Calculate Size of Neutral Earthing Transformer (NET) [Link]
Calculate Size of Neutral Earthing
Transformer (NET)
February 6, 2018
Calculate Size of Neutral Earthing Transformer (NET) having following
details
Main Transformer Detail :
Primary Voltage(PVL): 33KV
Secondary Voltage (SVL): 11 KV
Frequency(f)=50Hz
Transformer Capacitance / Phase(c1)=0.006 µ Farad
Transformer Cable Capacitance / Phase(c2)= 0003 µ Farad
Surge Arrestor Capacitance / Phase(c3)=0.25 µ Farad
Other Capacitance / Phase(c4)=0 µ Farad
Required for Neutral Earthing Transformer:
Primary Voltage of the Grounding Transformer (Vp) =11KV
Secondary Voltage of the Grounding Transformer (Vs) =240V
Neutral Earthing Transformer % Reactance (X%)=40%
% of Force field condition for Neutral Earthing Transformer (ff) =30%
Neutral Earthing Transformer overloading factor(Of)=2.6
Neutral Earthing Transformer Base KV (Bv) =240V=0.240KV
Calculation:
Phase to Neutral Voltage (Vp1) =SVL /1.732
Phase to Neutral Voltage (Vp1) =11 /1.732 = 6.35 KV
Phase to Neutral Voltage under Force Field Condition (Vf) =Vp +
(Vpxff)
Phase to Neutral Voltage under Force Field Condition (Vf)=6.35+ (6.35×30%)
=8.26KV
Total Zero Sequence Capacitance (C)=C1+C2+C3+C4
Total Zero Sequence Capacitance (C)=0.006+0.0003+0.25+0=0.47730 µ Farad
Total Zero Sequence Capacitance Reactance to Ground (Xc)=10×6 /
(2×3.14xfxC)
Total Zero Sequence Capacitance Reactance to Ground (Xc)=10×6 /
(2×3.14x50x0.47730)=6672.35 Ω/Phase
Capacitive charging current/phase (Ic)=Vf / Xc
Capacitive charging current/phase (Ic)=8.26×1000 / 6672.35 = 1.24Amp
Total Capacitive charging current (It) =3xIc
Total Capacitive charging current (It) =3xIc =3×1.24 =3.71Amp
Rating of Neutral Earthing Transformer (Pr)=VpxIt
1 of 3 13/03/2019, 9:25 pm
Calculate Size of Neutral Earthing Transformer (NET) [Link]
Rating of Neutral Earthing Transformer (Pr)=11×3.71=40.83KVA
Size of Neutral Earthing Transformer (P)=Pr/ Of
Size of Neutral Earthing Transformer (P)=40.83/ 2.6 = 16KVA
Residual Capacitive reactance (Xct) =Xc/3
l Capacitive reactance (Xct) = 6672.35 /3 =2224.12Ω
Turns Ratio of the Grounding Transformer (N)= Vp/Vs =11000/240 =45.83
Required Grounding Resistor value at Secondary side
(Rsec)=Xct/NxN
Required Grounding Resistor value at Secondary side (Rsec)=2224.12
/45.83×45.83 =1.059 Ω
Required Grounding Resistor value at primary side (Rp)=Xct
Grounding Resistor value at primary side (Rp)= 2224.12Ω
Neutral Earthing Transformer Secondary Current=P/Vs
Neutral Earthing Transformer Secondary Current=16000/230= 65.44Amp
Neutral Earthing Transformer Secondary Resistor Current (for 30
Sec)=1.3xItxN
Neutral Earthing Transformer Secondary Resistor Current (for 30
Sec)=1.3×3.71×45.83=221.18Amp
Neutral Earthing Transformer Reactance Base(Base X)=BvxBv/P/1000
Neutral Earthing Transformer Reactance Base(Base X)=0.24×0.24/11
/1000=3.67Ω
Neutral Earthing Transformer Reactance in PU (Xpu)=X% =40%=0.04Pu
Neutral Earthing Transformer Reactance (X)=Xpu x BaseX
Neutral Earthing Transformer Reactance (X)=0.04×3.67 =0.15Ω
Neutral Earthing Transformer X/R Ratio=X/Rsec
Neutral Earthing Transformer X/R Ratio=0.15/1.059 = 0.14
Fault current through Neutral (single line to ground fault)
(If)=Vp1/Rp
Fault current through Neutral (single line to ground fault)
(If)=6.35×1000/2224.12 =2.86Amp
Short time Rating of Neutral Earthing Transformer=PxOf =16×2.6 =41KVA
Result:
Rating of Neutral Earthing Transformer (P)=40.83/ 2.6 = 16KVA
Short time Rating of Neutral Earthing Transformer=41KVA
Ratio of Neutral Earthing Transformer =11000/240 Volt
Neutral Earthing Transformer Secondary Current=65.44A
Required Grounding Resistor value at primary side (Rp)=2224.12Ω
Required Resistance at secondary side (Rsec)= 1.059Ω
Neutral Earthing Transformer Secondary Resistor Current (for 30
Sec)= 221.2A
Filed under Uncategorized
About [Link]
2 of 3 13/03/2019, 9:25 pm
Calculate Size of Neutral Earthing Transformer (NET) [Link]
Jignesh Parmar has completed [Link] (Power System Control), B.E(Electrical). He is
member of Institution of Engineers (MIE) and CEng,India. Membership
No:[Link] has more than 16 years experience in Transmission -Distribution-
Electrical Energy theft detection-Electrical Maintenance-Electrical Projects
(Planning-Designing-Technical Review-coordination -Execution). He is Presently
associate with one of the leading business group as a Deputy Manager at
Ahmedabad,India. He has published numbers of Technical Articles in “Electrical
Mirror”, “Electrical India”, “Lighting India”,”Smart Energy”, “Industrial Electrix”
(Australian Power Publications) Magazines. He is Freelancer Programmer of Advance
Excel and design useful Excel base Electrical Programs as per IS, NEC, IEC,IEEE
codes. He is Technical Blogger and Familiar with English, Hindi, Gujarati, French
languages. He wants to Share his experience & Knowledge and help technical
enthusiasts to find suitable solutions and updating themselves on various
Engineering Topics.
3 of 3 13/03/2019, 9:25 pm