Diesel Generator Set
B3.3 Series
Specification Sheet
50-62.5 kVA, 40-50 kWe Prime
Latest Technology And Unmatched
Performance
Lowest Operating Cost And
Comprehensive Warranty
The Cummins B3.3 series rugged engine and world
class Stamford alternator powered diesel generator set
Advanced in-cylinder technology to meet latest
emission norms without any after-treatment device.
Smart aesthetic and superior finish
Compact in size with optimum power to weight ratio
Highly reliable and durable product
All elements are designed to work together to
maximize efficiency even at part loads, offering the
advantage of lowest operating costs.
500 Hours/ 1 year service interval
Industry acknowledged best-in-class comprehensive
warranty on the entire package including rubber
components
Environment Friendly Power
Class defining technology engine is designed to meet
stringent exhaust emission tests as per revised MoEF
norms, thus offering environment friendly power.
The Cummins diesel generator sets are available with
the lowest noise levels in its range
Single Source Power Assurance
All the major components the engine, alternator,
control system and canopy are designed,
manufactured and tested by Cummins India.
Best and Largest customer support network in India,
capable of providing round-the-clock service and
spares support
All these things put together, Cummins offers you
SINGLE SOURCE POWER ASSURANCE
Diesel Generator Set B3.3 Series
Engine
Cummins B3.3 series, 4 cylinder, In-line 4 stroke, radiator
cooled engine
Well designed air handling system with
Dry type, heavy duty, replaceable paper element air
cleaner with restriction indicator
Air to air aftercooling
Optimised turbocharger for increased altitude
capabilities
Best in class fuel economy with
Inline fuel pump with A1 class mechanical governing
Spin on fuel filter
Standard integral set-mounted radiator system, designed
and tested for 50C ambient temperature
Full flow spin on lube oil filter
First fill of lube oil and coolant
Electrical starter motor with soft start engagement feature
Battery charging alternator
1 x 12 V DC battery
Specification Sheet
PS0500 Features
Cummins PowerStart
PS0500 control is a
microprocessor based
generator set monitoring and
control system. This control
includes an intuitive operator
interface that allows for
complete generator set
control as well as system metering, fault annunciation,
configuration and diagnostics.
Intuitive operator interface which includes LED backlit LCD
display with tactile feel soft-switches & generator set status
LED lamps
Remote Start-Stop
Engine Metering: Oil pressure, Engine temperature, Starting
battery voltage, Engine running hours
AC Alternator Metering: L-L Voltage and L-N Voltage,
Current (phase and total), kVA (phase and total) and
Frequency.
Engine Protection: Low lube oil pressure, High/Low Coolant
temperature, Battery Over/Under/Weak Volts, Fail to Crank/
Start, Sensor failure, Cranking lockout, Low fuel level.
AC Alternator Protection: Over/Under Voltage, Over/Under
Frequency, Loss of AC sensing.
Data Logging: Engine Hours, Control Hours and upto 5
recent fault codes
Configurable glow plug control
12 Volt DC operation
Sleep mode
Modbus interface (RS485 RTU)
InPower Compatible (PC based service tool)
Certifications - meets the requirement of relevant ISO, EN,
Mil Std. and CE standards
Alternator
Silencer
Stamford UC22 alternator frames from Cummins Generator
Technologies
Brushless type, Screen protected, Revolving field, Self
excited alternator conforming to IS/IEC 60034-1
3 Phase reconnectable winding with 12 terminals brought
out for connection
Dedicated winding specially designed for 1 phase operation
Better motor starting capability
Best in class efficiency
Compact design with sealed bearings for longer life and
lesser maintenance
Impregnation on all wound components for better
mechanical strength
Critical grade silencer suitably optimized to meet stringent
noise emission standards laid down by MoEF / CPCB
Control Panel
Control panel is manufactured with 14/16 gauge CRCA sheet
and is powder coated for weather-proof and long lasting finish.
The control panel consists of the following parts:
PS0500 Controller
Aluminum bus bars with suitable capacity with incoming/
outgoing terminals
Indicating lamps for Load ON and Set Running
Instrument fuses duly wired and ferruled
MCCB of suitable rating with overload and short circuit
protections
Mounting Arrangement
Engine and alternator are mounted on a common MS
fabricated base frame with AVM pads.
Base frame with integral fuel tank is provided with drain
plug, air vent, inlet and outlet connection, level indicator and
provision for cleaning
Optional
Engine: Coolant heater, Oil drain pump, Electronic
governing
Alternator: PMG
Control Panel: Microprocessor / relay based AMF control
panel
Others: Trolley mounted mobile sets
Diesel Generator Set B3.3 Series
Acoustic Enclosure
Specially designed to meet stringent MoEF/ CPCB norms of
75 dBA @ 1mtr at 75% load under free field conditions
The acoustic enclosure is made of CRCA sheets in Munsel
green shade and a structural/ sheet metal base frame
painted in black.
High quality noise absorbant and fire-retardant grade
acoustic insulation material (P.U. Foam) complying to IS
8183
Two point lifting for easy handling at customer site
Specification Sheet
Designed to have optimum serviceability
Air inlet louvers specially designed to operate at rated load
Made on special purpose CNC machines for consistency in
quality and workmanship
11 tank pretreatment process and UV resistant powder
coating of all parts to withstand extreme environment
Use of special hardware for longer life
Flush styling - no projections
Fluid drains for lube oil and fuel
Fuel filling arrangement inside the enclosure
Technical Data
Generator Set Specification
Model
Duty
Power Rating kVA / kWe
No. of Phases
Output Voltage (V)
Power Factor
Current (3 phase/ 1 phase) (A)
Frequency (Hz) and RPM
Engine Specification
Make
Model
MoEF Certified Power (hp)
Required Power for Rated kVA (hp)
Cooling
Aspiration
No. of cylinders
Bore (mm) x Stroke (mm)
Compression ratio
Displacement (litre)
Fuel
Fuel consumption @75% load with radiator and fan* (litre/hr)
Fuel consumption @100% load with radiator and fan* (litre/hr)
Performance class of generator set
Starting system
Lube oil specification
Lube oil sump capacity, High-Low level (litre)
Total lubrication system capacity (litre)
Lube oil consumption @ full load** (litre/hr)
Total coolant capacity (litre)
Exhaust pipe size (inch)
Total wet weight (Engine+Radiator)## (kg)
Length x Width x Height (Engine) (mm)
Mean piston speed (m/s)
Combustion air intake @100% load (5%) (cfm)
Exhaust Temperature (C)
Alternator Specification
Make
Alternator frame
Enclosure
Voltage regulation (Max.)
Class of Insulation
Winding Pitch
Stator Winding
Rotor
Waveform distortion/ Total Harmonic Distortion
Maximum Unbalanced Load across phases#
Telephonic Harmonic factor
C50D5P
Prime
50/40
3 Phase
415 V
0.8 (lagging)
70
50 Hz, 1500 RPM
1 Phase
230 V
1
217
C62.5D5P
Prime
62.5/50
3 Phase
415 V
0.8 (lagging)
87
50 Hz, 1500 RPM
1 Phase
230 V
1
272
Cummins
4BTAA3.3-G11
84
66
Liquid Cooled (EG Compleat 50:50)
Turbocharged, Charge Air Cooled
4
95 x 115
17.3:1
3.3
High Speed Diesel
9.6
12.44
ISO 8528-5 G2
12 V DC Electrical
CI4+ 15W40
7 - 5.5
7.9
0.01
13
3
375
784 x 973 x 870
5.75
160
490
Cummins
4BTAA3.3-G11
84
81
Liquid Cooled (EG Compleat 50:50)
Turbocharged, Charge Air Cooled
4
95 x 115
17.3:1
3.3
High Speed Diesel
11.53
15.31
ISO 8528-5 G2
12 V DC Electrical
CI4+ 15W40
7 - 5.5
7.9
0.01
13
3
375
784 x 973 x 870
5.75
160
490
Stamford (CGT)
UCI224D
UCI224F
IP23
1%
H Class
2/3
Double layer lap
Dynamically Balanced
No load < 1.5 %, Non distorting
balanced linear load < 5 %
less than or equal to 25%
< 2%
Stamford (CGT)
UCI224 V
UCI224 G
IP23
1%
H Class
2/3
Double layer lap
Dynamically Balanced
No load < 1.5 %, Non distorting
balanced linear load < 5 %
less than or equal to 25%
< 2%
* Fuel consumption data is based on diesel having specific gravity of 0.85 and conforming to IS:1460. Fuel consumption tolerance is +5%
*Oil consumption data is based on oil having specific gravity of 0.89 and meeting CI4+ API categories
#
With the condition that none of the phases exceeds its rated current
Diesel Generator Set B3.3 Series
Specification Sheet
Rating Definitions
Conformance Standards
Prime Power (PRP):
Applicable for supplying power to varying electrical load for
unlimited hours. Prime Power (PRP) is in accordance with ISO
8528.
IS/IEC 60034-1
ISO 3046
IS 1460
ISO 9001
ISO 8528
IS 13018
Typical Enclosed Genset Dimensions
Genset
Model
Rating
(kVA)
Length
(mm)
Width
(mm)
Height
(mm)
Wet Weight##
(kg)
Standard Fuel tank
Capacity (litre)
C50D5P
50
2950
1150
1550
1470
110
C62.5D5P
62.5
2950
1150
1550
1470
110
##
Approximate Weight
Authorised Representative
Cummins Power Generation Offices
Bengaluru:
Chandigarh:
Chennai:
Gurgaon:
Hyderabad:
Jaipur:
Kolkata:
Lucknow:
Mohali:
Vadodara:
Tel.: (080) 2325 9161 / 63, 2325 9165 / 67
Fax: (080) 2325 9164
Tel.: (0172) 224 0371-73
Fax: (0172) 224 0372
Tel.: (044) 2446 8110 / 2446 8113
Fax: (044) 2491 1120
Tel.: (0124) 391 0900-01
Fax : (0124) 391 0916
Tel.: (040) 2340 9970 / 2340 9980
Fax. (040) 2340 9990
Tel.: (0141) 236 4944
Fax: (0141) 403 8794
Tel.: (033) 2287 8065 / 2287 2481
Fax: (033) 2290 3839
Tel.: (0522) 230 5049 / 230 5059
Fax: (0522) 230 5035
Tel.: (0172) 224 0371 / 72 / 73
Fax: (0172) 224 0371 / 72 / 73
Tel.: (0265) 233 0627 / 3053627
Fax: (0265) 234 0623
Visit our facebook page at :
Cummins Power Generation India
Our energy working for you.
2014 Cummins Power Generation Inc. All rights reserved.
Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand, AmpSentry, InPower and are trademarks of Cummins Power Generation.
Other company product or service names may be trademarks or service marks of others.
Specifications are subject to change without notice.
PGBU/CIL/010/B3.3 50-62.5 kVA/CPG/VW/July 2014/1000
Cummins India Limited
Power Generation Business Unit
Cummins India Office Campus
Tower-A, 6th Floor, S. No. 21,
Balewadi, Pune 411 045 (India)
Phone: +91 20 6706 7000
Email: cpgindia@[Link]
[Link]