This document provides information on designing a clean agent fire suppression system using FM-200. It includes calculations for determining the volume of a protected space, required FM-200 concentration, FM-200 quantity, number of nozzles, nozzle sizes, pipe sizes, and includes an example calculation for an FM-200 system in a data processing facility room. Contact information is provided for consulting services related to fire suppression and protection system design.

Uploaded by

Mimi Mimi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
453 views48 pages

FM-200 Fire Suppression System Guide

This document provides information on designing a clean agent fire suppression system using FM-200. It includes calculations for determining the volume of a protected space, required FM-200 concentration, FM-200 quantity, number of nozzles, nozzle sizes, pipe sizes, and includes an example calculation for an FM-200 system in a data processing facility room. Contact information is provided for consulting services related to fire suppression and protection system design.

Uploaded by

Mimi Mimi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

FM-200 Design

Frank Application
Manual For Application

FM-200 Design

Clean Agent Fire Suppression System


NFPA 2001
FM-200 DESIGN
Develop Application By Frank
You can consult fire suppression systems and fire Protection systems
Job consult design fire suppression systems and fire Protection systems
CONTACT US
[email protected]
https://www.facebook.com/pichairat.punta?ref=tn_tnmn
https://www.facebook.com/#!/FrankApplication?fref=ts
Thailand
FUNCTION
APPLICATION
FM-200 DESIGN
FUNCTION IN ABOUT FM-200 DESIGN
FUNCTION IN VOULME DESIGN
FUNCTION CLASS DESIGN
FUNCTION FM-200 CALCULATE
FUNCTION FM-200 CALCULATE
FUNCTION PIPE CALCULATE
FUNCTION PIPE SCHEDULE DESIGN
FUNCTION PIPE SCHEDULE DESIGN
Example Calculate & Design
FM-200 Design
Example1. Design a pipe and calculate Gas fire suppression system with FM-200 in a DATA
Processing Facilities Room.
DESIGN OPERATING DIAGRAM OF FIRE SUPPRESSION SYSTEM
Typical Clean Agent System Layout
Volume (m^3) = Is the result of the calculation of the volume of space that is used to figure out the amount of FM-200

Example. DATA Processing Facilities Room width 5 m. long 10 m. high 5 m.

Volume=W x L x H
Volume = cubic meter
W = Width (m.)
L = Long (m.)
Volume=
H = High (m.)

W= 5 m., L=10 m. , H= 5m.


Volume = 5 x 10 x5
Volume=250 
CALCULATION VOLUME ROOM AND AREA NOZZLE

W= 5 m., L=10 m. , H= 5m.


Volume = 5 x 10 x5
Volume=250 

W= 5 m., L=5 m.
AREA NOZZLE = 5 x 5
AREA NOZZLE =25 
CALCULATION VOLUME ROOM AND AREA ROOM

W= 5 m., L=10 m. , H= 5m.


Volume = 5 x 10 x5
Volume=250 

W= 5 m., L=10 m.
AREA ROOM = 5 x 10
AREA ROOM =50 
Design Concentrate (%) For FM-200
1. Concentrate (%) = The system design is to calculate the weight of the fire extinguishing song you want to achieve the desired concentration
within a protected area under consideration by the NFPA 2001 standard.
Class A Fire. Fire in ordinary combustible materials, such as wood, cloth, paper,rubber, and many plastics. For system design Class A in
calculate Concentrate For FM-200 By Concentrate (%) = 6.7% or Very > 6.7% henceforth
Class B Fire. Fire in flammable liquids, oils, greases, tars, oil-base paints, lacquers,
and flammable gases.
Class C Fire. Fire that involves energized electrical equipment where the electrical
resistivity of the extinguishing media is of importance. Design Class C about electrical equipment for example Room

• Electrical and Electronic Hazards


• DATA Processing Facilities
• Telecommunication Facilies
• Storage Rooms-Flammable Liquids and gases
• High value assets,where the associated down –time would be costly

By Class C Fire For system design Class C in calculate Concentrate For Novec-1230 By Concentrate (%) = 7.00% or Very >7.00%
henceforth
Function Design Concentrate (%) For FM-200

Concentrate (%)
Design
DATA Processing
Facilities Room
Concentrate
(%) = 7 %
Function Design Concentrate (%) For FM-200

Concentrate (%)
Design
DATA Processing
Facilities Room
Concentrate
(%) = 7.00 %
CALCULATE FM-200
CALCULATION FM-200
CALCULATION FM-200

W= 5 m., L=10 m., H= 5m.


Volume = 5 x 10 x5
Volume=250 

Concentrate (%) = 7.0 %

Temperature = 21.1 C

Calculation FM-200
Quantity
FM-200 =136.9 Kg.
FM-200 = 301.8 Lbs.
CALCULATION NOZZLE DESIGN

W= 5 m., L=10 m.
AREA ROOM = 5 x 10
AREA =50 
W= 5 m., L=5 m.
AREA NOZZLE = 5 x 5
AREA =25 
NUMBER NOZZLE = 2 HEAD
CALCULATE PIPE

Calculation FM-200
Quantity =136.9 Kg

Time For Inject


FM-200 = 8 sec

INJECT PIPE DESIGN


=8.56 Kg/sec
CALCULATION NOZZLE DESIGN AND CALCULATION PIPE

PIPE DESIGN
32 mm. or 40 mm.
CALCULATION NOZZLE DESIGN AND CALCULATION PIPE

PIPE DESIGN PIPE DESIGN


MAIN PIPE NOZZLE
= 65 mm. =40 mm.
CALCULATION NOZZLE DESIGN AND CALCULATION PIPE
END