Pile Analysis in Accordance With EN 1997-1:2004 Incorporating Corrigendum Dated February 2009 and The Recommended Values

The document provides calculations for the axial and lateral resistance of a driven steel pile with a length of 6000mm and diameter of 508mm installed into 3 soil strata. It includes details of the pile geometry, soil properties, load combinations, partial factors, and calculations of characteristic and design axial and lateral resistances to check if design resistances exceed applied loads. The calculations show that the design axial and lateral resistances exceed the applied loads for the given load combinations, indicating the pile design is adequate.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
262 views4 pages

Pile Analysis in Accordance With EN 1997-1:2004 Incorporating Corrigendum Dated February 2009 and The Recommended Values

The document provides calculations for the axial and lateral resistance of a driven steel pile with a length of 6000mm and diameter of 508mm installed into 3 soil strata. It includes details of the pile geometry, soil properties, load combinations, partial factors, and calculations of characteristic and design axial and lateral resistances to check if design resistances exceed applied loads. The calculations show that the design axial and lateral resistances exceed the applied loads for the given load combinations, indicating the pile design is adequate.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
  • Pile Analysis: Provides a detailed overview of pile analysis in accordance with relevant EN codes, including material properties and load characteristics.
  • Characteristic Values: Lists and calculates characteristic values for various forces acting on piles, including compression and tension.
  • Lateral Stratum Details: Details the lateral stratum characteristics with overburden pressure and associated parameters affecting pile stability.
  • Lateral Load Analysis: Analyzes the lateral load and determining factors including design loads exceeding resistance limits.

Project Job no.

Calcs for Start page no./Revision


1
Calcs by Calcs date Checked by Checked date Approved by Approved date
F-2 04/06/2020

PILE ANALYSIS
In accordance with EN 1997-1:2004 incorporating Corrigendum dated February 2009 and the recommended values
Tedds calculation version 1.0.01

Pile details
Installation method; Driven
Shape; CHS 508.0x12.0
Length; L = 6000 mm
Material details
Material; Steel
Modulus of elasticity; E = 210 kN/mm2
Geometric properties
Pile section end is closed; No
Plugging action assumed for bearing; No
Pile section depth; h = 508 mm
Bearing area; Abearing = A = 0.019 m2
Pile perimeter; Perimpile =   h = 1.596 m
Moment of inertia; I = Iz = 57536 cm4
Fd

F tr,d
3500 mm

qsk1 = 5.4 kN/m 2


6000 mm
5000 mm

qsk2 = 20.8 kN/m 2


qbk2 = 346 kN/m 2

Stratum 3

qski = Characteristic value, shaft resistance, q bki = Characteristic value, base

Stratum details
Stratum Geomaterial Thickness, tstratai Characteristic value, Characteristic value,
(mm) base, qbki shaft, qski
(kN/m2) (kN/m2)
1 Cohesionless 3500 - 5.4
2 Cohesive 5000 - 20.8
3 Cohesive 10000 346 20.8

Action details
Characteristic perm. unfav. action, compression; Gc,k,unfav = 35 kN
Project Job no.

Calcs for Start page no./Revision


2
Calcs by Calcs date Checked by Checked date Approved by Approved date
F-2 04/06/2020

Characteristic perm. fav. action, compression; Gc,k,fav = 0 kN


Characteristic variable unfav. action, compression; Qc,k = 15 kN
Characteristic perm. unfav. action, tension; Gt,k,unfav = 0 kN
Characteristic perm. fav. action, tension; Gt,k,fav = 0 kN
Characteristic variable unfav. action, tension; Qt,k = 0 kN
Characteristic unfavourable perm. lateral action; Gtr,k,unfav = 300 kN
Characteristic favourable permanent lateral action; Gtr,k,fav = 0 kN
Characteristic variable lateral action; Qtr,k = 42 kN
Geotechnical partial and model factors:
Design approach 1:
Model factor on axial resistance; model = 1.40
Permanent unfavourable, A1 (Table A.3); G,unfav,A1 = 1.35
Permanent favourable, A1 (1); G,fav,A1 = 1.00
Variable unfavourable, A1 (Table A.3); Q,A1 = 1.50
Permanent unfavourable, A2 (Table A.3); G,unfav,A2 = 1.00
Permanent favourable, A2 (Table A.3); G,fav,A2 = 1.00
Variable unfavourable, A2 (Table A.3); Q,A2 = 1.30

Characteristic axial resistance


Characteristic axial base resistance; Rbk = Abearing  qbk = 6.5 kN
Characteristic axial shaft resistance per stratum
Stratum 1; Rsk1 = qsk1  Perimpile  tstrata1 =30.2 kN
Stratum 2; Rsk2 = qsk2  Perimpile  (L - Dstrata2) =83 kN
Characteristic total axial shaft resistance; Rsk = Rsk1 + Rsk2 = 113.2 kN
Axial compressive resistance
Load combination 1: A1 + M1 + R1
Design compression action; Fc,d,C1 = G,unfav,A1  Gc,k,unfav - G,fav,A1  Gc,k,fav + Q,A1  Qc,k = 69.8 kN
Partial resistance factor, bearing (Table A.6); b,R1 = 1.00
Partial resistance factor, shaft (Table A.6); s,R1 = 1.00
Design compressive resistance; Rc,d,C1 = (Rbk / b,R1 + Rsk / s,R1) / model = 85.4 kN
Fc,d,C1 / R c,d,C1 = 0.816
PASS - Design compressive resistance exceeds design load
Load combination 2: A2 + M1 + R4
Design compression action; Fc,d,C2 = G,unfav,A2  Gc,k,unfav - G,fav,A2  Gc,k,fav + Q,A2  Qc,k = 54.5 kN
Partial resistance factor, bearing (Table A.6); b,R4 = 1.30
Partial resistance factor, shaft (Table A.6); s,R4 = 1.30
Design compressive resistance; Rc,d,C2 = (Rbk / b,R4 + Rsk / s,R4) / model = 65.7 kN
Fc,d,C2 / R c,d,C2 = 0.829
PASS - Design compressive resistance exceeds design load
Lateral analysis properties
Pile head fixity; Free
Eccentricity of applied action; eactual = 0 mm
Lateral action duration; Long-term
Axis parallel to lateral load direction; y axis
Project Job no.

Calcs for Start page no./Revision


3
Calcs by Calcs date Checked by Checked date Approved by Approved date
F-2 04/06/2020

Lateral stratum details


n
Overburden pressure, pozSi =   ' t
i 1
i stratai

Stratum Characteristic Characteristic friction Characteristic unit Characteristic


cohesion, angle, weight of soil, overburden pressure,
ci,k (kN/m2) i,k (degrees) i,k (kN/m3) pozSi,k (kN/m2)
1 0 22 18 63
2 0 22 21.4 170
3 0 22 0 170

Load combination 1: A1 + M1 + R1
Partial factors:
Angle of shearing resistance (Table A.4); ',M1 = 1.00
Effective cohesion (Table A.4); c',M1 = 1.00
Undrained shear strength (Table A.4); cu,M1 = 1.00
Weight density (Table A.4); ,M1 = 1.00
Lateral resistance factor; tr,R1 = 1.00
Stratum Design cohesion, Design friction angle, Design unit weight of Design overburden
ci,d (kN/m ) 2
i,d (degrees) soil, pressure, pozSi,d
i,d (kN/m3) (kN/m2)
1 0 22 18 63
2 0 22 21.4 170
3 0 22 0 170
Resisting soil is divided into 10 segments to determine lateral resistance
From iteration, assume depth of point of rotation; X = 4865 mm
Distance from lateral action to ground; e = eactual = 0 mm
Sum of moments about point of load application near zero;
Mtr = MtrS1 + MtrS2 + MtrS3 + MtrS4 + MtrS5 + MtrS6 + MtrS7 + MtrS8 + MtrS9t +
MtrS9b + MtrS10 = -0 kNm
Sum of moments about point of rotation;
MX = MXS1 + MXS2 + MXS3 + MXS4 + MXS5 + MXS6 + MXS7 + MXS8 + MXS9t +
MXS9b + MXS10 = 1007.2 kNm
Calculated soil lateral resist. (Tomlinson Eqn 7.52); Rtr,calc = MX / (e + X) = 207 kN
Design lateral action; Ftr,d,C1 = G,unfav,A1  Gtr,k,unfav - G,fav,A1  Gtr,k,fav + Q,A1  Qtr,k = 468 kN
Design lateral resistance; Rtr,d,C1 = Rtr,calc / tr,R1 = 207 kN
Ftr,d,C1 / R tr,d,C1 = 2.261
FAIL - Lateral load exceeds lateral design resistance
Load combination 2: A2 + M2 + R4
Partial factors:
Angle of shearing resistance (Table A.4); ',M2 = 1.25
Effective cohesion (Table A.4); c',M2 = 1.25
Undrained shear strength (Table A.4); cu,M2 = 1.40
Weight density (Table A.4); ,M2 = 1.00
Lateral resistance factor; tr,R4 = 1.00
Stratum Design cohesion, Design friction angle, Design unit weight of Design overburden
Project Job no.

Calcs for Start page no./Revision


4
Calcs by Calcs date Checked by Checked date Approved by Approved date
F-2 04/06/2020

ci,d (kN/m2) i,d (degrees) soil, pressure, pozSi,d


i,d (kN/m )
3 (kN/m2)
1 0 17.9 18 63
2 0 17.9 21.4 170
3 0 17.9 0 170
Resisting soil is divided into 10 segments to determine lateral resistance
From iteration, assume depth of point of rotation; X = 4857 mm
Distance from lateral action to ground; e = eactual = 0 mm
Sum of moments about point of load application near zero;
Mtr = MtrS1 + MtrS2 + MtrS3 + MtrS4 + MtrS5 + MtrS6 + MtrS7 + MtrS8 + MtrS9t +
MtrS9b + MtrS10 = -0 kNm
Sum of moments about point of rotation;
MX = MXS1 + MXS2 + MXS3 + MXS4 + MXS5 + MXS6 + MXS7 + MXS8 + MXS9t +
MXS9b + MXS10 = 700.4 kNm
Calculated soil lateral resist. (Tomlinson Eqn 7.52); Rtr,calc = MX / (e + X) = 144.2 kN
Design lateral action; Ftr,d,C2 = G,unfav,A2  Gtr,k,unfav - G,fav,A2  Gtr,k,fav + Q,A2  Qtr,k = 354.6 kN
Design lateral resistance; Rtr,d,C2 = Rtr,calc / tr,R4 = 144.2 kN
Ftr,d,C2 / R tr,d,C2 = 2.459
FAIL - Lateral load exceeds lateral design resistance