1
IS IT EXPANSION LOOP REQUIRED
1.1
1.2
1.3
1.4
1.5
1.6
Total Length of Straight Pipe
Material
Design Temperature
Expansion Rate of Pipe
Total Expansion at both ends of straight Pipe
(Virtual Anchor is assumed at centre of pipe)
Required Expansion at both end of straight Pipe
1.7
Expansion Loop Required or Not
SUFFICIENCY CHECK OF FIRST EXPANSION LOOP
2.1
LIMIT STOP LOCATION
'
Maximum distance at which anchor/limit stop to be
located from each end of straight pipe to restrict the
2.1.1 end displacement within the requirement
L'
Actual distance at which anchor/limit stop to be
located from each end of straight pipe due to steel
2.1.2 structure location
2.2
L''
IS IT ONE EXPANSION LOOP IS SUFFICIENT
Since two anchors are located opposite to each other, hence expansion loop is required to add
2.2.1 Assume the width of expansion loop
Actual Expansion inside of expansion loop (i.e at
elbow point connecting the expansion loop leg and
2.2.2 straight pipe leg)
''
Required Expansion inside of expansion loop
(i.e at elbow point connecting the expansion loop leg
2.2.3 and straight pipe leg)
'''
2.2.4 Second Expansion Loop is required or not
SUFFICIENCY CHECK OF SECOND EXPANSION LOOP
The first expansion loop used in section 2.0 is no more valid, hence start from first to determine
second expansion loop shall be located
3.1
FIRST EXPANSION LOOP LOCATION
The maximum distance at which left leg of first
expansion loop shall be located from left end limit
stop of piping segment to restrict the expansion of
3.1.1 left leg within the requirement
NEW LIMIT STOP
The maximum distance at which new limit stop shall
be located from right leg of first expansion loop to
restrict the expansion of right leg within the
3.1.2 requirement
The actual distance at which new limit stop shall be
located from right leg of first expansion loop to
restrict the expansion of right leg within the
3.1.3 requirement (as per steel location)
The distance at which new limit stop is located from
3.1.4 left leg of piping segment
The distance at which new limit stop is located from
3.1.5 right leg of piping segment
3.2
SECOND EXPANSION LOOP LOCATION
The maximum distance at which right leg of second
expansion loop shall be located from right end limit
stop of piping segment to restrict the expansion of
3.2.1 right leg within the requirement
The actual distance at which new limit stop is
3.2.2 located from left leg of second expansion loop
The actual expansion of left leg of second expansion
loop due to new limit stop used to restrict the right
3.2.3 leg of first expansion loop
3.2.4 Third Expansion Loop Required or not
300
A106 Gr.B
300
4
600
100
m
Deg C
mm/m
mm
mm
EXPANSION LOOP
REQUIRED
(L/2)*
Project Specific Requirement
If >', then expansion loop is required
ION LOOP
25
(It is the max. distance at which limit stop/anchor
shall be located from each end of straight pipe
segment)
22
L'' shall be less than L'
hence expansion loop is required to add flexibility. Preferiably at centre of piping segment.
4
(Generally, width shall be 3m or 4m)
504
mm
((L/2)-L''-(W/2))*
150
mm
Project Specific Requirement
SECOND EXPANSION
LOOP IS REQUIRED
If
NSION LOOP
valid, hence start from first to determine the distance at which first and
37.5
37.5
37
100.5
199.5
37.5
136
544
mm
THIRD EXPANSION
LOOP IS REQUIRED
It shall be less than the value mentioned in 3.2