CLIENT : NIGC PROJECT NO : 7905
PROJECT : Tabnak Gas Gathering & Treating Facilities DATED : 1/1/2002
S A Z E H
CONSULTANTS
SUBJECT : Oily Water Separator Calculation REV. : A
WASTE WATER PROPERTIES
QUANTITY UNIT QUANTITY SI UNIT
Flow Rate Qm 635.18 ft3/min 0.3 m3/sec
Ambient Temperature T 40 °f
Viscosity mw 0.0152 Cp
Waste Water Specific Gravity SW 1.00
Oil Specific Gavity So 0.70
Oil Particle Size dp 0.015 cm
RATE OF OIL PARTICLES' RISE
QUANTITY UNIT QUANTITY SI UNIT
Oil Rise Velocity Vt 0.48 ft/min 0.002 m/sec
HORIZONTAL FLOW VELOCITY
QUANTITY UNIT QUANTITY SI UNIT
Horizontal Velocity VH 3.0 ft/min 0.015 m/sec
MINIMUM HORIZONTAL AREA
QUANTITY UNIT QUANTITY SI UNIT
Turbulence & Short Circulation Factor F 1.39
Horizontal Area AH 1850.2 ft2 172.0 m2
MINIMUM VERTICAL CROSS - SECTIONAL AREA
QUANTITY UNIT QUANTITY SI UNIT
Vertical Area Ac 211.7 ft2 19.7 m2
MINIMUM CALCULATED LENGTH AND WIDTH
QUANTITY UNIT QUANTITY SI UNIT
Total Wide of Oily Water Separator B 46.1 ft 14.1 m
Minimum Required Length for Separator L 40.1 ft 12.2 m
Over Design Factor for Length f 60.0 % percent
NUMBER OF CHANNELS AND DIMENSION OF OILY WATER SEPARATOR
QUANTITY UNIT QUANTITY SI UNIT
Number of Channels n 3.0 3.0
Depth of Separator D 4.6 ft 1.4 m
Corrected wide for One Channel b 15.4 ft 4.7 m
Over Designed Length of Separator L 64.2 ft 19.6 m
REQUIRED TIME FOR RISE OF GLOBULES AND RETENTION TIME
QUANTITY SI UNIT
Calculated Rising Time for Globules t1 9.65 min
Retention Time Based on Oily Water Separator Volume t2 21.40 min
FINAL DATA QUANTITY SI UNIT
COLOR LEGEND Number of Channels 3.0
REQUIRED DATA Depth of Separator 1.4 m
CALCULATED DATA Wide of Separator 14.1 m
FINAL DATA Length of Separator 19.6 m
APPROVED BY : CHECKED BY : PREPARED BY :
SHEET 3 OF 3
P.KH R.M