5282 2/2-way Solenoid Valve
with servo diaphragm
Pivoted armature pilot drive with emergency
manual operation
Media separated
Circuit function can be modied
Adjustable switching times
(waterhammer-free)
Type 5282 can be combined with... Threaded port or ange connections
Approvals: FM
Type 2508 Type 1078 Type 2511 Type 8600
Cable plug Timer unit ASI cable plug Dosing control
The Type 5282 is a pilot-controlled normally closed Technical data
solenoid valve with a servo-diaphragm, media
Orice 1/2 - 2 (DN 13 - 65 mm)
separated, for universal use with liquid and gaseous
Body material
media corresponding to the material resistance.
Threaded port Brass, stainless steel 1.4581
As standard, the 3-way pivoted armature pilot drive
Flange Stainless steel 1.4541
has an emergency manual operation. The closing and
Seal material NBR, FKM, EPDM (on request)
opening times are continuously adjustable.
Media
NBR Neutral media, such as compressed air, water, hydraulic oil
EPDM Oil and fat-free media, incl. alkalis, hot water
FKM Hot air, oxygen, per-solutions, hot oil
Media temperature
Power consumption NBR 14F to 194F (-10C to +90C)
Inrush Hold EPDM -22F to 194F (-30C to +90C)
AC AC DC FKM 32F to 194F (0C to +90C)
[VA] [VA/W] [W] Ambient temperature Max. 131F (+55C)
24 14/8 8 Voltage tolerance 10%
A differential pressure of 7 PSI (0.5 bar) is required Duty cycle 100% continuous rating
to open the full orice. The response times can be Electrical connection Tag connector acc. DIN 43650 Form A for
changed by turning the restrictor screws (in the cable plug Type 2508
body cover). Protection class IP 65 with cable plug
Installation As required, preferably with actuator upright
* See our HazEx guide for ATEX and for FM Class 1, Div. 1 versions
[Link] Page 1/4
5282
Solenoid valve dimensions
Dimensions [mm]
Threaded port Flange port
DN D B1 E1 F L1 B2 G L2
13 NPT 1/2 123.0 40 14 65
20 NPT 3/4 131.0 60 16 100
25 NPT 1 141.0 70 18 115 184.5 120 160
32 NPT 1 1/4 147.0 85 20 126 192.0 140 180
40 NPT 1 1/2 156.0 85 22 126 201.0 150 200
50 NPT 2 177.5 115 24 164 225.0 165 230
Threaded port
65 NPT 2 1/2 185.0 115 27 180
Ordering chart for valves (other versions on request) UL recognized / CSA/ CE
Manual override, supplied without cable plug, different seal materials on request
Seal Brass Body
Port connection
Circuit function
Stainless Steel
Cv value water
Seal material
Seal material
Orifice [mm]
frequency
FKM Seal
pressure
Voltage/
Nominal
Item no.
Item no.
[V/Hz]
[GPM]
[NPT]
Body
NBR
[psi]
A 2/2-way valve, NC 13.0 NPT 1/2 4.7 2.8 - 145 024/DC 456 890 456 914
(Brass) 024/50-60 456 891 456 915
20.0 120/50-60 456 892 456 916
(Stainless steel) 240/50-60 456 893 456 917
or 20.0 NPT 3/4 5.8 2.8 - 145 024/DC 456 894 456 918
024/50-60 456 895 456 919
B 2/2-way valve, NO 120/50-60 456 896 456 920
240/50-60 456 897 456 921
25.0 NPT 1 11.7 2.8 - 145 024/DC 456 898 456 922
024/50-60 456 899 456 923
120/50-60 456 900 456 924
240/50-60 456 901 456 925
32.0 NPT 1 1/4 23.5 2.8 - 145 024/DC 456 902 456 926
024/50-60 456 903 456 927
120/50-60 456 904 456 928
240/50-60 456 905 456 929
40.0 NPT 1 1/2 23.5 2.8 - 145 024/DC 456 906 456 930
024/50-60 456 907 456 931
120/50-60 456 908 56 932
240/50-60 456 909 456 933
50.0 NPT 2 47.0 2.8 - 145 024/DC 456 910 456 934
024/50-60 456 911 456 935
120/50-60 456 912 456 936
240/50-60 456 913 456 937
Delivered as circuit function A
Change to the circuit function B by turning the pilot drive through 180
Mounting instructions:
Circuit function B Circuit function A
Arrangement of the pilot control
Flow direction Flow direction
Page 2/4
5282
Solenoid valve ordering chart
Ordering chart for valves (other versions on request) UL listed / FM class / Division 2 / CSA / CE
Manual override, supplied with cable plug type 2509, different seal materials on request
Port connection
Circuit function
Stainless Steel
Cv value water
Threaded port
Threaded port
Orifice [mm]
frequency
Pressure
Voltage/
Item no.
Item no.
[V/Hz]
[GPM]
range
Brass
[NPT]
FKM
NBR
[psi]
A 2/2-way valve NC 13.0 NPT 1/2 4.7 2.8 - 145 024/DC 457 870 457 894
(Brass) 024/50-60 457 871 457 895
20.0 120/50-60 457 872 457 896
(Stainless steel) 240/50-60 457 873 457 897
or 20.0 NPT 3/4 5.8 2.8 - 145 024/DC 457 874 457 898
024/50-60 457 875 457 899
B 2/2-way valve NO 120/50-60 457 876 457 900
240/50-60 457 877 457 901
25.0 NPT 1 11.7 2.8 - 145 024/DC 457 878 457 902
024/50-60 457 879 457 903
120/50-60 457 880 457 904
240/50-60 457 881 457 905
32.0 NPT 1 1/4 23.5 2.8 - 145 024/DC 457 882 457 906
024/50-60 457 883 457 907
120/50-60 457 884 457 908
240/50-60 457 885 457 909
40.0 NPT 1 1/2 23.5 2.8 - 145 024/DC 457 886 457 910
024/50-60 457 887 457 911
120/50-60 457 888 457 912
240/50-60 457 889 457 913
50.0 NPT 2 47.0 2.8 - 145 024/DC 457 890 457 914
024/50-60 457 891 457 915
120/50-60 457 892 457 916
240/50-60 457 893 457 917
Delivered as circuit function A
Change to circuit function B by turning the pilot drive through 180.
NOTE: All UL listed valves include type 2509 1/2 conduit cable plug
Type 2509 Dimensions [mm]
0.71
2
1.28
1.10
0.71
2.32
1.28
NPT 1/2
1.02
0.04
M3
Torque 0.74 ft-lb
0.17
1.10
without circuitry
Page 3/4
5282
In case of special application conditions, We reserve the right to make technical 0602/2_US-en
please consult for advice. changes without notice.
Page 4/4