Pressure Tank Sizing Guide

The document provides a formula and instructions for calculating the size of a pressure tank based on drawdown volume, pump capacity, number of starts/stops per hour, and cut-in and cut-out pressures. It then works through an example calculation using the provided data for a Grundfos pump to determine that the recommended pressure tank size is 500 liters, which is the closest standard size.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views1 page

Pressure Tank Sizing Guide

The document provides a formula and instructions for calculating the size of a pressure tank based on drawdown volume, pump capacity, number of starts/stops per hour, and cut-in and cut-out pressures. It then works through an example calculation using the provided data for a Grundfos pump to determine that the recommended pressure tank size is 500 liters, which is the closest standard size.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd

Project :

Calculating the pressure tank size


Pressure tank size formula is given as follows :

size = (

Drawdown volume
cut-out pressure - cut-in pressure
cut-out pressure + 1

Drawdown is based on pump capacity and the number of start/stops per hour and amount of
water which can be taken from the tank before the pump starts.

250 x Q
I

Drawdown in liters =

250 x Q x (cut-out pressure + 1)


I x ( cut-out pressure - cut-in pressure )

Tank size in liters = (

Where : Q is the average pump flow in m3/h


I is the number of starts/stops per hour.
cut in & cut out : pressure is indicated in bars.
Data :

Pump type & model :

P=

5.5

kw

Number of starts/stops

I =

50

1/h

Average pump flow


cut in pressure
cut out pressure

Q=
=
=

16
3.5
4.5

m3/h
bar
bar

calculated data

GRUNDFOS MODEL : CR 16 -30

Motor power rating

Tank size in liters =

input data

( from pump manufacturer )

250 x 16. x ( 4.5 + 1 )


)
50. x ( 4.5 - 3.5 )

The available standard size is :


Recommended tank size is :

440

liters

500

liters
liters

Note :
The standard sizes of pressure tanks are : 25; 60; 100; 200; 300; 500; 750; 1000 and 2000 liters.

Project :
Calculating the pressure tank size
Pressure tank size formula is given as follows :
Drawdown volume
size = (
cut-ou

You might also like