BTS 3900 External Alarms Patching through EMUB
BTS 3900 External Alarms patching
Wi-Tribe LTE Project
Huawei Technologies Co., Ltd.
By
Mohammed Usman Ali
2018-01-16 HUAWEI Technologies Page1, Total11
BTS 3900 External Alarms Patching through EMUB
Table of Contents
1. BTS 3900 External Alarm types .......................................................................................................... 3
1.1. Sensor Alarms .................................................................................................................................. 3
1.2. Dry Contact Alarms ......................................................................................................................... 3
2. BTS 3900 External Alarms Patching ................................................................................................... 4
3. EMUB ports for Sensor Alarms: .......................................................................................................... 6
4. EMUB ports for Dry Contact Alarms: ................................................................................................. 7
5. Dry contact alarm patching on EMUB:................................................................................................ 8
6. Configuring the External Alarms on Huawei BTS 3900: .................................................................. 11
2018-01-16 HUAWEI Technologies Page2, Total11
BTS 3900 External Alarms Patching through EMUB
1. BTS 3900 External Alarm types
There are 2 major types of alarms
Sensor alarms
Dry contact alarms
1.1. Sensor Alarms
There are four basic types of sensor alarms:
Temperature & Humidity
Smoke
Water
Door
1.2. Dry Contact Alarms
Following dry contact alarms would be integrated with BTS 3900:
Commercial Power Failure
Rectifier Input Failure
DC Low Voltage
Generator Running
Generator Failure
2018-01-16 HUAWEI Technologies Page3, Total11
BTS 3900 External Alarms Patching through EMUB
2. BTS 3900 External Alarms Patching
All external alarms would be patched on EMUB board, which is installed at all sites:
Firstly, power on the EMU board by connecting the DC power cable with DCDU:
2018-01-16 HUAWEI Technologies Page4, Total11
BTS 3900 External Alarms Patching through EMUB
Now, connect the RS-485 serial port of EMU with MON-0 port of UPEU as per following diagram:
After the BBU is powered up and connected with BBU, we are ready to patch alarms on EMU as per below
mentioned diagram:
2018-01-16 HUAWEI Technologies Page5, Total11
BTS 3900 External Alarms Patching through EMUB
3. EMUB ports for Sensor Alarms:
Sensor alarms can be patched on the designated ports on EMUB:
Following is an example of sensor alarm patching on EMUB:
2018-01-16 HUAWEI Technologies Page6, Total11
BTS 3900 External Alarms Patching through EMUB
4. EMUB ports for Dry Contact Alarms:
The dry contact alarms can be patched on the slots S1 to S32 of EMUB:
We would be using the EMUB ports for dry contact alarms in accordance with the following table:
Alarm Name EMUB Ports
Commercial Power Failure S1
Rectifier Input Failure S2
DC Low Voltage S3
Generator Running S5
Generator Failure S6
Door Alarm S7
2018-01-16 HUAWEI Technologies Page7, Total11
BTS 3900 External Alarms Patching through EMUB
5. Dry contact alarm patching on EMUB:
Use two separate CAT-6 cables for upper and below patched alarms on EMUB. Following is an
example of dry contact alarm patching on EMUB:
Connect the other end of alarm cables at slot S1, S2 & S3 on the Wi-Tribe ELTEK Rectifier Unit as
per blow mentioned table:
Alarm EMUB Ports Eltek-Rectifier Alarms ports
Commercial Power Failure S1 8 & 9 (Block 1)
Rectifier Input Failure S2 9 & 10 (Block 2)
DC Low Voltage S3 15 & 16 (Block 2)
Use CAT-6 cable for connectivity between EMUB and Eltek Recifier, while following the below
mentioned color code:
EMUB Port Color Coding Rectifier Port Color Coding
S1 + ORANGE 8 (Block 1) WHITE ORANGE
S1 - WHITE ORANGE 9 (Block 1) ORANGE
S2 + GREEN 9 (Block 2) WHITE GREEN
S2- WHITE GREEN 10 (Block 2) GREEN
S3 + WHITE BLUE 15 (Block 2) WHITE BLUE
S3 - BLUE 15 (Block 2) BLUE
2018-01-16 HUAWEI Technologies Page8, Total11
BTS 3900 External Alarms Patching through EMUB
Following is the example of alarm cable connectivity at Eltek rectifier:
Connect the other end of alarm cables at slot S5, S6 & S7 on the Wi-Tribe BCU as per blow
mentioned table:
Alarm EMUB Ports Wi-Tribe BTS Alarms ports
Generator Running S5 7 & 8 (Customer Input 5-8)
Generator Failure S6 5 & 6 (Customer Input 5-8)
Door Alarm S7 1 & 2 (Customer input 13-16)
Use CAT-6 cable for connectivity between EMUB and Wi-Tribe BTS, while following the below
mentioned color code:
EMUB Port Color Coding Wi-Tribe BTS Color Coding
S5+ WHITE ORANGE 7 (Customer Input 5-8) WHITE ORANGE
S5 - ORANGE 8 (Customer Input 5-8) ORANGE
S6+ WHITE GREEN 5 (Customer Input 5-8) WHITE GREEN
S6 - GREEN 6 (Customer Input 5-8) GREEN
S7+ WHITE BLUE 1 (Customer input 13-16) WHITE BLUE
S7 - BLUE 2 (Customer input 13-16) BLUE
2018-01-16 HUAWEI Technologies Page9, Total11
BTS 3900 External Alarms Patching through EMUB
Customer Input 13-16 on Wi-tribe BTS
Customer Input 5-8 on Wi-tribe BTS
2018-01-16 HUAWEI Technologies Page10, Total11
BTS 3900 External Alarms Patching through EMUB
6. Configuring the External Alarms on Huawei BTS 3900:
Use the following MML command to configure the sensor alarms on Huawei BTS 3900:
ADD EMU:MPN=0,SAAF=48V_DISABLE-1,SBAF=IS_DISABLE-1&GS_DISABLE-1;
Use the following MML command to configure the dry contact alarms on Huawei BTS 3900:
SET ALMPORT:CN=0,SRN=40,SN=0,PN=X,SW=ON,AID=XXXXX,PT=BOOL,AVOL=HIGH
Where Port Number can vary from 0 to 39 and Alarm ID can vary from 65033 to 65233.