MCC
Short Time Thermal Withstand Capability of Bus bar
=
( Isc / T ) / {14 x 10 log [T1
+258)/(T2+258)] }
Isc = Short Circuit Symmetrical Fault Current in KA
50
T = Fault duration in Sec
T1 = Initial Temperature of Busbar in Deg.C
85
T2 = Final Temperature in Deg.C
200
1.007851794
Minimum Cross Sectional Area of Busbar (A) In Sq.
Inches
A = Cross sectional area of busbar in [Link]
A in [Link] = A x 645.16
650.226
2.2
Required cross sectional Area
650.226 [Link] for pure aluminium.
2.2
Actual Cross section of Bus bar Selected (As per
Clause1.13) in [Link]
1250
Conclusion:
2.3
3
3.10
The required cross section 650.226 [Link] is less than actual cross section 1250 [Link] of the bus bar
selected. Hence, the bus bar size chosen is safe for the envisaged system.
Bus bar Selection for Continuous Current Rating :
Bus bar Selected
As per Clause1.11
Open air rating of bus bar for 50 Deg. C rise over
ambient in Amps.
1850
No. of times Interleaved (As per Clause1.11)
1 x 1850
Overall Rating of Bus Bar in Amps.
Phase spacing in mm.
:
:
1850
150
3.13
Enclosed Size in (W x D x H ) mm
5500 x 800 x 2400 mm
3.14
Bus bar Enclosed in (W x D ) mm
800 x 400 mm
3.15
Design Ambient Temperature
50 Deg. C
3.16
Maximum allowable temp. rise
35 Deg. C
3.17
Enclosure Material
MS Steel
3.11
3.12
Page 2 of 4
1000 A MCC BUSBAR SIZING CALCULATION
PROJECT
CLIENT
CONSULTANT
EPC
CONTRACTOR
Document ID
3.18
3.19
3.20
3.21
4
4.10
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
Revision : 01
M/s. K.P.R. SUGAR MILL LTD
Date : 24-05-2012
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
No. of Sheet - 4
ISGEC HEAVY ENGINEERING LIMITED
KR11-10302-CLC-001
De-rating / Up rating:
a Ambient correction factor for 35 Deg. Rise
0.9
b Enclosure correction factor corresponding to bus bar
0.87
c Enclosure Correction factor Material (MS)
d Proximity Effect Factor
e Bus bar Configuration Factor
g Combined Correction Factor
=
=
=
0.9
0.95
1
0.67
1850 x 0.67
De-rated Current rating of bus bar after applying
Correction factor in Amps.
= 1238.51025
Rating of Panel required (As per Clause 1.5)
= 1000
Conclusion :
The de-rated Current rating 1238.51 amp of Panel selected is more than the required current rating 1000 amp
of Bus duct Bus bar. Hence, the bus bar size chosen is safe for the envisaged system.
Support Insulator Span Calculation During Short Circuit
Fm = Peak Electromagnetic force along the centre
= K x 16 x Isc x 10 / S
line of busbar without enclosure
Isc = Short Circuit Symmetrical Fault Current in KA
50
S = Phase spacing in Meter
0.250
K = Multiplying factor (s-a)/(a+b)
0.904
corresponding to a that is 60
0.4 (Reffering to curve K is 0.9)
Fm (Nm / cm )
14400.000
Fm ( Kg / cm ) = (Fm x 0.1019716)
F = Force acting on top of the insulator
=
=
1468.391
Fm (H+h)/4H
38
75
1091.632813
Cantilever Strength of insulator / safety factor x F
Sk / (SF x F )
SK = Cantilever strength of insulator(Kg/cm)
1600
SF = Safety factor
2.5
586.278
4.12
a
b
Where, H = Cantilever Height of insulator in mm
h = Distance between surface of insulator to centre
of Bus bar in mm
F
4.13
Average span to be addopted in mm
b
Length of Span of insulator in mm
Adopted Span is
OK
Conclusion:
4.4
Average span of 586.278 mm is required but span adopted is 500 mm, hence it is safe for the system
envisaged.
Page 3 of 4
1000 A MCC BUSBAR SIZING CALCULATION
PROJECT
CLIENT
CONSULTANT
EPC
CONTRACTOR
Document ID
5000 TCD SUGAR PLANT WITH 30 MW POWER PLANT
Revision : 01
M/s. K.P.R. SUGAR MILL LTD
Date : 24-05-2012
M/s AVANT GARDE ENGINEERS AND CONSULTANT (P) LTD.
No. of Sheet - 4
ISGEC HEAVY ENGINEERING LIMITED
KR11-10302-CLC-001
Temperature Rise Calculation
5.1
Where, I1=Calculated Rating in Amps (After
deration) As per Clause 3.19
1238.51025
5.2
I2 = Specified Rating in Amps as per clause 1.5
1000
5.3
T1 = Max. Temp. Rise (in Deg.C) Specified
35
5.4
T2 = Temp. Rise in Deg. C to be calculated as
( I1 / I2 ) = ( T1 / T2)0.61
T1 / (I1 / I2 )
24.64
OK
T2
Calculated Temperature is
1.64
Conclusion :
5.5
The Calculated Temperature rise of bus bar is 24.64 Deg. C, which is within the design Specified Temp. 35
Deg. C and it is safe for the System envisaged.
Prepared By: Ganpat C
Checked By : Kamlakar D.
Page 4 of 4
Approved By : A.B.H