NGT & NGR Sizing Calculation

1) The document provides calculations to size the neutral grounding transformer and neutral grounding resistor for a power plant project with two 300 MW units. 2) It calculates the necessary kVA rating of the neutral grounding transformer to be 55 kVA based on the total charging current under field forcing conditions. 3) It also calculates the necessary resistance value of the neutral grounding resistor to be 0.222 ohms based on the transformer parameters and required current in the secondary of the neutral grounding transformer.

Uploaded by

jigyesh sharma
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views4 pages

NGT & NGR Sizing Calculation

1) The document provides calculations to size the neutral grounding transformer and neutral grounding resistor for a power plant project with two 300 MW units. 2) It calculates the necessary kVA rating of the neutral grounding transformer to be 55 kVA based on the total charging current under field forcing conditions. 3) It also calculates the necessary resistance value of the neutral grounding resistor to be 0.222 ohms based on the transformer parameters and required current in the secondary of the neutral grounding transformer.

Uploaded by

jigyesh sharma
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Project:2 X 300 MW Annexure-I Doc. No.

:EAP22401
(UNITS 1and 2) Calculation for NGT & NGR sizing Rev . No.: A
PATHADI TPS Date:.28.09.05
Project No.:T365000

Sizing of neutral grounding transformer and neutral grounding resistor for STG

1. Calculation for sizing of neutral grounding transformer


Input data:

Capacitance of generator winding C1 := 0.225 micro Farad

Capacitance of busduct C2 := 0.06 micro Farad

Capacitance of generator transformer LV winding C3 := 0.004 micro Farad

Surge capacitor in PT cubicle C4 := 0.25 micro Farad

Calculation :

Total capacitance C := C1 + C2 + C3 + C4

C = 0.539 micro Farad

1
Capacitive reactance Xc :=
2 ⋅ π ⋅ 50 ⋅ C ⋅ 10− 6

Xc = 5.905564 × 103 ohms

Normal voltage of generator (line to line) V1 := 20000 V

V1
Normal phase to neutral voltage Vp1 :=
3

Vp1 = 1.154701 × 104 V

Vp1
Charging current per phase IC1 :=
Xc

IC1 = 1.955276 A

Total charging current IC := 3 ⋅ IC1

IC = 5.865827 A

The primary winding Voltage has been considered same as line to line voltage.

Neutral Grounding Transformer selected Primary Rating = 20000 V.

Total charging current under field forcing conditions ICf := IC ⋅ 1.3

ICf = 7.625575 A

ICf
kVA rating of Neutral Grounding Transformer : kVA := V1 ⋅
1000

kVA = 152.511506
Page 1 of 4
Project:2 X 300 MW Annexure-I Doc. No.:EAP22401
(UNITS 1and 2) Calculation for NGT & NGR sizing Rev . No.: A
PATHADI TPS Date:.28.09.05
Project No.:T365000
kVA = 152.511506

Since , incase of Earth fault, unit will be tripped with in a Short time , Say 5 minute

Over load factor for 5 minute duty = 2.8

Neutral Grounding Transformer kVA rating( based on 5 min. duty cycle)

kVA
Sa :=
2.8
Sa = 54.468395

Nearest kVA of transformer selected = 55kVA

S := 55

NGT parameters :

kVA capacity of NGT : 55 kVA

Ratio : 20000/230V

Duty cycle : 5 minutes

2. Calculation for sizing of neutral grounding resistor

Primary voltage of NGT Vp := V1 V

Vp = 2 × 104
Secondary voltage of NGT Vs := 230 V

Vp
Transformer turns ratio N :=
Vs

N = 86.956522

For Resonance Grounding,

Ic = IL

3 x Vp/Xc =Vp/XL

Xc
XL :=
3

XL = 1.968521 × 103

Ohomic Value of the reactance w.r.t LV side=R

XL
R :=
2
N

R = 0.260337 ohms

Transformer Percentage impedance = Z

Z := 4%

Zpu := 0.04
Page 2 of 4
Project:2 X 300 MW Annexure-I Doc. No.:EAP22401
(UNITS 1and 2) Calculation for NGT & NGR sizing Rev . No.: A
PATHADI TPS Date:.28.09.05
Project No.:T365000

Zpu := 0.04

Base Impedance w.r.t LV Side = Zb

Vs ⋅ Vs
Zb :=
S ⋅ 1000

Zb = 0.961818 ohm

Transformer impedance w.r.t LV Side = Zlv

Zlv := Zpu ⋅ Zb

Zlv = 0.038473 ohm

Ohomic value of the Netral grounding resistor = NGR

NGR := R − Zlv

NGR = 0.221864

Current in Secondary of NGT = Is


Is := ICf ⋅ N

Is = 663.093503 A

Current rating is selected as 665 A

NGR parameters :

The resistance value of NGR = 0.222 ohms

Current Rating = 665 A

Duty cycle : 5 minutes

Page 3 of 4
Project:2 X 300 MW Annexure-I Doc. No.:EAP22401
(UNITS 1and 2) Calculation for NGT & NGR sizing Rev . No.: A
PATHADI TPS Date:.28.09.05
Project No.:T365000

Page 4 of 4