Kohler Generator
Kohler Generator
Models:
20-3250 kW
Controllers:
Decision-Makerr 550
TP-6200 10/12i
California Proposition 65
WARNING
Engine exhaust from this product contains chemicals
known to the State of California to cause cancer, birth
defects, or other reproductive harm.
6 TP-6200 10/12
Safety Precautions and Instructions
The equipment service requirements are very important Setup and Application Manual TP-6140
to safe and efficient operation. Inspect the parts often Service Parts Controllers TP-6780
and perform required service at the prescribed intervals. Program Loader Software Installation TT-1285
Maintenance work must be performed by appropriately SiteTecht Software Operation Manual TP-6701
skilled and suitably trained maintenance personnel Remote Serial Annunciator (RSA) TT-1377
familiar with generator set operation and service. Remote Serial Annunciator (RSA II) TT-1485
Controller Service Replacement TT-1310
The disk supplied with this generator set is a backup
copy of the generator set personality program Figure 1 Related Literature
containing data specific to the engine and alternator.
The engine and alternator data was preprogrammed in
the controller at the factory and no further use of the disk
should be necessary. Typically, your authorized
distributor stores this disk for possible future use such as
controller replacement or other circumstances requiring
a backup.
D Visit the Kohler Power Systems website at East China Regional Office, Shanghai
KohlerPower.com. Phone: (86) 21 6288 0500
Fax: (86) 21 6288 0550
D Look at the labels and stickers on your Kohler product India, Bangladesh, Sri Lanka
or review the appropriate literature or documents India Regional Office
included with the product. Bangalore, India
Phone: (91) 80 3366208
D Call toll free in the US and Canada 1-800-544-2444.
(91) 80 3366231
D Outside the US and Canada, call the nearest regional Fax: (91) 80 3315972
office. Japan, Korea
North Asia Regional Office
Headquarters Europe, Middle East, Africa Tokyo, Japan
(EMEA) Phone: (813) 3440-4515
Kohler Power Systems Fax: (813) 3440-2727
3 rue de Brennus
93200 Saint Denis Latin America
France Latin America Regional Office
Phone: (33) 1 49 178300 Lakeland, Florida, USA
Fax: (33) 1 49 178301 Phone: (863) 619-7568
Fax: (863) 701-7131
Asia Pacific
Power Systems Asia Pacific Regional Office
Singapore, Republic of Singapore
Phone: (65) 6264-6422
Fax: (65) 6264-6455
1 2 3 4 5 6
TP-6083-2
8 7
TP-6083-2
8 7
1. Generator set master switch, run/off-reset/auto positions 5. Digital display
(keyswitch option) 6. Keypad
2. Emergency stop switch 7. Operating guide
3. Alarm horn (see keypad for alarm silence) 8. Controller terminal strips (on circuit board)
4. Annunciator lamps (see keypad for lamp test)
Keypad Functions
Alarm (Horn) Off key silences the alarm horn at the
operator’s discretion. Place the generator set master
switch in the AUTO position before silencing the alarm TP-5829-2
horn. See Section 2.3.7, Controller Reset Procedure, Figure 1-5 Digital Display and Keypad
and Section 1.2.3, Switches and Controls.
AM/PM key provides time of day data entries when Alternator Output Displays (Menu 1)
programming.
AC Amps displays the alternator output current. The
Enter ↵ key provides confirmation entry when selecting display shows each line of 3-phase models.
menu or programming.
AC Volts displays the alternator output voltages. The
Lamp Test key tests the controller indicator lamps, display shows all line-to-neutral and line-to-line voltage
horn, and digital display. See Section 1.2.3, Switches combinations.
and Controls.
Alternator Duty Level displays the actual load kW
Menu down ↓ key provides navigation within menus divided by the nameplate kW rating as a percentage.
when necessary.
Frequency displays the frequency (Hz) of alternator
Menu right → key provides navigation within menus output voltage.
when necessary.
Hourmeter displays the generator set operating hours
Numeric 0--9 keys provide numeric data entries when loaded and unloaded for reference in scheduling
selecting menus or programming. maintenance.
Reset Menu key exits a menu, clears incorrect entries, KVA displays the total and individual L1, L2, and L3 kVA.
and cancels the auto-scroll feature.
KVAR displays the total and individual L1, L2, and L3
Stop Prog (Program) Run key allows the user to stop kVAR.
any previously programmed generator set run
Power Factor displays the kW/kVA and the individual
sequence. See Section 1.2.3, Switches and Controls.
line power factor values.
Yes/No keys provides data answer entries when
Watts displays the total and individual L1, L2, and L3
programming.
kilowatts.
Crankcase Pressure displays the engine crankcase Time Delay Displays (Menu 8)
pressure.
The time delays are user adjustable. See Section 2.8.8,
DC Volts displays the voltage of starting battery(ies). Menu 8—TIme Delays, for time delay adjustments. See
Section 1.3.1, Status Event and Fault Specifications, for
Fuel Pressure displays the fuel supply pressure. range and default settings.
Fuel Rate displays the calculated fuel consumption rate Crank On/Crank Pause displays the time allocated for
based on fuel injector outputs. generator set crank on and crank pause in
minutes:seconds.
Fuel Temperature displays the fuel supply
temperature. Engine Cooldown displays the time delay for engine
cooldown while the master switch is in the AUTO or RUN
Oil Level displays the engine oil level as a percent of full positions and not in the idle mode.
capacity.
Engine Start displays the time delay before the
Oil Pressure displays the engine oil pressure. generator set starts while the master switch is in AUTO
or RUN positions.
Oil Temperature displays the engine oil temperature.
Overcrank Shutdown (Number of) Crank Cycles
RPM (Tachometer) displays the engine speed. displays the number of unsuccessful crank cycles
(crank on/crank pause) before the generator set shuts
Used Last Run displays the accumulated amount of down on an overcrank fault.
fuel used since last reset by the engine DDEC reader.
Overvoltage displays the time delay before the
Operational Record Displays (Menus 4 and 5) generator set shuts down because of an overvoltage
condition.
The operational record displays events since last reset.
See Section 2.8.4, Menu 4—Operational Records, for Starting Aid displays the engine starting aid activation
resetting procedure. time.
Engine Start Countdown displays the time remaining Undervoltage displays the time delay before the
before the next generator set startup. generator set shuts down because of an undervoltage
condition.
1 2 3
TP-6083-2
ADV-6533-A
ADV-6533-A
Note: The engine ECM may limit the crank cycle even if
the controller is set to a longer time period.
6
ADV-6533-A
Refer to
Calibration Menu Digital Display Range Setting Default Selection
Voltage Adjustment 11 VOLT ADJ ±10% of system voltage— System voltage
Version 2.10
±20% of system voltage—
Version 2.11 or higher
Underfrequency Unload 11 FREQUENCY 40 to 70 Hz 1 Hz below system frequency (ECM)
Frequency Setpoint SETPOINT 2 Hz below system frequency (non-ECM)
Underfrequency Unload 11 SLOPE 0--10% of rated voltage 3.1% of system voltage
Slope volts per cycle
Reactive Droop 11 VOLTAGE 0--10% of system voltage 4% of system voltage
DROOP
VAR Control 11 KVAR ADJ 0 to rated kVAR generating 0
0 to 35% of rated kVAR absorbing
Power Factor (PF) Adjust 11 PF ADJ 0.7 to 1.0 leading 0.8 lagging
Control 0.6 to 1.0 lagging
Controller Gain 11 REGULATOR 1--10000 100
GAIN
VAR/PF Gain or Utility 11 VAR/PF GAIN 1--10000 100
Stability
1.3.2 Voltage Regulator and Calibration Voltage Adjustment. The voltage adjustment allows
Specifications the user to enter the desired generator set output level.
This regulated level setting is the average of the three
The 550 controller has a voltage regulation function that line-to-line voltages in three-phase configurations or
is internal to the processor. This means that no external L1-to-L2 in single phase configurations.
voltage regulator is necessary. The voltage regulation of
the controller uses root mean square (rms) sensing for Submenus display the individual line-to-line voltages.
fast response to changes in indicated and regulated These voltages are for reference only and are relevant in
voltages resulting in excellent regulation accuracy. unbalanced load conditions. The voltage adjust setpoint
can be changed to accommodate an important phase in
RMS voltage regulation is available for both paralleling an unbalanced system.
and utility application to control changes in the reactive
loads due to load changes, prime mover speed Underfrequency Unload Frequency Setpoint. This
variation, thermal drift, and other variations. See adjustment affects the voltage droop (volts per Hz) when
Figure 1-13 for data on the 550 controller voltage load is applied and underfrequency occurs. The
regulation. Refer to Appendix C to customize underfrequency unload setting defines the setpoint
adjustments for specific applications. where underfrequency starts. Any frequency below the
setpoint causes the voltage to drop thus reducing the
load allowing the engine speed to recover according to
1.3.3 Voltage Regulator Adjustments the underfrequency unload slope setting.
The descriptions of the voltage regulator adjustments
and features follow. See Appendix C, Voltage Regulator
Definitions and Adjustments, for additional information.
2.1 Prestart Checklist Fuel Level. Check the fuel level and keep the tank(s) full
to ensure adequate fuel supply.
To ensure continued satisfactory operation, perform the
following checks or inspections before or at each Oil Level. Maintain the oil level at or near, not over, the
startup, as designated, and at the intervals specified in full mark on the dipstick.
the service schedule. In addition, some checks require
Operating Area. Check for obstructions that could
verification after the unit starts.
block the flow of cooling air. Keep the air intake area
Air Cleaner. Check for a clean and installed air cleaner clean. Do not leave rags, tools, or debris on or near the
element to prevent unfiltered air from entering engine. generator set.
Air Inlets. Check for clean and unobstructed air inlets. 2.2 Exercising Generator Set
Battery. Check for tight battery connections. Consult Operate the generator set under load once each week
the battery manufacturer’s instructions regarding for one hour. Perform the exercise in the presence of an
battery care and maintenance. operator when the generator set does not have a
programmed exercise mode or an automatic transfer
Controller. After reconnecting the battery, set the switch with an exercise option.
controller time and date. See Section 2, Menu 14—
Programming Mode On and Menu 6—Time and Date. During the exercise period apply a minimum of 35% load
based on the nameplate standby rating, unless
Coolant Level. Check the coolant level according to the otherwise instructed in the engine operation manual.
cooling system maintenance information.
The operator should perform all of the prestart checks
Note: Block Heater Damage. The block heater will fail before starting the manual exercise procedure. Start the
if the energized heater element is not immersed in generator set according to the starting procedure in
coolant. Fill the cooling system before turning on Section 2.3, Controller Operation. While the generator
the block heater. Run the engine until it is warm, set is operating, listen for a smooth-running engine and
and refill the radiator to purge the air from the visually inspect generator set for fluid or exhaust leaks.
system before energizing the block heater.
The generator set exercise time can be programmed for
Drive Belts. Check the belt condition and tension of the a one-time exercise period. See Menu 4—Operational
radiator fan, water pump, and battery charging Records. The generator set controller does not provide
alternator belt(s). weekly scheduled exercise periods. For scheduled
exercise periods, refer to the automatic transfer switch
Exhaust System. Check for exhaust leaks and
(if equipped) literature.
blockages. Check the silencer and piping condition and
check for tight exhaust system connections.
The controller overrides the idle speed function when Note: After energizing the controller using the prime
the generator set is signaled to start while in the AUTO power switch, set the controller time and date.
position. This override provides emergency generator See Section 2.8.6, Menu 6—TIme and Date.
set power in the event of a utility power failure. When the
utility power returns and the generator set is signalled to Stop the generator set using the stopping procedures in
stop, the generator set continues to run for the duration Section 2.3.2 before placing the generator set in the
of the idle mode period when the idle mode is active. prime power mode. Move the prime power switch
When the idle mode is not active, the generator set will located on the back of the controller to the
shut down in the normal stopping mode including time CONTROLLER OFF position. When the generator set
delays. is is the prime power mode, all controller functions
including the digital display, LEDs, alarm horn, and
See Menu 9—Input Setup to activate the idle speed communications are inoperative.
function as a user-defined digital input. The idle speed
feature requires an ECM-equipped engine with the idle
speed function.
Common Protective Relay Output. The lamp Figure 2-1 High Battery Voltage Specs
illuminates when a common protective relay fault
High Coolant Temperature Warning. The lamp
occurs. The local display shows common pr output.
illuminates and the alarm horn sounds when the engine
(Paralleling applications only.)
coolant temperature approaches the shutdown range.
Customer Auxiliary (Warning). The lamp illuminates The local display shows hi cool temp warning.
and the alarm horn sounds when an auxiliary digital or
High Oil Temperature Warning. The lamp illuminates
analog inputs signals the controller. The user can define
and the alarm horn sounds when the engine high oil
inputs as shutdowns or warnings. The local display
temperatuare approaches the shutdown range. The local
shows digital input D01-D21 or analog input A01-A07.
display shows hi oil temp warning (DDC/MTU models with
Using the remote communications package, the user MDEC/ADEC and Waukesha-powered models only).
can label the auxiliary functions. The controller displays
Idle (Speed) Mode. The lamp illuminates when in the
the selected name instead of digital input D01-D21 or
idle (speed) mode. The local display shows idle mode
analog input A01-A07.
active.
Defined Common Faults. The lamp illuminates and
Intake Air Temperature Warning. The lamp illuminates
the alarm horn sounds when one or more of the
and the alarm horn sounds when the engine intake air
(user-selected) defined common faults are energized.
temperature approaches the shutdown range. The local
The local display shows defined common fault.
display shows intake air temp warn (DDC/MTU models
Detonation Warning. The lamp illuminates and the with MDEC/ADEC) and 03 intake air temp warn
alarm horn sounds when the engine detects combustion (Waukesha-powered models).
system detonation. The local display shows deton
Load Shed. The lamp illuminates when the generator
warning. (Waukesha-powered models only.)
set’s total kW load exceeds the programmed level for
ECM Yellow Alarm. The lamp illuminates and the alarm more than the load shed time. When the load shed alarm
horn sounds when ECM yellow alarm signals the sounds and resets more than twice in 1 minute, the load
controller. The local display shows ECM yellow alarm. shed warning lamp circuit latches and remains on until
This fault only relates to the DDC/MTU engine with the generator set shuts down. The local display shows
MDEC/ADEC. The user can navigate the menus to load shed kW over.
access the fault code. The engine operation manual
provides the fault code descriptions.
80%--95%
Generator Overspeed Overspeed Default 10 sec. 90% of nominal 80% of nominal
of nominal
Set Time Delay Range Hz Setting Hz
Frequency Hz Figure 2-6 Underfrequency Specs
60 0.25 sec. 65--70 70
Undervoltage. The lamp illuminates and the unit shuts
50 0.25 sec. 55--70 70 down when the voltage falls below the undervoltage
setting for the time delay period. The local display shows
Figure 2-4 Overspeed Specs
undervoltage. Undervoltage specifications follow. See
Overvoltage. The lamp illuminates and the unit shuts Figure 2-7.
down when the voltage exceeds the overvoltage setting
for the time delay period. The local display shows Undervoltage
overvoltage. Overvoltage specifications follow. See Undervoltage Default Setting Undervoltage
Setting Time Delay w-o/Parallelin Default Setting
Figure 2-5.
Range Range g w/Paralleling
Use the following procedure to restart the generator set 9. Silence the controller alarm horn by pressing the
after a system shutdown or to clear a warning lamp alarm off key.
condition. This procedure includes the resetting of the
optional remote annunciator and the audiovisual alarm. 10. Reconnect the generator set load via the line circuit
breaker or automatic transfer switch.
Refer to Section 2.3.3, Emergency Stop Switch Reset
Procedure, to reset the generator set after an 11. Move the generator set master switch to the AUTO
emergency stop. position for startup by the remote transfer switch or
the remote start/stop switch.
1. Move the generator set master switch to the AUTO When equipped, move the remote annunciator
position, if not already done. and/or audiovisual alarm switch to the NORMAL
position.
2. Silence the controller alarm horn by pressing the
alarm off key.
2.4 Menu List Summary
When equipped, the optional remote annunciator
and/or audiovisual alarm horn and lamp activate. Use the Menu List Summary section on the following
Move the alarm switch to the SILENCE position to pages after reading and understanding the features of
stop the alarm horn. The lamp stays lit. the keypad. See Section 1.2.2, Digital Display and
Keypad.
3. Disconnect the generator set load using the line
circuit breaker or automatic transfer switch. The Menu List Summary provides a quick reference to
the digital display data. Some digital display data may
4. Correct the cause of the fault shutdown or warning. not be identical to your display due to generator set
See the Safety Precautions and Instructions application differences. The closed bullet items
section of this manual before proceeding. represent main level data and the open bullet items are
sub-level data.
5. Start the generator set by moving the generator set
master switch to the OFF/RESET position and then Section 2.7, Reviewing the Menu Displays, provides a
to the RUN position. digital display menu overview and explains the
When equipped, the remote annunciator and/or navigation using the down and right arrow keys.
audiovisual alarm horn sounds when the alarm
switch is in the NORMAL position. When Section 2.8, Local Programming Mode On, contains the
necessary, move the alarm switch to the SILENCE keystroke details of each menu when programming.
position to stop the alarm horn. The lamp turns off.
User Inputs. Available user inputs are dependent on
6. Test operate the generator set to verify correction factory-reserved inputs for specific engine types, engine
of the shutdown cause. controls, and paralleling applications. See Figure 2-8
for analog and digital inputs that are not user-selectable.
7. Move the generator set master switch to the
OFF/RESET position to stop the generator set.
Figure 2-8 User Inputs (X) and Factory-Reserved Inputs (as shown)
(Question) ? asked by the control firmware; answer the D Fixed Phase when entry is beyond the range of
question by pressing the yes/no, numeric digit, or am/pm limited entries for the respective alternator. Occurs
key. when the alternator is not rated for the value entered.
Updated parameter files may be available by
Wait for System Reset (6 Sec) appears while the contacting an authorized service dealer/distributor.
EEPROM initializes.
Generator Set
Controller,
RS-232 to RS-485
Transfer Switch
port converter
Control, or
RS-485 Power Monitor
Personal up to
Computer 1220 m
(4000 ft.)
User Operating Mode Selection Menu 13—Communications Settings Menu 14—Programming Mode
User On Local Remote Single Programming Local Programming Remote
Activity Access Source Line? LAN? or LAN? Mode Off? Mode? Programming Mode?
Controller No No No Yes No No
Monitor
Direct PC Yes Yes No Yes No No
only
PC via Telephone Lines Yes No Yes Yes No No
Controller No No No No Yes No
Monitor
and Direct PC Yes Yes No No No Yes
Program PC via Telephone Lines Yes No Yes No No Yes
Remote Area Network The 550 controller can be used as an RS-232 to RS-485
port converter in a LAN network if the 550 controller is
A PC connects to a modem. The devices connect to a located within 15 m (50 ft.) of the device modem. This
LAN network. The PC communicates to the devices via configuration is the Remote LAN Conv option.
a telephone network that is interfaced to the LAN
Generator Set
Modem Modem Controller or
Transfer Switch
Control
RS-232 RS-232
Personal up to Telephone up to
Computer 15 m (50 ft.) Lines 15 m (50 ft.)
Note: Press any key on the keypad to activate the 6 Time and Date X
controller panel display. The panel display turns
7 Generator System X
off 5 minutes after the last keypad entry.
8 Time Delays X
Note: Press the Reset Menu key to clear error
messages. 9 Input Setup X
10 Output Setup X
Note: Press the Menu Right → key prior to entering
decimal values where necessary. 11 Voltage Regulator X
12 Calibration X
Menus displaying the # symbol represent one of the
following data types: 13 Communications X
14 Programming Mode X
D System-calculated data
D System-measured data 15 Protective Relays X
D User-entered data 20 Factory Setup X
Menus displaying the ? symbol require the user to enter Figure 2-17 Menu Displays for Viewing and Adjusting
data.
VOLTS & AMPS → V & A SUMMARY → POWER KW → POWER KVAR → POWER KVA →
L1-L2 VOLTS # V L1-L2 L2-L3 L3-L1 TOTAL KW # TOTAL KVAR # TOTAL KVA #
L1 AMPS # # # # PF # LEADING/LAGGING ABSORBING/GENERATING
L1-L0 VOLTS # For the auto-scroll function, L3 KW (3 PH) # L3 KVAR (3 PH) # L3 KVA #
L1 AMPS # press ENTER at PF # LEADING/LAGGING ABSORBING/GENERATING
V & A SUMMARY menu.
L3-L0 VOLTS #
L3 AMPS #
FREQUENCY # HZ
VOLTS & AMPS → V & A SUMMARY → POWER KW → POWER KVAR → POWER KVA →
L1-L2 VOLTS # V L1-L2 L1-L0 L2-L0 TOTAL KW # TOTAL KVAR # TOTAL KVA #
L1 AMPS # # # # PF # LEADING/LAGGING ABSORBING/GENERATING
FREQUENCY # HZ
Menu 2 Overview
MENU 2
ENGINE MONITORING
(DDEC/JDEC/EMS2/EDC3-
Equipped Engines only)
ENGINE MONITORING → ENGINE MONITORING →
BASIC DETAILED
OIL PRESSURE # PSI ENGINE FUEL → ENGINE COOLANT → ENGINE OIL → ENGINE MISC →
COOLANT TEMP #F
INTAKE AIR #F FUEL PRES # PSI COOLANT PRES # PSI OIL PRES # PSI ECM BATT VDC #
OIL TEMP (Waukesha) #F FUEL TEMP #F COOLANT TEMP #F OIL TEMP #F AMBIENT TEMP #F
ENGINE RPM # CHG AIR PRES # PSI COOLANT LEVEL #% OIL LEVEL #% ENGINE MODEL NO.
LOCAL BATT VDC # CHG AIR TEMP #F CRANKCASE PRES # PSI #
ENGINE WARMED UP
ECM FAULTS CODES #
#F
INTAKE AIR #F FUEL PRES # PSI OIL PRES # PSI ECU SUPPLY VDC #
OIL TEMP (Waukesha) #F FUEL TEMP #F OIL TEMP #F AMBIENT TEMP #F
* While these menu displays do appear on the 550 controller, the engine ECM is not currently set up to provide this data.
ANALOG 01 #
(USER DEFINED DESC)
ANALOG 03 #
(USER DEFINED DESC)
ANALOG 02 #
(USER DEFINED DESC)
ANALOG 04 #
(USER DEFINED DESC)
ANALOG 03 #
(USER DEFINED DESC) ANALOG 05 #
(USER DEFINED DESC)
ANALOG 04 #
(USER DEFINED DESC) ANALOG 06 #
(USER DEFINED DESC)
ANALOG 05 #
(USER DEFINED DESC) ANALOG 07 #
(USER DEFINED DESC)
ANALOG 06 #
(USER DEFINED DESC)
Menu 3 Overview (Waukesha Engines)
ANALOG 07 # MENU 3
(USER DEFINED DESC) ANALOG MONITORING
ANALOG 05 #
(USER DEFINED DESC)
ANALOG 06 #
(USER DEFINED DESC)
ANALOG 07 #
(USER DEFINED DESC)
Menu 4 Overview
MENU 4 NO. OF STARTS #
OPERATIONAL RECORDS LAST MAINT ##-###-##
NO. OF STARTS #
OPERATING DAYS #
LAST MAINT ##-###-##
Menu 6 Overview
MENU 6
TIME AND DATE
DATE ??-???-??
SYSTEM VOLTAGE
LINE-LINE ?
SYSTEM FREQ # HZ
KW RATING ?
RATED CURRENT #
OVERFREQUENCY
?% # HZ
UNDERFREQUENCY
?% # HZ
OVERSPEED
? HZ # RPM
Menu 8 Overview
MENU 8
TIME DELAYS
COOLDOWN TEMPERATURE
OVERRIDE Y/N
OVERCRANK SHUTDOWN
CRANK CYCLES ?
The user must enable the programming mode to edit the Shutdown Type A and Shutdown Type B. Choose
display. shutdown type A for standard shutdown where red
lamp illuminates and alarm horn sounds. Choose
See Section 2.8.9 to change settings in this menu. shutdown type B for shutdown where air damper
indicator RDO-23 energizes for two seconds, red lamp
Note: Press the down arrow to move to the start of the illuminates, and alarm horn sounds.
next input setup.
Analog Input A06—Analog Speed Adjust (VSG).
Note: See Figure 2-8 in User Inputs for factory Analog Input A06 may be used for analog speed adjust
reserved inputs which are not user selectable. when external control of engine speed is desired such as
paralleling applications or closed transition ATS. To
D Enabled. The controller will ignore the input until the
utilize this capability, the input must be calibrated. Refer
inhibit time expires. If the inhibit time is set to zero, the
to 2.8.12, Menu 12—Calibration.
input is monitored at all times, even when the
generator is not running. Analog inputs have Note: This feature is supported for Doosan, GM, and
separate warning and shutdown enabled choices. Volvo engines only.
D Inhibit Time Delay. The inhibit time delay is the time Analog Input A07—Analog Voltage Adjust. Analog
period following crank disconnect during which the voltage adjust is a feature that the user may choose to
generator set stabilizes and the controller does not enable. The input designated for use as Analog Voltage
detect the fault or status event. This menu indicates Adjust is analog input A07.
whether or not the input is enabled. If the input is not
enabled, the controller will ignore this input signal. Enable Analog Voltage Adjust through Menu 11.
The inhibit time delay range is from 0 to 60 seconds. Additionally, Monitor 2 or Monitor 3 may be used to
enable Analog Voltage Adjust by entering the proper
D Time Delay (shutdown or warning). The time delay description (Analog Volt Adjust) for A07. When Analog
follows the inhibit time delay. The time delay is the Voltage Adjust is enabled, the description for A07 is
time period between when the controller first detects Analog Volt Adjust. Changing the description using
the fault or status event and the controller warning or Monitor 2 or Monitor 3 disables the analog voltage
shutdown lamp illuminates. The delay prevents any adjust feature.
nuisance alarms. The time delay range is from 0 to
60 seconds. When Analog Voltage Adjust is enabled, no warning or
shutdown may be enabled for A07.
Additional Analog Input Entries. The analog input
selection typically requires entering four values—low Note: If the analog input A07 description does not
warning, high warning, low shutdown, and high match Analog Volt Adjust, input A07 will not
shutdown. function as the voltage adjust.
Battle Switch/Fault Shutdown Override Switch. The Identification and Descriptions. Descriptions for user
battle switch function forces the system to ignore normal inputs (auxiliary analog or auxiliary digital) may be
fault shutdowns such as low oil pressure and high entered using the Monitor II software accessory where
engine temperature. The battle switch does not override the user determines the descriptions in upper and lower
the emergency stop and overspeed shutdown. When case.
the battle switch function is enabled the generator set
DIGITAL INPUT 01 → DIGITAL INPUT 01 → DIGITAL INPUT 01 → DIGITAL INPUT 01 → DIGITAL INPUT 01 →
(USER DEFINED DESC) (see Group A) YES/NO ENABLED YES/NO INHIBIT TIME ?:?? DELAY TIME ?:??
Menu 10 Overview
MENU 10
OUTPUT SETUP
COMMON FAULT Y/N COMMON FAULT Y/N COMMON FAULT Y/N COMMON FAULT Y/N
(see Group B) (see Group C) (see Group D)LO WARNING→ HI WARNING→
Press down arrow to scroll Press down arrow to scroll Press down arrow to scroll COMMON FAULT Y/N
through available faults. through digital auxiliary through analog auxiliary LO SHUTDOWN→
inputs. inputs.
Press down arrow to scroll Press down arrow to scroll Press down arrow to scroll
RELAY DRV OUT Y/N
through available RDO through RDO digital auxiliary through RDO analog
LO SHUTDOWN→
faults. inputs. auxiliary inputs.
Menu 11 displays setup of the voltage regulator functions Note: The individual line-to-line voltages are displayed
including line-to-line voltages, underfrequency unloading for review purposes only.
(volts per Hz), reactive droop, power factor, and kVAR
adjustments. Note: Voltage regulator gain is used for adjusting
voltage stability and/or response.
The user must enable the programming mode to edit the
display. Note: Utility gain is used for VAR or PF stability adjust
while paralleling to a utility.
Menu 11 Overview
MENU 11
VOLTAGE REGULATOR
AVG L-L V # → L1-L2 VOLTS → L2-L3 VOLTS (3 PHASE) → L3-L1 VOLTS (3 PHASE) →
VOLT ADJ ?.? # # #
RESET REGULATOR
DEFAULTS? Y/N
Menu 12 Overview
MENU 12
CALIBRATION
GEN VOLTAGE LN GEN VOLTAGE LL GEN AMPS LOAD VOLTAGE LN RESTORE DEFAULTS Y/N
GEN L2--L0 V # GEN L2--L3 V (3 PHASE) # GEN L2 AMPS (3 PHASE) # LOAD L3--L0 V #
CALIB REF ? CALIB REF ? CALIB REF ? CALIB REF (PARALLEL) ?
CALIBRATE REGULATOR?
Y/N
ANALOG XX # SCAL 1 #V
SCALE VALUE 1 ? SCAL 2 #V
ANALOG XX # SCAL 1 #V
SCALE VALUE 2 ? SCAL 2 #V
Menu 13 Overview
MENU 13
COMMUNICATIONS
PROTOCOL → PROTOCOL →
KBUS MODBUS
SYSTEM ID ?
(Remote Connections)
Menu 14 Overview
MENU 14
PROGRAMMING MODE
Menu 15 Overview
MENU 15
PROTECTIVE RELAYS
SYNC VOLTAGE MATCH → SYNC FREQ MATCH → SYNC PHASE MATCH → TIME DELAY →
? VAC ? HZ ? DEG ? SEC
Menu 20 Overview
MENU 20
FACTORY SETUP
FINAL ASSEMBLY
CLOCK NO ?
OPERATING DAYS #
MODEL NO #
SPEC NO #
GENSET SERIAL NO #
ALTERNATOR PART NO #
ENGINE PART NO #
SERIAL NO #
CONTROLLER SERIAL NO
CODE VERSION #
COPYRIGHT XXXX
FINAL ASSEMBLY
CLOCK NO ?
OPERATING DAYS #
MODEL NO #
SPEC NO #
GENSET SERIAL NO #
ALTERNATOR PART NO #
ENGINE PART NO #
CONTROLLER SERIAL NO
CODE VERSION #
COPYRIGHT XXXX
MENU 1
GENERATOR MONITORING
Displays the menu number and name.
L1-L2 VOLTS #
L1 AMPS #
Displays L1 and L2 volts and L1 amps.
L2-L3 VOLTS #
Displays L2 and L3 volts and L2 amps.
L2 AMPS #
L3-L1 VOLTS #
L3 AMPS #
Displays L3 and L1 volts and L3 amps.
L1-L0 VOLTS #
L1 AMPS #
Displays L1-L0 volts and L1 amps.
L2-L0 VOLTS #
L2 AMPS #
Displays L2 and L0 volts and L2 amps.
L3-L0 VOLTS #
L3 AMPS #
Displays L3-L0 volts and L3 amps.
MENU 1
Returns the user to the menu number and name.
GENERATOR MONITORING
V & A SUMMARY →
Displays the volts and amps summary heading.
A L1 L2 L3
# # # Displays L1, L2, and L3 amps.
V & A SUMMARY →
Returns the user to the volts and amps summary heading.
POWER KW →
Displays the power kilowatt heading.
TOTAL KW #
Displays total kilowatts and leading or lagging power factor.
PF # LEADING/LAGGING
L1 KW #
PF # LEADING/LAGGING
Displays total L1 kilowatts and leading or lagging power factor.
L2 KW #
Displays total L2 kilowatts and leading or lagging power factor.
PF # LEADING/LAGGING
TOTAL KW #
% OF RATED KW # Displays the total kW and percent of rated kilowatts.
POWER KW →
Returns the user to the power kilowatt heading.
POWER KVAR →
Displays the power kVAR heading.
TOTAL KVAR #
ABSORBING/GENERATING
Displays total kVAR, absorbing or generating.
L1 KVAR #
ABSORBING/GENERATING
Displays L1 kVAR, absorbing or generating.
L2 KVAR #
ABSORBING/GENERATING Displays L2 kVAR, absorbing or generating.
L3 KVAR #
ABSORBING/GENERATING
Displays L3 kVAR, absorbing or generating. (3 ph. only)
POWER KVAR →
Returns the user to power kVAR heading.
POWER KVA →
Displays the power kVA heading.
TOTAL KVA #
Displays total kVA.
L1 KVA #
Displays L1 kVA.
L2 KVA #
Displays L2 kVA.
L3 KVA #
Displays L3 kVA.
POWER kVA →
Returns the user to power kVA heading.
MENU 1
GENERATOR MONITORING
Displays the menu number and name.
L1-L2 VOLTS #
L1 AMPS #
Displays L1 and L2 volts and L1 amps.
L1-L2 VOLTS #
L2 AMPS #
Displays L1 and L2 volts and L2 amps.
L1-L0 VOLTS #
L1 AMPS #
Displays L1-L0 volts and L1 amps.
L2-L0 VOLTS #
L2 AMPS #
Displays L2 and L0 volts and L2 amps.
MENU 1
Returns the user to the menu number and name.
GENERATOR MONITORING
V & A SUMMARY →
Displays the volts and amps summary heading.
A L1 L2
# # Displays L1 and L2 amps.
V & A SUMMARY →
Returns the user to the volts and amps summary heading.
POWER KW →
Displays the power kilowatt heading.
TOTAL KW #
Displays total kilowatts and leading or lagging power factor.
PF # LEADING/LAGGING
L1 KW #
PF # LEADING/LAGGING
Displays total L1 kilowatts and leading or lagging power factor.
L2 KW #
Displays total L2 kilowatts and leading or lagging power factor.
PF # LEADING/LAGGING
TOTAL KW #
% OF RATED KW # Displays the total kW and percent of rated kilowatts.
POWER KW →
Returns the user to the power kilowatt heading.
POWER KVAR →
Displays the power kVAR heading.
TOTAL KVAR #
ABSORBING/GENERATING
Displays total kVAR, absorbing or generating.
L1 KVAR #
ABSORBING/GENERATING
Displays L1 kVAR, absorbing or generating.
L2 KVAR #
ABSORBING/GENERATING Displays L2 kVAR, absorbing or generating.
POWER KVAR →
Returns the user to power kVAR heading.
POWER KVA →
Displays the power kVA heading.
TOTAL KVA #
Displays total kVA.
L1 KVA #
Displays L1 kVA.
L2 KVA #
Displays L2 kVA.
POWER kVA →
Returns the user to power kVA heading.
Key
Entry Display Description
MENU 2
Displays the menu number and name.
ENGINE MONITORING
ENGINE MONITORING →
Displays the basic engine monitoring heading.
BASIC
ENGINE RPM #
Displays the engine rpm and local battery VDC.
LOCAL BATT VDC #
HCT WARN #F
Displays the high coolant temperature warning and shutdown
HCT SDOWN #F
setpoints.
ENGINE WARMED UP
#F Displays the engine warmed up temperature setpoint.
MENU 2
ENGINE MONITORING Returns the user to the menu number and name.
ENGINE MONITORING →
Returns the user to basic engine monitoring heading.
BASIC
ENGINE MONITORING →
Returns the user to the detailed engine monitoring heading.
DETAILED
ENGINE FUEL →
Displays the engine fuel subheading.
ENGINE COOLANT →
Displays the engine coolant subheading.
COOLANT LEVEL #%
Displays the coolant level as a percent of full capacity.
ENGINE COOLANT →
Returns the user to engine coolant subheading.
ENGINE OIL →
Displays the engine oil subheading.
OIL LEVEL #% Displays the oil level as a percent of full capacity and crankcase
CRANKCASE PRES # PSI pressure.
ENGINE OIL →
Returns the user to engine oil subheading.
ENGINE MISC →
Displays the miscellaneous engine subheading.
UNIT NO. #
ECM S/N # Displays the unit number and ECM serial number.
ENGINE MISC →
Returns the user to the miscellaneous engine subheading.
ENGINE MONITORING →
Returns the user to the detailed engine monitoring heading.
DETAILED
ENGINE FUEL →
Displays the engine fuel subheading.
ENGINE OIL →
Displays the engine oil subheading.
ENGINE OIL →
Returns the user to engine oil subheading.
ENGINE MISC →
Displays the miscellaneous engine subheading.
ECU HOURS #
Displays the ECU operating hours.
ENGINE MISC →
Returns the user to the miscellaneous engine subheading.
* While these menu displays do appear on the 550 controller, the engine ECM is not currently set up to provide this data.
The User Defined Desc display refers to a description Note: If the analog display shows O/R (out of range), no
entered into the controller using the PC software. This input is connected.
description remains as the display for future review until
changed by the PC software user. The display has Note: Some data require entry using a PC in the
20 characters maximum. Remote Programming mode. See the monitor
software operation manual for details.
Analog Voltage Adjust. When the analog voltage
adjust option is enabled (see Menu 11), analog input 7 is Note: See Figure 2-8 in User Inputs for factory
predefined as voltage adjust. The voltage of this input reserved inputs which are not user selectable.
will define the adjustment from the setting in Menu 11,
Voltage Regulator. The normal analog input range of Note: This menu is for monitoring only; no adjustments
0.5 to 4.5 corresponds to a ±10% of system voltage. The or user settings can be entered.
MENU 3
Displays the menu number and name.
ANALOG MONITORING
ANALOG 01 #
Displays analog 01 and the user-defined description.
(USER DEFINED DESC)
ANALOG 02 #
(USER DEFINED DESC) Displays analog 02 and the user defined description.
ANALOG 03 #
Displays analog 03 and the user-defined description.
(USER DEFINED DESC)
ANALOG 04 #
Displays analog 04 and the user-defined description.
(USER DEFINED DESC)
ANALOG 05 #
Displays analog 05 and the user-defined description.
(USER DEFINED DESC)
ANALOG 06 #
Displays analog 06 end the user-defined description.
(USER DEFINED DESC)
ANALOG 07 #
Displays analog 07 and the user-defined description.
(USER DEFINED DESC)
OR
ANALOG 07 # Displays analog 07 voltage adjustment VDC value when analog
ANALOG VOLT ADJUST voltage adjust is enabled.
MENU 3
Displays the menu number and name.
ANALOG MONITORING
ANALOG 03 #
Displays analog 03 and the user-defined description.
(USER DEFINED DESC)
ANALOG 04 #
Displays analog 04 and the user-defined description.
(USER DEFINED DESC)
ANALOG 05 #
Displays analog 05 and the user-defined description.
(USER DEFINED DESC)
ANALOG 06 #
Displays analog 06 end the user-defined description.
(USER DEFINED DESC)
ANALOG 07 #
Displays analog 07 and the user-defined description.
(USER DEFINED DESC)
OR
Displays analog 07 voltage adjustment VDC value when this option is
ANALOG 07 #
enabled. Note: This function may be overridden by changing the
ANALOG VOLT ADJUST
description using the optional Monitor III software or by disabling in
Menu 11.
ANALOG MONITORING Returns user to analog monitoring heading.
MENU 3 Note: Enter data using a PC in the Remote Programming Mode.
MENU 3
Displays the menu number and name.
ANALOG MONITORING
ANALOG 05 #
Displays analog 05 and the user-defined description.
(USER DEFINED DESC)
ANALOG 06 #
Displays analog 06 end the user-defined description.
(USER DEFINED DESC)
ANALOG 07 #
Displays analog 07 and the user-defined description.
(USER DEFINED DESC)
OR
Displays analog 07 voltage adjustment VDC value when this option is
ANALOG 07 #
enabled. Note: This function may be overridden by changing the
ANALOG VOLT ADJUST
description using the optional Monitor III software or by disabling in
Menu 11.
ANALOG MONITORING Returns user to analog monitoring heading.
MENU 3 Note: Enter data using a PC in the Remote Programming Mode.
MENU 4
Displays the menu number and name.
OPERATIONAL RECORDS
NO. OF STARTS #
Displays the number of engine starts.
RUN TIME HR:MN→ Displays the run time (hours:minutes) feature. When required, use
??:?? the numeric keys to enter the selected run time (hours:minutes) and
press the Enter key.
RUN TIME HR:MN→ Confirms entry and displays the selected run time (hours:minutes).
##:## The generator set will start after activation. Note: Activate the
generator set run time feature by pressing the Yes and Enter keys.
See the following steps.
ENGINE START? Y/N→ Returns the user to the start and countdown subheading. Enter Yes
COUNTDOWN ##:## to start the generator set.
RUN TIME HR:MN→ Confirms the entry. The generator set will begin cranking and run
##:## based on the run time (hours:minutes) period and all previously
established time (hours:minutes) delays from Menu 8—Time Delays.
Note: Press the STOP PROG RUN key to stop the generator set
when in the run time mode, if necessary.
RECORDS MAINT → Displays the records maintenance subheading.
RESET RECORDS? → Displays the reset records option. After performing maintenance or
when required, enter Yes to reset.
RECORDS MAINT →
Returns the user to records maintenance subheading.
OPERATING DAYS #
LAST MAINT ##-###-##
Displays the operating days since the last maintenance.
NO. OF STARTS # Displays the number of starts since the last maintenance date
LAST MAINT ##-###-## (day-month-year).
LENGTH OF RUN
Displays the length of last run in (un)loaded hours.
(UN)LOADED HRS #
MENU 4
OPERATIONAL RECORDS Returns the user to the operational records heading.
(MESSAGE TEXT) Displays the message text, date (day-month-year) and time
##-###-## ##:## AM/PM (hours:minutes). Scroll through up to 100 stored events. See
Section 2.3.5, System Warning Lamp, for fault descriptions.
MENU 5
Returns the user to event history heading.
EVENT HISTORY
MENU 6
Displays the menu number and name.
TIME AND DATE
DAY OF WEEK ##-###-## Displays the day of the week, date (day-month-year), and time
##:## AM/PM (hours:minutes).
TIME ??:?? AM/PM Displays the time (hours:minutes) of day entry. When required, use
the numeric and am/pm keys to set the time (hours:minutes) of day
and press the Enter key.
DAY OF WEEK ##-###-##
##:## AM/PM
Displays the corrected time (hours:minutes) of day.
DATE ??-???-?? Displays the date (day-month-year) entry. When required, use the
numeric keys to set the day of the month.
AND
DATE ??-???-?? Use the Menu Right → key to select the month.
AND
DATE ??-???-?? Use the numeric keys to set the two-digit year and press the Enter
key.
AND
DAY OF WEEK ##-###-##
##:## AM/PM
Displays the corrected date (day- month-year).
OPERATING MODE → Displays the operating mode selection. Note: The display sample
(see note) YES may differ depending upon previous entries. The previously selected
operating mode appears first, either standby or prime power.
OPERATING MODE → Displays the optional operating mode selection. When required, enter
STANDBY NO YES for standby operating mode. Note: This display indicates the
generator set application.
OPERATING MODE → Enter YES to change the operating mode selection to standby and
STANDBY YES press the Enter key.
OPERATING MODE →
STANDBY YES
Confirms the entry.
OR
OPERATING MODE → Displays the optional operating mode selection. When required, enter
PRIME POWER NO YES for the prime power operating mode. Note: This display
indicates the generator set application.
OPERATING MODE → Enter YES to change the operating mode selection to prime power
PRIME POWER YES and press the Enter key.
OPERATING MODE →
PRIME POWER YES
Confirms the entry.
SYSTEM VOLTAGE Displays the line-to-line system voltage as entered data. When
LINE-LINE ? required, use the numeric keys to set new value. Press the Enter
key.
SYSTEM VOLTAGE
Displays the corrected line-to-line system voltage. See NOTE A.
LINE-LINE #
SYSTEM FREQ # HZ Displays the system frequency as entered data. When required, use
the numeric keys to set the new value. Press the Enter key.
SYSTEM FREQ # HZ
Displays the corrected system frequency. See NOTE A.
PHASE →
3 PHASE DELTA YES Confirms the entry. See NOTE A.
OR
PHASE → Displays the optional phase configuration selection. When required,
3 PHASE WYE NO use the YES key to choose the wye phase configuration.
PHASE → Enter YES to change the phase configuration to a wye phase
3 PHASE WYE YES configuration and press the Enter key.
PHASE →
3 PHASE WYE YES Confirms the entry. See NOTE A.
OR
PHASE → Displays the optional phase configuration selection. When required,
SINGLE-PHASE NO use the YES key to choose the single-phase configuration.
PHASE →
SINGLE-PHASE YES Confirms the entry. See NOTE A.
RATED CURRENT # Displays the generator set rated current as entered data. Note: This
is a read-only display.
LOAD SHED OUTPUT → Displays the load shed output setting. When required, use the
?% # KW numeric keys to set the new value. Press the Enter key. See Menu
10, Output Setup for Group B User-Defined Systems Events
LOAD SHED OUTPUT →
#% # KW Displays the corrected load shed output setting.
TIME DELAY MIN:SEC → Displays the load shed time (minutes:seconds) delay setting. When
??:?? required, use the numeric keys to set the new value. Press the Enter
key.
TIME DELAY MIN:SEC →
##:##
Displays the corrected load shed time (minutes:seconds) delay
setting.
LOAD SHED OUTPUT →
#% # KW
Returns the user to the load shed output setting.
OVERVOLTAGE → Displays the overvoltage setting. When required, use the numeric
?% # VAC keys to set the new value. Press the Enter key.
OVERVOLTAGE →
Displays the corrected overvoltage setting.
#% # VAC
TIME DELAY MIN:SEC → Displays the overvoltage time (minutes:seconds) delay setting. When
??:?? required, use the numeric keys to set the new value. Press the Enter
key.
TIME DELAY MIN:SEC → Displays the corrected overvoltage time (minutes:seconds) delay
##:## setting.
OVERVOLTAGE →
#% # VAC
Returns the user to the overvoltage setting.
UNDERVOLTAGE → Displays the undervoltage setting. When required, use the numeric
?% # VAC keys to set the new value. Press the Enter key.
UNDERVOLTAGE →
#% # VAC
Displays the corrected undervoltage setting.
TIME DELAY MIN:SEC → Displays the undervoltage time (minutes:seconds) delay setting.
??:?? When required, use the numeric keys to set the new value. Press the
Enter key.
TIME DELAY MIN:SEC → Displays the corrected overvoltage time (minutes:seconds) delay
##:## setting.
UNDERVOLTAGE →
Returns the user to the undervoltage setting.
#% # VAC
OVERFREQUENCY Displays the overfrequency setting. When required, use the numeric
?% # HZ keys to set the new value. Press the Enter key.
OVERFREQUENCY
#% # HZ Displays the corrected overfrequency setting.
UNDERFREQUENCY
Displays the corrected underfrequency setting.
#% # HZ
OVERSPEED
Displays the overspeed setting. When required, use the numeric
? HZ # RPM
keys to set the new value. Press the Enter key.
OVERSPEED
# HZ # RPM Displays the corrected overspeed setting.
BATTERY VOLTAGE → Displays the battery voltage selection. Note: The display sample
(see note) YES may differ depending upon previous entries. The user-selected
battery voltage appears first, either 12 VDC or 24 VDC.
BATTERY VOLTAGE → Displays the 12 VDC battery voltage selection. When required, use
12 VDC NO the YES key to choose the 12 VDC battery voltage.
BATTERY VOLTAGE → Enter YES to change the battery voltage to 12 VDC and press the
12 VDC YES Enter key.
BATTERY VOLTAGE →
12 VDC YES Confirms the entry.
OR
BATTERY VOLTAGE → Displays the 24 VDC battery voltage selection. When required, use
24 VDC NO the YES key to choose the 24 VDC battery voltage.
BATTERY VOLTAGE → Enter YES to change the battery voltage to 24 VDC and press the
24 VDC YES Enter key.
BATTERY VOLTAGE →
24 VDC YES Confirms the entry.
LOW BATTERY VOLTAGE Displays the low battery voltage setting. When required, use the
?.? VDC numeric keys to set the new value. Press the Menu Right → key
AND prior to entering the decimal value.
LOW BATTERY VOLTAGE
?.? VDC Use the numeric keys to enter the decimal value. Press the Enter
key.
LOW BATTERY VOLTAGE
Displays the corrected low battery voltage setting.
#.# VDC
HIGH BATTERY VOLTAGE Displays the high battery voltage setting. When required, use the
?.? VDC numeric keys to set the new value. Press the Menu Right → key
AND prior to entering the decimal value.
HIGH BATTERY VOLTAGE
?.? VDC
Use the numeric keys to enter the decimal value. Press the Enter
key.
BLOCK HEATER ON #F Displays the block heater energize temperature setting. When
required, use the numeric keys to set the new value. Applies to
DDC/MTU engines with MDEC/ADEC only.
AND
BLOCK HEATER ON ?F
Use the numeric keys to enter the decimal value. Press the Enter
key.
BLOCK HEATER ON #F
Displays the corrected block heater energize temperature setting.
BLOCK HEATER OFF #F Displays the block heater deenergize temperature setting. When
required, use the numeric keys to set the new value. Applies to
Detroit Diesel engines with MDEC/ADEC engine controls only.
AND
BLOCK HEATER OFF ?F
Use the numeric keys to enter the decimal value. Press the Enter
key.
BLOCK HEATER OFF #F
Displays the corrected block heater deenergize temperature setting.
OR
ENABLE VSG YES
ENABLE VSG NO
Confirms the entry..
OR
ENABLE DSC YES
ENABLE DSC NO
Confirms the entry..
METRIC UNITS NO
METRIC UNITS YES Enter YES to change to metric displays and press the Enter key.
OR
METRIC UNITS YES
METRIC UNITS NO
Enter NO to change to English displays and press the Enter key.
METRIC UNITS NO
Confirms the entry.
SET NFPA-110 Y/N Displays the NFPA 110 default yes or no selection. Note: See
DEFAULTS Menu 10—Output Setup, Overview for a list of the NFPA-110 faults.
SET NFPA-110 NO
DEFAULTS
SET NFPA-110 YES Enter YES to select the NFPA 110 default selection and press the
DEFAULTS Enter key.
SET NFPA-110 YES
Confirms the entry.
DEFAULTS
OR
SET NFPA-110 YES
DEFAULTS
SET NFPA-110 NO Enter NO to deselect the NFPA 110 default selection and press the
DEFAULTS Enter key.
SET NFPA-110 NO
Confirms the entry.
DEFAULTS
MENU 7
Returns the user to the generator system heading.
GENERATOR SYSTEM
Cooldown Temperature Override. This feature If the engine is at or below the preset temperature and
provides the ability to bypass (override) the generator the unit is signalled to shut down or the TDES is running,
set’s smart cooldown temperature shutdown and force the unit will shut down without waiting for the time delay
to expire.
TIME DELAY MIN:SEC Displays the starting aid time delay in minutes:seconds. When
STARTING AID ??:?? required, use the numeric keys to set the new value. Press the Enter
key.
TIME DELAY MIN:SEC Displays the corrected starting aid time (minutes:seconds) delay
STARTING AID ##:## setting.
TIME DELAY MIN:SEC Displays the crank on time delay in minutes:seconds. When required,
CRANK ON ??:?? use the numeric keys to set the new value. Press the Enter key.
TIME DELAY MIN:SEC Displays the crank pause time delay in minutes:seconds. When
CRANK PAUSE ??:?? required, use the numeric keys to set the new value. Press the Enter
key.
TIME DELAY MIN:SEC
Displays the corrected crank pause time (minutes:seconds) delay
CRANK PAUSE ##:##
setting.
TIME DELAY MIN:SEC Displays the engine cooldown time delay in minutes:seconds. When
ENG COOLDOWN ??:?? required, use the numeric keys to set the new value. Press the Enter
key.
TIME DELAY MIN:SEC Displays the corrected engine cooldown time (minutes:seconds)
ENG COOLDOWN ##:## delay setting.
COOLDOWN TEMPERATURE Displays the cooldown temperature override. When required, use the
OVERRIDE Y/N Yes key to override the cooldown temperature time delay.
COOLDOWN TEMPERATURE Enter YES to select cooldown temperature override time delay and
OVERRIDE YES press the Enter key.
COOLDOWN TEMPERATURE
Confirms the entry.
OVERRIDE Y/N
OVERCRANK SHUTDOWN Displays the engine crank cycles before overcrank shutdown. When
CRANK CYCLES ? required, use the numeric keys to set the new value. Press the Enter
key.
OVERCRANK SHUTDOWN Displays the corrected engine crank cycles before overcrank
CRANK CYCLES # shutdown setting.
TIME DELAY MIN:SEC Displays the overvoltage time delay in minutes:seconds. When
OVERVOLTAGE ??:?? required, use the numeric keys to set the new value. Press the Enter
key.
TIME DELAY MIN:SEC Displays the corrected overvoltage time (minutes:seconds) delay
OVERVOLTAGE ##:## setting.
TIME DELAY MIN:SEC Displays the undervoltage time delay in minutes:seconds. When
UNDERVOLTAGE ??:?? required, use the numeric keys to set the new value. Press the Enter
key.
TIME DELAY MIN:SEC Displays the corrected undervoltage time (minutes:seconds) delay
UNDERVOLTAGE ##:## setting.
MENU 8
Returns the user to the time delays heading.
TIME DELAYS
Each analog input has the following nine features: When this input is enabled the yellow warning lamp
illuminates and stored warning/shutdown events that
D One warning enabled and one shutdown enabled are ignored continue to log in Menu 5—Event History.
D One inhibit time period
Idle Mode Active. The idle time is defined by the digital
D One warning delay and one shutdown delay
input time delay. Set the desired time in
D Two warning levels (high and low) minutes:seconds,up to 10 minutes (600 seconds). If
D Two shutdown levels (high and low) manual control of the idle mode is desired, an unlimited
time can be entered as 9:99. The generator set will
Note: The user must scale the analog input value in remain at idle speed as long as the input is active and the
order to calculate the low/high warning and generator set master switch is in the AUTO position.
shutdown values based on a 0--5 VDC scale.
See Menu 12—Calibration. Shutdown Type A and Shutdown Type B. Choose
shutdown type A for standard shutdowns where the
Time after Crank Disconnect red lamp illuminates and the alarm horn sounds.
Inhibit Time Time Choose shutdown type B for shutdowns where air
Analog Time Delay Delay damper indicator RDO-23 energizes for two seconds,
Values Period ! Period ! Complete
the red lamp illuminates, and the alarm horn sounds.
High shutdown value High
is above the high shutdown
warning value function
High warning value is The High warning
above the acceptable The controller function
value controller does view
does not the analog
Acceptable analog System ready
view the input signal
value status
analog value and
Low warning value is input signal the time Low warning
below the acceptable value delay function
value begins
Low shutdown value Low
is below the low shutdown
warning value function
MENU 9
Displays the menu number and name.
INPUT SETUP
SETUP DIGITAL →
AUXILIARY INPUTS
Displays the setup of digital auxiliary inputs heading.
DIGITAL INPUT 01 → Displays the digital input 01 with the user-defined description.
(USER DEFINED DESC) Note: Press the down arrow to move to the start of the next input
setup.
DIGITAL INPUT 01 → Identifies the signal source for digital input 01. Use the menu down ↓
(see Group A) YES/NO key to select the digital input.
DIGITAL INPUT 01 →
Displays the digital input 01, enabled yes or no selection.
ENABLED YES/NO
DIGITAL INPUT 01 →
Entering YES enables digital input 01.
ENABLED NO
DIGITAL INPUT 01 →
Press the Enter key.
ENABLED YES
DIGITAL INPUT 01 →
Confirms the entry.
ENABLED YES
OR
DIGITAL INPUT 01 →
ENABLED YES Entering NO disables digital input 01.
DIGITAL INPUT 01 →
ENABLED NO Press the Enter key.
DIGITAL INPUT 01 →
Confirms the entry.
ENABLED NO
DIGITAL INPUT 01 → Displays the digital input 01 inhibit time (minutes:seconds) setting.
INHIBIT TIME ?:?? When required, use the numeric keys to set the new values. Press
the Enter key.
SETUP DIGITAL →
AUXILIARY INPUTS Returns the user to setup digital auxiliary inputs.
SETUP ANALOG →
AUXILIARY INPUTS Displays the setup of analog auxiliary inputs heading.
ANALOG INPUT 01 →
Entering YES enables the warning analog input 01.
WARNING ENABLED NO
ANALOG INPUT 01 →
Press the Enter key.
WARNING ENABLED YES
AND
ANALOG INPUT 01 →
Confirms the entry.
WARNING ENABLED YES
OR
ANALOG INPUT 01 →
WARNING ENABLED YES Entering NO disables the warning analog input 01.
ANALOG INPUT 01 →
WARNING ENABLED NO Press the Enter key.
AND
ANALOG INPUT 01 →
Confirms the entry.
WARNING ENABLED NO
ANALOG INPUT 01 →
SHUTDOWN ENABLED Y/N
Displays the analog input 01, shutdown enabled selection.
ANALOG INPUT 01 →
SHUTDOWN ENABLED NO Entering YES enables the shutdown analog input 01.
ANALOG INPUT 01 →
Press the Enter key.
SHUTDOWN ENABLED YES
AND
ANALOG INPUT 01 →
Confirms the entry.
SHUTDOWN ENABLED YES
OR
ANALOG INPUT 01 →
Entering NO disables the shutdown analog input 01.
SHUTDOWN ENABLED YES
ANALOG INPUT 01 →
Press the Enter key.
SHUTDOWN ENABLED NO
AND
ANALOG INPUT 01 →
Confirms the entry.
SHUTDOWN ENABLED NO
ANALOG INPUT 01 → Displays the analog input 01, inhibit time (minutes:seconds) setting.
INHIBIT TIME ?:?? When required, use the numeric keys to set the new values. Press
the Enter key.
ANALOG INPUT 01 →
Displays the corrected inhibit time (minutes:seconds) setting.
INHIBIT TIME #:##
ANALOG INPUT 01 → Displays the analog input 01, warning time (minutes:seconds) delay
WARN DELAY TIME ?:?? setting. When required, use the numeric keys to set the new values.
Press the Enter key.
ANALOG INPUT 01 →
Displays the corrected warning time (minutes:seconds) delay setting.
WARN DELAY TIME #:##
ANALOG INPUT 01 → Displays the analog input 01, shutdown time (minutes:seconds) delay
SDWN DELAY TIME ?:?? setting. When required, use the numeric keys to set the new values.
Press the Enter key.
ANALOG INPUT 01 → Displays the corrected shutdown time (minutes:seconds) delay
SDWN DELAY TIME #:## setting.
ANALOG INPUT 01 → Displays the analog input 01, low shutdown value. When required,
LO SDWN VALUE ? use the numeric keys to set the new values. Press the Enter key.
Note: The user must scale the analog input value in order to calculate
the low/high warning and shutdown values based on a 0--5 VDC
scale. See Menu 12—Calibration.
ANALOG INPUT 01 →
LO SDWN VALUE #
Displays the corrected low shutdown value.
ANALOG INPUT 01 → Displays the analog input 01, low warning value. When required, use
LO WARN VALUE ? the numeric keys to set the new values. Press the Enter key.
Note: The user must scale the analog input value in order to calculate
the low/high warning and shutdown values based on a 0--5 VDC
scale. See Menu 12—Calibration.
ANALOG INPUT 01 →
Displays the corrected low warning value.
LO WARN VALUE #
ANALOG INPUT 01 → Displays the analog input 01, high warning value. When required,
HI WARN VALUE ? use the numeric keys to set the new values. Press the Enter key.
Note: The user must scale the analog input value in order to calculate
the low/high warning and shutdown values based on a 0--5 VDC
scale. See Menu 12—Calibration.
ANALOG INPUT 01 →
Displays the corrected high warning value.
HI WARN VALUE #
ANALOG INPUT 01 → Displays the analog input 01, high shutdown value. When required,
HI SDWN VALUE ? use the numeric keys to set the new values. Press the Enter key.
Note: The user must scale the analog input value in order to calculate
the low/high warning and shutdown values based on a 0--5 VDC
scale. See Menu 12—Calibration.
ANALOG INPUT 01 →
Displays the corrected high shutdown value.
HI SDWN VALUE #
ANALOG INPUT 01 →
Returns the user to analog input 01.
(USER DEFINED DESC)
ANALOG INPUT XX → Displays analog inputs A02 to A07. Note: Press the down arrow to
(USER DEFINED DESC) scroll through additional analog auxiliary inputs or enter the input
number. Note: ECM engines have inputs A01--A07 and non-ECM
engines have inputs A03--A07. Waukesha engines have inputs
A05--A07.
Note: Press the right arrow at each analog auxiliary input for the
following selections and settings:
Warning enabled
Shutdown enabled
Inhibit time
Warning delay time
Shutdown delay time
Low shutdown value
Low warning value
High warning value
High shutdown value
See the Analog Input 01 instructions for the complete procedure.
SETUP ANALOG →
AUXILIARY INPUTS
Returns the user to the setup analog auxiliary input heading.
SETUP DIGITAL →
Returns the user to the setup digital auxiliary input heading.
AUXILIARY INPUTS
DEFINE COMMON →
FAULTS
Displays the common faults heading.
SYSTEM EVENTS →
Displays the system events heading.
COMMON FAULT Y/N Gives the user the option to add or delete the selection from the
(see Group B) defined system events group. Press the Menu Down key to continue
to the next selection (repeat as necessary).
COMMON FAULT NO
(see Group B)
Entering YES adds the selection to the defined system event group.
OR
COMMON FAULT YES Entering NO removes the selection from the defined system event
(see Group B) group.
COMMON FAULT NO
Press the Enter key.
(see Group B)
COMMON FAULT NO
(see Group B)
Confirms the entry.
DIGITAL INPUTS →
Displays the digital inputs heading.
COMMON FAULT Y/N Gives the user the option to add or delete selection from the defined
Dxx (see Group C) digital faults starting with D01. Note: Press the Menu Down key to
continue to the next selection D02--D21 (repeat as necessary).
COMMON FAULT NO Entering YES adds the selection to the defined digital fault group.
Dxx (see Group C)
COMMON FAULT NO
Confirms the entry.
Dxx (see Group C)
Group C
Up to 21 PC user-defined digital
status and fault inputs designated
as D01 to D21 can result in an
digital input common fault.
ANALOG INPUTS →
Displays the analog inputs heading.
COMMON FAULT Y/N Gives the user the option to add or delete selection from the defined
Axx(see Group D) LO analog faults starting with A01. Note: Press the Menu Down key to
WARNING→ continue to the next selection A02--A07 (repeat as necessary).
Group D
Up to 7 analog inputs, PC user-
defined status events and faults
designated as A01 to A07.
Each of the 7 is assignable as a
shutdown or warning with high
and low settings.
COMMON FAULT NO Entering YES adds the low warning selection to the defined analog
A01 LO WARNING→ fault group.
COMMON FAULT YES Press the Enter key.
A01 LO WARNING→
OR
COMMON FAULT YES Entering NO removes the low warning selection from the defined
A01 LO WARNING→ analog fault group.
COMMON FAULT NO
A01 LO WARNING→ Press the Enter key.
COMMON FAULT NO
Confirms the entry.
A01 LO WARNING→
COMMON FAULT Y/N Indicates whether the previously user-defined analog output was
A01 HI WARNING→ selected (yes or no) as a high warning fault.
COMMON FAULT NO Entering YES adds the high warning selection to the defined analog
A01 HI WARNING→ fault group.
OR
COMMON FAULT YES Entering NO removes the high warning selection from the defined
A01 HI WARNING→ analog fault group.
COMMON FAULT NO
A01 HI WARNING→ Press the Enter key.
COMMON FAULT NO
Confirms the entry.
A01 HI WARNING→
COMMON FAULT Y/N Indicates whether the previously user-defined analog output was
A01 LO SHUTDOWN→ selected (yes or no) as a low shutdown fault.
COMMON FAULT NO Entering YES adds the low shutdown selection to the defined analog
A01 LO SHUTDOWN→ fault group.
COMMON FAULT YES Press the Enter key.
A01 LO SHUTDOWN→
OR
COMMON FAULT YES Entering NO removes the low shutdown selection from the defined
A01 LO SHUTDOWN→ analog fault group.
COMMON FAULT NO
A01 LO SHUTDOWN→ Press the Enter key.
COMMON FAULT NO
A01 LO SHUTDOWN→ Confirms the entry.
COMMON FAULT Y/N Indicates whether the previously user-defined analog output was
A01 HI SHUTDOWN→ selected (yes or no) as a high shutdown fault.
COMMON FAULT NO Entering YES adds the high shutdown selection to the defined analog
A01 HI SHUTDOWN→ fault group.
COMMON FAULT YES Press the Enter key.
A01 HI SHUTDOWN→
OR
COMMON FAULT YES Entering NO removes the high shutdown selection from the defined
A01 HI SHUTDOWN→ analog fault group.
COMMON FAULT NO Press the Enter key.
A01 HI SHUTDOWN→
COMMON FAULT Y/N Returns the user to common fault (analog inputs) heading.
A01 LO WARNING→ Press the Menu Down key to continue to the next selection A02--A07
(repeat as necessary).
COMMON FAULT Y/N Gives the user the option to add or delete selection from the next
Axx(see Group D) LO defined analog fault. Note: Use the A01 common fault analog input
WARNING→ setup procedure shown above for A02--A07. Go to
Group D
Up to 7 analog inputs, PC user-
defined status events and faults
designated as A01 to A07.
Each of the 7 is assignable as a
shutdown or warning with high
and low settings.
DEFINE COMMON →
FAULTS
Returns the user to the define common faults heading.
RELAY DRV OUT 01 → Gives the user previously selected items for relay driver outputs
(user defined) (RDO) starting with 01. Note: Press the down arrow to continue to
the next relay driver output 02--31 or enter the RDO number.
Note: The RDO can be assigned from the SYSTEM EVENTS,
DIGITAL INPUTS, or ANALOG INPUTS groups. The start of each of
these groups are highlighted on the following pages.
SYSTEM EVENTS →
Displays the system events heading.
RELAY DRV OUT 01 Y/N Gives the user the option to assign a system event to an RDO. Press
(see Group B) the Menu Down key to continue to the next selection (repeat as
necessary).
RELAY DRV OUT 01 NO Entering YES adds the selection to the RDO group.
(see Group B) Note: Func(Function) Used by (RDO) XX Reassign? appears when
the user attempts to assign an RDO to a function already assigned.
Note: Cannot Change (because the) NFPA is Enabled appears when
the user attempts to modify the RDO setting that is a NFPA 110
default requirement.
RELAY DRV OUT 01 YES
Press the Enter key.
(see Group B)
DIGITAL INPUTS →
Displays the digital inputs heading.
Gives the user the option to assign a digital input to an RDO starting
RELAY DRV OUT 01 Y/N
with D01. Press the Menu Down key to continue to the next selection
Dxx (see Group C)
D02--D21 (repeat as necessary).
Note: Func(Function) Used by (RDO) XX Reassign? appears when
the user attempts to assign an RDO to a function already assigned.
RELAY DRV OUT 01 NO Entering YES adds the selection to the RDO group.
Dxx (see Group C) Note: Func(Function) Used by (RDO) XX Reassign? appears when
the user attempts to assign an RDO to a function already assigned.
Note: Cannot Change (because the) NFPA is Enabled appears when
the user attempts to modify the RDO setting that is a NFPA 110
default requirement.
RELAY DRV OUT 01 YES
Press the Enter key.
Dxx (see Group C)
Group C
Up to user-defined digital status
and fault inputs designated as
D01 to D21 can result in a digital
input common fault.
ANALOG INPUTS →
Displays the analog inputs heading.
RELAY DRV OUT 01 Y/N Gives the user the option to assign an analog input to an RDO
Axx(see Group D) LO starting with A01. Note: Press the Menu Down key to continue to the
WARNING→ next selection A02-A07 (repeat as necessary).
Group D
Up to 7 analog inputs, user-
defined status events and
faults designated as A01 to
A07. Each of the 7 is
assignable as a shutdown or
warning with high or low
settings.
RELAY DRV OUT 01 Y/N Indicates whether the previously user-defined analog RDO was
A01 LO WARNING→ selected (yes or no) as a low warning fault.
RELAY DRV OUT 01 NO Entering YES adds the low warning selection to the defined analog
A01 LO WARNING→ RDO group.
OR
RELAY DRV OUT 01 YES Entering NO removes the low warning selection from the defined
A01 LO WARNING→ analog RDO group.
RELAY DRV OUT 01 Y/N Indicates whether the previously user-defined analog RDO was
A01 HI WARNING→ selected (yes or no) as a high warning fault.
RELAY DRV OUT 01 NO Entering YES adds the high warning selection to the defined analog
A01 HI WARNING→ RDO group.
OR
RELAY DRV OUT 01 YES Entering NO removes the high warning selection from the defined
A01 HI WARNING→ analog RDO group.
RELAY DRV OUT 01 Y/N Indicates whether the previously user-defined analog RDO was
A01 LO SHUTDOWN→ selected (yes or no) as a low shutdown fault.
RELAY DRV OUT 01 NO Entering YES adds the low shutdown selection to the defined analog
A01 LO SHUTDOWN→ RDO group.
RELAY DRV OUT 01 YES
A01 LO SHUTDOWN→ Press the Enter key.
OR
RELAY DRV OUT 01 YES Entering NO removes the low shutdown selection from the defined
A01 LO SHUTDOWN→ analog RDO group.
RELAY DRV OUT 01 Y/N Indicates whether the previously user-defined analog RDO was
A01 HI SHUTDOWN→ selected (yes or no) as a high shutdown fault.
RELAY DRV OUT 01 NO Entering YES adds the high shutdown selection to the defined analog
A01 HI SHUTDOWN→ RDO group.
OR
RELAY DRV OUT 01 YES Entering NO removes the high shutdown selection from the defined
A01 HI SHUTDOWN→ analog RDO group.
RELAY DRV OUT 01 Y/N Returns the user to the analog RDO (analog inputs) heading. Press
A01 LO WARNING→ the Menu Down key to continue to the next selection A02--A07
(repeat as necessary).
RELAY DRV OUT 01 Y/N Gives the user the option to add or delete a selection for the next
Axx(see Group D) LO analog RDO. Note: Use the A01 analog RDO setup procedure
WARNING→ shown above for A02--A07. Go to
ANALOG INPUTS → Returns the user to the analog inputs heading. Press the Menu Right
key.
RELAY DRV OUT XX → Gives the user the option to add or delete a selection for the next
(user defined) RDO. Note: Use the RDO 01 setup procedure shown above for
RDOs 02--31. Go to
MENU 10
Displays the menu number and name
OUTPUT SETUP
DEFINE COMMON →
FAULTS
Displays the common faults heading.
RELAY DRV OUT XX → Gives the user previously selected items for the relay driver outputs
S’WARE CONTROLLED #X (RDO). Press the down arrow to scroll through relay driver outputs
1--31 or enter the RDO number. Locate the SCRDO display.
DEACTIVATE RDO? → When required (SCRDO is currently active), enter the YES key to
deactivate the SCRDO.
Note: 350--2000 kW models only, see 1.3.2 Voltage Marathonr and DVRr are registered trademarks of Marathon Electric
Regulator and Calibration Specifications Mfg. Corp.
regarding the use of the Marathonr DVRr 2000
voltage regulator on some earlier generator sets.
MENU 11
Displays the menu number and name.
VOLTAGE REGULATOR
AVG L-L V #→ Displays the average running line-to-line volts and voltage
VOLT ADJ ?.? adjustment. Enter the desired nominal voltage using the numeric
keys. Press the Menu Right → key prior to entering the decimal
AND
value.
AVG L-L V #→
VOLT ADJ ?.?
Use the numeric keys to enter the decimal value. Press the Enter
key.
AVG L-L V #→
Confirms the entry.
VOLT ADJ #.#
L1-L2 VOLTS →
Displays L1-L2 volts.
#
L3-L1 VOLTS →
Displays L3-L1 volts (3 phase only).
#
AVG L-L V #→ Returns the user to the average line-to-line volts and voltage
VOLT ADJ # adjustment heading.
UNDER FREQ UNLOAD → Displays the under frequency (volts per Hz) unloading (yes or no)
ENABLED N/Y selection.
OR
UNDER FREQ UNLOAD → Entering NO disables the underfrequency unloading feature.
ENABLED YES
SLOPE →
Confirms the entry.
#.# VOLTS-PER-CYCLE
REACTIVE DROOP →
Displays the reactive droop selection (yes or no).
ENABLED N/Y
REACTIVE DROOP →
ENABLED NO
Entering YES enables the reactive droop feature.
REACTIVE DROOP →
Press the Enter key.
ENABLED YES
REACTIVE DROOP →
ENABLED YES
Confirms the entry.
OR
REACTIVE DROOP →
Entering NO disables the reactive droop feature.
ENABLED YES
REACTIVE DROOP →
Press the Enter key.
ENABLED NO
.8 PF RATED LOAD → Displays the reactive (voltage) droop as a percentage of the rated
VOLTAGE DROOP ?.?% voltage at rated load. When required, enter the desired reactive
droop using the numeric keys. Press the Menu Right → key prior to
entering the decimal value.
AND
.8 PF RATED LOAD →
Use the numeric keys to enter the decimal value. Press the Enter
VOLTAGE DROOP ?.?%
key.
.8 PF RATED LOAD →
Confirms the entry.
VOLTAGE DROOP #.#%
REACTIVE DROOP →
ENABLED N/Y Returns the user to reactive droop selection heading.
VAR CONTROL →
Displays the VAR control selection (yes or no).
ENABLED N/Y
VAR CONTROL →
Confirms the entry.
ENABLED YES
OR
VAR CONTROL →
ENABLED YES Entering NO disables the VAR control feature.
VAR CONTROL →
ENABLED NO
Press the Enter key.
VAR CONTROL →
Confirms the entry.
ENABLED NO
TOTAL KVAR #→ Displays total kVAR (running) and kVAR adjustment settings. Enter
KVAR ADJ ?.? the desired kVAR adjustment using the numeric keys. Press the
Menu Right → key prior to entering the decimal value.
AND
TOTAL KVAR #→
Use the numeric keys to enter the decimal value. Press the Enter
KVAR ADJ ?.?
key.
TOTAL KVAR #→
KVAR ADJ #.# Confirms the entry.
GENERATING YES→ Displays the generating kVAR selection. When required, use the NO
key to choose absorbing kVAR.
GENERATING NO→ Press the Enter key.
ABSORBING YES→
Confirms the entry.
OR
ABSORBING YES→ Displays the absorbing kVAR selection. When required, use the NO
key to choose generating kVAR.
ABSORBING NO→
Press the Enter key.
GENERATING YES→
Confirms the entry.
VAR CONTROL →
Returns the user to VAR control selection heading.
ENABLED N/Y
PF CONTROL →
ENABLED N/Y
Displays the power factor control selection (yes or no).
PF CONTROL →
Confirms the entry.
ENABLED YES
OR
PF CONTROL → Entering NO disables the power factor control feature.
ENABLED YES
PF CONTROL →
Press the Enter key.
ENABLED NO
PF CONTROL →
Confirms the entry.
ENABLED NO
AVERAGE PF #→ Displays the present running average power factor and power factor
PF ADJ ?.? adjustment settings. Enter the desired kVAR adjustment using the
numeric keys. Press the Menu Right → key prior to entering the
decimal value.
AND
AVERAGE PF #→
Use the numeric keys to enter the decimal value. Press the Enter
PF ADJ ?.?
key.
AVERAGE PF #→
PF ADJ #.# Confirms the entry.
LAGGING YES→ Displays the lagging PF selection. When required, use the NO key to
choose leading PF.
LAGGING NO→
Press the Enter key.
OR
LEADING YES→ Displays the leading PF selection. When required, use the NO key to
choose lagging PF.
LAGGING YES→
Confirms the entry.
PF CONTROL →
Returns the user to the power factor control selection heading.
ENABLED N/Y
REGULATOR GAIN ADJ Displays the generator set voltage regulator gain adjustment. When
GAIN # required, use the numeric keys to enter the desired gain value.
VAR/PF GAIN ADJ Displays the utility (VAR/PF) gain adjustment. When required, use
GAIN # the numeric keys to enter the desired gain value.
RESET REGULATOR
Displays the reset regulator defaults selection.
DEFAULTS Y/N
RESET REGULATOR When required, use the YES key to reset the regulator defaults.
DEFAULTS YES
RESET REGULATOR
DEFAULTS Y/N Confirms the entry.
Connect a meter with a minimum accuracy of 1% to Note: For VSG on Analog Aux. Input 06 calibrate:
the generator set output leads to calibrate the Volvo: 0.5V=1250; 4.5V=8750
voltage-sensing logic. Configure the generator set GM/Doosan at 60 Hz: 0.5V=2375; 4.5V=2625
controller for the system operating configuration using GM/Doosan at 50 Hz: 4.5V=2327; 4.5V=2624
Menu 7—Generator System. Adjust the generator set
voltage using Menu 11—Voltage Regulator, when Analog input A07 is the voltage adjustment for
required and adjust the frequency at the generator set paralleling applications only. This input adjusts the input
governor before making calibration adjustments. up or down from the value entered in Menu 11, Voltage
Regulator. Calibration is not necessary.
Reduce the voltage regulator gain using Menu 11,
Voltage Regulator until the voltage is stable prior to Note: Press the Menu Right → key prior to entering
calibration. decimal values where necessary.
The user must scale the analog input value in order to Changes to the generator set system parameters
calculate the low/high warning and shutdown analog causes a CHECK CALIBRATION display message. If
values based on a 0--5 VDC scale. the generator set system parameters are changed,
verify the controller display calibration by comparing the
ECM engines have user-defined analog inputs results to a known measured value.
A01--A07. Non-ECM engines have user-defined analog
Menu 12—Calibration
Menu 12 Displays with Key Entries (Scale AC Analog Inputs)
Key
Entry Display Description
SCALE AC ANALOG
Displays the scale AC analog inputs heading.
INPUTS
GEN VOLTAGE LN
Displays the generator set voltage line-to-neutral heading.
GEN L1-L0 V # Note: The generator set must be running for the following steps.
CALIB REF ?.?
Measure the generator set output voltage for single and three-phase
models between L1-L0 using a voltmeter and enter the result using
the numeric keys. Press the Menu Right → key prior to entering the
decimal value.
AND
GEN L1-L0 V # Use the numeric keys to enter the decimal value. Press the Enter
CALIB REF ?.? key.
GEN L1-L0 V #
Confirms the entry.
CALIB REF #.#
GEN L2-L0 V # Measure the generator set output voltage for three-phase models
CALIB REF ?.? between L2-L0 using a voltmeter and enter the result using the
numeric keys. Press the Menu Right → key prior to entering the
decimal value.
AND
GEN L2-L0 V # Use the numeric keys to enter the decimal value. Press the Enter
CALIB REF ?.? key.
GEN L2-L0 V #
Confirms the entry.
CALIB REF #.#
GEN L3-L0 V # Three-Phase Models only. Measure the generator set output
CALIB REF ?.? voltage for three-phase models between L3-L0 using a voltmeter and
enter the result using the numeric keys. Press the Menu Right → key
prior to entering the decimal value.
AND
GEN L3-L0 V #
CALIB REF ?.?
Use the numeric keys to enter the decimal value. Press the Enter
key.
GEN L3-L0 V #
Confirms the entry.
CALIB REF #
GEN VOLTAGE LN
Returns the user to the generator set voltage line-to-neutral heading.
GEN VOLTAGE LL
Displays the generator set voltage line-to-line heading.
GEN L1-L2 V # Note: The generator set must be running for the following steps.
CALIB REF ?.?
Measure the generator set output voltage for single and three-phase
models between L1-L2 using a voltmeter and enter the result using
the numeric keys. Press the Menu Right → key prior to entering the
decimal value.
AND
GEN L1-L2 V #
CALIB REF ?.?
Use the numeric keys to enter the decimal value. Press the Enter
key.
GEN L1-L2 V #
Confirms the entry.
CALIB REF #.#
GEN L2-L3 V # Three-Phase Models only. Measure the generator set output
CALIB REF ?.? voltage for three-phase models between L2-L3 using a voltmeter and
enter the result using the numeric keys. Press the Menu Right → key
prior to entering the decimal value.
Note: The generator set must be running for the following steps.
AND
GEN L2-L3 V #
CALIB REF ?.?
Use the numeric keys to enter the decimal value. Press the Enter
key.
GEN L2-L3 V #
Confirms the entry.
CALIB REF #.#
GEN L3-L1 V # Three-Phase Models only. Measure the generator set output
CALIB REF ?.? voltage for three-phase models between L3-L1 using a voltmeter and
enter the result using the numeric keys. Press the Menu Right → key
prior to entering the decimal value.
AND
GEN L3-L1 V #
CALIB REF ?.?
Use the numeric keys to enter the decimal value. Press the Enter
key.
GEN L3-L1 V #
Confirms the entry.
CALIB REF #
CALIBRATE REGULATOR?
Confirms the entry.
Y/N
GEN VOLTAGE LL
Returns the user to the generator set line-to-line voltage heading.
GEN AMPS
Displays the generator set amps heading.
GEN L1 AMPS # Note: The generator set must be running for the following steps.
CALIB REF ?.? Measure the generator set output current for single- and three-phase
models at L1 using an AC ammeter and enter the result using the
numeric keys. Press the Menu Right → key prior to entering the
AND decimal value.
GEN L1 AMPS # Use the numeric keys to enter the decimal value. Press the Enter
CALIB REF ?.? key.
GEN L1 AMPS #
CALIB REF # Confirms the entry.
GEN L2 AMPS # Measure the generator set output current for three-phase models at
CALIB REF ?.? L2 using an AC ammeter and enter the result using the numeric keys.
Press the Menu Right → key prior to entering the decimal value.
AND
GEN L2 AMPS #
Use the numeric keys to enter the decimal value. Press the Enter
CALIB REF ?.?
key.
GEN L3 AMPS # Three-Phase Models only. Measure the generator set output
CALIB REF ?.? current for three-phase models at L3 using an AC ammeter and enter
the result using the numeric keys. Press the Menu Right → key prior
to entering the decimal value.
AND
GEN L3 AMPS # Use the numeric keys to enter the decimal value. Press the Enter
CALIB REF ?.? key.
GEN L3 AMPS #
CALIB REF #
Confirms the entry.
GEN AMPS
Returns the user to the generator set amps heading.
LOAD VOLTAGE LN
Displays the load voltage line-to-neutral voltage heading.
LOAD L1--L0 V # Note: The generator sets must be running for the following steps.
CALIB REF (PARALLEL) ?.?
Paralleling Applications. Measure the load voltage between L1-L0
using a voltmeter and enter the result using the numeric keys. Press
the Menu Right → key prior to entering the decimal value.
AND
GEN L1-L0 V #
CALIB REF ?.?
Use the numeric keys to enter the decimal value. Press the Enter
key.
GEN L1-L0 V #
Confirms the entry.
CALIB REF #
LOAD L3--L0 V # Note: The generator sets must be running for the following steps.
CALIB REF (PARALLEL) ?.?
Paralleling Applications. Measure the load voltage for three-phase
models between L3-L0 using a voltmeter and enter the result using
the numeric keys. Press the Menu Right → key prior to entering the
decimal value.
AND
GEN L3-L0 V #
CALIB REF ?.?
Use the numeric keys to enter the decimal value. Press the Enter
key.
GEN L3-L0 V #
Confirms the entry.
CALIB REF #
LOAD VOLTAGE LN
Returns the user to the load voltage line-to-neutral voltage heading.
RESTORE DEFAULTS? YES When required, enter YES to activate the restore calibration defaults
setting. Press the Enter key. Note: Entering Yes will delete all of the
previously entered voltage and current data based on system voltage
and kW and restore the calibration default settings.
RESTORE DEFAULTS? Y/N
Confirms the entry.
GEN VOLTAGE LN
Returns the user to the generator set voltage line-to-neutral heading.
SCALE AC ANALOG
Displays the scale AC analog inputs heading.
INPUTS
ZERO AUX. ANALOG Gives the user the option to calibrate the auxiliary analog inputs for
INPUTS? zero input signals. Note: ECM engines have inputs A01--A07 and
non-ECM engines have inputs A03--A07. A07 may be used for
analog voltage adjust. Waukesha engines have inputs A05-- A07.
ZERO AUX. ANALOG When required, enter YES to activate the auto-zero auxiliary analog
INPUTS? YES inputs feature. Press the Enter key.
ANALOG 01 # Displays the analog 01 and scale value 1 settings. Use the numeric
SCALE VALUE 1 ? keys to enter the minimum value based on the previously calculated
5 VDC analog input value.
SCAL 1 #--#.#V Note: Press the Menu Right → key to review both the scale value 1
SCAL 2 #--#.#V and scale value 2 settings any time during the setup procedure.
ANALOG 01 # Displays analog 01 and scale value 2 settings. Use the numeric keys
SCALE VALUE 2 ? to enter the maximum value based on the previously calculated
5 VDC analog value.
Menu 13—Communications
Menu 13 Displays with Key Entries
Key
Entry Display Description
MENU 13
COMMUNICATIONS Displays the menu number and name.
PROTOCOL →
Displays the KBUS protocol heading.
KBUS
OR
KBUS ONLINE YES Entering NO deactivates the online KBUS selection.
KBUS ONLINE NO
Confirms the entry.
CONNECTION TYPE → Displays the user-defined connection type. Press the Down arrow
(USER DEFINED) Y/N key if the correct connection type is displayed. If the desired
connection type is not displayed, press the Right arrow key until the
desired connection type appears.
CONNECTION TYPES
LOCAL SINGLE Y/N
LOCAL LAN N/Y
LOCAL LAN CONV N/Y Entering YES selects the connection type shown. Note: Selecting
REMOTE SINGLE N/Y one connection type deselects any previously selected choice.
REMOTE LAN N/Y
REMOTE LAN CONV N/Y
CONNECTION TYPE →
Press the Enter key.
(USER DEFINED) YES
CONNECTION TYPE →
(USER DEFINED) YES
Confirms the entry.
PRIMARY PORT → Displays the user-defined primary port subheading. Press the Down
(USER DEFINED) Y/N arrow key if the correct primary port type is displayed. If the desired
primary port type is not displayed, press the Right arrow key until the
desired primary port type appears.
PRIMARY PORTS Entering YES selects the primary port shown. Note: Selecting one
RS-232 Y/N primary port deselects any previously selected choice.
RS-485 ISO 1 N/Y
PRIMARY PORT →
Press the Enter key.
(USER DEFINED) YES
PRIMARY PORT →
Confirms the entry.
(USER DEFINED) YES
ADDRESS ? Displays the LAN connection address number. Use the numeric keys
(LAN Connections) to enter the desired address 1--128. Use one address number per
unit and use consecutive numbers. Individual addresses are
necessary for the software to call up the desired unit.
ADDRESS #
Confirms the entry.
(LAN Connections)
SYSTEM ID ? Displays the system ID request. Use the numeric keys to enter the
(Remote Connections) required system ID of remote connections. The system ID is a
password. The user must use the same password for all devices at a
site.
SYSTEM ID #
Confirms the entry.
(Remote Connections)
BAUD RATE → Displays the user-defined baud rate selection. Press the Down arrow
(USER DEFINED) Y/N key if the correct baud rate is displayed. If the desired baud rate is
not displayed, press the Right arrow key until the desired baud rate
appears.
BAUD RATES
1200 Y/N Entering YES selects the baud rate shown. Note: Selecting one
2400 N/Y
baud rate deselects any previously selected choice.
9600 N/Y
BAUD RATE →
Press the Enter key.
(USER DEFINED) YES
BAUD RATE →
Confirms the entry.
(USER DEFINED) YES
MENU 13
COMMUNICATIONS Returns the user to the menu number and name.
PROTOCOL →
Returns the user to KBUS protocol heading.
KBUS
PROTOCOL →
MODBUS
Displays the Modbus protocol heading.
OR
MODBUS ONLINE YES Entering NO deactivates the online Modbus selection.
MODBUS ONLINE NO
Press the Enter key.
MODBUS ONLINE NO
Confirms the entry.
CONNECTION TYPE → Displays the user-defined connection types. Press the Down arrow
(USER DEFINED) Y/N key if the correct connection type is displayed. If the desired
connection type is not displayed, press the Right arrow key until the
desired connection type appears.
CONNECTION TYPES Entering YES selects the connection type shown. Choices are a
SINGLE Y/N single or RS-232 to RS-485 convertor. Note: Selecting one
CONVERTOR N/Y connection type deselects any previously selected choice.
CONNECTION TYPE →
Press the Enter key.
(USER DEFINED) YES
CONNECTION TYPE →
Confirms the entry.
(USER DEFINED) YES
PRIMARY PORT → Displays the user-defined primary ports. Press the Down arrow if the
(USER DEFINED) Y/N correct primary port is displayed. If the desired primary port is not
displayed, press the Right arrow key until the desired primary port
appears.
PRIMARY PORTS
RS-232 Y/N Entering YES selects the primary port shown. Note: Selecting one
RS-485 N/Y primary port deselects any previously selected choice.
PRIMARY PORT →
Press the Enter key.
(USER DEFINED) YES
PRIMARY PORT →
(USER DEFINED) YES Confirms the entry.
ADDRESS ? Displays the address number. Use the numeric keys to enter the
desired address 1--128. Use one address number per unit and use
consecutive numbers. Individual addresses are necessary for the
software to call up the desired unit.
ADDRESS #
Confirms the entry.
BAUD RATE → Displays the user-defined baud rate. Press the Down arrow key if the
(USER DEFINED) Y/N correct baud rate is displayed. If the desired baud rate is not
displayed, press the Right arrow key until the desired baud rate
appears.
BAUD RATES
9600 N/Y Entering YES selects the baud rate shown. Note: Selecting one
19200 N/Y baud rate deselects any previously selected choice.
BAUD RATE →
(USER DEFINED) YES Press the Enter key.
BAUD RATE →
Confirms the entry.
(USER DEFINED) YES
PROTOCOL →
Returns the user to Modbus protocol heading.
MODBUS
Menu 14 allows altering controller data either locally D Local—using the controller keypad
using the keypad or remotely using a PC or other device. D Remote—using a PC
D Off—no programming is permitted
The user must enter a password (access code) to
enable the programming mode. Enter Yes to one mode to change the other two choices
to No.
Local Programming. Local programming is data
alteration using the controller keypad and display.
Note: Use the generator set controller to initially set up
remote programming. Remote programming is
Remote Programming. Remote programming is data
alteration using devices connected to a communication not allowed from a PC unless the controller is first
port using KBUS or Modbusr including Monitor III set for remote programming using Menu 14.
software. Note: After completing the programming always place
Note: Log into the local programming mode to edit the the controller back in the Programming Mode Off
position to prevent inadvertent program changes.
programming access code. The factory default
access code is the number 0. Modbusr is a registered trademark of Schneider
Use Menu 14 to change the access code. Record the Electric.
new number and give the access code to authorized
individuals only. Should the controller logic not accept
the access code or if the new code number is lost,
contact your local authorized distributor/dealer for
password information.
PROGRAMMING MODE → Displays the user-defined programming mode. Press the Down
(USER DEFINED) Y/N arrow key if the correct programming mode is displayed. If the
desired programming mode is not displayed, press the Right arrow
key until the desired programming mode appears.
PROGRAMMING MODES
OFF Y/N Entering YES selects the programming mode shown.
LOCAL N/Y Note: Selecting one programming mode deselects any previously
REMOTE N/Y selected choice.
PROGRAMMING MODE Changing the programming mode requires entering the access code.
ENTER CODE * Enter the access code and press the Enter key.
Note: The factory default access code is the number 0.
PROGRAMMING MODE →
Confirms the entry.
(USER DEFINED) YES
PROGRAMMING MODE → Displays the programming mode and changes the access code.
CHANGE ACCESS CODE Press the Down arrow key if you do not wish to change the access
code. To change the access code, press the Right arrow key.
PROGRAMMING MODE
Enter the old access code and press the Enter key.
ENTER OLD CODE *
PROGRAMMING MODE
Enter the new access code and press the Enter key.
ENTER NEW CODE *
PROGRAMMING MODE →
Confirms the entry.
CHANGE ACCESS CODE
MENU 14
PROGRAMMING MODE
Returns the user to the programming mode heading.
PR OVERVOLTAGE → Displays the overvoltage % value. When required, use the numeric
?% #VAC keys to enter the desired overvoltage % value and press the Enter
key.
PR OVERVOLTAGE →
Displays the corrected overvoltage % value.
#% #VAC
TIME DELAY → Displays the overvoltage time delay. When required, use the numeric
?SEC keys to enter the desired time delay value and press the Enter key.
TIME DELAY →
Displays the corrected overvoltage time delay value.
#SEC
PR OVERVOLTAGE →
Returns the user to the overvoltage % value display.
?% #VAC
PR UNDERVOLTAGE → Displays the undervoltage % value. When required, use the numeric
?% #VAC keys to enter the desired undervoltage % value and press the Enter
key.
PR UNDERVOLTAGE →
Displays the corrected undervoltage % value.
#% #VAC
TIME DELAY → Displays the undervoltage time delay. When required, use the
?SEC numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY →
Displays the corrected undervoltage time delay value.
#SEC
PR UNDERVOLTAGE →
Returns the user to the undervoltage % value display.
?% #VAC
TIME DELAY → Displays the overfrequency time delay. When required, use the
?SEC numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY →
Displays the corrected overfrequency time delay value.
#SEC
PR OVERFREQUENCY →
Returns the user to the overfrequency % value display.
?% #VAC
TIME DELAY → Displays the underfrequency time delay. When required, use the
?SEC numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY →
Displays the corrected underfrequency time delay value.
#SEC
PR UNDERFREQUENCY →
Returns the user to the underfrequency % value display.
?% #HZ
PR REVERSE POWER → Displays the reverse power % value. When required, use the
?% #KW numeric keys to enter the desired reverse power % value and press
the Enter key.
PR REVERSE POWER →
Displays the corrected reverse power % value.
#% #KW
TIME DELAY → Displays the reverse power time delay. When required, use the
?SEC numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY →
Displays the corrected reverse power time delay value.
#SEC
PR REVERSE POWER →
Returns the user to the reverse power % value display.
?% #KW
SD REVERSE POWER → Displays the reverse power shutdown % value. When required, use
?% #KW the numeric keys to enter the desired reverse power shutdown %
value and press the Enter key.
SD REVERSE POWER →
Displays the corrected reverse power shutdown % value.
#% #KW
TIME DELAY → Displays the reverse power shutdown time delay. When required,
?SEC use the numeric keys to enter the desired time delay value and press
the Enter key.
TIME DELAY →
Displays the corrected reverse power shutdown time delay value.
#SEC
SD REVERSE POWER →
Returns the user to the reverse power shutdown % value display.
?% #KW
PR OVER POWER → Displays the over power % value. When required, use the numeric
?% #KW keys to enter the desired over power % value and press the Enter
key.
PR OVER POWER →
Displays the corrected over power % value.
#% #KW
TIME DELAY → Displays the over power time delay. When required, use the numeric
?SEC keys to enter the desired time delay value and press the Enter key.
TIME DELAY →
Displays the corrected over power time delay value.
#SEC
PR OVER POWER →
?% #KW
Returns the user to the over power % value display.
SD OVER POWER → Displays the over power shutdown % value. When required, use the
?% #KW numeric keys to enter the desired over power shutdown % value and
press the Enter key.
SD OVER POWER →
Displays the corrected over power shutdown % value.
#% #KW
TIME DELAY → Displays the over power shutdown time delay. When required, use
?SEC the numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY →
Displays the corrected over power shutdown time delay value.
#SEC
SD OVER POWER →
Returns the user to the over power shutdown % value display.
?% #KW
PR LOSS OF FIELD → Displays the loss of field % value. When required, use the numeric
?% #KVAR keys to enter the desired loss of field % value and press the Enter
key.
PR LOSS OF FIELD →
Displays the corrected loss of field % value.
#% #KVAR
TIME DELAY → Displays the loss of field time delay. When required, use the numeric
?SEC keys to enter the desired time delay value and press the Enter key.
TIME DELAY →
Displays the corrected loss of field time delay value.
#SEC
PR LOSS OF FIELD →
Returns the user to the loss of field % value display.
?% #KVAR
SD LOSS OF FIELD → Displays the loss of field shutdown % value. When required, use the
?% #KVAR numeric keys to enter the desired loss of field % value and press the
Enter key.
SD LOSS OF FIELD →
Displays the corrected loss of field shutdown % value.
#% #KVAR
TIME DELAY → Displays the loss of field shutdown time delay. When required, use
?SEC the numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY →
Displays the corrected loss of field shutdown time delay value.
#SEC
SD LOSS OF FIELD →
Returns the user to the loss of field shutdown % value display.
?% #KVAR
PR OVERCURRENT VR → Displays the over current with voltage restraint (VR) % value. When
?% #AMPS required, use the numeric keys to enter the desired over current %
value and press the Enter key.
PR OVERCURRENT VR →
Displays the corrected over current % value.
#% #AMPS
TIME DELAY → Displays the over current time delay. When required, use the numeric
?SEC keys to enter the desired time delay value and press the Enter key.
TIME DELAY →
Displays the corrected over current time delay value.
#SEC
PR OVERCURRENT VR →
Returns the user to the over current % value display.
?% #AMPS
SD OVER CURRENT VR → Displays the over current shutdown with voltage restraint (VR) %
?% #AMPS value. When required, use the numeric keys to enter the desired over
current shutdown % value and press the Enter key.
SD OVER CURRENT VR →
Displays the corrected over current shutdown % value.
#% #AMPS
TIME DELAY → Displays the over current shutdown time delay. When required, use
?SEC the numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY → Displays the corrected over current shutdown time delay value.
#SEC
SD OVER CURRENT VR → Returns the user to the over current shutdown % value display.
?% #AMPS
SYNC VOLTAGE MATCH → Displays the synchronization matching voltage value. When required,
? VAC use the numeric keys to enter the desired synchronization matching
voltage value and press the Enter key.
SYNC VOLTAGE MATCH →
Displays the corrected synchronization matching voltage value.
# VAC
SYNC FREQ MATCH → Displays the synchronization matching frequency value. When
? HZ required, use the numeric keys to enter the desired synchronization
matching frequency value and press the Enter key.
SYNC FREQ MATCH →
# HZ Displays the corrected synchronization matching frequency value.
SYNC PHASE MATCH → Displays the synchronization matching phase value. When required,
? DEG use the numeric keys to enter the desired synchronization matching
phase value and press the Enter key.
SYNC FREQ MATCH →
# DEG Displays the corrected synchronization matching phase value.
TIME DELAY → Displays the synchronization time delay. When required, use the
?SEC numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY →
Displays the corrected synchronization time delay value.
#SEC
SYNC VOLTAGE MATCH → Returns the user to the synchronization matching voltage value
? VAC display.
FINAL ASSEMBLY
Displays the final assembly clock number at the factory.
CLOCK NO #
OPERATING DAYS #
Displays the generator set operating days.
MODEL NO #
Displays the generator set model number.
SPEC NO #
Displays the generator set specification number.
GENSET SERIAL NO #
Displays the generator set serial number.
ALTERNATOR PART NO #
Displays the alternator part number.
ENGINE PART NO #
Displays the engine part number.
SERIAL NO CONFIRM →
Displays the generator set serial number confirmation display.
CONFIRM SERIAL? Y/N Press YES, if the display matches the generator set nameplate serial
###### number. Refer to the Menu 20 NOTE above if the serial numbers do
not match.
CONFIRM SERIAL? YES
Press the Enter key.
######
SERIAL NO CONFIRM →
Returns user to the Serial No. Confirm display.
CONTROLLER SERIAL NO #
Displays the controller serial number.
CODE VERSION #
Displays the controller software (code) version.
COPYRIGHT XXXX
Under normal operating conditions, the generator set’s Disabling the generator set. Accidental starting can
alternator requires no routine service. Consult cause severe injury or death. Before working on the
Section 2.1, Prestart Checklist, for a list of routine generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
checks.
OFF position. (2) Disconnect the power to the battery
charger. (3) Remove the battery cables, negative (--) lead
first. Reconnect the negative (--) lead last when reconnecting
3.1 Alternator Service the battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
When operating the generator set under dusty or dirty start/stop switch, or engine start command from a remote
conditions, use dry compressed air to blow dust out of computer.
the alternator while the generator set is running. Direct
the stream of air through openings in the generator set
WARNING
end bracket.
WARNING WARNING
3.4.2 300--2250 kW Models with 4. Tighten the bleed screw. Wipe up any fuel leakage.
Single-Bearing Alternator 5. Place the fuel valves in the normal operation
The alternator bearing requires lubrication at intervals position. Open the fuel valve located between the
specified in the generator set technical manual. Use pipe tee and the engine. Close the fuel valves on
Chevron SRI or equivalent antifriction, high-quality each side of the fuel prime pump.
grease with a lubrication temperature range of --30°C to
175°C (--22°F to 350°F).
Note: Bleed air from the fuel system according to the Valve Open Valve Closed PK-272000-H
Pushbutton Description
Off Pushbutton disables the ECM for routine
maintenance to the tank system.
On Pushbutton activates the ECM after the
OFF pushbutton is depressed. On
power-up after a power outage, the ECM
automatically turns on.
Test Pushbutton lights front panel LEDs for
3 seconds and activates the pump/motor
for as long as the pushbutton is
depressed. The alarm relays maintain
their original positions.
Internal test Pushbutton (located inside the ECM) tests
224825
each alarm LED and remote annunciation
relay in sequential order (high fuel to ECM
Figure 3-2 ECM Front Panel Layout functional).
Servicing the day tank. Hazardous voltage can cause Figure 3-4 ECM Pushbuttons
severe injury or death. Service the day tank electrical
control module (ECM) as prescribed in the equipment
manual. Disconnect the power to the day tank before
ECM Alarms
servicing. Press the day tank ECM OFF pushbutton to The ECM has five standard alarm conditions indicated
disconnect the power. Notice that line voltage is still present
within the ECM when the POWER ON light is lit. Ensure that
locally by LEDs and remotely by relays. Figure 3-5
the generator set and day tank are electrically grounded. Do describes the five alarm conditions. Make controller
not operate the day tank when standing in water or on wet connections to the normally open and normally closed
ground because these conditions increase the risk of relay contacts provided.
electrocution.
Alarm Description
ECM General Function High fuel Alarm activates at 106% of normal fuel
level.
The ECM controls a pump/motor that maintains the day Low fuel Alarm activates at 62% of normal fuel
tank fuel level. The ECM motor relay is connected to the level. The alarm provides time to respond
pump/motor. The ECM starts the pump when the fuel to a potential problem before a low fuel
shutdown occurs.
level drops to 87% of full and stops the pump when the
Critical low fuel Alarm activates at 6% of normal fuel level
day tank is full. (engine shutdown) to warn the operator to shut down the
generator set before fuel runs out.
ECM Function Indicator LEDs Fuel in rupture Alarm activates when the ECM detects
basin, if equipped fuel in the rupture basin.
Two LEDs on the front panel indicate ECM operation. ECM functional Alarm activates to indicate a problem with
See Figure 3-2 for the locations of the LEDs. Figure 3-3 the ECM operation.
describes the LED functions. Note: The ECM functional alarm relay
activates a user-installed alarm when the
relay deenergizes.
Function Description
Power On LED lights to indicate that power is applied Figure 3-5 ECM Alarms
to the ECM.
Pump Running LED lights when the pump starts.
Most models operate on either natural gas or LPG fuel N5 not used 65 65 LFP2--COM
by performing the fuel conversion procedure. A hang 73B not used QCON--10 (LPG fuel solenoid valve)
tag on the fuel regulator may provide additional 65 not used N5 N5 not used
conversion setup information. Fuel conversion may 63 LFP1--NC low fuel pressure sensor (if used)
decrease generator set output. Refer to the respective
70E2 P6--B (15 amp fuse)
generator set spec sheet for ratings based on fuel
selection. Changing fuel does not alter the emissions Figure 3-9 Gas Fuel Electrical Connections
compliance of the generator set engine. Consult your
local generator set distributor/dealer for additional
3.6.4 Fuel System Changeover Kits
information.
(Dual Fuel)
Note: If a gas-fueled model has the fuel type changed
(LPG to natural gas or natural gas to LPG), order Automatic Changeover
a new nameplate from an authorized distributor/
dealer with the updated ratings and attach to the A changeover fuel system kit provides automatic
generator set. changeover from natural gas to LPG vapor. The
primary and backup fuels each have a fuel solenoid
To change the fuel type, change the electrical valve. The primary fuel is natural gas; the backup fuel is
connections between the fuel system and the engine LPG vapor. Before starting, both fuel solenoid valves
ECM. The engine ECM has fuel tables and spark are closed. When the generator set starts, the primary
advance curves programmed for both natural gas and fuel solenoid valve opens. The primary fuel line has a
LPG. The information shown below, in Figure 3-9, and in pressure switch in series with a relay connected to the
Figure 3-10 generally apply to all models and all fuels. start/run circuit.
Be sure to review the respective wiring diagram for your
specific model for possible special applications. When the primary fuel pressure drops below 0.6 kPa
(1.4 oz./in.2) or 6.4 cm (2.5 in.) water column , a relay
Natural Gas Operation opens the backup fuel solenoid valve and closes the
D Disconnect lead 65 from lead N5. primary fuel solenoid valve. When the primary fuel
pressure rises above 0.6 kPa (1.4 oz./in.2) or 6.4 cm
D Disconnect lead 73B from the fuel solenoid valve.
(2.5 in.) water column, the generator set uses the
D Connect lead 73A to the fuel solenoid valve. primary fuel. Contact an authorized service
distributor/dealer for kit availability.
LPG Vapor Operation
D Disconnect lead 73A from the fuel solenoid valve.
D Connect lead 73B to the fuel solenoid valve (LPG
vapor).
D Connect lead 65 to lead N5 (ground).
TT-1560
3.7.1 Coolant Level Check
4 3
1. Heater element Check the coolant level in the coolant recovery tank.
2. Inline connector Maintain the coolant level between the high and low
3. Thermostat marks.
4. AC power cord
Note: Periodically check the coolant level by removing
Figure 3-11 Crankcase Ventilation Heater Kit
the pressure cap. Do not rely solely on the level in
the coolant recovery tank. Add fresh coolant until
3.7 Cooling System the level is just below the overflow tube opening of
the filler neck.
The cooling system maintenance information applies to
radiator-cooled models and city-water-cooled (heat
exchanger) models. The cooling systems function
similarly even though they use different components.
Radiator-cooled models have a radiator with a pressure
cap and coolant recovery tank. City-water-cooled
models have a heat exchanger and an expansion/surge
tank with a pressure cap.
D Inspect the radiator’s exterior for obstructions. 1. Flush the cooling system with clean water.
Remove dirt and foreign material using a soft brush or
cloth to avoid damaging the radiator fins. 2. If the inside of the radiator still has mineral deposits,
use a radiator cleaner to remove the remaining
D Check the hoses and connections for leaks. Replace deposits following the manufacturer’s instructions.
any cracked, frayed, or spongy hoses.
3. Drain, clean, and flush the coolant recovery tank.
D Check the condition and tension of the radiator fan
and water pump belt(s). Follow the belt tension 3.7.5 Procedure to Refill Cooling
procedure in this manual and/or the engine operation
manual.
System
See the generator set spec sheet for coolant capacity.
D Check the pressure cap seal and replace a cracked or
deteriorated cap. Remove dirt and other debris from Note: Do not add coolant to a hot engine. Adding
the pressure cap and filler neck. The pressure cap coolant to a hot engine can cause the cylinder
raises the boiling point of the coolant, enabling higher block or cylinder head to crack. Wait until the
operating temperatures. Replace a leaking pressure engine has cooled.
cap with one rated for the same pressure. The
pressure cap rating usually appears on the pressure 1. Remove the pressure cap.
cap.
2. Close the radiator and/or engine block coolant
drain valve(s) and tighten the cooling system hose
3.7.3 Procedure to Drain Cooling clamps.
System
3. Open the air-bleed petcocks, if equipped. Close
For optimum protection, drain, flush, and refill the the air-bleed petcocks when coolant begins to flow
cooling system at the intervals listed in the service from them.
schedule.
4. Add coolant additives or water pump lubricants
Note: Dispose of all waste materials (oil, fuel, coolant, according to the engine manufacturer’s
filters, and gaskets) in an environmentally safe recommendations in the engine operation manual.
manner.
5. Fill the cooling system with the recommended
1. Deenergize the block heater, if equipped. coolant/antifreeze mixture of 50% ethylene glycol
and 50% clean, softened water to inhibit
2. Remove the pressure cap to allow the entire
rust/corrosion and prevent freezing.
system to drain and prevent air pockets from
restricting coolant flow through the engine block. Note: A coolant solution of 50% ethylene glycol
provides freezing protection to --37°C
3. Open the radiator and/or engine block coolant drain
(--34°F) and overheating protection to
valve(s) and allow the system to drain.
129°C (265°F). A coolant solution
4. If the inside of the radiator has mineral deposits or containing less than 50% ethylene glycol
the used coolant contains dirt or grease, refer to may not provide adequate freezing and
Section 3.7.4, Procedure to Flush and Clean the overheating protection. A coolant solution
Cooling System. If the cooling system does not containing more than 50% ethylene glycol
have mineral deposits, go to Section 3.7.5, can cause engine or component damage.
Procedure to Refill the Cooling System. Do not use alcohol or methanol antifreeze
or mix them with the specified coolant.
Refer to the engine operation manual for
recommendations regarding the coolant
mixture to use in extreme temperatures.
D Socket wrench sets American Standard and Metric 9. Replace the fan guards, screens, and covers that
sizes were removed to access the radiator fan hardware.
D Torque wrench, up to 203 Nm (150 ft. lb.)
10. Check that the generator set master switch is in the
OFF position.
Procedure
11. Reconnect the generator set engine starting
1. Place the generator set master switch in the OFF/
battery, negative (--) lead last.
RESET position.
12. Reconnect power to the battery charger, if
2. Disconnect the power to the battery charger, if
equipped.
equipped.
3.9 Radiator Expansion Joint 4. Inject grease into the two bearings on the fan shaft
block and the two bearings on the idler shaft block
Loosening—Initial Setup Only using a grease gun until a 3--6 mm (0.13--0.25 in.)
grease column shows at the bearing pressure relief
Loosen the radiator expansion joint nuts on
port. See Figure 3-14.
1200--2000 kW generator sets that have radiators
manufactured by Young Radiator Company. Expansion Note: The fan shaft and idler shaft bearings have
joints located on each side of the radiator permit pressure relief ports to prevent bearing
differential thermal expansion of the radiator tank. The damage caused by overlubrication.
factory tightens the 12 expansion joint nuts before
generator set shipment. Loosen the expansion joint
nuts one full turn before running the generator set. See 1
Figure 3-13.
2 5
3 2
TP-5353-3
1. Air flow
2. Expansion joint nuts for rear tank, left side
3. Expansion joint nuts for front tank, left side
4. Top front of radiator
3
3.10 Radiator Fan Bearing TP-5353-3
Lubrication 1
1. Grease fittings
The following procedure applies only to 1200 kW and 2. Pressure relief port
larger generator sets. Lubricate the radiator fan shaft 3. Radiator assembly
4. Idler shaft grease fittings
and idler shaft bearings at every engine oil change to 5. Fan shaft grease fittings
avoid bearing damage. Lubricate the bearings every
200 hours of operation when the generator set runs in Figure 3-14 Radiator Fan Bearings and Pressure
ambient temperatures below 29°C (85°F) or when the Relief Ports, Typical
generator set runs in a dusty and/or humid environment.
Battery electrolyte is a diluted sulfuric acid. Battery acid Clean the battery and cables and tighten the battery
can cause severe injury or death. Battery acid can cause terminals according to the service schedule
blindness and burn skin. Always wear splashproof safety recommendations. Clean the battery by wiping it with a
goggles, rubber gloves, and boots when servicing the battery. damp cloth. Keep the electrical connections dry and
Do not open a sealed battery or mutilate the battery case. If tight.
battery acid splashes in the eyes or on the skin, immediately
flush the affected area for 15 minutes with large quantities of If corrosion exists, disconnect the cables from the
clean water. Seek immediate medical aid in the case of eye battery and remove the corrosion with a wire brush.
contact. Never add acid to a battery after placing the battery in
Clean the battery and cables with a solution of baking
service, as this may result in hazardous spattering of battery
acid. soda and water. Do not allow the cleaning solution to
enter battery cells. Flush the battery and cables with
clean water and wipe the battery with a dry cloth.
1 2 1 2
1 2
1 2 3 4
KW-272000-B
EZ-273000-J 1. To positive (+) terminal on starter solenoid.
1. To positive (+) terminal on starter solenoid. 2. To ground (--) terminal on or near starter motor.
2. To ground (--) terminal on or near starter motor. 3. To positive (+) terminal on second starter solenoid.
4. To ground (--) terminal on or near second starter motor.
Figure 3-16 12-Volt Engine Electrical System Single
Starter Motor Typical Battery Connection Figure 3-18 24-Volt Engine Electrical System Dual
Starter Motors Typical Battery
1 2
Connections
1-046
1. Filler caps
2. Electrolyte level
caps. Holding the hydrometer vertically, read the 65.6 150 + .028
Example No. 1
number on the glass bulb at the top of the electrolyte + .026
temperature in Figure 3-20 and correct the specific 48.9 120 + .016 Subtract .024 Specific Gravity
+ .014
Corrected Specific Gravity is 1.226
gravity by the amount shown. The battery is fully
charged if the specific gravity is 1.260 at an electrolyte 43.3 110 + .012 1.250 -- .024 = 1.226
temperature of 26.7_C (80_F). Maintain the specific + .010
gravities between cells within ±0.01 of each other. 37.8 100 + .008
Charge the battery if the specific gravity is below 1.215 + .006 Example No. 2
at an electrolyte temperature of 26.7_C (80_F). 32.2 90 + .004
Temperature above 26.7°C (80°F)
+ .002
Note: Some battery testers have four or five beads in a 26.7 80 0 Hydrometer Reading 1.235
test tube. Draw electrolyte into the tube as with -- .002
Acid Temperature 37.8°C (100°F)
the battery hydrometer described in this section 21.1 70 -- .004
or use the manufacturer’s instructions. Use --. 006 Add .008 Specific Gravity
Corrected Specific Gravity is
Figure 3-21 to interpret typical test results. 15.6 60 -- .008
1.243
-- .010
-- 6.7 20 -- .024
3. With the engine still warm, drain the oil from the
crankcase.
A-364162-B
3. Run the generator set until the engine stops. 5. Spread a light film of oil over unpainted metallic
surfaces to inhibit rust and corrosion.
4. Place the generator set master switch in the
OFF/RESET position.
3.14.6 Battery
3.14.4 Internal Engine Components Perform battery storage after all other storage
(Gas-Fueled Engines) procedures.
If you have access to a fogging agent or SAE 10 oil 1. Place the generator set master switch in the
prepare the pistons and cylinders for storage as follows: OFF/RESET position.
1. While the engine is running, spray a fogging agent 2. Disconnect the battery(ies), negative (--) lead first.
or SAE 10 engine oil into the air intake for about two
3. Clean the battery. Refer to Section 3.11.1 for the
minutes until the engine stops.
battery cleaning procedure.
2. Place the generator set master switch in the
4. Place the battery in a cool, dry location.
OFF/RESET position.
5. Connect the battery to a float/equalize battery
If a fogging agent is not available perform the following:
charger or charge it monthly with a trickle battery
1. Remove the spark plugs. charger. Refer to the battery charger
manufacturer’s recommendations.
2. Pour 15 cc (0.5 oz.) of engine oil into each spark
plug hole. Maintain a full charge to extend battery life.
This section contains generator set troubleshooting, Battle Switch/Fault Shutdown Override Switch. The
diagnostic, and repair information. battle switch function forces the system to ignore normal
fault shutdowns such as low oil pressure and high
Note: The controller clock must be set each time the engine temperature. The battle switch does not override
engine battery(ies) are disconnected. The the emergency stop and overspeed shutdown. When
controller clock determines exercise run time and the battle switch function is enabled, the generator set
event records. See Menu 6—Time and Date, for continues to run regardless of shutdown signals where
setup. potential engine/alternator damage can occur.
Use the following charts to diagnose and correct When this input is enabled, the yellow warning lamp
common problems. First check for simple causes such illuminates and stored warning/shutdown events that
as a dead engine starting battery or an open circuit are ignored continue to log in Menu 5—Event History.
breaker. The charts include a list of common problems,
possible causes of the problem, recommended See Section 2.8.9, Menu 9—Input Setup, for information
corrective actions, and references to detailed on how to enable the battle switch feature.
information or repair procedures.
Cooldown Temperature Override Function. This
Maintain a record of repairs and adjustments performed function provides the ability to bypass the generator set
on the equipment. If the procedures in this manual do cooldown temperature shutdown and force the unit to
not explain how to correct the problem, contact an wait for the engine cooldown time delay.
authorized distributor/dealer. Use the record to help
describe the problem and repairs or adjustments made See Section 2.8.8, Menu 8—Time Delays, for
to the equipment. information on how to enable the cooldown temperature
override feature.
Section or
Publication
Cranks but
does not start
Starts hard
Stops suddenly
Lacks power
Overheats
Low oil pressure
High fuel
consumption
Excessive or
abnormal noise
Displays error
message/locks up
Probable Causes Recommended Actions Reference*
* Sec./Section—numbered section of this manual; ATS—Automatic Transfer Switch; Eng.—Engine; Gen.—Generator Set; I/M—Installation Manual; O/M—Operation Manual;
S/M—Service Manual; S/S—Spec Sheet; W/D—Wiring Diagram Manual
[ Have an authorized service distributor/dealer perform this service.
TP-6200 10/12
Trouble Symptoms
TP-6200 10/12
Section or
Publication
Cranks but
does not start
Starts hard
Stops suddenly
Lacks power
Overheats
Low oil pressure
High fuel
consumption
Excessive or
abnormal noise
Displays error
message/locks up
Probable Causes Recommended Actions Reference*
Controller
x x Controller circuit board(s) inoperative Replace the controller circuit board. Gen. S/M
x Controller fault Troubleshoot the controller.[ Gen. S/M
x x x Controller fuse blown Replace the blown controller fuse. If the fuse blows again, Section 2, W/D
troubleshoot the controller.[
x 10/12
TP-6200 Controller master switch inoperative Replace the controller master switch. —
x Controller master switch in the Move the controller master switch to the RUN or AUTO Section 2
OFF/RESET position position.
x Engine start circuit open Move the controller master switch to the RUN position to Section 2, W/D,
test the generator set. Troubleshoot the auto start circuit Gen. I/M, S/M
and time delays. ATS O/M, S/M
x x Voltage regulation inoperative Replace the controller fuse, If the fuse blows again, Section Fuses,
troubleshoot the controller. Gen. S/M
x Controller firmware error Review the controller display troubleshooting chart. Section 4.2
x Controller clock not set Reset time and date. Section 2.8.6,
Menu 6
Engine
x x x x Air cleaner clogged Clean or replace the filter element. Eng. O/M
x x x x x Compression weak Check the compression.[ Eng. S/M
x x x x x Engine overload Reduce the electrical load. See the generator set spec S/S
sheet for wattage specifications.
x Exhaust system leak Inspect the exhaust system. Replace the inoperative I/M
exhaust system components.[
x Exhaust system not securely installed Inspect the exhaust system. Tighten the loose exhaust I/M
system components.[
x x x x Governor inoperative Adjust the governor.[ Gen. S/M
x x Valve clearance incorrect Adjust the valves.[ Eng. S/M
x Vibration excessive Tighten all loose hardware. —
x x x Ignition system inoperative Check the ignition system Eng. O/M
(gas/gasoline only) (spark plugs, spark plug wires, etc.).
* Sec./Section—numbered section of this manual; ATS—Automatic Transfer Switch; Eng.—Engine; Gen.—Generator Set; I/M—Installation Manual; O/M—Operation Manual;
S/M—Service Manual; S/S—Spec Sheet; W/D—Wiring Diagram Manual
[ Have an authorized service distributor/dealer perform this service.
Section or
Publication
Cranks but
does not start
Starts hard
Stops suddenly
Lacks power
Overheats
Low oil pressure
High fuel
consumption
Excessive or
abnormal noise
Displays error
message/locks up
Probable Causes Recommended Actions Reference*
Cooling System
x x Air openings clogged Clean the air openings. —
* Sec./Section—numbered section of this manual; ATS—Automatic Transfer Switch; Eng.—Engine; Gen.—Generator Set; I/M—Installation Manual; O/M—Operation Manual;
S/M—Service Manual; S/S—Spec Sheet; W/D—Wiring Diagram Manual
[ Have an authorized service distributor/dealer perform this service.
TP-6200 10/12
4.2 Controller Display and Voltage Regulation Troubleshooting Chart
Section or Publication
Trouble Symptoms Probable Causes Recommended Actions Reference*
Controller Display and Voltage Regulator
TP-6200 10/12
Display is black No/low battery charge Recharge/replace battery Section 3, Battery
Display shows single segment Low battery voltage Recharge battery Section 3, Battery
Display shows an error message Controller firmware or keypad entry error Review the Request and Error Message Section Section 2.5.3
Display shows an EEPROM WRITE EEPROM fault caused by component failure, lightening strike, or Reinitialize the problem data block [ Contact an Authorized
ERROR message voltage spike Distributor/Dealer
Display locks up No/low battery charge Recharge/replace battery Section 3, Battery
Output voltage ramps Defective exciter winding Troubleshoot alternator components [ Generator Service Manual
Output voltage unstable Voltage regulation calibration incorrect
TP-6200 10/12 Readjust voltage regulation [ Menu 11, Voltage Regulator
Speed adjust does not function Analog input A06 is supported with Doosan, GM, and Volvo Check calibration values Menu 12, Calibration
engines only
Voltage adjust does not function for Analog input A07 description does not match Analog Volt Adjust Change description to Analog Volt Adjust using Monitor III Monitor Software Manual,
paralleling applications software or enable analog voltage adjust in Menu 11 Menu 9, Input Setup
* Sec./Section—numbered section of this manual; ATS—Automatic Transfer Switch; Eng.—Engine; Gen.—Generator Set; I/M—Installation Manual; O/M—Operation Manual;
S/M—Service Manual; S/S—Spec Sheet; W/D—Wiring Diagram Manual
[ Have an authorized service distributor/dealer perform this service.
The instructions provided with the accessory kit Single-Relay Dry Contact
supersede these instructions where there are Ten-Relay Dry Contact
differences. In general, run AC and DC wiring in Twenty-Relay Dry Contact
separate conduit. Use shielded cable for all analog Wireless Monitor
inputs. Observe all applicable national, state, and local
electrical codes during accessory installation. Figure 6-1 Optional Accessories
GM13984-
identification.
Figure 6-4 Common Failure Relay Kit
GM13984-
CHARGER MALFUNCTION
LV HV CM BATTERY CHARGER
ALARM TERMINAL STRIP
GM16088A-A
A relay contact for customer connection indicates a 1. Reconnect battery, if not already done.
ground fault condition and is part of a ground fault alarm.
See Figure 6-8 for electrical connections and the 2. Place the controller master switch to the AUTO
following procedure for controller setup. Use the position.
instructions with the kit when provided to install and
3. Press the Alarm Off key to silence the alarm horn, if
setup this accessory.
necessary.
POWER SUPPLY GENERATOR
DC 12 -- TB3-9 N
4. If the programming mode LED is not flashing, go to
or 24 V + TB3-4 See assembly
drawing and the step 5. If the programming mode LED is
pick list for
neutral to
ground cable.
flashing, go to step 6.
GFA 300
Generator
system
a. Press keys .
ground
connect to
ground bus.
Disabling the generator set. Accidental starting can c. Press once to select this input.
cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery d. Press until Ground Fault is displayed.
charger. (3) Remove the battery cables, negative (--) lead
first. Reconnect the negative (--) lead last when reconnecting
the battery. Follow these precautions to prevent starting of the e. Press to define Digital Input #06 as
generator set by an automatic transfer switch, remote ground fault. Entry Accepted is displayed.
start/stop switch, or engine start command from a remote
computer.
f. Press to display Digital Input #06 Inhibit
Time.
h. Press to display Digital Input #06 Delay 11. After 2-3 minutes, reconnect the battery negative
TIme. (--) lead.
GM16088A-A
a. Press .
Figure 6-9 Idle (Speed) Mode Switch
GM16088A-A
Use the single glass piece located inside the switch for REMOTE RESET SWITCH ≈
CONTACTS NORMALLY OPEN
replacement and order additional glass pieces as MOMENTARY CLOSED TO
service parts. See Section 2.3.3, Emergency Stop ACTIVATE
Switch Reset Procedure. See Section 6.2, Accessory
Connections, for terminal identifications.
A-222654 GM16088A-A-
TP-5352-1
Figure 6-14 Emergency Stop Kit Figure 6-16 Remote Reset Switch Connections
GM16088A-A
273705
TB10
GM16088A-A
BR-273000-C
1. Optional Remote Speed Pot
GM16088A-A
GM13984-/354246B-
GM16759D-C
2
5
GM16088A-A/GM10193B-A
1. TB1 terminal strip 4. TB4 terminal strip
2. TB2 terminal strip 5. P23 Connector
3. TB3 terminal strip
Figure 6-37 Terminal Strips on Controller Interconnection Circuit Board (Controller Back Panel Folded Down)
Figure 6-39 Terminal Strips TB6, TB7, TB8, and TB9 on the Controller Connection Kit in the Junction Box
Figure 6-40 Controller (Customer) Connection Kit Terminal Strip Identification with Relay Driver Outputs (RDOs)
Use the table below to record user-defined settings Note: Inhibit time delay is the time delay period after
during the generator set controller setup and calibration. crank disconnect.
The controller default settings and ranges provide
guidelines. The table contains all faults with ranges and Note: The engine ECM may limit the crank cycle even if
time delays including items that do not have the controller is set to a longer time period.
adjustments. Not adjustable user-defined settings
result when the controller logic does not allow changes
or the values are engine limited.
User-Defined Settings
Relay Inhibit
Refer Driver Time Time
Status Event to Output Default Delay Delay User-Defined
or Fault Menu Digital Display (RDO) Range Setting Selection (sec.) (sec.) Settings
Access Code 14 User-Selectable 0 (zero)
(password)
AC Sensing Loss 10 AC SENSING RDO-25 * Not adjustable
LOSS
Air Damper Control 10 Not adjustable
(if used) **
Air Damper Indicator —
(if used), see D20 **
Air/Fuel Module 10 AFM ENG Fixed Not adjustable
(AFM) Engine Start START DELAY
Delay ]
Air/Fuel Module 10 AFM REMOTE RDO-25 ] Not adjustable
(AFM) Remote START
Start ]
Air/Fuel Module Not adjustable
(AFM) Shutdown
(see D11) ]
Alternator Protection 10 ALTERNATOR Not adjustable
Shutdown PROTECTION
Analog Aux. Input 0 9 LOCAL BATT Fixed Not adjustable
VDC
Analog Aux. Inputs 9 USER-DEFINED Default Values with 30 sec. 0--60 0--60
A01--A07 A01--A07 Warning Enabled: inhibit,
HI warning 90% 5 sec. delay
LO warning 10%
HI shutdown 100%
LO shutdown 1%
Analog Aux. Input 9 A01 Default Values with 30 sec. Not adjustable
A01 (non-ECM only) COOLANT Warning Enabled: inhibit,
TEMP HI/LO warning and 0 sec. delay
HI/LO shutdown are warning,
all engine dependent 5 sec. delay
shutdown
Analog Aux. Input 9 A02 Default Values with 30 sec. Not adjustable
A02 (non-ECM only) OIL Warning Enabled: inhibit,
PRESSURE HI/LO warning and 0 sec. delay
HI/LO shutdown are warning,
all engine dependent 5 sec. delay
(255 psi max.) shutdown
Analog Aux. Input 9 A03 Default Values with 30 sec. Not adjustable
A03 ] INTAKE AIR Warning Enabled: inhibit,
TEMP HI/LO warning are 0 sec. delay
all engine dependent warning
Analog Aux. Input 9 A04 Default Values with 30 sec.
A04 * FUEL LEVEL Warning Enabled: inhibit,
HI/LO warning are 0 sec. delay
engine dependent warning
* All models, except Waukesha-powered models. ** NFPA applications
[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC
] Waukesha-powered models ]] FAA only
w Paralleling applications
The following definitions and adjustment/setting squared divided by the impedance. As the voltage is
specifications are intended for users planning to adjust reduced, the power delivered by the alternator
the voltage regulator beyond the default settings in order decreases by a squared relationship. Since it is the
to customize the alternator for a specific application. power in the alternator that translates into engine torque,
the engine load is also reduced.
This information is not intended to be a comprehensive
explanation of all the terms mentioned. There are By changing various parameters of this compensation
numerous documents available that define these terms technique, the controlling system can be tailored to
more completely than described herein. Any user match the performance capabilities of most engine and
planning to change the generator set controller alternator combinations. The point at which the
adjustment settings or to apply the generator set to unloading begins to act or how much unloading occurs
these types of applications should understand these can be adjusted to impact maximum voltage droop,
terms. maximum speed droop, or time to recover. Some
applications may not need unloading and, in these
This appendix contains references to other sections of cases, set the unloading parameter to disable the
this manual. Please refer to these sections for further function. These parameters are further described
information and explanation. below. An example is provided to help clarify the
relationship between these parameters.
Paralleling generator sets can be a complicated and
dangerous exercise. Application programming must be
performed by appropriately skilled and suitably-trained Underfrequency Unload Slope
personnel.
Underfrequency unload slope is the term used to
describe the amount that the voltage is reduced,
Definitions per-cycle-per-second or per-hertz (Hz), when in an
underfrequency condition. The slope or schedule is
sometimes called the volts-per-hertz slope. When the
Underfrequency Unloading electrical frequency drops below the cut-in point (see
Underfrequency unloading is a function used in the below), the excitation control system temporarily
reduces the regulated voltage to reduce the subsequent
alternator excitation control system to improve the
overall generator set system (engine and alternator) torque on the engine. The amount that the control
system reduces voltage is defined as the product or
response. In particular, underfrequency unloading
multiplication of the slope and the amount of frequency
relates to large-block load applications. When applied to
engine-driven alternators, large-block loads cause a or speed below the cut-in point. For every Hz below the
cut-in point, the control system reduces the line-to-line
subsequent transient torque load on the engine. This
torque load can reduce the engine’s speed below the voltage by an amount equal to the slope.
normal operating point. Typically, the engine speed
Because each engine responds differently to the various
controller or governor will compensate for this by loads encountered, the slope may be adjusted to
commanding an increase in fuel. If, however, the fuel
improve the system response. If, when large loads are
system is inadequate to recover from a relatively large applied to the generator set, the engine speed drops
load, the speed may never recover. In these instances, below the acceptable limit (as determined by the
other measures must be taken. This is where the
particular loads applied), the slope may need to be
underfrequency unloading occurs. increased. Increasing the slope will cause the voltage to
droop more during load applications, consequently
When the excitation control system detects a drop in the
speed or electrical frequency below some reducing the load torque on the engine and allowing the
speed to increase. If, however, the voltage drops below
predetermined point, the control system enters an
unloading condition. This can be described as moving to an acceptable lower limit (as determined by the
particular loads connected to the generator set), a lower
a lower voltage regulation point. By reducing the output
slope may work better. The underfrequency unloading
voltage of the alternator, the load on the generator set is
reduced. This can be shown mathematically by Ohm’s function may be disabled by setting the slope to zero.
law, which states that power is equal to the voltage
By introducing reactive droop, the reactive current can When a generator set will be connected in parallel with
be better predicted and controlled. If the current is the utility, VAR or PF control should be ENABLED. If
measured, the regulator/controller can adjust the there are multiple generator sets in parallel as well, then
excitation up or down accordingly, reducing excitation as reactive droop should be ENABLED also.
more current is supplied or increasing excitation as the
reactive current decreases. If all the parallel generator Example
sets incorporate this type of compensation, the reactive
current can be shared equally based on the proportional Two 100 kilowatt (kW) generator sets are paralleled to
size of the generator sets. For an example, see below. provide 150 kW of power at 0.8 PF and wired for a
277/480-volt wye system.
The stability and accuracy of this technique depends on
several factors. Most important, the regulation point for Total kVA load:
each generator set must be equal. That is, each voltage
adjust setting must be the equal to the other(s). This is a kVA = kW / PF
basic requirement prior to the actual paralleling
connection. Also, the effects of the reactive current in 187.5 = 150 / 0.8
each generator set must be compensated for
KVAR load:
individually, which requires an adjustable droop for each
generator set. This adjustment happens to be the kVAR = kVA * sin (acos [ PF ] )
reactive droop adjust. The reactive droop adjust is
quantified as the droop in operating voltage from the 112.5 = 187.5 * 0.6
adjusted setting when full rated load with 0.8 power
factor (PF) is applied. A droop setting of 4% voltage at Line current:
full rated load is a recommended starting point. If the
reactive current is not shared proportionately in each I = ( VA / 3 ) / VL-N
generator set, the respective droops may need
adjustment. Adjust those generator sets that have 226 amps = (187500 / 3) / 277
proportionately higher current for more droop and those
Reactive current:
generator sets with lower reactive current for less droop.
If the reactive current is not stable in the system, adjust I = (VAR / 3) / VL-N
the droop lower in all generator sets.
Lagging/Leading
KVAR Adjust
It is possible to select either a leading or lagging PF for
Using the kVAR adjust sets the desired operating value utility parallel applications. The selected mode is
for the generator set’s reactive load when the generator displayed. A NO entry switches the controller to use the
set operates in a utility paralleling application. The other reference. Because the most common mode of
desired generator set load is entered directly as kVARs. operation will be with a lagging PF, LAGGING is the
The value entered may be as low as zero or as high as default value. Because this mode should not be
the rated value (rated kW x 0.75). Any entry beyond the changed while the generator set is running, attempting
rated value will not be accepted, and a RANGE ERROR to change this mode during operation will return a
message will be displayed. RANGE ERROR message. Always shut down the
generator set to change the lagging/leading mode
The default value for kVAR adjust is zero. Each time the setting.
system’s rated kW is changed, the kVAR adjust will
revert to zero. The displayed kVAR setting may change
if the kVAR setting is changed via other inputs.
The 550 controller has built-in thermal protection for the The current and time limits are defined by actual test
alternator. This feature functions similarly to a thermal data and are maintained in the personality parameter
circuit breaker. When the output current exceeds the file. Although the equation for detecting a fault is
nominal rating for a short period of time the condition proprietary, some of the important limits are shown
causes the fault shutdown. The amount of time at which below for informational purposes.
current is over the rating is inversely related to the
amount of current above the nominal rating. In other Rated Current Time Delay
words, the higher the current, the shorter the acceptable 200% 40 seconds
time.
300% 10 seconds
425% 5 seconds
950% 1 second
The controller inputs and system events are typically engine ECMs provide additional items that the controller
driven by the engine manufacturer’s ECM. NFPA 110 will display. The following table illustrates the available
guidelines provide specific requirements that all alternator and engine outputs for monitoring and factory
controllers must have for compliance. While the reserved connections.
controller displays all NFPA 110 required data, some
NFPA 110 Paralleling DD/MTU Engines Waukesha
Controller Inputs and System Events Applications Applications with MDEC/ADEC Engines 125RZG
AC Sensing Loss Warning
Air Damper Control (if engine equipped) X
Air Damper Indicator Shutdown (see D20) (if engine
equipped) X