Project:2 X 300 MW Annexure-I Doc. No.
:EAP22401
(UNITS 1and 2) Calculation for NGT & NGR sizing Rev . No.: A
PATHADI TPS Date:.28.09.05
Project No.:T365000
Sizing of neutral grounding transformer and neutral grounding resistor for STG
1. Calculation for sizing of neutral grounding transformer
Input data:
Capacitance of generator winding C1 := 0.225 micro Farad
Capacitance of busduct C2 := 0.06 micro Farad
Capacitance of generator transformer LV winding C3 := 0.004 micro Farad
Surge capacitor in PT cubicle C4 := 0.25 micro Farad
Calculation :
Total capacitance C := C1 + C2 + C3 + C4
C = 0.539 micro Farad
1
Capacitive reactance Xc :=
2 ⋅ π ⋅ 50 ⋅ C ⋅ 10− 6
Xc = 5.905564 × 103 ohms
Normal voltage of generator (line to line) V1 := 20000 V
V1
Normal phase to neutral voltage Vp1 :=
3
Vp1 = 1.154701 × 104 V
Vp1
Charging current per phase IC1 :=
Xc
IC1 = 1.955276 A
Total charging current IC := 3 ⋅ IC1
IC = 5.865827 A
The primary winding Voltage has been considered same as line to line voltage.
Neutral Grounding Transformer selected Primary Rating = 20000 V.
Total charging current under field forcing conditions ICf := IC ⋅ 1.3
ICf = 7.625575 A
ICf
kVA rating of Neutral Grounding Transformer : kVA := V1 ⋅
1000
kVA = 152.511506
Page 1 of 4
Project:2 X 300 MW Annexure-I Doc. No.:EAP22401
(UNITS 1and 2) Calculation for NGT & NGR sizing Rev . No.: A
PATHADI TPS Date:.28.09.05
Project No.:T365000
kVA = 152.511506
Since , incase of Earth fault, unit will be tripped with in a Short time , Say 5 minute
Over load factor for 5 minute duty = 2.8
Neutral Grounding Transformer kVA rating( based on 5 min. duty cycle)
kVA
Sa :=
2.8
Sa = 54.468395
Nearest kVA of transformer selected = 55kVA
S := 55
NGT parameters :
kVA capacity of NGT : 55 kVA
Ratio : 20000/230V
Duty cycle : 5 minutes
2. Calculation for sizing of neutral grounding resistor
Primary voltage of NGT Vp := V1 V
Vp = 2 × 104
Secondary voltage of NGT Vs := 230 V
Vp
Transformer turns ratio N :=
Vs
N = 86.956522
For Resonance Grounding,
Ic = IL
3 x Vp/Xc =Vp/XL
Xc
XL :=
3
XL = 1.968521 × 103
Ohomic Value of the reactance w.r.t LV side=R
XL
R :=
2
N
R = 0.260337 ohms
Transformer Percentage impedance = Z
Z := 4%
Zpu := 0.04
Page 2 of 4
Project:2 X 300 MW Annexure-I Doc. No.:EAP22401
(UNITS 1and 2) Calculation for NGT & NGR sizing Rev . No.: A
PATHADI TPS Date:.28.09.05
Project No.:T365000
Zpu := 0.04
Base Impedance w.r.t LV Side = Zb
Vs ⋅ Vs
Zb :=
S ⋅ 1000
Zb = 0.961818 ohm
Transformer impedance w.r.t LV Side = Zlv
Zlv := Zpu ⋅ Zb
Zlv = 0.038473 ohm
Ohomic value of the Netral grounding resistor = NGR
NGR := R − Zlv
NGR = 0.221864
Current in Secondary of NGT = Is
Is := ICf ⋅ N
Is = 663.093503 A
Current rating is selected as 665 A
NGR parameters :
The resistance value of NGR = 0.222 ohms
Current Rating = 665 A
Duty cycle : 5 minutes
Page 3 of 4
Project:2 X 300 MW Annexure-I Doc. No.:EAP22401
(UNITS 1and 2) Calculation for NGT & NGR sizing Rev . No.: A
PATHADI TPS Date:.28.09.05
Project No.:T365000
Page 4 of 4