FM-200 Design
Frank Application
Manual For Application
FM-200 Design
Clean Agent Fire Suppression System
NFPA 2001
FM-200 DESIGN
Develop Application By Frank
You can consult fire suppression systems and fire Protection systems
Job consult design fire suppression systems and fire Protection systems
CONTACT US
[email protected] https://www.facebook.com/pichairat.punta?ref=tn_tnmn
https://www.facebook.com/#!/FrankApplication?fref=ts
Thailand
FUNCTION
APPLICATION
FM-200 DESIGN
FUNCTION IN ABOUT FM-200 DESIGN
FUNCTION IN VOULME DESIGN
FUNCTION CLASS DESIGN
FUNCTION FM-200 CALCULATE
FUNCTION FM-200 CALCULATE
FUNCTION PIPE CALCULATE
FUNCTION PIPE SCHEDULE DESIGN
FUNCTION PIPE SCHEDULE DESIGN
Example Calculate & Design
FM-200 Design
Example1. Design a pipe and calculate Gas fire suppression system with FM-200 in a DATA
Processing Facilities Room.
DESIGN OPERATING DIAGRAM OF FIRE SUPPRESSION SYSTEM
Typical Clean Agent System Layout
Volume (m^3) = Is the result of the calculation of the volume of space that is used to figure out the amount of FM-200
Example. DATA Processing Facilities Room width 5 m. long 10 m. high 5 m.
Volume=W x L x H
Volume = cubic meter
W = Width (m.)
L = Long (m.)
Volume=
H = High (m.)
W= 5 m., L=10 m. , H= 5m.
Volume = 5 x 10 x5
Volume=250
CALCULATION VOLUME ROOM AND AREA NOZZLE
W= 5 m., L=10 m. , H= 5m.
Volume = 5 x 10 x5
Volume=250
W= 5 m., L=5 m.
AREA NOZZLE = 5 x 5
AREA NOZZLE =25
CALCULATION VOLUME ROOM AND AREA ROOM
W= 5 m., L=10 m. , H= 5m.
Volume = 5 x 10 x5
Volume=250
W= 5 m., L=10 m.
AREA ROOM = 5 x 10
AREA ROOM =50
Design Concentrate (%) For FM-200
1. Concentrate (%) = The system design is to calculate the weight of the fire extinguishing song you want to achieve the desired concentration
within a protected area under consideration by the NFPA 2001 standard.
Class A Fire. Fire in ordinary combustible materials, such as wood, cloth, paper,rubber, and many plastics. For system design Class A in
calculate Concentrate For FM-200 By Concentrate (%) = 6.7% or Very > 6.7% henceforth
Class B Fire. Fire in flammable liquids, oils, greases, tars, oil-base paints, lacquers,
and flammable gases.
Class C Fire. Fire that involves energized electrical equipment where the electrical
resistivity of the extinguishing media is of importance. Design Class C about electrical equipment for example Room
• Electrical and Electronic Hazards
• DATA Processing Facilities
• Telecommunication Facilies
• Storage Rooms-Flammable Liquids and gases
• High value assets,where the associated down –time would be costly
By Class C Fire For system design Class C in calculate Concentrate For Novec-1230 By Concentrate (%) = 7.00% or Very >7.00%
henceforth
Function Design Concentrate (%) For FM-200
Concentrate (%)
Design
DATA Processing
Facilities Room
Concentrate
(%) = 7 %
Function Design Concentrate (%) For FM-200
Concentrate (%)
Design
DATA Processing
Facilities Room
Concentrate
(%) = 7.00 %
CALCULATE FM-200
CALCULATION FM-200
CALCULATION FM-200
W= 5 m., L=10 m., H= 5m.
Volume = 5 x 10 x5
Volume=250
Concentrate (%) = 7.0 %
Temperature = 21.1 C
Calculation FM-200
Quantity
FM-200 =136.9 Kg.
FM-200 = 301.8 Lbs.
CALCULATION NOZZLE DESIGN
W= 5 m., L=10 m.
AREA ROOM = 5 x 10
AREA =50
W= 5 m., L=5 m.
AREA NOZZLE = 5 x 5
AREA =25
NUMBER NOZZLE = 2 HEAD
CALCULATE PIPE
Calculation FM-200
Quantity =136.9 Kg
Time For Inject
FM-200 = 8 sec
INJECT PIPE DESIGN
=8.56 Kg/sec
CALCULATION NOZZLE DESIGN AND CALCULATION PIPE
PIPE DESIGN
32 mm. or 40 mm.
CALCULATION NOZZLE DESIGN AND CALCULATION PIPE
PIPE DESIGN PIPE DESIGN
MAIN PIPE NOZZLE
= 65 mm. =40 mm.
CALCULATION NOZZLE DESIGN AND CALCULATION PIPE
END