AUSTDOOR - General Structural Brief
AUSTDOOR - General Structural Brief
Cilent: AUSTDOOR
Project: NEW FACTORY
Itemt: XUONG DUN
Location: NHON TRACH - DONG NAI - VIETNAM
Issue Date: 17/08/20178
Rev Time: 0
Rev Content: N/A
DESIGN PROCEDURE
Design parameter:
Project were designed by following American & Canadian code
ASCE 7-10 : Minimum Design Loads for Buildings and Other Structures.
IBC 2012 : International Building Code.
AISC ASD 89 : Allowable Stress Design.
MBMA 2012 : Metal Building Manufactures Association.
Load case:
Dead load_(DL) : By structural components
Colateral load : 10 kg/m2
Roof live load_(RL) : 30 kg/m2
Windload_(W) : v=83 mph
Exposure : B
Crane Load : By 5Tons Crane
Earthquake load : Neglected
Load combination:
By ASCE 7-10 for Allowable Stress Design (ASD) combinations
Analysis type:
Direct Analysis Method (DAM), including P-Delta effect, Notional load automatic creation
Serviceability check:
RL L/150
1 Rafter Vertical deflection MBMA Table 1.3.1b
II Building and other structures except those listed in Risk Category I,III and IV
Buildings and other structures that represent a substantial hazard to human life in the event of failure, including but not limited to:
- Buildings and other structures whose primary occupancy is public assembly with an occupant load greater than 300.
- Buildings and other structures containing elementary school, secondary school or day care facilities with an occupa load
greater than 250.
- Buildings and other structures containing adult education facilities, such as colleges and universities, with an occupant load
greater than 500.
- Group 1-2 occupancies with an occupant load of 50 or more resident care recipients but not having surgery or emergencv
treatment facilities.
III
- Group 1-3 occupancies.
- Any other occupancy with an occupant load greater than 5,000'’.
- Power-generating stations, water treatment facilities for potable water, waste water treatment facilities and other public utility
facilities not included in Risk Category IV.
- Buildings and other structures not included in Risk Category IV containing quantities of toxic or explosive materials that:
Exceed maximum allowable quantities per control area as given in Table 307.1 (1) or 307.1(2) or per outdoor control area in
accordance with the International Fire Code', and
Are sufficient to pose a threat to the public if released b
Building and other structures designated as essential facilities, including but not limited to:
- Group 1-2 occupancies having surgery or emergency treatment facilities.
- Fire, recuse, ambulance and police stations and emergency vehicle garages.
- Designated earthquake, hurricane or other emergency shelters.
- Designated emergency preparedness, communications and operations centers and other facilities required for emergency
response.
- Power-generating stations and other public ultility facilities required as emergency backup facilities for Risk Category IV
IV structures.
- Building and other structures containing quantities of highly toxic materials that :
Exceed maximum allowable quantities per control area as given in table 307.1(2) or per outdoor control area in accordance
with the International Fire code and
Are sufficient to pose a treat to the public if releaseb
- Aviation control towers, air traffic control centers and emergency aircraft hangars.
- Building and other structures having critical national defense functions.
- Water strorage facilities and pump structures required to maintain water pressure for fire suppression.
Notes:
1 Note that beginning with ASCE 7-10, there is no importance factor for wind because this is
Roof memberse:
Notes:
a. For structural roofing and siding made of formed metal sheets, the total load deflection shall not exceed L/60. For secondary roof structural members
supporting formed metal roofing, the live load deflection shall not exceed L/150. For secondary wall members supporting formed metal siding, the design wind
load deflection shall not exceed L/90. For roofs, this exception only applies when the metal sheets have no roof covering. (Note: Requirements of this Note "a"
have been added to Table 1.3.1(b) for clarification purposes.)
b. Interior partitions not exceeding 6 feet in height and flexible, folding and portable partitions are not governed by the provisions of this section. The deflection
criterion for interior partitions is based on the horizontal load defined in Section 1607.13.
c. See Section 2403 for glass supports.
d. For wood structural members having a moisture content of less than 16 percent at time of installation and used under dry conditions, the deflection resulting
from Live + Dead is permitted to be substituted for the deflection resulting from Live + Dead.
e. The above deflections do not ensure against ponding. Roofs that do not have sufficient slope or camber to assure adequate drainage shall be investigated
for ponding. See Section 1611 for rain and ponding requirements and Section 1503.4 for roof drainage requirements. Note that Section 1611.2 of IBC 2012
requires that bays of roofs susceptible to ponding instability shall be evaluated in accordance with Section 8.4 of ASCE 7-10. A susceptible bay is defined in
Section 202, cross-referenced by Section 1602.1 of IBC 2012 as a roof or portion thereof with (1) a slope less than 1/4-inch per foot, or (2) on which water is
impounded upon it, in whole or in part, and the secondary drainage system is functional but the primary drainage system is blocked. A roof surface with a
slope of 1/4-inch per foot or greater towards points of free drainage is not a susceptible bay.
f. The wind load is permitted to be taken as 0.42 times the "component and cladding" loads for the purpose of determining deflection limits herein.
g. For steel structural members, the dead load shall be taken as zero.
h. For aluminum structural members or aluminum panels used in skylights and sloped glazing framing, roofs or walls of sunroom additions or patio covers, the
total load deflection shall not exceed L/60. For aluminum sandwich panels used in roofs or walls of sunroom additions or patio covers, the total load deflection
shall not exceed L/120.
i. For cantilever members, L shall be taken as twice the length of the cantilever.
Metal panels/ Bare frame Driff Perpendicular to Wall H/60 to H/100 (Max) 10 Year wind
Metal panels/ Girts Horizontal Deflection L/120 (Max) 10 Year wind
Metal panel/ Wind Column Horizontal Deflection L/120 (Max) 10 Year wind
Precast Walls/ Bare frame Driff Perpendicular to Wall H/100 (Max) 10 Year wind
Unreinforced Masonry Walls/ Bare 1/16 inch crack Base of 10 Year wind
Driff Perpendicular to Wall
frame Wall
Foundation
Reinforced Masonry Walls/ Bare 10 Year wind
Driff Perpendicular to Wall H/200 (Max)
frame
Masonry Walls/ Girts Horizontal Deflection L/240, 1.5 inch (Max) 10 Year wind
Masonry Walls/ Wind Column Horizontal Deflection L/240, 1.5 inch (Max) 10 Year wind
Masonry Walls/ Lintel Vertical Deflection L/600, 0.3 inch (Max) DL+LL
Masonry Walls/ Lintel Rotation ≤1 degree (Max) DL+LL
Pre-Assembled Units/ Columns Relative Shortening 1/4 inch (Max) 0.5LL
Column
Pre-Assembled Units/ Bare frame Racking H/500 10 Year wind
Curtain Walls/ Bare frame Vertical Deflection H/500 10 Year wind
Curtain Walls/ Spandrels Vertical Deflection 3/8 inch (Max) DL Prior to Cladding
Curtain Walls/ Spandrels Vertical Deflection L/480, 5/8 inch (Max) Total DL
Spandrel
Curtain Walls/ Spandrels Vertical Deflection L/360, 1/2 inch (Max) 0.5LL
DL, including
Curtain Walls/ Spandrels Vertical Deflection L/600, 3/8 inch (Max)
Cladding Seft weight
Table 5: Serviceability Considerations – Celling & Partitions (Table 3.4 MBMA 2012)
Finished type
Structural Elements Deformation Recommendation Loading
0.5LL or 50 Year
Plastered Celling Roof member Vertical Deflection L/360 (Max)
Snow
0.5LL or 50 Year
Roof member Vertical Deflection L/240 (Max)
Non Plastered Celling Snow
Floor Beam/ Girder Vertical Deflection L/360,1 inch (Max) DL
Frame Horizontal Movement H/500 (Max) 10 Year wind
0.5LL or 50 Year
Partitions Roof member Vertical Deflection 3/8 inch to 1 inch (Max)
Snow
Floor Beam/ Girder Vertical Deflection L/360,1 inch (Max) 0.5LL
Table 6: Serviceability Considerations – Equipment (Table 3.5 MBMA 2012)
Equipment Type
Structural Elements Deformation Recommendation Loading
0.5LL or 50 Year
Runway supports Total Inward ,movement 1/2 inch (Max)
Snow
Runway supports Total Outward ,movement 1 inch (Max) Snow
Where: D = Dead Load, L = Live load, Lr = Roof live load, S = Snow load, R = Rain load, W = Wind load, E = Earthquake load
1.8 Dead Load:
The weight of materials of construction incorporated into the building, including but not limited to walls, floors, roofs, ceilings, stairways, built-in partitions,
finishes, cladding, and other similarly incorporated architectural and structural items, and the weight of fixed service equipment, such as cranes, plumbing
stacks and risers, electrical feeders, heating ventilating and air-conditioning systems and automatic sprinkler systems. (Ref. IBC 2012, Section 202, cross-
referenced by Section 1602.1). Further definition is provided in IBC Section 1606 as follows:
Dead loads shall be considered permanent loads.
For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information,
values used shall be subject to the approval of the building official.
Note that it is customary in the metal building industry to refer to the "weights of fixed service equipment" as collateral load. This distinction is made because
this portion of the dead load is not part of the system provided by the manufacturer. This could also include other dead load such as partitions, finishes, and
ceilings. See Table 7 for typical values that may be used as a guide to specify collateral loads.
Cellings
F ≥ 12 12 12 12
Buildings
Main Wind Force Resisting System 0.85
Components and Cladding 0.85
Trussed Towers
Triangle, Square, Rectangular 0.85
All other cross sections 0.95
Table 10: Velocity Pressure coefficients, Kh and Kz ( for all heights) (Table 27.3-1 ASCE7-10)
Height above
Exposure
Ground level, z
(ft) (m) B C D
0-15 0-4.6 0.57 0.85 1.03
20 6.1 0.62 0.90 1.08
25 7.6 0.66 0.94 1.12
30 9.1 0.7 0.98 1.16
40 12.2 0.76 1.04 1.22
50 15.2 0.81 1.09 1.27
60 18 0.85 1.13 1.31
70 21.3 0.89 1.17 1.34
80 24.4 0.93 1.21 1.38
90 27.4 0.96 1.24 1.40
100 30.5 0.99 1.26 1.43
120 36.6 1.04 1.31 1.48
140 42.7 1.09 1.36 1.52
160 48.8 1.13 1.39 1.55
180 54.9 1.17 1.43 1.58
200 61.0 1.20 1.46 1.61
250 76.2 1.28 1.53 1.68
300 91.4 1.35 1.59 1.73
350 106.7 1.41 1.64 1.78
400 121.9 1.47 1.69 1.82
450 137.2 1.52 1.73 1.86
500 152.4 1.56 1.77 1.89
Note:
The velocity pressure exposure coefficients Kz may be determined from the following formula:
For 15(ft) ≤ z ≤ zg For z < 15(ft)
Kz = 2.01 (z/zg)2/α Kz = 2.01 (15/zg)2/α
1.10.6 Design Pressure for Main Wind Force Resisting System (MWFRS):
1.10.6.1 Envelope Procedure for Low-Rise Buildings:
The design wind pressure used for the main wind force resisting system (MWFRS) is to computed as follows:
Step 1: Determine Risk category of Buildings or other Structures, see Table 1.5-2 (ASCE7-10).
Step 2: Determine the basic Wind speed ,v, for applicable Risk Category, see Fig. 26.5-1A, B, or C (for USA).
Step 3: Determine Wind load parameters:
Wind directionality factor, Kd, see Section 26.6 and Table 26.6-1 (ASCE7-10).
Exposure category B, c or D, see Section 26.7 (ASCE7-10).
Topographic factor, Kzt, see Section 26.8 and Fig. 26.8-1 (ASCE7-10).
Enclosure classification, see Section 26.10 (ASCE7-10).
Internal Pressure coefficient, (GCpi), see Section 26.11 and Table 26.11-1 (ASCE7-10).
Step 4: Determine Velocity Pressure Exposure coefficient, Kz or Kh, see Table 28.3-1 (ASCE7-10).
Step 5: Determine Velocity Pressure, qz or qh, Eq. 28.3-1 (ASCE7-10).
Step 6: Determine External Pressure coeeficient, (GCp), Fig. 28.4-1 for Flat and Gable Roofs (ASCE7-10).
Step 7: Caculate Wind Pressure, p, p = qh[(GCpf) - (GCpi)] Eq. 28.4-1 (ASCE7-10).
where:
p = Design wind pressure in pounds per square foot (psf).
qh = Velocity pressure in pounds per square foot (psf).
GCpf = External pressure coefficient from Figure 28.4-1, ASCE 7-10.
GCpi = Internal pressure coefficient from Table 26.11-1, ASCE 7-10.
h = Mean roof height above ground. Eave height may be substituted for mean roof height if 9 < 10°. For single slope buildings, the lower eave
height may be substituted for the mean roof height if θ < 10°.
Table 12: Walls and Roofs External pressure coefficients (GCpf) for Low-Rise h ≤ 60ft (Fig 28.4-1 ASCE7-10)
Roof angle, θ Load Case B
deg
Building Surface
1 2 3 4 5 6 1E 2E 3E 4E 5E 6E
0 - 90 -0.45 -0.69 -0.37 -0.45 0.4 -0.29 -0.48 -1.07 -0.53 -0.48 0.61 -0.43
Notes:
1. Plus and minus signs signify pressures acting toward and away from the surfaces, respectively.
2. For values of θ other than those shown, linear interpolation is permitted.
3. The building must be designed for all Wind directions using the 8 loading patterns shown. The load patterns are applied to each building corner in turn as
the Windward Corner.
4. Combinations of external and internal pressures shall be evaluated as required to obtain the most severe loading.
5. For the Torsional load case shown below, the pressures in zone designated with a “T” shall be 25% of the full design Wind pressure (zone 1,2,3,4,5,6)
Exception: One story buildings with h less than or equal to 30(ft)/ 9.1(m), building two stories or less framed with light frame construction, and buildings two
stories or less designed with flexible diaphragms need not to be designed for the Torsional load case.
Torsional loading shall apply to all eight basic load patterns using the figures above applied at each Windward Corner.
6. For purpose of designing a building’s MWFRS, the total horizontal shear shall not be less than that determined by neglecting the Wind force on the roof.
7. For flat roof, use θ =0 (deg) and locate the zone 2/3 and zone 2E/3E boundary at the mid-width of the building.
8. The roof pressure coefficient (GCpf), when negative in Zone 2 and 2E, shall be applied in Zone 2/2E for a distance from the edge of roof equal to 0.5 times
the horizontal dimension of the building parallel to the direction of the MWFRS being designed or 2.5 times the eave height at the windward wall, whichever
is less : the remainder of zone 2/2E extending to the Ridge line shall use the pressure coefficient (GCpf) for zone 3/3E
9. Notation:
a: 10% of least horizontal dimension or 0.4h, whichever is smaller, but not less than either 4% of least horizontal dimension or 3(ft)/ 0.9(m).
h:Mean roof height, except that eavea height shall be used for θ ≤ 10(deg).
θ:Angle of plane of roof from horizontal, in degrees.
10. Roof overhangs : The Positive external pressure on the bottom surface of windward roof overhangs shall be determined using Cp = 0.7 (ASCE7-10), Cp =
0.68 ( MBMA 2012), in combination with the top surface pressures determined using Table 11 ( Fig 28.4-1 ASCE 7-10).
1.10.6.2 Directional Procedure for all height Buildings:
The design wind pressure used for the main wind force resisting system (MWFRS) is to computed as follows:
Step 1: Determine Risk category of Buildings or other Structures, see Table 1.5-2 (ASCE7-10).
Step 2: Determine the basic Wind speed ,v, for applicable Risk Category, see Fig. 26.5-1A, B, or C (for USA).
Step 3: Determine Wind load parameters:
Wind directionality factor, Kd, see Section 26.6 and Table 26.6-1 (ASCE7-10).
Exposure category B, c or D, see Section 26.7 (ASCE7-10).
Topographic factor, Kzt, see Section 26.8 and Fig. 26.8-1 (ASCE7-10).
Enclosure classification, see Section 26.10 (ASCE7-10).
Internal Pressure coefficient, (GCpi), see Section 26.11 and Table 26.11-1 (ASCE7-10).
Gust Effect factor, G see Section 26.9 (ASCE7-10).
Step 4: Determine Velocity Pressure Exposure coefficient, Kz or Kh, see Table 27.3-1 (ASCE7-10).
Step 5: Determine Velocity Pressure, qz or qh, Eq. 27.3-1 (ASCE7-10).
Step 6: Determine External Pressure coeeficient, Cp or CN, Fig. 27.4-1 for Walls, Flat, Gable, Hip, Monoslope or Mansard Roofs.
Fig. 27.4-2 for Domed Roofs.
Fig. 27.4-3 for Arched Roofs.
Fig. 27.4-4 for Monoslope Roofs, Open Buildings.
Fig. 27.4-5 for Pitched Roofs, Open Buildings.
Fig. 27.4-6 for Troughed Roofs, Open Buildings.
Fig. 27.4-7 for along-ridge/ valley Wind load case for Monoslpoe, Pitched
or Troughed Roofs, Open Buildings.
Step 7: Caculate Wind Pressure, p, on each Building surface
p = qGCp – qi(GCpi) Eq. 27.4-1 for Rigid Buildings, Endclosed or Partially Endclosed.
p = qGfCp – qi(GCpi) Eq. 27.4-2 for Flexible Buildings, Endclosed or Partially Endclosed.
p = qhGCN Eq. 27.4-3 for Monoslope, Pitched or Troughed free Roofs Open Buildings.
where:
q = qz for windward walls evaluated at height z above the ground.
q = qh for leeward walls, side walls, and roofs evaluate bat height h
qi = qh for windward walls, side walls, leeward walls, and roofs of endclosed buildings and for negative internal pressure evaluation in partially
endclosed buildings.
qi = qz for positive internal pressure evaluation in partially endclosed building where height z is defined as the level of the highest opening in the
building that could affect the positive internal pressure.
G = Gust-effec factor, see Section 26.9.
Cp = External pressure coefficient from Figs 27.4-1, 27.4-2 and 27.4-3.
(GCpi) = Internal pressure coefficient from table 26.11-1
Table 13: Wall External pressure coefficients Cp for All height buildings (Fig 27.4-1 ASCE7-10)
Surface Wall Pressure Coefficients, Cp
L/B Cp Use with
Winward Wall All values 0.8 qz
0-1 -0.5
Leeward Wall
2 -0.3
qh
≥4 -0.2
Side Wall All values -0.7
Table 14: Roof External pressure coefficients Cp for All height buildings (Fig 27.4-1 ASCE7-10)
Winward Leeward
Wind Direction Angle θ (deg)
Angle θ (deg)
h/L 10 15 20 25 30 35 45 ≥ 60 10 15 ≥ 20
-0.17 -0.5 -0.3 -0.2 -0.2 0.0*
≤ 0.25 0.01θ -0.3 -0.5 -0.6
-0.18 0.0* 0.2 0.3 0.3 0.4 0.4
Nomal to Ridge for
θ ≥ 10 (deg) -0.9 -0.7 -0.4 -0.3 -0.2 -0.2 0.0*
0.5 0.01θ -0.5 -0.5 -0.6
-0.18 -0.18 0.0* 0.2 0.2 0.3 0.4
-1.3** -1.0 -0.7 -0.5 -0.3 -0.2 0.0*
≥1 0.01θ -0.7 -0.6 -0.6
-0.18 -0.18 -0.18 0.0* 0.2 0.2 0.3
Horizontal distance from winward edge
-0.18 * value is provided for interpolation purpose
0 to h/2 -0.9
** value can be reduced linearly with area
≤ 0.5 h/2 to h -0.9 -0.18 over which it is applicable as follows
Normal to Ridge for θ h to 2h -0.5 -0.18
<10 and parallel to Ridge
> 2h -0.3 -0.18
for all θ
Area Reduction factor
0 to h/2 -1.3** -0.18 ≤ 100 (9.3m2) 1.0
≥1
250 (23.2m2) 0.9
> h/2 -0.7 -0.18 ≥ 1000 (92.9m2) 0.8
Notes:
1. Plus and minus signs signify pressures acting toward and away from the surfaces, respectively.
2. Linear interpolation is permitted for values of L/B, h/L and θ other than shown. Interpolation shall only be carried out between values of the same sign.
Where no value of the same sign is given, assume 0.0 for interpolation purpose.
3. Where two case of Cp are listed, this indicates that the Windward roof slope is subjected to either positive or negative pressures and the roof structure shall
be designed for both conditions. Interpolation for intermediate ratios of h/L in this case shall only be carried out between Cp values of like sign..
4. For monoslope roofs, entire roof surface is either a Windward or Leeward surface.
5. For flexible buildings use apporiate Gf as determined by Section 26.9.4.
6. Refer to Fig 27.4-2 for domes and Fig 27.4-3 for arched roofs.
7. Notation:
B: Horizontal dimension of building, in feet (meter), measured normal to Wind direction.
L: Horizontal dimension of building, in feet (meter), measured parallel ton Wind direction.
h: Mean roof heght in feet (meters), except that eave height shall be used for θ ≤ 10 degrees.
z: Height above ground, in feet (meters).
G: Gust effect factor.
qz, qhVelocity pressure, in pounds per square foot (N/m2), evaluate at respective height.
θ:Angle of plane of roof from horizontal, in degrees.
8. For mansard roofs, the top horizontal surface and leeward inclined surface shall be treated as leeward surfaces from the table.
9. Except for MWFRS’s at the roof consisting of moment resisting frames, the total horizontal shear shall not be less than that determined by neglecting wind
forces on roof surfaces.
10.For roof slopes greater than 80, Use Cp = 0.8
Notes:
1. CNW and CNL denote net pressure (contributions from top and bottom surfaces) for winward and leeward half of roof surfaces, respectively.
2. Clear wind flow denotes relative unobstructed wind flow with blockage less than or equal to 50%. Obstructed wind flow denotes objects below roof inhibiting
wind flow ( >50% blockage).
3. For value of θ between 7.5(deg) and 45(deg), linear interpolation is permitted. For values of θ less than 7.5(deg), use load coefficients for 0(deg).
4. Plus and minus signs signify pressure acting towards and away from the top roof surface, respectively.
5. All load case shown for each roof angle shall be investigated.
6. Notation:
L: Horizontal dimension of roof, measured in the along wind direction, ft (m).
h: Mean roof heght in feet (meters)
γ: Direction of Wind, degrees
θ: Angle of plane of roof from horizontal, in degrees.
Notes:
1. CNW and CNL denote net pressure (contributions from top and bottom surfaces) for winward and leeward half of roof surfaces, respectively.
2. Clear wind flow denotes relative unobstructed wind flow with blockage less than or equal to 50%. Obstructed wind flow denotes objects below roof inhibiting
wind flow ( >50% blockage).
3. For value of θ between 7.5(deg) and 45(deg), linear interpolation is permitted. For values of θ less than 7.5(deg), use load coefficients for 0(deg).
4. Plus and minus signs signify pressure acting towards and away from the top roof surface, respectively.
5. All load case shown for each roof angle shall be investigated.
6. Notation:
L: Horizontal dimension of roof, measured in the along wind direction, ft (m).
h: Mean roof heght in feet (meters)
γ: Direction of Wind, degrees
θ: Angle of plane of roof from horizontal, in degrees.
Notes:
1. CNW and CNL denote net pressure (contributions from top and bottom surfaces) for winward and leeward half of roof surfaces, respectively.
2. Clear wind flow denotes relative unobstructed wind flow with blockage less than or equal to 50%. Obstructed wind flow denotes objects below roof inhibiting
wind flow ( >50% blockage).
3. For value of θ between 7.5(deg) and 45(deg), linear interpolation is permitted. For values of θ less than 7.5(deg), use load coefficients for 0(deg).
4. Plus and minus signs signify pressure acting towards and away from the top roof surface, respectively.
5. All load case shown for each roof angle shall be investigated.
6. Notation:
L: Horizontal dimension of roof, measured in the along wind direction, ft (m).
h: Mean roof heght in feet (meters)
γ: Direction of Wind, degrees
θ: Angle of plane of roof from horizontal, in degrees.
Table 18: Roof Net pressure coefficients CN for Troughed Free Roofs (Fig 27.4-6 ASCE7-10)
Horizontal Roof angle Load case Clear Wind O Obstructed
Distance from Windward Edge θ Flow Wind Flow
CN CN
All shape A -0.8 -1.2
≤h
θ ≤ 45 B 0.8 0.5
All shape A -0.6 -0.9
>h , ≤ 2h
θ ≤ 45 B 0.5 0.5
All shape A -0.3 -0.6
≤ 2h
θ ≤ 45 B 0.3 0.3
Figure 8: External pressure coefficients,GCp h ≤ 60ft
Endclosed, Partially Endclosed buildings Arched Roofs
Arched roofs.
Notes:
1. Value listed are for the determination of average loads on MWFRS.
2. Plus and minus signs signify pressure acting towards and away from the top roof surface, respectively.
3. For wind directed parallel to the axis of the arch, use pressure coefficients from Fig 27.4-1 with wind directed parallel to Ridge.
4. For C&C: (1) At roof perimeter, use the external pressure coefficients in Fig 30.4-2A , 2B, and 2C with θ base on spring-line slope and (2) for remaining roof
areas, use external pressure coefficients of this table multiplied by 0.87.
Table 18: Roof Net pressure coefficients Arched Roofs (Fig 27.4-3 ASCE7-10)
Conditions Rise-to-span ratio,r Cp
Roof on springing from Ground level 0 < r ≤ 0.6 1.4r -0.7 - r -0.5
Table 19: Wall Coefficients ( GCp – GCpi ) Outward pressure for Components and Cladding
Zone Effective Wind Load Area (ft2) Endclosed Buildings Partially Endclose Buildings
A ≤ 10 -1.58 -1.95
Corner (5) 10 < A < 500 +0.353 logA – 1.93 +0.353 logA – 2.30
A ≥ 500 -0.98 -1.35
A ≤ 10 -1.28 -1.65
Interior (4) 10 < A < 500 +0.176 logA – 1.46 +0.176 logA – 1.83
A ≥ 500 -0.98 -1.35
Table 20: Wall Coefficients ( GCp – GCpi ) Inward pressure for Components and Cladding
Zone Effective Wind Load Area (ft2) Endclosed Buildings Partially Endclose Buildings
A ≤ 10 +1.18 +1.55
All zones 10 < A < 500 -0.176 logA + 1.36 -0.176 logA + 1.73
A ≥ 500 +0.88 +1.25
Table 21: Wall Coefficients ( GCp – GCpi ) Outward pressure for Components and Cladding w/10% Reduction
Zone Effective Wind Load Area (ft2) Endclosed Buildings Partially Endclose Buildings
A ≤ 10 -1.44 -1.81
Corner (5) 10 < A < 500 +0.318 logA – 1.76 +0.318 logA – 2.13
A ≥ 500 -0.90 -1.27
A ≤ 10 -1.17 -1.54
Interior (4) 10 < A < 500 +0.176 logA – 1.33 +0.176 logA – 1.70
A ≥ 500 -0.90 -1.27
Table 22: Wall Coefficients ( GCp – GCpi ) Inward pressure for Components and Cladding w/10% Reduction
Zone Effective Wind Load Area (ft2) Endclosed Buildings Partially Endclose Buildings
A ≤ 10 +1.08 +1.45
All zones 10 < A < 500 -0.159 logA + 1.24 -0.159 logA + 1.61
A ≥ 500 +0.81 +1.18
Notes:
1. Plus and minus signs signify pressure acting towards and away from the top roof surface, respectively.
2. Each component shall be design for maximum positive and negative pressures.
3. Value of GCp for walls shall be reduced by 10% when θ ≤ 10(deg).
4. Notation:
a : 10 percent of least horizontal dimension or 0.4h, whichever is smaller, but not less than either 4 percent of least horizontal dimension or 3ft (0.9m).
h : Mean roof height, in feet (meters), except that eave height shall be used for θ ≤ 10(deg).
θ : Angle of plane of roof from horizontal, in degrees.
Figure 10: External pressure coefficients,GCp h ≤ 60ft
Endclosed, Partially Endclosed buildings Gable Roofs 0 ≤ θ ≤ 45 (deg)
ASCE7-10
Fig 30.4-1: Gable roofs.
Table 23: Roof Coefficients ( GCp – Gcpi ) Uplift pressure for Components and Cladding, Gable Roofs, 0 ≤ θ ≤ 7
Zone Effective Wind Load Area (ft2) Endclosed Buildings Partially Endclose Buildings
A ≤ 10 -2.98 -3.35
Corner (3) 10 < A < 100 +1.70 logA – 4.68 +1.70 logA – 5.05
A ≥ 100 -1.28 -1.65
A ≤ 10 -1.98 -2.35
Edge (2) 10 < A < 100 +0.7 logA – 2.68 +0.7 logA – 3.05
A ≥ 100 -1.28 -1.65
A ≤ 10 -1.18 -1.55
Interior (1) 10 < A < 100 +0.10 logA – 1.28 +0.10 logA – 1.65
A ≥ 100 -1.08 -1.45
Table 24: Roof Coefficients ( GCp – GCpi ) Downward pressure for Components and Cladding Gable Roofs, 0 ≤ θ ≤ 7
Zone Effective Wind Load Area (ft2) Endclosed Buildings Partially Endclose Buildings
A ≤ 10 +0.48 +0.85
All zones 10 < A < 100 -0.1 logA + 0.58 -0.1 logA + 0.95
A ≥ 100 +0.38 +0.75
Table 25: OverHang Roof Coefficients ( GCp – GCpi ) Uplift pressure for Components and Cladding Gable Roofs, 0 ≤ θ ≤ 7
Zone Effective Wind Load Area (ft2) Endclosed Buildings or
Partially Endclose Buildings
A ≤ 10 -2.80
Corner (3) 10 < A < 100 +2.00 logA – 4.80
A ≥ 100 -0.8
A ≤ 10 -1.7
10 < A ≤ 100 +0.10 logA – 1.80
Edge (2) and Interior (1)
100 < A ≤ 500 +0.715 logA – 3.03
A ≥ 500 -1.10
Table 26: Roof Coefficients ( GCp – Gcpi ) Uplift pressure for Components and Cladding, Gable Roofs, 7 ≤ θ ≤ 27
Zone Effective Wind Load Area (ft2) Endclosed Buildings Partially Endclose Buildings
A ≤ 10 -2.78 -3.15
Corner (3) 10 < A < 100 +0.60 logA – 3.38 +0.60 logA – 3.75
A ≥ 100 -2.18 -2.55
A ≤ 10 -1.88 -2.25
Edge (2) 10 < A < 100 +0.50 logA – 2.38 +0.50 logA – 2.75
A ≥ 100 -1.38 -1.75
A ≤ 10 -1.08 -1.45
Interior (1) 10 < A < 100 +0.10 logA – 1.28 +0.10 logA – 1.55
A ≥ 100 -0.98 -1.35
Table 27: Roof Coefficients ( GCp – GCpi ) Downward pressure for Components and Cladding Gable Roofs, 7 ≤ θ ≤ 27
Zone Effective Wind Load Area (ft2) Endclosed Buildings Partially Endclose Buildings
A ≤ 10 +0.68 +1.05
All zones 10 < A < 100 -0.20 logA + 0.88 -0.20 logA + 1.25
A ≥ 100 +0.48 +0.85
Table 28: OverHang Roof Coefficients ( GCp – GCpi ) Uplift pressure for Components and Cladding Gable Roofs, 7 ≤ θ ≤ 27
Zone Effective Wind Load Area (ft2) Endclosed Buildings or
Partially Endclose Buildings
A ≤ 10 -3.70
Corner (3) 10 < A < 100 +1.20 logA – 4.90
A ≥ 100 -2.50
Table 29: Roof Coefficients ( GCp – Gcpi ) Uplift pressure for Components and Cladding, Gable Roofs, 27 ≤ θ ≤ 45
Zone Effective Wind Load Area (ft2) Endclosed Buildings Partially Endclose Buildings
A ≤ 10 -1.38 -1.75
Corner (3) and Edge (2) 10 < A < 100 +0.20 logA – 1.58 +0.20 logA – 1.95
A ≥ 100 -1.18 -1.55
A ≤ 10 -1.18 -1.55
Interior (1) 10 < A < 100 +0.20 logA – 1.38 +0.20 logA – 1.75
A ≥ 100 -0.98 -1.35
Table 30: Roof Coefficients ( GCp – GCpi ) Downward pressure for Components and Cladding Gable Roofs, 27 ≤ θ ≤ 45
Zone Effective Wind Load Area (ft2) Endclosed Buildings Partially Endclose Buildings
A ≤ 10 +1.08 +1.45
All zones 10 < A < 100 -0.10 logA + 1.18 -0.10 logA + 1.55
A ≥ 100 +0.98 +1.35
Table 31: OverHang Roof Coefficients ( GCp – GCpi ) Uplift pressure for Components and Cladding Gable Roofs, 27 ≤ θ ≤ 45
Zone Effective Wind Load Area (ft2) Endclosed Buildings or
Partially Endclose Buildings
A ≤ 10 -2.00
Corner (3)
10 < A < 100 +0.2 logA – 2.20
and Edge (2)
A ≥ 100 -1.80
Figure 11: External pressure coefficients,GCp h ≤ 60ft
Endclosed, Partially Endclosed buildings Multispan Gable Roofs
Table 32: Roof Coefficients ( GCp – Gcpi ) Uplift pressure for Components and Cladding, Multispan Roofs, 10 ≤ θ ≤ 30
Zone Effective Wind Load Area (ft2) Endclosed Buildings Partially Endclose Buildings
A ≤ 10 -2.88 -3.25
Corner (3) 10 < A < 100 +1.00logA – 3.88 +0.60 logA – 4.25
A ≥ 100 -1.88 -2.25
A ≤ 10 -2.38 -2.75
Edge (2) 10 < A < 100 +0.50 logA – 2.88 +0.50 logA – 3.25
A ≥ 100 -1.88 -2.25
A ≤ 10 -1.78 -2.15
Interior (1) 10 < A < 100 +0.20 logA – 1.98 +0.20 logA – 2.35
A ≥ 100 -1.58 -1.95
Table 33: Roof Coefficients ( GCp – GCpi ) Downward pressure for Components and Cladding Multispan Roofs, 10 ≤ θ ≤ 30
Zone Effective Wind Load Area (ft2) Endclosed Buildings Partially Endclose Buildings
A ≤ 10 +0.78 +1.15
All zones 10 < A < 100 -0.20 logA + 0.98 -0.20 logA + 1.35
A ≥ 100 +0.58 +0.95
Table 34: Roof Coefficients ( GCp – Gcpi ) Uplift pressure for Components and Cladding, Multispan Roofs, 30 ≤ θ ≤ 45
Zone Effective Wind Load Area (ft2) Endclosed Buildings Partially Endclose Buildings
A ≤ 10 -2.78 -3.15
Corner (3) 10 < A < 100 +0.90logA – 3.68 +0.90 logA – 4.05
A ≥ 100 -1.88 -2.25
A ≤ 10 -2.68 -3.05
Edge (2) 10 < A < 100 +0.80 logA – 3.48 +0.80 logA – 3.85
A ≥ 100 -1.88 -2.25
A ≤ 10 -2.18 -2.55
Interior (1) 10 < A < 100 +0.20 logA – 3.08 +0.90 logA – 3.45
A ≥ 100 -1.28 -1.65
Table 35: Roof Coefficients ( GCp – GCpi ) Downward pressure for Components and Cladding Multispan Roofs, 30 ≤ θ ≤ 45
Zone Effective Wind Load Area (ft2) Endclosed Buildings Partially Endclose Buildings
A ≤ 10 +1.18 +1.55
All zones 10 < A < 100 -0.20 logA + 1.38 -0.20 logA + 1.75
A ≥ 100 +0.98 +1.35
A ≤ 10 -2.78 -3.15
High-Side
10 < A < 100 +1.0logA – 3.78 +1.0 logA – 4.15
Corner (3)
A ≥ 100 -1.78 -2.15
A ≤ 10 -1.98 -2.35
Low-Side
10 < A < 100 +0.60 logA – 2.58 +0.60 logA – 2.95
Corner (3)
A ≥ 100 -1.38 -1.75
A ≤ 10 -1.78 -2.15
High-Side
10 < A < 100 +0.10 logA – 1.88 +0.10 logA – 2.25
Edge (2)
A ≥ 100 -1.68 -2.05
A ≤ 10 -1.48 -1.85
Low-Side
10 < A < 100 +0.10 logA – 1.58 +0.10 logA – 1.95
Edge (2)
A ≥ 100 -1.38 -1.75
Table 37: Roof Coefficients ( GCp – GCpi ) Downward pressure for Components and Cladding Single Roofs, 3 ≤ θ ≤ 10
Zone Effective Wind Load Area (ft2) Endclosed Buildings Partially Endclose Buildings
A ≤ 10 +0.48 +0.85
All zones 10 < A < 100 -0.10 logA + 0.58 -0.10 logA + 0.95
A ≥ 100 +0.38 +0.75
Table 38: Roof Coefficients ( GCp – Gcpi ) Uplift pressure for Components and Cladding, Single Slope Roofs, 10 ≤ θ ≤ 30
Zone Effective Wind Load Area (ft2) Endclosed Buildings Partially Endclose Buildings
A ≤ 10 -3.08 -3.45
High-Side
10 < A < 100 +0.90 logA – 3.98 +0.9 logA – 4.35
Corner (3)
A ≥ 100 -2.18 -2.55
A ≤ 10 -1.78 -2.15
Edge (2) 10 < A < 100 +0.40 logA – 2.18 +0.40 logA – 2.55
A ≥ 100 -1.38 -1.75
A ≤ 10 -1.48 -1.85
Interior (1) 10 < A < 100 +0.20 logA – 1.68 +0.20 logA – 2.05
A ≥ 100 -1.28 -1.65
Table 39: Roof Coefficients ( GCp – GCpi ) Downward pressure for Components and Cladding Single Roofs, 10 ≤ θ ≤ 30
Zone Effective Wind Load Area (ft2) Endclosed Buildings Partially Endclose Buildings
A ≤ 10 +0.58 +0.95
All zones 10 < A < 100 -0.10 logA + 0.68 -0.10 logA + 1.05
A ≥ 100 +0.48 +0.85
A ≤ 10 -4.28 -4.65
Span A 10 < A ≤ 100 +0.40 logA – 4.68 +0.4 logA – 5.05
Corner (3) 100 < A < 500 +2.289 logA – 8.46 +2.289 logA – 8.83
A ≥ 500 -2.28 -2.65
A ≤ 100 -2.78 -3.15
Span B, C, & D
100 < A < 500 +1.001 logA – 4.78 +1.001 logA – 5.15
Corner (3)
A ≥ 500 -2.08 -2.45
A ≤ 10 -3.38 -3.75
Edge (2) 10 < A < 500 +0.942 logA – 4.32 +0.942 logA – 4.69
A ≥ 500 -1.78 -2.15
A ≤ 10 -2.38 -2.75
Interior (1) 10 < A < 500 +0.647 logA – 3.03 +0.647 logA -3.40
A ≥ 500 -1.28 -1.65
Table 41: Roof Coefficients ( GCp – Gcpi ) Downward pressure for Components and Cladding, Sawtooth Roofs
Zone Effective Wind Load Area (ft2) Endclosed Buildings Partially Endclose Buildings
A ≤ 10 +0.98 +1.25
Corner (3) 10 < A < 100 -0.10 logA + 1.08 -0.3 logA + 1.55
A ≥ 100 +0.88 +0.95
A ≤ 10 +1.28 +1.65
Edge (2) 10 < A < 100 -0.30 logA +1.58 -0.30 logA +1.95
A ≥ 100 +0.98 +1.35
A ≤ 10 +0.88 +1.25
Interior (1) 10 < A < 500 -0.177 logA +1.06 -0.177 logA +1.43
A ≥ 500 +0.58 +0.95
Table 42: Net Pressure Coefficients CN for Components and Cladding, Monoslope Free Roofs
Roof Angle Effective Endclosed Buildings Partially Endclose Buildings
Wind
Load
Area (ft2)
A ≤ 10 +0.98 +1.25
10 < A < -0.10 logA + 1.08 -0.3 logA + 1.55
Corner (3)
100
A ≥ 100 +0.88 +0.95
A ≤ 10 +1.28 +1.65
10 < A < -0.30 logA +1.95
Edge (2) -0.30 logA +1.58
100
A ≥ 100 +0.98 +1.35
Interior A ≤ 10 +0.88 +1.25
(1) 10 < A < -0.177 logA +1.06 -0.177 logA +1.43
500
A ≥ 500 +0.58 +0.95
Site class:
Based on the site Soil properties, the site shall be classified as Site Class A, B, C, D, E, or F in accordance with Table 7. Where the soil properties are not
known in sufficient detail to determine the site class, Site Class D shall be used unless the authority having jurisdiction or geotechnical data determines Site
Class E or F soils are present at the site.
S1 Deposits consisting, or containing a layer at least 10 m thick, of soft clays/silts < 100 - 10-20
with a high plasticity index (PI > 40) and high water content
S2 Deposits of liquefiable soils, of sensitive clays, or any other soil profile not
included in types A - E or S1
Structural system :
Space Frame system: A 3D structural system composed of interconnected members, other than bearing walls, that is capable of supporting vertical loads and,
where designed for such an application, is capable of providing resistance to seismic force.
Seismic Ground motion value:
The parameters Ss and S1 shall be determined from the 0.2s and 1.0 s spectral response accelerations in National Building Code. Where S1 is less than or
equal to 0.04 and Ss is less than or equal to 0.15.
Flexible Diaphram:
The stiffness of the horizontal diaphragm is very small relative to the stiffeness of the vertical system.
Rigid Diaphram:
The stiffness of the horizontal diaphragm is very large compared to the stiffness of the vertical system
Site coefficients and adjusted Maximum Considered Earthquake (MCE) Spectral Response Acceleration parameters:
The MCE spectral response acceleration for short periods (SMS) and at 1 s (SM1), adjusted for Site Class effects, shall be determined by:
SMS = FaSs
SM1 = FV S1
Where:
SS = the MCE spectral response acceleration at short periods
S1 = the MCE spectral response acceleration at a period of 1s
Fa and Fv are site coefficients defined in Tables