Temperature Monitoring of The Motor Winding: G2TFKN02

This document provides information on a G2TFKN02 motor winding temperature monitoring relay. The relay monitors up to 6 PTC temperature probes in accordance with DIN 44081 standards. It has additional selectable functions for short circuit monitoring of the thermistor line and zero-voltage latching. The relay has 2 potential free changeover contacts, LED indicators, and can be reset via an external key connection. It is designed for DIN rail mounting and has overvoltage and short circuit protection.

Uploaded by

Malek Kamel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
98 views2 pages

Temperature Monitoring of The Motor Winding: G2TFKN02

This document provides information on a G2TFKN02 motor winding temperature monitoring relay. The relay monitors up to 6 PTC temperature probes in accordance with DIN 44081 standards. It has additional selectable functions for short circuit monitoring of the thermistor line and zero-voltage latching. The relay has 2 potential free changeover contacts, LED indicators, and can be reset via an external key connection. It is designed for DIN rail mounting and has overvoltage and short circuit protection.

Uploaded by

Malek Kamel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

G2TFKN02

Temperature monitoring of the motor winding

Monitoring relays - GAMMA series


Short circuit monitoring of thermistor line
Zero-voltage latch
Supply voltage selectable via power modules
2 change-over contacts
External reset key connectable
Width 22.5mm
Industrial design

Technical data
1. Functions Mechanical life: 20 x 106 operations
Temperature monitoring of the motor winding (max. 6 PTC) with fault Electrical life: 2 x 105 operations
latch, for temperature probes in accordance with DIN 44081, test function at 1000VA resistive load
with integrated test/reset key and the following additional functions which Switching frequency: max. 60/min at 100VA resistive load
are selected by means of rotary switch: max. 6/min at 1000VA resistive load
Off Basic function (in accordance with IEC 60947-5-1)
+K Short circuit monitoring of thermistor line Overvoltage category: III (in accordance with IEC 60664-1)
+N Zero-voltage latch Rated surge voltage: 4kV
+K+N Short circuit monitoring and zero-voltage latch
7. Measuring circuit
2. Time ranges Input: terminals T1-T2
Adjustment range Initial resistance: <1.5kΩ
Start-up suppression time: - Response value (relay in off-position): ≥3.6kΩ
Tripping delay: - Release value (relay in on-position): ≤1.8kΩ
Disconnection (short circuit thermistor): <20Ω
3. Indicators Measuring voltage T1-T2: ≤2.5V DC at R ≤4.0kΩ
Green LED ON: indication of supply voltage (in accordance with DIN VDE 0660 part 302)
Yellow LED ON/OFF: indication of relay output Overvoltage category: III (in accordance with EC 60664-1)
Red LED ON/OFF: indication of failure Rated surge voltage: 4kV

4. Mechanical design 8. Control contact R


Self-extinguishing plastic housing, IP rating IP40 Function: external reset key
Mounted on DIN-Rail TS 35 according to EN 60715 Loadable: no
Mounting position: any Line length R-T2: max. 10m (twisted pair)
Shockproof terminal connection according to VBG 4 (PZ1 required), Control pulse length: -
IP rating IP20 Reset: potential free normally open contact,
Tightening torque: max. 1Nm terminals R-T2
Terminal capacity:
1 x 0.5 to 2.5mm² with/without multicore cable end 9. Accuracy
1 x 4mm² without multicore cable end Base accuracy: ±10% (of maximum scale value)
2 x 0.5 to 1.5mm² with/without multicore cable end Frequency response: -
2 x 2.5mm² flexible without multicore cable end Adjustment accuracy: -
Repetition accuracy: ≤1%
5. Input circuit Voltage influence: ≤2.3%
Supply voltage: Temperature influence: ≤0.1% / °C
12 to 400V AC terminals A1-A2 (galvanically separated)
selectable via power modules TR2 10. Ambient conditions
Tolerance: according to specification of power module Ambient temperature: -25 to +55°C
Rated frequency: according to specification of power module (in accordance with IEC 60068-1)
Rated consumption: 2VA (1.5W) -25 to +40°C
Duration of operation: 100% (in accordance with UL 508)
Reset time: 500ms Storage temperature: -25 to +70°C
Residual ripple for DC: - Transport temperature: -25 to +70°C
Drop-out voltage: >30% of the supply voltage Relative humidity: 15% to 85%
Overvoltage category: III (in accordance with IEC 60664-1) (in accordance with IEC 60721-3-3
Rated surge voltage: 4kV class 3K3)
Pollution degree: 3 (in accordanc with IEC 60664-1)
6. Output circuit Vibration resistance: 10 to 55Hz 0.35mm
2 potential free change-over contacts (in accordance with IEC 60068-2-6)
Rated voltage: 250V AC Shock resistance: 15g 11ms
Switching capacity: 750VA (3A / 250V AC) (in accordance with IEC 60068-2-27)
If the distance between the devices is less
than 5mm.
Switching capacity: 1250VA (5A / 250V AC)
If the distance between the devices is
greater than 5mm.
Fusing: 5A fast acting

[Link]
G2TFKN02

Functions Connections
No additional function (OFF)
If the supply voltage U is applied (green LED illuminated) and the
cumulative resistance of the PTC-circuit is less than 3.6kΩ (standard
temperature of the motor), the output relays switch into on-position.
Pressing the test/reset key under this conditions forces the output relays
to switch into off-position. They remain in this state as long as the test/
reset key is pressed and thus the switching function can be checked in
case of fault. The test function is not effective using an external reset
key. When the cumulative resistance of the PTC-circuit exceeds 3.6kΩ
(at least one of the PTCs has reached the cut-off temperature), the
output relays switch into off-position (red LED illuminated). The output
relays again switch into on-position (red LED not illuminated), if the
cumulative resistance drops below 1.8kΩ by cooling down of the PTC
and either a reset key (internal or external) was pressed or the supply
voltage was disconnected and re-applied.

Dimensions

Zero voltage latch (N)


If the supply voltage is interrupted and the additional function “Zero
voltage latch” (+N or +N+K) is activated, the actual status of the output
relays is stored and they switch into off-position if necessary.
If the supply voltage is re-applied the status is restored.
If this function is activated a fault can only be cleared by pressing the
internal or external reset key.

U
N

Short circuit monitoring (K)


In case of a line break or a short circuit of the probe line (cumulative
resistance less than 20Ω) the output relays switch into off-position (red
LED illuminated) if the additional function “Short circuit monitoring” (+K
or +K+N) is activated.
Under these conditions however the output relays do not change their
state, neither by pressing a reset key nor by disconnecting and re-
applying the supply voltage.

RELEASE 2011/04