AI-702M/704M/706M High Performance Intelligent Multi-Channel Indicators
AI-702M/704M/706M High Performance Intelligent Multi-Channel Indicators
AI-702M/704M/706M
SUMMARY
AI-702M, AI-704M and AI-706M multi-channel indicators provide 1-2, 1-4, 1-6 channels of
independent process indications, and are ideal for the measurement, indication, alarm,
calculation and retransmission of temperature, pressure, flow, level and humidity etc.
Features:
★ Programmable and modular inputs. Multiple input types of thermocouples and RTDs,
voltage/current inputs and two-wire transmitters are field- selectable.
★ Each channel can have independent input specification. All channels are equipped with
digital adjustment and filtering functions and each channel have individual digital
adjustment and filtering parameters.
★ Customized channel number for easy reading when measuring more than 6 channels,
e.g. instrument 1 shows CH1 ~ CH6 while instrument 2 shows CH7 ~ CH12.
★ High performance hardware design, greatly reduce the temperature drift and the
interference between channels, thus multi-channel measurement accuracy is 0.2% full
scale, the same as that of single channel.
★ Provide high accuracy compensation function such as ice-point compensation, copper
resistance compensation and thermostat compensation to thermocouple inputs.
★ Build-in accurate internal calculation functions including square root extraction,
summation, subtraction and multiplication.
★ Support up to 2 isolated retransmission output. Any input channel can be retransmitted
to OUTP port or all channels are cyclically retransmitted.
★ Provide manual/auto pilot display, with 2 pilot speed selectable.
★ Support up to 7 on-off signal inputs/outputs which can work as alarm output or on-off
signal I/O for host computer.
★ Each input channel has independent low/high limit alarm which can be assigned to any
alarm output.
★ Advanced communication function. Provide high accuracy and stability multi-channel
analog data sampling function to host computer. The host computer can also input up
to 7 channel on-off signal or execute on-off operation via the indicator.
★ Up to12 customized field parameters.
★ Multiple dimensions are selectable. 100~240VAC universal power supply.
★ Achieved ISO9001 and CE certificates, comply with EMC standard, high reliability and
stability. The power and I/O terminals have passed the anti-interference test of
4KV/5KHz burst of pulses.
Yudian (H.K.) Automation Technology Co. Ltd.
Website: [Link] [Link]
Email: sales@[Link]
Tel: +852-2770 8785 Fax: +852-2770 8796
ORDERING CODE
AI-706M - A - J1 - J2 - J5 - L5 - L5 - S - 24VDC
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨
Above code symbols a AI-706M instrument with: front panel dimension 96×96mm, 2
thermocouple inputs, 2 two-wire RTD inputs, 2 current inputs, 4 alarm relay outputs, RS485
communication interface and the supply power is 24VDC. The explanation for each code is
below:
② Shows dimension.
The depth of the instrument is about 13.5mm(foreside) + 100mm(rearward).
Front Panel Cut-out
Model Remarks
(width x height) (width x height)
A 96x96mm 92x92mm
B 160X80mm 152x76mm
C 80x160mm 76x152mm
E 48x96mm 45x92mm
E5 is no panel design. It is installed on DIN
trail and programmed by connecting to
E5 96x48mm
external display or computer (S/S5 module
required).
F 96x48mm 92x45mm
⑨ Shows power supply: Null indicates 100~240VAC power supply, and “24VDC” indicates
20~32VDC/AC power.
Yudian (H.K.) Automation Technology Co. Ltd.
Website: [Link] [Link]
Email: sales@[Link]
Tel: +852-2770 8785 Fax: +852-2770 8796
TECHNICAL SPECIFICATION
Input:
Square root extraction calculation input: (with J3 voltage or J4 current input module)
1~5V, 4~20mA etc.
Two-wire transmitter inputs: (with J5 module that provides 24VDC power supply)
Connect to 4~20mA two wires transmitter
Measurement range:
Measurement accuracy:
Note 1: For thermocouple inputs with internal cold junction compensation, 1℃ CJC error
should be taken into consideration. For those with Cu resistor, ice point or thermostat bath
compensation, the accuracy is as above.
Note 2: Accuracy is not guaranteed between 0 and 600℃ for type B thermocouple input.
Yudian (H.K.) Automation Technology Co. Ltd.
Website: [Link] [Link]
Email: sales@[Link] Tel: +852-2770
8785 Fax: +852-2770 8796
● Temperature drift :
≤0.01%FS/℃ (typical 50ppm/℃ )
Electromagnetic compatibility:
IEC61000-4-4, ±4KV/5KHz; IEC61000-4-5, 4KV
Response time:
≤1.5 seconds(if digital filter parameter is set as 0 or 1)
Alarm function:
High and low alarm, configurable separately for each channel
Alarm output:
Relay contact output(NO or NC) :250VAC/1A or 30VDC/1A
No contact discrete output(NO or NC):250VAC/0.3A(transient current 1A)
Power supply:
100~240VAC/50Hz, 24VDC
Power consumption:≤6W
OP1/IN5 + +N/ON/ON/ON/O
OP1/IN5
3 3 1313
+ +A A OUTP/M3
OUTP/M3
B B IN2
IN2
4 4 1414
COMM
COMM COM
COM
This graph is for upright
5 5 + +N/CN/C 1515
IN4IN4 instruments with
+ +N/ON/ON/ON/OAL1AL1 dimension A, C, E.
+ +N/ON/O
IN3IN3
6 6 + +N/CN/CN/ON/OAL2AL2 1616
M2/MIO
M2/MIO 注:本图为 A、C、E 型竖
COM COM
COM COM IN1
IN1
式面板的式仪表接线图。
7 7 1717
ALM
ALM
For instruments with
8 8 + +1818
IN2IN2 dimension B, F , just
+ +N/ON/ON/ON/OAU1AU1 clockwise rotate the
AU2
AU2 ++
IN1IN1
graph for 90 degree,
本图顺时针旋转 90 度后
9 9 + +N/CN/CN/ON/O 1919
M1M1 and
为 B、 the terminal
F 型横式面板仪表
COM COM
COM COM numbers keep
的接线图,端子编号不
1010 CJC
CJC 2020 unchanged.
变。
AUX
AUX
Thermocouple wiring:
When wiring a thermocouple input, the compensation wire should be qualified and directly connect to the
corresponding terminals in correct direction. When M1 module is installed in J1 socket, a Cu50 resistor can
be connected between terminal 17 and 20 to compensate the cold junction; short terminal 17 and 20 to have
ice-point compensation.
AI-702M/704M/706M can measure the lead wire resistance of two-wire method and save it to parameter “Sc”.
However, the lead wire resistance changes as the temperature changes. If the lead wires has the same
ambient temperature as that of the instrument and no other resistor series connects to the lead wire, the
indicators can compensate the resistance change by measuring the ambient temperature (compensation
coefficient is 0.004/℃ ); otherwise, two-wire method is not recommended.
Maximum 3 channel of three-wire RTD is accepted. The channel number automatically shifts forward,
affecting the parameter application. E.g. J0 module is installed in M1 and M2 slot for two three-wire RTD. J2
module is installed in M3. This implies the instrument accept four channels (Parameter: Cn=4, AF.B=1).
There is no IN5 and IN6. Three-wired RTD is recommended to install in prior slot to avoid confusion.
○
1 Upper display window PV
○
2 Lower display window ①
○
3 Set key
○
4 Data shift key (also for switching between
manual/auto cyclic display) SV
○
5 Data decrease key (also for switch to ②
display the previous channel)
○
6 Data increase key (also for switch to MAN PRG MIO COM OP1 OP2 AL1 AL2 AU1 AU2
⑦
⑥
display the next channel)
○
5 10 LED indication lights.
③ ⑥
“MAN” on: Means manual circular display,
A/M RUN/HOLD STOP
“MAN” off: Means auto circular display. ④ ⑥
⑤
MIO, OP1, OP2, AL1, AL2, AU1, AU2 AI
indicate the input/output action of the
corresponding module. “COM” on: communicating with the host computer.
BASIC OPERATION DESCRIPTION
Press to display next channel, and press to display previous channel. Press can switch
between auto cyclic display and manual display.
2. Parameter setting:
When the parameter lock is unlocked, press and hold for about 2 seconds until parameter is
displayed. At this moment, press in short; all parameters will be displayed one by one. When the
parameters are set and the parameter lock is locked, press can access Field Parameter Table.
The value of a parameter can be modified by , or . Press to go to next parameter.
Press and hold can return to the previous parameter. Press + can exit parameter
setting status.
3. Alarm display:
The lower display window shows channel number. If high or low alarm occurs, the first digit from the left
of lower display window will show “H” or “L”, and flickers, and if over range occurs (for example, wire
broken for thermocouple input), the upper display window will show high or low limit valve, and the lower
display window flickers.
If only 2 input channels configured, then the upper and lower display window will show
the input values of channel 1 and 2 respectively. When over range occurs, the corresponding display
window will flickers.
The unit of Sc is 1/20000 of the scale of the corresponding RTD. At 0℃ , the total resistance of the two lead
wire of Pt100 or 0~400ohm should be less than 4ohm, and that of Cu50 should be less than 2ohm.
Otherwise, wire resistant compensation will not function. The smaller the resistance of the lead wire, can
provide more accurate measurement.
DIN mounted type (dimension E5) has no display window. It can input analog signals or input/output on-off
signals for host computer or PLC, and it can also work as a two-channel programmable re-transmitter.
E5 dimension instrument has one LED indication light. When the instrument is communicating with the host
computer, the light flashes with light on time different to light off time. When the instrument hasn’t received
signal from the host computer for 6 seconds, the indication light should flash with the same light on time and
light off time.
It means:
That the on-off period is as long as 1.6 second means no communication and no alarm (it can be treated
as normal);
The light flashing with period 0.6 second means no communication and general error occurs.
The light quickly flashing with period 0.3 second means no communication and severe error such as
input over range occurs.
The light keeping off means the instrument power off or damaged; the light keep on (longer than 8
seconds) means the instrument power on but damaged.
The parameters of E5 dimension instrument can be set by connecting external display to the 1394 socket.
Note: The 1394 socket of the instrument only supports Yudian external display.
The instrument can connect PC or PLC to monitoring or capture the data. We can provide the FREE protocol
for user or order our monitoring software-AIDCS. Please contact Yudian Sales Dept. for more detail.
By connecting 2 units of three-wire PT100 input, is can become the dry bulb, wet bulb humidity measurement.
1. Install J0 (RTD input module) in both M1 and M2 slot. Set Sn1=22, Sn2=42.
2. Atmospheric pressure and wind speed defined by parameter “Po” and “SPEd”
3. Initialize measurement by wrapping dry bulb with wet muslin, giving same condition with wet bulb
4. Once reading is stable, adjust parameter Sc2 to offset reading to 100%,
5. Remove wet muslin after the adjustment.
6. Recommended to set parameter (dIP1=1, dIP2=0) to have more stable reading with resolution 0.1℃
and 1%RH.
Yudian (H.K.) Automation Technology Co. Ltd.
Website: [Link] [Link]
Email: sales@[Link] Tel: +852-2770
8785 Fax: +852-2770 8796
PARAMETER DESCRIPTION
*x refers to channel number, can be 1~2, 1~4, 1~6 for AI-702M, 704M and 706M respectively.
For example:
ALP1=43, low limit alarm ([Link]) of channel 1 output to AL2,
ALP2=53, low limit alarm ([Link]) of channel 2 output to AU1,
and both high limit alarms([Link]) of both channel are sent to
AL1.
Low limit of
OPL retransmission When OUTP works as re-transmitter, OPL/OPH define the 0~110
current low/high limit of re-transmisson. The unit is 0.1mA.
For example, to transmit the channel 1 input 0~600℃ into
High limit of 4~20mA output, the parameters should be set as below:
OPH retransmission dIL1=0, dIH1=600, OPn=1, OPL=40, OPH=200 0~220
current
Atmospheric Defined atmospheric pressure, when dry bulb, wet bulb
Po 1~120.0
pressure humidity measurement activated. Unit = KPa
Defined wind speed, when dry bulb, wet bulb humidity
SPEd Wind speed 0.01~10.00
measurement was activated. Unit = m/S
Every instrument in the same communication line should
be assigned to different communication address. The
Communication communication applies AIBUS protocol. Every input
Addr 0 ~100
address channel takes one address. For example, if Cn=3 and
Addr=10, then the communication address 10~12 are
assigned to the instrument.
When COMM module interface is used for communication,
bAud defines the baud rate with range 300~19200bit/s.