ARTIFICIAL INTELLIGENCE
TEMPERATURE CONTROLLER
AI-208
(V7.6)
User Manual
I. Model Code Symbol
The type of AI-208 is made up of 4 parts:
AI-208
L2
Part 1 (series)
Part 2 (Size)
Part 3 (Oupt)
Part 4 (AUX)
I. Model Code Symbol
1. (Part 1) Basal function of instrument
AI-208, standard temperature controller 0.3%FS1
Multiple thermocouples and RTDs are selectable
Suit for 0~999 application. Maximum support two alarms contact output
Universal voltage input (100~240VAC)
ISO9001 certification and CE certified, achieving word class level of quality, anti-interference
ability and safety
2. (Part 2) Front panel dimension
Front Panel
Cut Out
widthheight
widthheight
9696mm
9292mm
100mm
16080mm
76152mm
100mm
7272mm
6868mm
95mm
D2
4848mm
4545mm
95mm
4896mm
4592mm
100mm
9648mm
9245mm
100mm
Size
Depth Behind Mounting Surface
3. (Part 3 and 4) indicate the module installed in OUTP and AUX sockets.
Allowed modules in each socket are as below:
Allowed Type
L1
L5
Module Socket
3. OUTP (main output)
4. AUX (Auxiliary output)
(or none) no module installed
Relay contact output module (Capacity: 5A/250VAC and 5A/30VDC, normal open terminal can
absorb spark)
L1
Relay contact output module (Capacity: 2A/250VAC, small volume)
L5
Output module of dual normal open relay contact (Capacity: 2A/250VAC, support AL1 and AL2
alarm output)
SSR voltage output module (30mA/5VDC)
II. TECHNICAL SPECIFICATION
1. Input type :
Thermocouple: K, E, J, N
Resistance temperature Detector: Pt100
2. Instrument Input range :
K, E, J, N : (0~+999) ;
Pt100: (0~+800)
3. Measurement accuracy : 0.3%FS1
4. Temperature display resolution : 1
5. Control mode:
On-off control mode
AI artificial intelligence control, including fuzzy logic PID control and advanced control algorithm with
the function of parameter auto tuning.
6. Alarm function: High limit alarm, Lower limit alarm, Deviation High Alarm.
7. Power supply voltage rating: 100-240VAC, -15%, +10% / 50-60Hz.
8. Power consumption: 2W
9. Ambient temperature: -10~+60, Humidity: 0~90RH%
III. FRONT PANEL AND OPERATION
Process Value(PV), or parameter code
Set Value(SV), alarming code, or value of a parameter
PV
Setup key, for accessing parameter table, and confirming change.
Data shift key, also for activating auto turning
Data decrease key
Data increase key
Status display LED
SV
OP1
Basal display status:
AU1
AU2
RUN
When power on, will shows the process value (PV),shows the set point (SV).
lf the input signal is out of the measurable range (for example, the thermocouple
or RTD circuit is break, or input specification sets wrong),
Will alternately display orA and the high limit or the low limit of PV,
RUN
AT
and the instrument will automatically stop output.
STOP
AI
IV. OPERATION DESCRIPTION
Set Value Setting:
In basal display status, if the parameter lock Loc isn't locked,
key to decrease the value,
pressing
SPH.
or
Press
key to move to the digit expected to modify.
Keep
we can set setpoint (SV) by pressing
key to increase the value, and
, the speed of decreasing or inscreasing value get quick.
The range of setpoint is between the parameter
The default range is 0 to 400.
Parameter Setting:
In basal display status, press
next parameter; pressing
parameter. Press
and hold for about 2 seconds can access Field Parameter Table.
or
can modify a parameter.
(don't release) and then press
Press and hold
Pressing
press
can go to the
can return to the preceding
key simultaneously can escape from the parameter table. The
instrument will escape auomatically from the parameter table if no key is pressed within 30 seconds.
or
Setting Loc=808 and then
can access System Parameter Table.
AI artificial intelligence control and auto tuning
When AI artificial intelligence control method is chosen (CrL=AI), the PID parameters can be obtained by running auto-tuning.
basal display status, press
to on, then press
for 2 seconds, the At parameter will appear.
to active the auto-tuning process.
Press
During auto tuning, the instrument executes on-off control.
times of on-off action, the instrument will obtain the optimal control parameter value.
press and hold the
In
to change the value of At from oFF
After 2-3
If you want to escape from auto tuning status,
key for about 2 seconds until the "At" parameter appear again.
Change At from on to oFF, press
to
confirm, then the auto tuning process will be cancelled.
Note 1:
If the setpoint is different, the parameters obtained from auto-tuning are possible different.
often-used value or middle value first, and then start auto-tuning.
be set at the highest applicable temperature.
So youd better set setpoint to an
For the ovens with good heat preservation, the setpoint can
Depending on the system, the auto-tuning time can be from several seconds to
several hours.
Note 2:
Parameter Ctl (on-off differential, control hysteresis) has influence on the accuracy of auto-tuning.
value of Ctl, the higher the precision of auto tuning.
from error action around setpoint due to the oscillation of input.
Note 3:
Generally, the smaller the
But Ctl parameter value should be large enough to prevent the instrument
AI series instrument has the function of self-learning.
Ctl is recommended to be 2.0.
It is able to learn the process while working.
The control effect at the
first run after auto tuning is probably not perfect, but excellent control result will be obtained after a period of time because of
self-learning.
V. PARAMETER AND SETTING
Field parameter table (Press
Code
Name
HIA
High limit alarm
LoA
Lower Limit
alarm
HdA
and hold for 2 seconds to access)
Deviation high
alarm
Loc
Parameter Lock
AHY
Hysteresis
Description
0999
0999
Alarm on when PV-SV>HdA;
alarm off when PV-SV<HdA-AHY
0999
Loc=0~1: Allowed to modify parameters HIA, LoA, HdA and SV.
Loc=2~3: Allowed to modify parameters HIA, LoA, HdA. But cannot
change SV.
Loc=4~255: NOT allowed to modify any parameters and SV.
Loc=808, Set to 808 and press
, allowed modify all parameters.
Avoid frequent alarm on-off action because of the fluctuation of PV,
usually sets to AHY=2
Alarm
HdA
LoA
HIA
(x100)
(x10)
(x1)
None
AU1
AU2
Output to
AOP
Setting Range
Alarm on when PV (Process Value) >HIA;
alarm off when PV<HIA-AHY
Alarm on when PV (Process Value) < LoA;
alarm off when PV > LoA+AHY
Alarm output
assignment
0255
0~200
0~444
eg: AOP=201 means HdA have alarm action from AU2, LoA, no alarm
action , HIA alarm action output from AU1.
z
onF : On-off control, When PV=SV, Output stop. When
PV<SV-CHY, start output.
AI : AI PID control, high precision and no-overshoot,
CrL
Control mode
Proportion band
Proportion band in PID with unit
Time of Integral
Time of Integral in PID. No integral effect when I=0
0~999 Sec
Time of
Derivative
Time of Derivative in PID. No derivative effect when d=0
0~999 Sec
Ctl
Control period
CHY
Control
Hysteresis
InP
Input
specification
Scb
Input Shift
1~999
Small value can improve control accuracy.
For SSR output, generally 0.5 to 3 seconds.
For Relay output, generally 15 to 40 seconds, because small value will
cause the frequent On-Off of mechanical switch and shorten its service
life. Ctl is recommended to be 1/4 1/10 of derivative time. When
control under on-off control, Ctl use as restart delay time after off, for
protect compressor application.
CHY is used for ON-OFF Control.
PV > SV, Output turns OFF;
PV<SV-CHY, Output turns ON.
Sn
0
4
6
8-20
Input spec.
K
E
Spare
Spare
0.5-300 SEC
0~200
Sn
1-3
5
7
21
Input spec.
Spare
J
N
Pt100
Scb is used to make input shift to compensate the error produced by
sensor or input signal.
PV after compensation= PV before compensation + Scb.
021
-99+99
FIL
PV input filter
Fru
Selection of
power frequency
and temperature
scale
The value of FIL will determine the ability of filtering noise.
When a large value is set, the measurement input is stabilized but the
response speed is slow. Generally, it can be set to 1 to 3.
If great interference exists, then you can increase parameter FIL
gradually to make momentary fluctuation of measured value less than
2 to 5.
When the instrument is being metrological verified, FIL s can be set
to 0 or 1 to shorten the response time.
040
50C: 50Hz,
50F: 50Hz,
60C: 60Hz,
60F: 60Hz,
SPH
Upper limit of SV
Maximum value that SV allowed to be. When SPH=400, the SV range
will 0~400
VI. INSTRUMENT INSTALLATION AND WIRING
Wiring graph for instruments with dimension A, B, E or F
1
100-240VAC~
2
3
Alarm Output
N/O N/O AU1
N/C N/O AU2
COM COM
5
6
Main Output
AUX
N/O
COM
Note: The graph suits for
upright instruments with
dimension A or E
8
9
10
For
instruments
with
dimension B or F size, just
clockwise rotate the graph
90 degree.
0999
Wiring graph for D2 dimension48X48mminstruments
COM
100-240VAC~
6
Main Output
N/O
OUTP
3
Alarm
Output
N/O N/O AU1
N/C N/O AU2
8
9
COM COM
AUX
10