Ground Fault Protection Guide
Ground Fault Protection Guide
APPLICATION
application GUIDE GUIDE
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2. Ground Current Sensing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3. Single Ground Fault Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4. Selective Ground Fault Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4.1 Time Co-ordinated System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
4.2 Zone Selective Instantaneous Protection-ZSIP . . . . . . . . . . . . . . . . . . 4
4.3 Combination Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5. Recommended Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5.1 Single Relay on the Main Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . 5
5.2 Multi-Zone Time Co-ordinated Systems . . . . . . . . . . . . . . . . . . . . . . . 6
5.3 Zone Selective Instantaneous Protection-ZSIP . . . . . . . . . . . . . . . . . . 6
6. Ground Fault Protection Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1. General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.1 Vectoral Summation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2 Direct Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2. Unit-Substations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3. Multi-Transformer Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.1 Double-ended Substations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.2 Multi-Transformer Supplied Double-ended Substations . . . . . . . . . . . 14
3.3 Multi-Transformer Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
4. Network Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5. Electrical Systems with Standby or Emergency Power . . . . . . . . . . . . . . 17
6. Auxiliary Switch Requirement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
7. Relay and Sensor Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
7.1 MGFR Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
7.2 Current Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
7.3 Function Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
1. General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2. Zone Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3. Basic Conditions for ZSIP Application . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4. Relay Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.1 Type MGFR Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
4.2 Guide Points for ZSIP Application . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5. Multiple Source Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6. Auxiliary Switch Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7. Field Testing of ZSIP Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
1
1. GENERAL
1. INTRODUCTION
Originally all electrical systems were ungrounded systems. Both AC and DC generator systems were used for
power distribution, before the invention of practical transformers. One problem that became evident was that
intermittent ground faults caused escalating DC voltages on the power lines to cause insulation failures. This
was solved by grounding the systems.
The grounding was achieved by connecting a line to ground (Corner Ground in a Delta system) or if the system
had a star point, by grounding that point. Overcurrent and short circuit protection was added to prevent fire and
all was well, so they thought, until a series of fires in the United States caused a review of protection systems.
The reason, of course, was that arcing faults to ground on the power systems could not activate the short
circuit or overload relays due to the low current levels which were within the overcurrent ratings of the breakers.
An arcing fault, they discovered could cause complete destruction of a switchboard that was thought to be
completely protected, by fuses and thermal-magnetic circuit breakers. Arcing faults are difficult to contain and
can spread quickly to other circuits and cause a complete destruction of a switchboard unless steps are taken
to prevent this situation. One method that was adopted by the Canadian Electrical Code and National Electrical
Code in the U.S. was to include Ground Fault Relay Protection in the System Requirements for Main Service
Protection, in addition to overcurrent relay protection.
This, while a step in the right direction, does not completely eliminate the problem of arcing fault damage, as
will be seen. The codes require that ground fault relays are required if the ampacity of the service is more than
1000A for systems with voltages between 150 and 750V (or 2000A below 150V). The allowable fault level is
1200A maximum for a delay time not exceeding 1 second at 3000A. This suggesting that inverse characteristics
are allowed.
An arcing fault can exist on a 480V or 600V system with current level well below 1200A, in which case the
prescribed maximum may not provide much protection. The CEC recognizes this and suggests that multi-stage
protection may be required. Although the code refers specifically, and only to, wye-connected solidly grounded
systems, as stated already, many delta-connected systems are solidly grounded at the corner or at the centre
point of one leg. They are just as prone to destruction by arcing ground faults as are equivalent wye-connected
systems, and should be protected by ground fault devices. Fortunately, ground fault protection can be applied
in the same way as for wye-connected systems.
2. the vectorial summation method, or differential method, where the sensor(s) monitors the outgoing ground
currents by making a vectorial summation of the phase and neutral (if any) currents. This method can be either
residual, when 3 separate phase sensors and a neutral current sensor are used, or zero sequence, when a
single sensor is applied which surrounds all load conductors, but not the ground wire or the shield of the cable.
Sometimes a modified zero sequence connection is used with two sensors - one on the 3 line conductors and one
on the neutral conductor.
2
The ground return method can be used only for the incoming main disconnect and only for wye-connected systems.
Only the second method can be used for feeders, but it can be used on the incoming mains, instead of (1). The
location of a current sensor defines the point beyond which down-stream (in direction of power flow) ground faults
can be detected. Consequently, it should be located as close to its associated disconnecting means as possible
and is usually mounted immediately down-stream (or up-stream) from it.
Generally, only zero sequence method can operate effectively below trip levels under 100A, due to the accuracy
limitations of the line current measurements of current sensors, when used in the other configurations.
For correct application, the following conditions should be checked before the ground current sensing method
is selected:
a) The ground return method can be used on radial distribution transformer systems or separately derived multi-
source distribution systems.
b) The ground return method should not be used on distribution systems fed from networks. The main service to
each system supplied by a network is connected to the common bus and the neutral is grounded in each system,
so multiple paths exist for the return of ground fault current to the source. Thus, if the ground current return
method is used in a switchboard fed by a network, there is a possibility that the sensor will see only a part of the
ground fault current originating in its own system. (The remainder returns through the grounding conductors of
other systems fed by the network grounding connection). Furthermore, it may also see some part of the ground
fault current originating in any other system fed by the same network. These conditions lead to errors in detection
which can result in unwanted tripping of critical breakers.
c) System-grounding points should be restricted to the main switchboard area and/or the supply transformer wye
point. Whenever other grounding points can not be avoided, additional ground strap sensors should be applied
on these connection points, connected in parallel to those in the switchboard. Ground current may return to the
source through any one, or all, grounding points, equally or unequally, and all must be included for an accurate
fault current measurement.
d) Vectorial summation sensing method by zero sequence transformers, can be used on any type of distribution
systems for feeder and/or main protection when all the phase conductors, and the neutral if used, (but not the
grounding conductor or the shield of the cable) are encircled by a sensor. Neutral currents must be summed with
line currents or an error will occur on unbalanced systems which will cause unwanted tripping.
e) The neutral must be grounded only on the line side of a zero sequence current sensor or on the load side of
the neutral sensors when a dual system is grounded at the neutral tie point. No other ground(s) shall exist on the
opposite side.
f) Zero sequence current sensors can be mounted on either the line or the load side of the protected
disconnect device.
h) Systems in which multiple individually grounded power sources are used, such as utility and emergency
generator sy tems, need careful consideration. It is usually essential that no tie exists between the neutrals of the
sources, e.g. 4 pole transfer switches or tie breakers may be needed.
3
3. SINGLE GROUND FAULT RELAY
A single ground fault relay on the main disconnect device is the minimum equipment required by the Code.
In this case, ground fault protection is provided for all points on the load side of the main disconnect. No provision
can be made for selective tripping of ground faults occurring on the load side on the down-stream feeders. Even if
the 1200 Amperes maximum current setting, allowed in the Code, is used on the main ground fault relay, tripping
of the main disconnect can occur for the ground fault on the load side of the feeder and branch circuits. The single
relay application is not recommended where maximum continuity of service is required.
A definite time relay, or inverse time delay relay, such as MGFR can be used for single relay application.
KWC = VA IG t/1000 KWC where VA = Arc Voltage (V), IG = Arc Current (A) and t = Time duration (Cycles)
The arc voltage can be assumed to be 100V for low voltage applications up to 600V. Also, since it is
inverse, the time/current characteristic of the constant KWC curves is a straight line on log-log scale
graph. Any damage greater than 10,000 KWC is considered to be unacceptable in most applications.
4
The magnitude of the fault current and the arc voltage can not be controlled by a protective relay
system, since they are determined by the impedance of the faulted circuit and the nature of the arc.
Only the fault duration can be controlled by a protective relay, which, ideally, should limit the fault
duration to the circuit breaker clearing time, plus the operating time of the relay itself. Operating time of
ground fault relays should ensure that arcing faults will be kept below the 10,000 KWC line on a co-
ordination plot of the system devices. The Zone Selective Instantaneous Protection (ZSIP), included
in I-Gard Relays, achieves the objective of instantaneous response to ground faults and yet is fully
selective, thus minimizing damage and providing full system co-ordination. If there is a ground fault on
a circuit, protected by a ZSIP Relay, and the magnitude of the fault current exceeds the pick-up setting,
the relay will trip instantaneously, providing that the fault is within that relay’s zone.
NOTE: A zone is defined as a section of a system protected by a relay and includes all of the system
from the load side of the relay’s zero sequence current sensor to the line side of any down-stream zero
sequence current sensor, if present. See Section 3 for more details of ZSIP operation.
Selectivity between zones is achieved by a signal generated by the first ground fault relay up-stream
of the fault, which operates immediately. This signal is sent to all relays further up-stream and
restrains them from tripping instantaneously. The fault is then removed by the relay closest to the
fault. If this relay, or its associated breaker, fails to clear, for any reason, the next relay up-stream
provides selective, time delayed back-up protection. Zone Selective Instantaneous Protection can be
applied to any size system. There is no limit, generally, to the number of zones that can be protected
in this manner.
All types of MGFR Relays are designed with ZSIP mode included. Probably the most cost effective
ground fault protection schemes are the two-zone ZSIP in Unit Substations and the three-zone ZSIP in
double-ended substations where all relays are located in the main switchgear. It is almost as easy to
install as a time co-ordinated system with all the advantages of the ZSIP system.
5. RECOMMENDED SETTINGS
The following general rules are suggested, to establish the settings of ground fault relays as a starting position, in
the absence of a formal co-ordination study:
5.1 SINGLE RELAY ON THE MAIN DISCONNECT
5.1.1 PICK-UP SETTINGS
Use 20% of Full Load rating, e.g. 1000 Amperes on a 5000A breaker.
5
5.1.2 TIME DELAY SETTINGS
In time co-ordinated systems, the maximum delay should co-ordinate with the maximum
acceptable KWC damage curve and will generally be inverse to achieve this condition. See
Section 6.
Use a time setting as short as possible and a current setting of 200 Amperes or less for an
individual branch circuit.
5.2.2
Use 0.1 second longer time delay setting for the feeder relays than is used on the branch
circuit protection.
5.2.3
Use 0.2 second longer time delay setting for the main disconnect than that of the relay for
the next down-stream disconnect. Use 0.1 second longer time delay when the next down-
stream disconnect is a molded case circuit breaker rated 800 Amperes or less.
5.2.4
For feeder or main disconnect relay, use a current setting no lower than 150% of the current
setting of the next down-stream relay.
5.2.5
Set instantaneous and short time trip of related overcurrent devices to the lowest practical
value, bearing in mind the possibility of inrush currents and their duration.
Zone co-ordination should be achieved by pick-up and time band settings. Use the same time
delay and current settings as recommended for time co-ordinated systems. The interlocking
(restraint) circuitry will normally provide approximately 0.03 second time delay for a ground
fault occurring anywhere on the system. The longer time delays corresponding to the dial
setting will only be necessary in the unlikely event that the nearest relay up-stream of the fault
fails to clear, or the breaker fails to open in its predetermined time and the next up-stream relay
operates as back-up protection.
6
4. Establish ground fault protection requirements. Examine possible ground-fault current paths, and select
the location and the type of the sensors. Check for existing ground fault devices to see if they can be used
effectively.
5. In case of parallel ground fault current paths, eliminate the multiple ground points or separate the neutral bus
into sections. Use parallel sensors and relay logic control schemes, where necessary, e.g. when tie breakers
are closed.
6. Select ground fault protection system components, and check that they meet cost requirements.
7. Detail the ground fault protection system, including the necessary interlocking.
8. Provide the necessary shunt trips, auxiliary switches, etc. required for the system, including a reliable
tripping power supply.
9. Determine the current and time settings of the relays by co-ordination study and compare with
superimposed KWC curves for arcing faults (straight lines on log-log paper).
10. Detail the changes or modifications required if the system is an existing one.
7
Note: Residual Sensing with one Sensor on each line and a fourth on the neutral (for 4-Wire systems)
or Modified Zero Sequence connection with a remote neutral Sensor connected in parallel with the
main ZSCT, cannot be successfully implemented below 100A pickup normally, because the error in
transformation of the Sensor becomes significant compared to the threshold current at low pickup
levels. For example if the accuracy of the Sensor under load is 1% and the load current is say 500A,
then the accuracy is ±5A. If the pick-up setting is 20A, then the error is already ±25%, which would be
intolerable in most cases. In the case of Ground Strap Sensors in parallel, however, because they have
no load current flowing through them – only Ground current – the Trip level can be reduced to a lower
level depending on the Sensor accuracy.
2. UNIT SUBSTATIONS
The term “Unit Substation” used here, refers to the distribution systems fed by one transformer only. In unit
substations, the number and location of the system neutral grounds has no effect on the sensing method selection.
Either vector summation or direct ground current sensing can be applied for the main breaker relay, but only vector
summation method can be used for feeder breaker relays as shown in Figure 2.1 and Figure 2.2 respectively.
“GR” in all the figures indicates MGFR Relay.
When direct ground current sensing is used, sometimes it is necessary to have two ground strap sensors installed,
one on each system neutral to ground connection, as in Figure 2.2. In this case two sensors are required, and they
should be paralleled for total ground current sensing.
Figure 2.1 Unit Substations - Vectorial Summation Sensing for Main and Feeder Relays
Figure 2.2 Unit Substations - Direct Current Sensing for the Main, and Vectorial Summation
Sensing for Feeder Relays
8
3. MULTI-TRANSFORMER SUPPLIES
The correct application of the ground fault protection to a distribution system, fed by two or more transformers,
requires special consideration on one very important factor, the location and number of system neutral to ground
connections. This factor influences the cost of the switchgear and the performance of the protection.
Three basic grounding methods may be applied as follows:
a) systems, grounded in the switchboard only, with a single ground connection,
b) systems grounded at the transformers only,
c) systems grounded at the transformers and also in the switchgear.
The grounding methods also control the neutral bus arrangement and dictate whether 3 pole tie breaker(s) can be
used for the selected neutral bus arrangement or if the application of 4 pole tie breaker(s) is necessary to
prevent nuisance [Link] may be caused by either circulating neutral currents or undetected parallel ground
return paths.
The selection of the ground current sensing is also important, but it may depend on the normal operation
condition of the tie breaker(s). When vector summation and direct ground current sensing are used for
the main and tie breaker relays respectively, or only direct ground current sensing is applied for the main and
tie breaker relays in double-ended substations, nuisance tie breaker tripping should be expected. It may occur
when one of the main and the tie breakers are closed and a ground fault occurs on the closed main side. Ground
current will return through the ground and the ground strap current sensor of the tie breaker relay will cause the
tie to trip.
Full selectivity can be achieved only with vectorial summation current sensing for the main and tie breaker relays.
Automatic isolation, using mixed ground current sensing methods, as described above, is recommended for
multi-transformer supplies with normally open tie breakers, while fully selective protection (vectorial summation
sensing only) must be used with normally-closed tie breakers.
The recommended locations of ground current sensors for the main and the breaker (if used)
relays are shown in the following diagrams, based on some of the most common neutral bus and
grounding arrangements.
9
THREE POLE TIE BREAKER APPLICATIONS
Figure 3.1.1 – indicates a typical T ground arrangement without tie breaker protection, while Figure 3.1.2 –
shows the same system with protected tie.
Alternatively, Zero Sequence summation can be used to detect faults where access to the grounding buses may
not be practical. Figure 3.1.3 indicates such a system. In this case no tie breaker protection is provided and the
tie breaker is Normally Open. The breakers would be interlocked to allow closing the tie breaker, only when one
of the mains is open. The return path for neutral currents back to the transformer when the tie is closed must be
summed for both halves of the board, hence the need to connect the CT secondaries in parallel when the tie is
closed. In order to protect the tie breaker, Figure 3.1.4 – shows a similar arrangement with a protected tie breaker.
Note: If external neutral grounds are used in the transformer section for example, then these must be summed
with the main neutral ground strap sensor, using additional sensors, of the same ratio.
10
Figure 3.1.3 Double-Ended Substation – Neutral Collector Bus Without Tie Breaker
Control – Summation Sensing.
Figure 3.1.4 Double-Ended Substation – Neutral Collector Bus With Tie Breaker
Control – Summation Sensing on the Mains, Direct Sensing on the Tie Breaker.
When the tie must provide protection and the ground straps are inaccessible, sensing can be obtained by
summation sensing on the tie also. Figure 3.1.5 shows a system with fully selective protected tie.
Figure 3.1.5 Double-Ended Substation – Neutral Bus Collector With Tie Breaker
Control and Summation Sensing for Mains and Tie.
11
THREE POLE TIE BREAKER APPLICATIONS
Use of a 4-Pole Breaker for the tie breaker greatly simplifies the relay control logic, but increases the cost of the
tie breaker. Figure 3.1.6 shows a typical system, where the neutrals are grounded at the transformers and in the
switchboard. No tie protection is provided in this simple system. Summation sensing is used for the main relays.
Figure 3.1.7 shows the same system with direct ground current sensing.
If tie breaker is to provide protection then the circuit can be configured with both summation and direct current
sensing as shown in Figure 3.1.8 indicates the requirement where the neutral grounded at the transformer and in
the switchboard. Summation sensing is applied to the main relays and direct ground current sensing is used for
the tie relay.
12
Figure 3.1.8 Double-Ended Substation – 4 Pole Tie Breaker – Neutrals Grounded at
Transformers and Switchboard, With Tie Breaker Control – Summation Sensing on
Mains, Direct Current Sensing on Tie.
Where direct current sensing is desired in cases where zero sequence sensors can’t be used for size or accuracy
limitations, the system of Figure 3.1.9 shows essentially the same system, but with direct ground current sensing
used for all relays.
A simpler approach might be to place a zero sequence sensor on the bus to control the tie breaker as shown in
Figure 3.1.10. This is the same system, as in the previous two diagrams but with summation sensing applied
for all relays, using a zero sequence.
13
Figure 3.1.10 Double-Ended Substation – 4 Pole Tie Breaker – Neutrals Grounded at
Transformers and Switchboard, With Tie Breaker Control – Summation Sensing on
Mains with Zero Sequence on the Tie.
When two or more transformers are supplying each half of a double-ended substation, the normal
state of the tie breaker (Normally Open (N.O.) or Normally Closed (N.C.)) and the grounding
requirements determine which sensing method should be selected. It is necessary to provide
ground fault protective relays for the tie breaker and separately for each main breaker to achieve
co-ordinated protection.
Figure 3.2.1 indicates the requirements with N.O. tie breaker using collector neutral bus with a
single ground in the switchboard. The arrangement permits three-pole tie breaker application.
Summation sensing applied for the main relays and direct ground current sensing is used for the
tie relay. Note that although the main relays are connected essentially in parallel, that they will each
see half of the fault current. If a fault occurs down-stream both Zero sequence sensors will ‘see’
the fault, providing twice the secondary current. Each relay then, will receive half of that current
which means that the relays still work properly.
Figure 3.2.1 Multi-Transformer supplied, Double-Ended Substation with N.O. Tie Breaker
with Neutral Collector Bus – Summation Sensing for Main, Direct Sensing for Tie.
14
Figure 3.2.2 shows the requirement with a N.C. tie breaker. The multiple grounding arrangement
necessitates 4-pole breaker application as main and ties. For fully selective protection vector
summation sensing is used for all relays.
Figure 3.2.2 Multi-Transformer supplied, Double-Ended Substation with N.C. Tie Breaker
with Multiple Grounding Arrangement – Summation Sensing for all Relays..
Where more than two sources with multiple tie breakers are required the use of 3 Pole or 4
Pole breakers for the tie, depends on whether the tie is Normally Open or Normally Closed. The
recommended location of the ground current sensors in a multi-transformer fed substation, where
each bus section is supplied by a transformer and the adjacent bus sections can be interconnected
by tie breakers, is shown in the following diagrams. It is necessary to provide Ground Fault Relays
for the tie breakers to achieve co-ordinated protection.
Figure 3.3.1 Multi-Transformer Supplies with 2 N.O. Tie Breakers using Neutral
Collector Bus – Summation Sensing for the Main, Direct Ground Current
Sensing for the Tie Relays. 15
3 Mains, 2 tie systems
Figure 3.3.1 indicates the requirements with N.O. tie breaker using neutral collector bus with a single ground
in the switchboard. The arrangement permits 3 Pole tie breakers application. Summation sensing is used for
the main relays and direct ground current sensing applied for the tie breaker relays. If the transformer neutrals
are also grounded at the transformers, additional sensors should be installed on these grounding for total
ground current sensing. Figure 3.3.2 shows the requirements with N.C. tie breakers. The multiple grounding
necessitates 4 Pole breaker application as mains and ties. For fully selective protection vector summation
sensing is used for all relays.
Figure 3.3.2 Multi-Transformer Supplies with 2 [Link] Breakers With Multiple Grounding
Arrangement – Summation Sensing for all Relays.
Figure 3.3.3 Multi-Transformer Supplies with 3 [Link] Breakers using Neutral Collector Bus –
Summation Sensing for the Main, Direct Ground Current Sensing for the Tie Relays.
16
Figure 3.3.4 Multi-Transformer Supplies with 3 N.C. Tie Breakers with Multiple Grounding
Arrangement – Summation Sensing for all Relays.
4. NETWORK SUPPLIES
When double or multiple connections are provided from a low voltage network system to a distribution system
and interconnection(s) between the distribution sections are required, the interconnecting tie breaker(s) are
always of 3 Pole design. The neutral bus in the switchboard is not continuous throughout the board, but installed
in sections, separated at the tie breaker(s). Figure 4.1 indicates fully selective G.F. protection using vector
summation sensing method for all relays.
The incomplete sensing and nuisance tripping can be eliminated by 4 Pole transfer switch application (Figure 5.1),
which will also classify the Standby/Emergency supply as a separately derived system.
The Canadian Electrical Code does not require, nor is it general practice to provide additional ground fault
protection where the essential loads are energized from a separately derived power system, such as an engine-
driven generator set.
It is recommended that no ground fault protection is applied to any emergency system where the capacity of
a generator is 500 kW or less. This is a trade-off in possible electrical equipment damage, in order to keep the
essential circuits in operation, as decided by an operator.
Ground Fault protection for the Generator itself can be desirable under the following conditions:
a) The capacity of a single generator is over 500 kW, but less than 2000 kW,
b) The emergency system consists of two generators operating independently,
c) The generator has sufficient capacity to back-up operation (interlocked tie breaker prevents parallel connection).
In this case it is advisable to provide a ground fault protection for the stator windings as illustrated in Figure
5.2(A). The relay(s) will not “see” external ground faults and operate(s) on internal generator fault only,
eliminating costly repairs due to internal faults.
18
For generators of 2000 kW and over, the application of differential protection (either constant or variable
percentage type), is recommended, as shown in Figure 5.2B.
The probability is that practically all generator faults will be single-phaseto- ground. Therefore, the application
of automatic neutral circuit breakers, or alternatively, 4 Pole generator breakers is recommended when
differential protection, or restricted ground fault protection is applied.
This will minimize the damage. Additionally, the field winding breaker should be opened (if used) and/or the
diesel should be shut-down, reducing the generator voltage to zero in a very short time.
In multiple generator installations the 4 Pole or the neutral breaker will also isolate the generator neutral
from the neutral bus for increased safety during maintenance and/or repair. When ground fault protection is
specified for large standby systems, where load requirements necessitate parallel operation of two or more
generators, selective protection can not be arranged, due to the number of parallel ground current return paths.
Non-selective ground fault protection may trip-out operating generators, at once, if one of the large feeder
breakers fails to clear a down-stream fault and the fault current returns on multiple system grounds equally.
In a case when the current is unequally divided, one of the generators will trip on ground fault and the others
on overload conditions. The application of high resistance grounding is recommended as the most suitable
grounding method for multiple parallel operating generators which can provide the maximum service continuity
required for standby systems even with a single ground fault.
I-Gard Type DSP-MKII Ground Fault Alarm and trip system will provide selective ground fault indication with priority
second fault tripping for the distribution system, including the generators under all operating modes. Three-phase
overcurrent relays and a shunt trip device should be provided on each protected circuit. Single-phase loads should
be supplied with separate single-phase or three-phase delta/grounded wye-connected transformers.
19
6. AUXILIARY SWITCH REQUIREMENT
As shown on the preceding diagrams, Ground Fault Relays for certain applications require auxiliary switch
contacts on the main and tie breakers to do the following functions:
a) Transfer sensor output from one relay to the other for total fault current sensing,
b) Connection of two or more sensors for summation and zero output (under normal conditions),
c) Short-out sensor when its breaker is open, and
d) Prevent unnecessary relay tripping and remove relay burden from the sensor when its breaker is open and
two, or more, sensors are parallel connected.
The MGFR Relays can be operated by a wide range of current sensors both for ground strap sensing
and zero sequence sensing of ground fault currents. The R1-3 ground strap current sensors can
be applied to theground strap between the neutral and the equipment ground bus. Zero sequence
current sensors, that encircle the phase conductors and the neutral in the circuit being protected, are
available in two designs. Toroidal zero sequence current sensors type T (series A) are intended for use
with cable conductors and the rectangular zero sequence current sensors type R and RZ are intended
for use on bus bars. Split core Sensors are available in two toroidal sizes. Figure 7.1 shows a typical
Time co-ordinated system using MGFR Relays.
20
7.2 CURRENT SENSORS
Any of the following sensors can be used as
Ground Strap Sensors, however R1-3 Sensor
is intended specifically for this purpose. It
is intended to be mounted on the neutral-
to-ground connection. Zero Sequence
Summation sensors must encircle all the
phase conductors and the neutral (if it exists),
but not the grounding wire or the shield of the
cable. Although the relays themselves are not
phase dependent, it is important to observe
polarity of Sensors when connecting them in
parallel. All sensors should be installed with
their polarity marks towards the supply. This
ensures correct output cancellation or addition
required for various sensor connections used
for main and tie breaker relays.
The available ground current sensors are listed
Figure 7.1 Typical Time Co-ordinated Relay System Using
MGFR Relays. in Table 7.1.
COMPATIBLE
CAT NO. INCHES MM
RELAYS
T2A 1.875 DIA 48 DIA
GM Meter;
T3A 2.75 DIA 70 DIA DSP-OHMNI;
T3A-SI 2.75 DIA 70 DIA MGFR;
SENTRI
T6A 5.75 DIA 146 DIA
T6A-SI 5.75 DIA 146 DIA
T9A 8.75 DIA 222 DIA
T9A-S 8.75 DIA 222 DIA
R417A 4.25 x 17.625 108 x 448
R7-13A 7.5 x 13.5 191 x 343
R8-26A 8 x26.5 203 x 674
RZ 5-11 4.5 x 11 114 x 280
RZ 5-21 4.5 x 21 114 x 534
RZ 5-31 4.5 x 31 114 x 788
RZ 5-35 4.5 x 35 114 x 890 SENTRI
RZ 10-11 10.5 x 11 267 x 280
RZ10-21 10.5 x 21 267 x 534
RZ 10-31 10.5 x 31 267 x 788
21
There are general requirements for locating rectangular ZSCS’s on bus bar connections, in
switchboards. Any current carrying bus bars must be kept as far from the current sensor as possible,
since a current carrying bus bar placed parallel to the sensor will produce noise voltage, which may
cause nuisance tripping when no ground current flows. As a guideline the clearances (X) of Table 7.2
and Figure 7.1 should be applied:
These requirements are also applicable to the toroidal ZSCS’s. However, one-half the clearances can
be used except for lower load currents when the clearances can be reduced to a minimum of two
inches (50.8 mm). For type RZ sensors, up to 3000 Amperes, use toroidal clearances. For over 3000A
use rectangular clearances.
22
3. zone selective instantaneous protection systems
1. GENERAL
The Zone Selective Instantaneous Protection (ZSIP) system provides a higher ground fault protection than the
conventional time co-ordinated system because it eliminates the “waiting period” (time delay), which is necessary
with conventional methods to achieve selectivity, by instantaneously tripping of the faulted circuit while preserving
complete selectivity.
Where there are multiple levels on the power system, or zones, there is a need fr coordination of the zones so that
higher levels are unaffected by downstream faults whenever possible. The branch circuits are like a tree branch and
all of the relays will “see” the fault current in a particular branch when the fault is downstream.
Usually coordination is done by setting protective relay time delays progressively higher, with upstream relays set
to maximum delays, to prevent nuisance tripping of main breakers. This can cause unnecessary damage, should a
fault develop at a high level, requiring the time delay to expire before clearing the fault. A better way is to use zone
selective interlocking protection scheme, where the relays are all set for Instantaneous Trip Protection but are wired
together and downstream relay will signal to the upper zones that it will clear the fault and block them from tripping.
This interlocking scheme is referred to as a ZSIP ( Zone Selective Instantaneous Protection) or ZSI ( Zone Selective
Interlocking). This scheme provides coordination with instantaneous clearance of arcing faults thus preventing major
damage at all levels in the system.
ZSIP reduces the damage produced by arcing ground faults on grounded systems. The damage is reduced to
such an extent that location of the breakdown remains evident, but replacement of any components may not be
necessary and virtually eliminates destruction.
The extent of the damage has a direct relationship to the amount of electrical energy, which is allowed to pass into
the arcing faults. Note that overcurrent devices such as fuses or breakers cannot generally clear arcing faults since
the current may be within the rating of the device.
ZSIP system detects ground fault currents at a fraction of the continuous rating of the devices and removes them
instantly without destroying the selectivity of the system, reducing the let-through arc energy to the fault.
Let-through energy can be expressed in kW cycles and is a product of the fault arc voltage, RMS value of fault
current and the duration of the fault expressed in cycles.
The destruction of equipment and melting of metal are as follows, based on actual observation of damage under
test conditions and supported by calculations based on specific heats of various metals:
a) 100 kW Cycles. Location of fault identifiable by observation, there will be spit marks on metal and
smoke marks.
b) 2000 kW Cycles. Little damage - likely not even hardware has to be replaced. Equipment can usually be
restored by cleaning smoke marks and repairing punctures in the insulation.
c) 6000 kW [Link] is the recommended maximum let-through.
d) 10,000 kW Cycles. Fault will probably be contained by a metal enclosure.
e) 20,000 kW Cycles. Fault will probably burn through a single thickness enclosure and spread to other
sections of gear.
f) Over 20,000 kW Cycles. Considerable destruction in proportion to the let-through energy occurs.
23
The following Figure 1 (a), (b) and (c) shows the effect of ZSIP on the reduction of the let-through kW Cycles of
arc energy.
a) Feeder protected by HRC Type fuses and no provision for ground fault protection.
b) Same feeder with conventional type ground fault protection (time separation to provide selectivity).
c) Same feeder with ZSIP system applied.
24
Illustration 1 (a) No Ground Fault Protection
25
The difference between a conventional “time delay” selective system and the ZSIP system is illustrated in Figure 1.4
and Figure 1.5. Each diagram shows a three-zone system, where zones represent sections of a distribution system
between zero sequence current sensors, e.g. zone (1) covers the main switchboard bus and all feeder breakers;
zone (2) covers all load side connections of feeder breakers and the sub-feeder breakers themselves, etc.
Selectivity is provided by a “restraining signal” generated by a relay in a “down-stream zone”, and transmitted to
a relay in the “up-stream zone”. When a number of relays are used in a “down-stream zone” the restraining signal
outputs of all of these relays are parallel connected. Therefore, only one pair of control wires is required between the
zones regardless of the number of relays in each zone.
In the event of a failure by a “down-stream” relay or interrupting device to clear a fault the “up-stream” protective
device will act as a back-up and will clear the fault after the pre-selected time.
Figure 1.4 Typical Time Delay Co-ordinated Connection. Figure 1.5 Typical 3-Zone ZSI Connection.
2. ZONE SELECTION
The Zone Selective Instantaneous Protection can be applied to any size system. The MGFR Ground Fault Relays
in ZSI mode can be used. There is no limit to the maximum number of zones that can be protected with MGFR
Relays. Furthermore the ZSI outputs of down-stream and inputs of up-stream relays can be connected in parallel
when necessary.
NOTE: Zone is defined as a section protected by a relay and includes all of the system from the load side of the
relay’s zero sequence current sensor, to the line side of any down-stream zero sequence current sensor,
if present.
26
The consideration to what extent should ZSIP be applied to a system is cost versus the degree of protection
achieved. The relationship between cost and the “degree” of protection is determined by the degree of required
selectivity of trip-outs due to ground faults.
Naturally there is a definite point of “diminishing returns” for each specified system where the cost of additional
relays may not be justified by the additional protection it will offer.
In many instances, such a point will be reached, while retaining full selectivity when ground fault protection is
extended to 200 amp circuits. The damage that will have to be accepted is the damage created by the “let-through”
energy that is permitted to pass by the overcurrent devices below 200 amp rating. Naturally if the ground fault
protection is cut-off at higher rating than 200 Amperes, the damage that has to be accepted will correspond to the
“let-through” energy of the overcurrent devices above 200 Amperes.
The most cost effective ground fault protection schemes are the two-zone ZSIP in Unit Substations and the three
zone ZSIP in double-ended switchboards.
4. RELAY TYPES
4.1 TYPE MGFR RELAYS
The MGFR Relays are highly suitable for ZSIP application. These relays are capable of restraining
up-stream relays. If the down-stream relay “sees” the fault it sends the signal up to the Restraint Input
terminal of the up-stream relay. This prevents the up-stream relay from Instantly Tripping while the
down-stream relay eliminates the fault. See Figure 1.5 for typical three-zone system.
In the ZSIP mode, the response of the MGFR Relays to a ground fault is determined by the signal from
a down-stream relay or the absence of such a signal.
The responses are as follows:
a) No signal at restraint in terminal. No down-stream relay senses a ground fault; so the fault is
within this relay’s zone. Tripping is instantaneous regardless of the time band setting.
b) Signal received at the restraint in terminal. The ground fault is outside this relay’s zone. If a
down-stream relay or protective device fails to clear the fault, this up-stream relay will trip in
accordance with the time-band setting.
4.2.1
Maximum distance between MGFR Relay at the extreme ends of the zones should not exceed
2000 ft. (600 meters). For longer restraint circuit lengths consult factory.
4.2.2
One pair of 14 AWG wires per conduit should be used for restraint signal transmission. Use of
a common conduit for power and signal circuits is not recommended. Signal wires must be
installed in separate conduit.
27
4.2.3
4.2.4
In a ZSIP system all relays in the chain should be set for ZSIP operation.
4.2.5
Zone co-ordination should be achieved by time-delay separation. The interlocking (restraint)
circuitry will normally provide approximately 30 milliseconds time delay for a ground fault
occurring anywhere on the system. Longer time delays, corresponding to the dial setting, may
be selected while within the ZSIP mode but will only be invoked when the nearest ZSIP
Relay up-stream of the fault, fails to clear and the next up-stream relay operates as backup
protection. It is recommended that a delay of at least 0.1 second is selected for all but the most
down-stream relay in a ZSIP chain of relays, which can be instantaneous.
4.2.6
Down-stream ZSIP outputs can be connected in parallel as in the case of a number of feeders
restraining the same main breaker relay.
4.2.7
Up-stream inputs can also be parallel connected when, for example, there are two Main
Breakers involved.
Figure 5.1 shows a typical Main-Tie-Main system where the tie breaker is Normally Open. The MGFR Relays are
connected so that the tie breaker is restrained by the feeder breakers from either side when one of the Main
Breakers is open. The feeder breaker relays provide restraint to the Mains when the Tie breaker is open. Also
when the tie breaker is closed it restrains the Mains instead of the feeder breaker relays such that a three
zone system is formed from Main to Tie to Feeder.
28
relay catalogue number table
29
7. FIELD TESTING OF ZSIP SYSTEMS
Field testing during installation and commissioning is recommended to ensure that the installation is correctly
wired and is satisfactory. Consult I-Gard to obtain a detailed test procedure.
I-Gard provides resistors to create current limited faults so that the relays can pick up and demonstrate the ground
fault protection and the implemented Zone Selective Instantaneous Protection function. By applying such test faults
at various locations in the distribution system proper operation is verified of the Zone Selection and coordination,
the breaker trip circuits, sensor wiring, wiring of restraint signals and operating times of relays. Such field testing can
be repeated at designated maintenance intervals to ensure satisfactory operation.
30
Notes
31
Phone: 905-673-1553 Fax: 905-673-8472
Toll Free: 1-888-737-4787 sales@[Link]
[Link]