BITZER Software v6.12.0 rev2326 2020-01-09 / All data subject to change.
1/9
Selection: Semi-hermetic Reciprocating Compressors
Input Values
Compressor type Recips, semi-hermetic
Mode Refrigeration and Air conditioning
Refrigerant R404A
Reference temperature Dew point temp.
Liq. subc. (in condenser) 3,00 K
Suct. gas superheat 10,00 K
Operating mode Auto
Power supply 400V-3-50Hz
Capacity control 100%
Useful superheat 100%
Overview
A
Evaporating SST -35,00 °C
Condensing SDT 45,0 °C
Qe Pe EER Ratio
kW kW W/W %
Total 53,0 48,6 1,09 --
6GE-34Y-40P 17,67 16,19 1,09 33,3
6GE-34Y-40P 17,67 16,19 1,09 33,3
6GE-34Y-40P 17,67 16,19 1,09 33,3
BITZER Software v6.12.0 rev2326 2020-01-09 / All data subject to change. 2/9
Application Limits
6GE-34
100% 6GE-34
Legend
additional cooling or suction gas
superheat ≤20K
additional cooling or max. toh
<0°C
M1: motor 1
M2: motor 2
BITZER Software v6.12.0 rev2326 2020-01-09 / All data subject to change. 3/9
Result
A
Evaporating SST -35,00 °C
Condensing SDT 45,0 °C
Compressor Total 6GE-34Y 6GE-34Y 6GE-34Y
Capacity steps 100% 66% 33% 100% 66% 33% 100% 66% 33%
Cooling capacity 53,0 kW 17,67 kW 11,66 kW 5,83 kW 17,67 kW 11,66 kW 5,83 kW 17,67 kW 11,66 kW 5,83 kW
Cooling capacity * -- 21,3 kW -- -- 21,3 kW -- -- 21,3 kW -- --
Evaporator capacity 53,0 kW 17,67 kW 11,66 kW 5,83 kW 17,67 kW 11,66 kW 5,83 kW 17,67 kW 11,66 kW 5,83 kW
Ratio -- 33,3 % 22,0 % 11,00 % 33,3 % 22,0 % 11,00 % 33,3 % 22,0 % 11,00 %
Power input 48,6 kW 16,19 kW 11,72 kW 7,08 kW 16,19 kW 11,72 kW 7,08 kW 16,19 kW 11,72 kW 7,08 kW
Current (400V) 91,4 A 30,5 A 24,8 A 20,2 A 30,5 A 24,8 A 20,2 A 30,5 A 24,8 A 20,2 A
Voltage range -- -- -- -- -- -- -- -- -- --
Condenser capacity 101,6 kW 33,9 kW -- -- 33,9 kW -- -- 33,9 kW -- --
COP/EER 1,09 1,09 1,00 0,82 1,09 1,00 0,82 1,09 1,00 0,82
COP/EER * -- 1,31 -- -- 1,31 -- -- 1,31 -- --
Mass flow 2087 kg/h 696 kg/h 459 kg/h 230 kg/h 696 kg/h 459 kg/h 230 kg/h 696 kg/h 459 kg/h 230 kg/h
Operating mode Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard
Discharge gas temp. w/o cooling 89,2 °C 89,2 °C -- -- 89,2 °C -- -- 89,2 °C -- --
Consider notes in detailed resp. part load calculation!
*According to EN12900 (20°C suction gas temp., 0K liquid subcooling)
BITZER Software v6.12.0 rev2326 2020-01-09 / All data subject to change. 4/9
Technical Data: 6GE-34Y
Dimensions and Connections
Technical Data
Technical Data
Displacement (1450 RPM 50Hz) 126,8 m³/h
Displacement (1750 RPM 60Hz) 153,0 m³/h
No. of cylinder x bore x stroke 6 x 75 mm x 55 mm
Weight 228 kg
Max. pressure (LP/HP) 19 / 32 bar
Connection suction line 54 mm - 2 1/8''
Connection discharge line 35 mm - 1 3/8''
Oil type R134a/R407C/R404A/R507A/R407A/R407F BSE32(Standard) | R134a tc>70°C: BSE55 (Option)
Oil type R22 (R12/R502) B5.2(Option)
Oil type R1234yf/R1234ze BSE32 (Standard) | R1234ze tc>70°C & to>0°C: BSE55
(Option) | R1234ze to>15°C: BSE85K (Option)
Motor data
Motor version 2
Motor voltage (more on request) 380-420V PW-3-50Hz
Max operating current 65.5 A
Winding ratio 50/50
Starting current (Rotor locked) 141.0 A Y / 233.0 A YY
Max. Power input 40,0 kW
Extent of delivery (Standard)
Motor protection SE-B2, CM-RC-01(Option)
Enclosure class IP54 (Standard), IP66 (Option)
Vibration dampers Standard
Oil charge 4,75 dm³
Discharge shut-off valve Standard
Suction shut-off valve Standard
Available Options
Discharge gas temperature sensor Option
Start unloading Option
Capacity control 100-66-33% (Option)
Capacity Control - infinite 100-10% (Option)
Additional fan Option
Refrigerant Injection (RI) Option
Oil service valve Option
Crankcase heater 140 W (Option)
Oil pressure monitoring MP54 (Option), Delta-PII
Sound measurement
Sound power level (-10°C / 45°C) 83,3 dB(A) @50Hz
Sound power level (-35°C / 40°C) 89,5 dB(A) @50Hz
Sound pressure level @ 1m (-10°C / 45°C) 75,3 dB(A) @50Hz
Sound pressure level @ 1m (-35°C / 40°C) 81,5 dB(A) @50Hz
Sound power level (-10°C / 45°C) R134a 81,3 dB(A) @50Hz
Sound pressure level @ 1m (-10°C / 45°C) R134a 73,3 dB(A) @50Hz
BITZER Software v6.12.0 rev2326 2020-01-09 / All data subject to change. 5/9
Semi-hermetic Reciprocating Compressors
Semi-hermetic Reciprocating Compressors
Motor 1 = e.g. 4TES-12 with 12 "HP", primary for air-conditioning (e.g. R22,R407C) and air-conditioning with R134a at high
ambient temperatures.
Motor 2 = e.g. 4TES-9 with 8 "HP", universal Motor for medium and low temperature application (e.g. R404A, R507A, R407A,
R407F) and air-conditioning with R134a
Motor 3 = e.g. 4TES-8, for medium temperature applications and R134a
For more information concerning the application range use the "Limits" button.
Operation modes 4VES-7 to 6FE-44 and 44JE-30 to 66FE-88 with R407F/R407A/R22
CIC = liquid injection with low temperature application, suction gas cooled motor.
ASERCOM certified performance data
The Association of European Refrigeration Component Manufacturers has implemented a procedure of certifying performance
data. The high standard of these certifications is assured by:
* plausibility tests of the data performed by experts.
* regular measurements at independent institutes.
These high efforts result in the fact that only a limited number of compressors can be submitted. Due to this not all BITZER
compresors are certified until now. Performance data of compressors which fulfil the strict requirements may carry the label
"ASERCOM certified". In this software you will find the label at the respective compressors on the right side below the field
"result" or in the print out of the performance data. All certified compressors and further information are listed on the homepage
of ASERCOM.
Condensing capacity
The condensing capacity can be calculated with or without heat rejection. This option can be set in the menu
Program ⟹ Options. The heat rejection is constantly 5 % of the power consumption. The condensing capacity is to be found in
the line Condensing cap. (with HR) resp. Condensing capacity.
Data for sound emission
Data based on 50 HZ apllication (IP-units 60 Hz) and R404A if not declared.
Sound pressure level: values based on free field area conditions with hemisperhical sound emission in 1 meter distance.
General remarks regarding sound data
Listed sound data were measured under testing conditions in our laboratory. For this purpose the free-standing test sample is
mounted on a solid foundation plate and the pipework is connected vibration-free to the largest extend possible. Suction and
discharge lines are fixed in a flexible configuration, such that a transmission of vibrations to the environment can be largely
excluded. In real installations considerable differences might be observed, compared to the measurements in the laboratory.
The airborne sound emitted by the compressor can be reflected from surfaces of the system and this may increase the airborne
sound level measured close to the compressor. Vibrations caused by the compressor are also transferred to the system by the
compressor feet and piping depending on the damping ratio of the fixings. Thus, the vibrations can induce other components to
such an extent that these components contribute to an increase in airborne sound emission. If required, the transfer of
vibrations to the system can be minimized by suitable fixing and damping elements.
Legend of connection positions according to "Dimensions":
1 High pressure connection (HP)
2 Connection for discharge gas temperature sensor (HP) (for 4VE(S)-6Y .. 4NE(S)-20(Y) connection for CIC sensor as
alternative)
3 Low pressure connection (LP)
4 CIC system: injection nozzle (LP)
4b Connection for CIC sensor
4c Connection for CIC sensor (MP / operation with liquid subcooler)
5 Oil fill plug
6 Oil drain
7 Oil filter (magnetic screw)
8 Oil return (oil separator)
8* Oil return with NH3 and insoluble oil
9 Connection for oil and gas equalization (parallel operation)
9a Connection for gas equalization (parallel operation)
9b Connection for oil equalization (parallel operation)
10 Oil heater connection
11 Oil pressure connection +
12 Oil pressure connection –
13 Cooling water connection
14 Intermediate pressure connection (MP)
15 Liquid injection (operation without liquid subcooler and with thermostatic expansion valve)
16 Connection for oil monitoring (opto-electrical oil monitoring "OLC-K1" or differential oil pressure switch "Delta-PII")
BITZER Software v6.12.0 rev2326 2020-01-09 / All data subject to change. 6/9
17 Refrigerant inlet at liquid subcooler
18 Referigerant outlet at liquid subcooler
19 Clamp space
20 Terminal plate
21 Maintenance connection for oil valve
22 Pressure relief valve to the atmosphere (discharge side)
23 Pressure relief valve to the atmosphere (suction side)
24 IQ MODULE
SL Suction gas line
DL Discharge gas line
Dimensions can show tolerances according to EN ISO 13920-B.
BITZER Software v6.12.0 rev2326 2020-01-09 / All data subject to change. 7/9
Selection: Vertical receivers
Input Values
Common Yes
Auto
Operating point Auto
Operating Points
A
to [°C] -35
tc [°C] 45
Result
Compressor: 6GE-34Y
Recommendation: FS1602
Selection FS1602
Recommended operating point: A
Selected operating point: A
Receiver volume 160,0 dm³
max refrigerant charge 153,8 kg
receiver load 82,9 %
Receiver unit --
lower fixing rails --
upper fixing rails --
upper fixing plate --
#1: Receiver selection for compact systems without condensing pressure control. Precise calculation only via refrigerant charge (see notes).
BITZER Software v6.12.0 rev2326 2020-01-09 / All data subject to change. 8/9
Technical Data: FS1602
Dimensions and Connections
Technical Data
Technical Data
Weight 133,0 kg
Total width 470 mm
Total height 1788mm
Receiver volume refrigerant 160,0 l
Max. refrigerant charge 90% at 20°C / 68°F
R22 174,3 kg
R134a 176,5 kg
R407C 166,9 kg
R404A/R507A 153,8 kg
R448A 160,3 kg
R449A 160,9 kg
R450A 171,7 kg
R513A 176,3 kg
R1234yf 159,9 kg
R1234ze 169,6 kg
Max. pressure 33 bar
Max. Operating Temperature 120°C
Connection inlet KL 54mm - 2 1/8''
Connection thread/ -flange 112x 112
Connection outlet FL 42mm - 1 5/8''
Connection thread/ -flange 2 1/4'' - 12 UN
Gauge 7/16'' 20UNF
Connection for pressure relief valve 1 1/4''-12UNF
Adapter for pressure relief valve Option
Minimum level control Option
Maximum level control Option
Electric liquid level control Option
*According PED 2014/68/EU Standard
Special Approvals (on request) Option
BITZER Software v6.12.0 rev2326 2020-01-09 / All data subject to change. 9/9
Liquid receiver
Selection of the receivers:
1) "Approx. according to cooling capacity":
The receiver volume is determined by the design of the unit, the operating mode and the function of the receiver (receiving the
complete refrigerant charge in the receiver or only compensating capacity variations). When selected via cooling capacity, an
approximate selection of the receiver is obtained.Receivers in systems with long pipelines, winter control or in very compact
systems should be selected according to method 2).
2) "According to refrigerant charge in the receiver":
The calculation is made on the basis of the specified refrigerant charge. The receiver volume is determined at 20°C and at a
maximum filling charge of 95% of the possible receiver content.
Compressor units equipped with receiver
The BITZER range of products comprises compressor units with horizontal receivers. In the output window of the accessories
these units, which are included in the standard delivery, are marked with “mounted” in the compressor unit line. Units that can
be mounted, but are not included in the Bitzer delivery program, are marked with “single parts”.Units in which the compressor
does not fit onto the receiver are marked with "--".