Single Family Dwelling Unit, More than 150 Square Meters Floor Area, 230 Volts
Single Phase Service
Floor Area = 250 sq. m
5.1 Air Conditioning Load: (See Section 2.20.3.23)
Two 6-kVA package type air conditioning units
= 12 000 volt-amperes
Provide two 70-ampere package type acu circuits.
Six 2-HP room air-conditioning units,
14 A x 230 V x 6
= 19 320 volt-amperes
Provide six 30-ampere room acu circuits.
5.2 Lighting and Convenience Receptacle Load:
(See Section 2.20.3.23)
250 sq. m x 24 volt-amperes per sq. m
Provide at least two 20-ampere lighting and
Convenience receptacle circuits.
= 6 000 volt-amperes
5.3 Cooking Load: (See section 2.20.3.16)
Two 4-kW wall mounted ovens,
4 000 VA x 2
Provide two 30-ampere wall
mounted oven circuits.
One 8-kW electric range
Provide one 40-ampere
Electric range circuit.
Subtotal Load
= 8 000 volt-amperes
= 8 000 volt-amperes
16 000 volt-amperes
Application of Demand Factor: (See Table 2.20.3.16 Column C)
16 000 volt-amperes x 0.55
= 8 800 volt-amperes
One 1.5 kW microwave oven
(See Table 2.20.3.16 Column B)
Provide one 20-ampere
microwave oven circuit.
One 12-kW electric range
(See Table 2.20.3.16 Column A)
Provide one 60-ampere
electric range circuit
Total Load
5.4 Other Loads:
= 1 200 volt-amperes
= 8 000 volt-ampere
18 000 volt-ampere
One 20-ampere small appliance
circuit @ 1 500 volt-amperes
[ See Section 2.20.1.11(c)(1)]
Provide one 20-ampere
small appliance circuit.
One laundry washing machine
@ 1 500 volt-amperes
[See Section 2.20.1.11(c)(2)]
Provide one 20-ampere
laundry circuit.
One 5-kW clothes dryer
Provide one 30-ampere
dryer circuit.
Four 5-kW water heaters
Provide four 30-ampere water
heater circuits.
One 1.5-HP water pump,
10 A x 230 V
Provide one 20-ampere
Water pump circuit.
Total Other Loads
= 1 500 volt-amperes
= 1 500 volt-amperes
= 5 000 volt-amperes
= 20 000 volt-amperes
= 2 300 volt-amperes
30 300 volt-amperes
Application of Demand Factor: (See Table 2.20.3.23)
30 300 volt-amperes x 0.40
Total Net Computed Load
= 12 120 volt-amperes
= 67 440 volt-amperes
5.5 Circuit Requirement:
Use six 20-ampere 2-wire branch circuits, thirteen 30-ampere 2-wire
branch circuits, one 40-ampere 2 wire branch circuit, one 60-ampere2
wire branch circuit and two 70-ampere 2-wire branch circuits.
5.6 Service Entrance Conductors:
Total Full Load Current: (See Sections 4.30.2.4 and 4.40.1.7)
[67 440 VA + 25% (6 000 VA)]
Use two 325
mm
230 V = 300 Amperes
THW wires
Note: See Section 2.20.2.3 for conductor and overcurrent protection ampere rating.