0% found this document useful (0 votes)
339 views4 pages

Method Statement for 33kV Cable Testing

This document provides a method statement for 33kV power cable plug-in testing, relay testing, and cable stability work at the Jarziz project in Oman. It outlines the purpose, specifications, safety plan, responsibilities, tools, manpower, and procedures for the testing activities. The work includes identifying cables, supporting cables, performing hipot testing at 68kV for 15 minutes, testing relays and stability from the PSS end, and maintaining documentation records.

Uploaded by

kannanrk1984
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
339 views4 pages

Method Statement for 33kV Cable Testing

This document provides a method statement for 33kV power cable plug-in testing, relay testing, and cable stability work at the Jarziz project in Oman. It outlines the purpose, specifications, safety plan, responsibilities, tools, manpower, and procedures for the testing activities. The work includes identifying cables, supporting cables, performing hipot testing at 68kV for 15 minutes, testing relays and stability from the PSS end, and maintaining documentation records.

Uploaded by

kannanrk1984
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
  • Method Statement Overview
  • Project Information
  • Method Statement Details

Document Reference

PROJECT No.: DPC-DN-Z1B-2016-33 kV-3 JARZIZ/E/3015/A4


CONSTRUCTION OF 2X20 MVA, 33/11KV PSS DESIGNATED AS
Rev No 0
JARZIZ (DPC/TENDER/2016/201)
Rev Date 21.05.2017
PROJECT COMPANY DHOFAR POWER COMPANY
OWNER’S ENGINEER HAMED ENGINEERING SERVICES LLC
CONTRACTOR SHARIKAT FANNIYA OMANIYA LLC

METHOD OF STATEMENT

JARZIZ - ELECTRICAL WORKS

Prepared /Reviewed by SFO Approved by SFO Approved by HES


TITLE
Electrical Engineer Site Manager Electrical Engineer
NAME

SIGNATURE

DATE

Page 1
Document Reference
PROJECT No.: DPC-DN-Z1B-2016-33 kV-3 JARZIZ/E/3015/A4
CONSTRUCTION OF 2X20 MVA, 33/11KV PSS DESIGNATED AS
Rev No 0
JARZIZ (DPC/TENDER/2016/201)
Rev Date 21.05.2017
PROJECT COMPANY DHOFAR POWER COMPANY
OWNER’S ENGINEER HAMED ENGINEERING SERVICES LLC
CONTRACTOR SHARIKAT FANNIYA OMANIYA LLC

METHOD STATEMENT: -33kV POWER CABLE PLUG-IN AND TESTING


- RELAY TESTING AND CABLE STABILITY

DOCUMENT REFERENCE NUMBER: AL SAADA II/SFO/CO443/MS/E/14

Page 2
Document Reference
PROJECT No.: DPC-DN-Z1B-2016-33 kV-3 JARZIZ/E/3015/A4
CONSTRUCTION OF 2X20 MVA, 33/11KV PSS DESIGNATED AS
Rev No 0
JARZIZ (DPC/TENDER/2016/201)
Rev Date 21.05.2017
PROJECT COMPANY DHOFAR POWER COMPANY
OWNER’S ENGINEER HAMED ENGINEERING SERVICES LLC
CONTRACTOR SHARIKAT FANNIYA OMANIYA LLC

POWER CABLE TESTING AND PLUGGING AND RELAY TESTING INSIDE AS SAADA GSS
The following activities shall be ensured by the Electrical Engineer /Testing Engineer/ QC Engineer at site:

1.0 PURPOSE

The purpose of this method statement is to provide the guidelines for activities carried out during plug-in and testing of
33kv power cable and relay testing.

2.0 APPLICABLE SPECIFICATIONS, REFERENCE STANDARDS & APPROVED DRAWINGS


Scope of work
Volume 2, Section 4, 11
Method Statement

3.0 JOB SAFETY PLAN

3.1 HAZARD IDENTIFICATION


 Stored energy
 Hand and power tools
 Slipping and Tripping Hazard
 Electrical hazard
 Physical hazard
 Weather condition
 Live apparatus

3.2 ACTION BY THE EXECUTION TEAM.


 Identification and barricading of live panels
 Use Proper Personnel Protective Equipment during working.
 Tripping hazard to be mechanically removed.

4.0 RESPONSIBILITY
The Electrical Engineer / Testing engineer shall be the responsible person in supervising the above activities at site.
The Quality Control Engineer shall monitor the activities for the compliance of the Specifications.
The Safety steward shall be all time available at site to monitor the safety aspects during the activity at site.

5.0 TOOLS AND EQUIPMENTS


 Cutting tools
 Hand tools
 Drilling machine
 Hipot test kit.
 Multimeter
 Megger 5kV
 Gas torch

Page 3
Document Reference
PROJECT No.: DPC-DN-Z1B-2016-33 kV-3 JARZIZ/E/3015/A4
CONSTRUCTION OF 2X20 MVA, 33/11KV PSS DESIGNATED AS
Rev No 0
JARZIZ (DPC/TENDER/2016/201)
Rev Date 21.05.2017
PROJECT COMPANY DHOFAR POWER COMPANY
OWNER’S ENGINEER HAMED ENGINEERING SERVICES LLC
CONTRACTOR SHARIKAT FANNIYA OMANIYA LLC

 Fire extinguisher

6.0 MANPOWER
a) 33kv cable Plug-in and testing
 Cable jointers- 1 No.
 Protection Engineer- 1 No.
 Fabricator – 1 No.
 Electrician – 1 No.
 Helper – 1 No.

7.0 PROCEDURE

a) 33kv cable plug-in and power cable testing ( 1 DAY)


 Upon receipt of necessary permit, conduct the tool box talk.
 Work area shall be secured with signage’s and barricades.
 The power cable of shall be identified properly.
 33kv switchgear panels shall be identified and nameplates shall be provided as per DPC recommendation.
 Cable plug in shall be done by competent person only.
 Prior to cable plug in termination cable hipot test to be carried at the recommended voltage(68kV, 15 min)
 Power cables shall be supported properly with cable clamps and supports shall be earthed to the nearest earth
bus.
 33kv cable hipot shall be carried out after plug in and 33kv Circuit breaker in open condition. After proper tagging
and barricading at the GSS end, High voltage of 45kV shall be applied at the PSS end and leakage current shall be
noted down.

b) 33kv Relay testing and cable stability (1 DAY)

 All necessary permits shall be obtained prior to commissioning of work.


 Relay testing and cable stability testing shall be done by DCRP approved testing engineers only.
 All the current injection during the relay testing and cable stability test shall be from the PSS end only.
 All be testing activities will be witnessed by DPC/HES Protection Engineer.

8.0 DOCUMENTS & RECORDS.

 Records shall include the following,


 All quality records. (Check List)
 As built Drawing.

Page 4