NICE1000 Elevator Integrated Controller: Setup Manual - Brief Version 1.4
NICE1000 Elevator Integrated Controller: Setup Manual - Brief Version 1.4
Page 1 of 49
Version : 1.4
Date of issue : 03-07-14
In this manual, the notices are graded based on the degree of danger:
DANGER indicates that failure to comply with the notice will result in severe personal injury or even
death.
WARNING indicates that failure to comply with the notice will result in potential risk of severe
personal injury or even death.
CAUTION indicates that failure to comply with the notice will result in minor or moderate personal
injury or equipment damage.
In addition, NOTE appearing in other chapters indicates that an unintended result or situation may occur if the
notice is not complied with. The notices in this manual you have to observe are aimed at guaranteeing your
personal safety, as well as to prevent damage to the controller or the parts connected to it. Read this manual
carefully so that you have a thorough understanding and perform all operations by following the notices in this
chapter. Monarch will assume no liability or responsibility for any injury or loss caused by improper operation.
USE SAFETY
PRECAUTIONS
STAGE GRADE
This controller has hazardous high voltage and the controlled motor
is a dangerous rotating device. Failure to comply with the notices
may result in personal injury or damage to the property.
Transportation, installation, operation and maintenance of the
WARNING controller can be performed only by qualified personnel after they
Warning get familiar with the safety information in this manual. This is the
prerequisite of safe and stable running of the equipment.
Do not open the front cover or touch the power terminals on the
main circuit within 10 minutes after the controller is powered off.
The capacitor on the DC circuit still has residual high voltage even
after power-off. Failure to comply will result in electric shock.
Do not install the equipment if you find water seepage,
component missing or damage upon unpacking.
During Do not install the equipment if the packing list does not conform
Installation DANGER to the product you received.
Install the equipment on incombustible objects such as metal, and
keep it away from combustible materials. Failure to comply may
result in a fire.
Page 2 of 49
Version : 1.4
Date of issue : 03-07-14
CAUTION Set the parameters again after the controller is replaced. All the pluggable
components must be plugged or removed only after power-off. Strictly
obey the laws and regulations and repair and maintain the elevator
Page 4 of 49
Version : 1.4
Date of issue : 03-07-14
Perform the insulation test when the motor is used for the first time, or when it is reused after being stored for a
long time, or in a regular check-up, in order to prevent the poor insulation of motor windings from damaging
the controller. The motor must be disconnected from the controller during the insulation test. A 500-V mega-
Ohm meter is recommended for the test. Ensure that the insulation resistance is not less than 5 MΩ.
If the rated capacity of the motor selected does not match that of the controller, especially when the rated power
of the controller is greater than that of the motor, adjust the motor protection parameters on the operation panel
of the controller or install a thermal relay for the motor circuit for protection.
The output of the controller is pulse width modulation (PWM) wave with certain harmonic wave, and therefore,
the motor temperature rise, noise, and vibration are slightly greater than those at running with the power
frequency (50 Hz).
The controller outputs PWM waves, and therefore, do not install the capacitor for improving power factor or
lightning protection voltage-sensitive resistor on the output side of the controller. Otherwise, the controller may
suffer transient overcurrent or even be damaged.
When a contactor is installed between the input side of the controller and the power supply, the controller must
not be started or stopped by opening or closing the contactor. When a contactor is installed between the output
side of the controller and the motor, do not open or close the contactor when the controller has output.
Otherwise, modules inside the controller may be damaged.
The controller must not be used outside the allowable voltage range specified in this manual. Otherwise,
components inside the controller may be damaged. If required, use a corresponding voltage step-up or step-
down device.
Page 5 of 49
Version : 1.4
Date of issue : 03-07-14
The controller has a built-in voltage dependent resistor (VDR) for suppressing the surge voltage generated when
the inductive loads (electromagnetic contactor, electromagnetic relay, solenoid valve, electromagnetic coil and
electromagnetic brake) around the controller are switched on or off. If the inductive loads generate very high
surge voltage, use a surge suppressor for the inductive load or also use a diode.
Note
Do not connect the surge suppressor on the output side of the controller.
In places where the altitude is above 1000 m and the cooling effect reduces due to thin air, it is necessary to de-
rate the controller. Contact Monarch for technical support.
9. Adaptable motor
The controller is adaptable to squirrel-cage asynchronous motor or AC PMSM. Select a proper controller
according to motor nameplate. The default parameters configured inside the controller are squirrel-cage
asynchronous motor parameters. It is still necessary to perform motor auto-tuning or modify the default values
based on actual conditions. Otherwise, the running effect and protection performance will be affected. For
PMSM, motor auto-tuning must be performed.
Tripping may be caused if an improper RCCB is selected when the controller drives the motor. This is because
the output wave of the controller has high harmonics and the motor cable and the cable connecting the
controller and the motor produce leakage current, which is much larger than the current when the motor runs at
power frequency (50 Hz). Thus, it is necessary to determine the proper RCCB sensitivity based on the general
leakage current of the cables and the motor. The leakage current is dependent on the motor capacity, cable
length, insulation class and wiring method. Generally, the leakage current on the output side of the controller is
three times of the current when the motor runs at power frequency (50 Hz).
Adopting different protective functions for different levels of faults, the NICE1000 provides the elevator
running system with full abnormality protection. For detailed solutions to the faults, Faults of the controller are
classified as follows:
1. Speed abnormal
The controller monitors the encoder feedback speed and output torque. Once the feedback speed exceeds the
limit or the deviation between the torque limit and the speed feedback is too large, the controller performs
protection immediately, reports an alarm and prohibits running.
The related faults include drive overcurrent, overvoltage/under voltage, power input/ output phase loss,
overload, and storage abnormality. If such a fault occurs, the controller performs protection immediately, stops
output, applies the brake and prohibits running.
Page 6 of 49
Version : 1.4
Date of issue : 03-07-14
The related faults include encoder phase loss, direction reversing, wire-breaking, and pulse interference. If such
a fault occurs, the controller performs protection immediately to avoid unexpected accidents. If pulse
interference is large, the controller reports an alarm immediately. If pulse interference is small, the controller
performs position correction every time it receives a levelling signal and clears the accumulative error.
The related faults include sensor failure or sensor stuck. The controller judges whether a fault occurs based on
the levelling signal change. If the levelling signal does not change within the set time, the system reports an
alarm.
The system stores the floor information through the shaft auto-tuning. If the floor data is abnormal, the system
prompts the fault information at the first-time running. During actual running, the controller continuously
compares position information input by Dis with the stored floor data. If the deviation is large, the system
reports an alarm.
Note:-
This commissioning setup manual is to be referred along with the NICE1000 Electrical Drawing
and User Manual.
Separate NICE 1000 Integrated Controller models are available for both Synchronous and
Asynchronous Lift Hoist Motor. As it is a closed loop system, feedback device (Motor Shaft
Encoder) is must for the function.
Page 7 of 49
Version : 1.4
Date of issue : 03-07-14
Page 8 of 49
Version : 1.4
Date of issue : 03-07-14
Model NICE-L-G-4005
Power 5.5KW
INPUT 3PH AC380V 14.8A 50HZ/60HZ
OUTPUT 3PH AC380V 13A 0~90HZ
S/N
Suzhou MONARCH Control Technology Co., Ltd.,
Model NICE-L-V-4005
Power 5.5KW
INPUT 3PH AC380V 14.8A 50HZ/60HZ
OUTPUT 3PH AC380V 13A 0~90HZ
S/N
Suzhou MONARCH Control Technology Co., Ltd.,
b) Terminal Function:
Controller output cables of U, V and W should be routed in separate metal pipe with Grounding and
apart from the Control circuit cables and Encoder cable.
If the cables between the motor and controller are too long, Electrical resonance may occur which make
the NICE controller go into protective status.
Grounding terminal must be connected to proper Earth point; the grounding cable should be thick and
short. The recommended grounding cable should be Yellow-Green cable above 4sq.mm with multi
strand copper cores.
Grounding resistance should be less than 4. Don’t share the earth with neutral line of the main supply.
Page 10 of 49
Version : 1.4
Date of issue : 03-07-14
L1~L20
X1~X24 Input LED indicator
LED indicators
ER, OK, MOD
LED indicator
CN10, CN11
CN6
(X1~X24 Input (LED Keypad)
Terminals)
J11 (Expansion/PG
card)
CN3 CN2
(Y0, M0)~ (Y3, (Encoder Input
M3) Terminals Terminal)
CN4, CN5
(Y6~Y22 Output
Terminals)
CN3
(XCM, X25~X27
Input Terminals)
Page 11 of 49
Version : 1.4
Date of issue : 03-07-14
Page 12 of 49
Version : 1.4
Date of issue : 03-07-14
Page 13 of 49
Version : 1.4
Date of issue : 03-07-14
The Expansion board is placed on the connector J11 of Main Control Board (MCB)
b) Connector CN12 and CN13, indicator and Jumper details of Expansion board
PG wire should be laid separately in pipe and metal enclose should be grounded and keep
distance from the control circuit and driver circuit
PG wire should be shield wire and shield layer should connect to PE near controller. In order
to avoid being disturbed, only one side of the PG Grounding wire should be connected to the
ground
Page 14 of 49
Version : 1.4
Date of issue : 03-07-14
Page 15 of 49
Version : 1.4
Date of issue : 03-07-14
‘D’ Type 5 1
10 6 Pin Solder side
15Pin Connector 15 11
1 B- Red/Black
7 GND White/Green
7 GND White
8 B+ Blue/Black ECN413
/1313
9 M5V Brown/Green
10 CLK+ Violet
11 CLK- Yellow
12 DATA+ Grey
13 DATA- Pink
15 U5V
Page 16 of 49
Version : 1.4
Date of issue : 03-07-14
Up Key
Multifunction Key
Down Key
Page 17 of 49
Version : 1.4
Date of issue : 03-07-14
PRG PRG ENTER >>
F0 15.00 15.00 10.00 10.00
In the three level menu, if the parameter has no flash bit, it means the function code can’t be changed and
the possible reasons are
The actually detected parameter value and running record parameter value
Some Function code parameter value can’t be modified while the NICE 1000 is running
Page 18 of 49
Version : 1.4
Date of issue : 03-07-14
Contactors
EIS/ERO
Transformer & Choke
Control Terminals
Power Terminals
4.1 Switch off all the control panel breakers to avoid an unexpected controller power up
OFF
Controller INS
Page 19 of 49
Version : 1.4
Date of issue : 03-07-14
4.3.1 Check all Field Wiring (Machine Room, Controller, Hoist-way, Car top, COP and LOP) are
connected as per the given Electrical Drawing
4.3.2 Check controller wiring and field wiring for loose connection.
4.3.3 Check control panel wiring for short circuit using Multi meter (Field and control panel wiring)
(OR)
4.3.4 Check Controller power terminal U V W are correctly connected corresponds to the Motor U V W
terminal.
4.3.5 Check the Machine Brake wiring is done correctly as per the requirement
4.3.6 Confirm that the main power supply source MCCB is OFF. Now Connect the Controller Power
terminal R S T to the main power supply source.
4.4 Connect the Encoder wires to the NICE 1000 system; for connection wiring, follow the earlier
mentioned steps (2.3.4) for Geared/Gearless machine.
Page 20 of 49
Version : 1.4
Date of issue : 03-07-14
5.1.1 Before Control Panel Power Up, Disconnect all the Control Terminal wiring which are connected to
MCTC-MCB-G of NICE 1000
5.1.2 Switch on the main power supply Circuit Breaker; check the incoming voltage level between R vs S, S
vs T, T vs R and R S T with respect to N at Lift Control Panel using Multi meter
MULTIMETER
5.1.3 Make sure that the Incoming Voltage level satisfies the specification
5.1.4 Turn ON the Control Panel Circuit Breakers one by one and check the voltage level simultaneously;
Make sure that the voltage levels are within specified limits (Refer Electrical Drawing)
ON
Page 21 of 49
Version : 1.4
Date of issue : 03-07-14
5.1.6 After confirming the correct voltage level, switch OFF the Control Panel Circuit Breakers
OFF
Connected the Safety circuit wiring to the field as per the Electrical drawing. Safety circuit terminal
starts from 101 and ends at 132 terminal
Connected the wiring for Up/Down terminal floor Limit and slowdown switches
The distance for terminal floor slowdown should be 1300mm~L/2 from the floor level and the distance for
terminal floor direction limit switches should be 30 to40 mm above the floor level in top terminal/ below the
floor level in bottom terminal
LTerminal floor height
Page 22 of 49
Version : 1.4
Date of issue : 03-07-14
5.1.8 Verify the connection and Elevator control Panel Earthing once again before power ON.
Now TURN ON the control panel Circuit Breakers
ON
Page 23 of 49
Version : 1.4
Date of issue : 03-07-14
After switching ON the controller MCBs, the Safety Contactor (SC), Door Lock
Contactor (DLC) and JT relay will get ON if Safety Circuit is properly closed
Once SC contactor ON, the three phase power supply will be given to the Main NICE
drive(Note: If SC is OFF, then there would not be any display on Drive on board
Display)
Input terminal points X1~X24 of MCB located left side of the Board are Positive
Logic Signal Inputs which needs +24VDC positive power supply for enabling and
disabling the any given input signal
High Voltage Input terminal Points (X25~X27) of MCB which located bottom side of
the Board are Active High Inputs which needs Phase (P) of 110VAC power supply for
enabling and disabling the safety circuit function.
The 110VAC voltage safety points (X25~X27) are very significant and most priority
inputs in the NICE1000 Lift controller
Err41 will be displayed if the Safety circuit feedback LED X25 is OFF. The safety
circuit wiring should be followed as per the NICE1000 Electrical drawing.
Err35 will be displayed on every power ON until the Learn Run/Shaft Tuning is done.
Err35 will not affect the Inspection Run
For PMSM Gearless machine, Err20 will be displayed if Machine Encoder is not
connected with suitable PG-E card on NICE unit, Encoder Parameter is not set properly
(F1-00=0) and also if the encoder signal wiring sequence is wrong/improper
If all the power supply connections and field wirings are ok, then the corresponding
Green LED’s on the Main Control Board (Located above the Drive) will glow.
Page 24 of 49
Version : 1.4
Date of issue : 03-07-14
Page 25 of 49
Version : 1.4
Date of issue : 03-07-14
5.5.1 Take down the motor parameter and encoder details; enter the following actual Parameter value in
NICE1000 using LED keypad.
Description Parameter Set actual value Remarks
Motor Parameter Details
Rated Power (KW) F1-01
Rated Voltage (V) F1-02 Enter the correct Motor nameplate
Rated Current (I) F1-03 value in to the corresponding Drive
Rated Frequency (F) F1-04 Parameter
Rated Speed (RPM) F1-05
Encoder Parameter Details
Encoder Type Selection F1-00 0Syn 2Asyn
Enter the correct Encoder details
Pulse Per Revolution F1-12
(PPR)
Elevator Running Speed Parameter Details
(Enter the Elevator Enter the Rated speed of the elevator
Rated speed of Elevator F0-04
Rated speed in m/s)
(Enter the required Enter the Max speed of the Elevator
Max speed of Elevator F0-03
Max. speed in m/s) (Limited by Rated speed setting F0-04)
Slow speed F3-11 Used for Inspection speed
Page 26 of 49
Version : 1.4
Date of issue : 03-07-14
Step 1: Set F0-01=0, now the control mode is selected to the operating LED keypad control
Step 2: Make the NICE1000 Drive output contactor (SW) permanently ON or bypass the output contactor
which makes the NICE 1000 U V W terminals directly connected to Machine Motor’s U V W terminals
Step 3: Verify the parameter (F1-01~F1-05) values are correctly set to the actual motor nameplate
ENTER
Step 4: Set the parameter F1-11=1 and press button , operating LED keypad display shows ‘TUNE’,
RUN
then press button on Keypad. Now the tuning process starts and NICE 1000 calculate the
following parameters during the tuning process
F1-06Stator Resistance
F1-07Rotor Resistance
F1-08Leakage Inductance
F1-09Mutual Inductance
F1-10No-Load Excitation Current
Once the tuning process is over then the operating LED keypad displays the normal status
Step 5 : After successful motor tuning, set back the F0-01=1(Elevator Logic Control)
Step 1: On –load tuning will be conducted on Inspection mode, all the input and Output functional
Sequence should be consider (Refer Content 5.4 & 5.6.3)
Page 27 of 49
Version : 1.4
Date of issue : 03-07-14
Step 3: Verify the parameter (F1-01~F1-05) values that are correctly set to the actual motor nameplate
Step 4: Set the parameter F1-00=0 according to the actual encoder mounted on Motor shaft,
Set the value 0: Sin/Cos and F1-12=2048 PPR for Sin/Cos Encoder
Step 5: For Inspection speed setting, use parameter F3-11=0.250mps. Please refer content of 5.2 (Page-18)
for MCB’s LED sequence for Inspection operation
ENTER
Step 6: Select the parameter F1-11=1 and press button, now operating LED keypad shows ‘TUNE’
Step 7: Using the control panel Inspection button, press UP/DOWN button, now the Synchronous motor
runs few (One & two)rotation. During tuning process, keep pressing the UP/DOWN button until
the Tuning gets finished. NICE 1000 system calculate the following parameters
F1-06Encoder initialized angle
F1-08Wiring connection
F1-09ADC sampling delay
F1-10Selection check of encoder’s signal
Once tuning process is over, ‘TUNE’ display goes off and LED keypad displays the Inspection
Reference speed value.
Step 8: Follow the above tuning process more than 3 times and verify the parameter F1-06 value that the
Error tolerance is within the range of ±5%
Step 2: Set F0-01=0, now the control mode is selected to the operating LED keypad control
Step 3: Make sure that the machine Brake is powered ON for free movement of Machine rotor
Step 4: Verify the motor parameter (F1-01~F1-05) values are correctly set as per the actual motor
Nameplate and Encoder details (F1-00=0 & F1-12=2048)
Step 5: Select parameter F1-11=2 and press ENTER button, operating LED keypad display shows
‘TUNE’. RUN
Then press button on Keypad. Now the tuning process starts and NICE 1000 calculate the following
parameters during the tuning process, F1-06, F1-07, F1-08, F1-09 and F1-10.
Once tuning process is over, ‘TUNE’ display goes off and LED keypad displays to normal status.
Step 6: Follow the above tuning process more than 3 times and verify the parameter F1-06 value that the error
tolerance is within the range of ±5%
Page 28 of 49
Version : 1.4
Date of issue : 03-07-14
Geared/Gearless
Gearless Machine Machine
Function
(PMSM motor) (Induction/PMSM Remarks
motor)
Inspection X4 OFF X4 OFF X4 OFF for Inspection Mode
Mode X4 ON for Normal Mode
INS Up X5 ON X5 ON If X5 is not ON while UP button pressed,
button
then the lift will not give any output
Command
INS Down X6 ON X6 ON If X6 is not ON while Down button pressed,
Button
then the lift will not give any output
Command
Y22 ON Y3 ON
RCR
X22 OFF X22 OFF Applicable only for Manual Door
Contactor
Y3 ON Applicable for all PMSM Gearless machine.
FX-Shorting X22 OFF Not Applicable Improper operation leads to Err29. Check
Contactor
corresponding parameter setting
SW-Drive Y1 ON Y1 ON Improper operation sequence leads to Err36.
Output X2 OFF X2 OFF) Check corresponding parameter setting and
Contactor wiring
Y2 ON Y2 ON Improper operation sequence leads to Err37.
BY-Brake
X3 OFF X3 OFF Check corresponding parameter setting and
Contactor
wiring
Page 29 of 49
Version : 1.4
Date of issue : 03-07-14
Now the Lift is ready for Inspection running. Please refer content of 5.2 (Page-18) for MCB’s
LED sequence for Inspection operation
Make sure that the all safety switches are connected and functioning properly
Make sure that the Up & Down terminal Limit and terminal slowdown switches are wired up
and located in the right position as given in the manual
Use the UP and DOWN Button in the Inspection board on controller/Car-Top to run the lift in
Inspection speed.
Check the direction of the lift running. X5 LED in the Main Control Board (MCB) glows when UP
button is pressed. During this time, lift should run in UP direction and for DOWN button, X6
LED glows and lift runs in Down direction.
If the running direction is wrong, then modify the parameter F2-10(1↔2, 0↔3)
If Err20 comes after some distance travelled in Inspection mode, then modify the parameter F2-10
(0↔2, 1↔3). (For Geared lift, interchange PG-A and PG-B wires)
If the system gives Err20 and the direction of running is also wrong, then modify the F2-10
(0↔1, 2↔3)
Page 30 of 49
Version : 1.4
Date of issue : 03-07-14
If pulse variation is reverse, then modify the parameter F2-10 (0↔2, 1↔3).
Make sure that the all required mechanical installation and field wiring are completed. Take the lift to
bottom terminal floor level using control panel Inspection in inspection speed.
Observe the X1~X24 input terminal LEDs for proper operation of Floor/Door zone(X1 LED) and
Up/Down terminal Limit and slowdown switches(X09,X10,X11 & X12 LEDs)
Locate the lift car in bottom most floor level, Down terminal Slowdown switch gets operated (X12
‘OFF’) and Floor level/Door Zone Switch (F5-01=003) gets operated (X1 ‘ON’)
Step 3: Now select the parameter F1-11=3(Shaft auto learning mode) and Enter
or
Keep Pressing ‘S1’ button located on MCTC-MCB of NICE 1000 for minimum 3secs
NICE 1000 system is capable for double side door operator system (Front and Back Doors)
Door Open Limit and Door Close Limit switches feedbacks are mandatory for NICE 1000 system
function (to be connected to X14 and X18 Default input terminals for Front door)
Field Wiring Diagram suitable for NICE 900 Door Drive with NICE1000 Controller
Motor
L U
Power
N V
Supply
E W
NICE900 +24VDC
Door Drive PG-A
PG-B
PG-Z
COM MCTC-MCB
If the third party door drive system is used, follow the door drive commissioning instruction and
commission the door drive along with NICE1000 input and output interconnections as shown in above
model wiring diagram
Follow the commissioning procedure provided by door operator system supplier
Once door operator function is completed successfully, Elevator is ready for Normal operation with
rated speed
Page 32 of 49
Version : 1.4
Date of issue : 03-07-14
Feed Back Signal Door Fully Closed Door In between Door Fully opened Remark
Page 33 of 49
Version : 1.4
Date of issue : 03-07-14
Door Close
Open Door Closing Fully
command
End Closed
Y7 ON
Door Open
Fully Door Opening Close
Command
Opened End
Y6 ON
X14 LED
ON OFF
F5-14=022
X18 LED
OFF ON
F5-18=024
X26 LED
OFF ON
F5-26=02
X27 LED
OFF ON
F5-27=03
Note:
Improper sequence of Door open Limit (X14), Door Close Limit (X18), Car safety (X26) and Landing safety
(X27) can lead to the Err53 and stops the Elevator function.
Page 34 of 49
Version : 1.4
Date of issue : 03-07-14
The first two digits represent the bit number and the last single digit to enable or disable the
corresponding selected bit number.
Using UP/DOWN key on the keypad, select bit3 & Enable the bit
Value to
Parameter Default Function
be set
F5-20 0 143 DRC contactor NC feedback enable function setting
F7-06 6 31 DRC contactor Function enable setting
F6-11 201 0 Disabling the auto door DO function
F6-12 202 0 Disabling the auto door DC function
F5-14 22 0 Disabling the auto door open limit function
F5-15 126 0 Disabling the auto door sensor function
F5-18 124 0 Disabling the auto door Close limit function
Retiring Cam enable duration to verify landing door
FB-12 3 5
safety contact
Retiring Cam disable duration to verify the landing door
FB-13 30 5
safety contact
Adjust FB-03=5(Default) to modify Floor waiting time to attend the next registered call
Door open Buzzer output terminal is Y21 in the Main Control Board (MCB)
If the landing door is kept open after usage, NICE1000 tries for three times by giving the output to
the DRC contactor until the landing door safety contact is closed (landing door close). During this
period NICE1000 also gives door open buzzer output at Y21 terminal. If the landing door is not
closed within the three time try, NICE1000 cancels all registered calls and goes to idle mode.
NOTE:
For earlier software version used (FA-04=30169), to enable manual door function, please enable
bit 03 in FE-14.
Software versions prior to this (Ex. FA-04=30168, 30167) does not have manual door feature.
Page 35 of 49
Version : 1.4
Date of issue : 03-07-14
Input signal status of Main Control Board (MCB) while the lift at top terminal floor level with doors are
closed in normal mode
Page 36 of 49
Version : 1.4
Date of issue : 03-07-14
For Floor Level Adjustment, Confirm that the Floor level/Door zone cutting cam/magnet centre
is matched with the centre of the switch when the lift is in exact floor level.
Reed Switch
80 to 200mm
Switch
Centre Axis Centre Axis
Maintain the same gap between Cutting Cam to Reed switch/ Magnet strip to Reed switch in every
floor
For further adjustment, use the F4-00 = 30(default). Increase this value bit by bit if the lift car stops
before the floor level and vice versa.
For example, lift car stops 10mm above the floor level in the landing while comes from bottom floor to
this floor, then reduce the F4-00 = 20 (30-10)
All Car and Landing calls can be given to the L1~L20 terminal in Main Control Board (MCB) of
NICE1000
Call Function input terminal L1~L20 of MCB can be programmed in F6-11~F6-30 using Keypad
In NICE1000, Car functions are programmable and the default NICE1000 unit is programmed for 5
floor full collective function
Page 37 of 49
Version : 1.4
Date of issue : 03-07-14
9 Floors (G+8) Down Collective configuration setting and its functional output terminal
Floor Call Details Corresponding Parameter Call buttons Connection
Setting Terminal in MCB
Car Call Function
Gnd (Bottom most) floor Car Call F6-15=211(Default) L5
1st Floor Car call F6-16=212 (Default) L6
2nd Floor Car call F6-17=213 (Default) L7
3rd Floor Car call F6-18=214 (Default) L8
4th Floor Car call F6-19=215 (Default) L9
5th Floor Car call F6-20=216 L10
6th Floor Car Call F6-21=217 L11
7th Floor Car Call F6-22=218 L12
8th Floor Car Call F6-23=219 L13
Landing Call Function
Gnd Floor UP Landing call F6-26=221 L16
1st Floor Down landing Call F6-27=232(Default) L17
2nd Floor Down landing Call F6-28=233(Default) L18
3rd Floor Down landing Call F6-29=234(Default) L19
4th Floor Down landing Call F6-30=235(Default) L20
5th Floor Down landing Call F6-24=236(Default) L14
6th Floor Down landing Call F6-25=237(Default) L15
7th Floor Down landing Call F6-13=238(Default) L3
8th Floor Down landing Call F6-14=239(Default) L4
Page 38 of 49
Version : 1.4
Date of issue : 03-07-14
NICE 1000 Lift Integrated Controller can provide three different output functions for third party
floor display.
They are
7 Segment output selection FE-12=0
Binary Code output selection FE-12=3
BCD output selection FE-12=1(Default)
To modify the 7 segment floor display digit, use the following parameters
FE-01 to FE-10 for landing level 1 to 10
Page 39 of 49
Version : 1.4
Date of issue : 03-07-14
Confirm the ARD functional wiring is done as per the NICE1000 Electrical drawing to
connect the Suitable rated UPS to the controller
Set the following parameter to enable the ARD function
Page 40 of 49
Version : 1.4
Date of issue : 03-07-14
Weighing 0Invalid
Input F8-08 1Reserved 0
Selection 2Analog Sampling
Keep F8-01=2, if no
0Pre-set torque invalid
Preset load weigh system is
1Pre-set torque Valid
Torque F8-01 0 used (Applicable for
2Automatic pre-torque
Selection Synchronous
compensation
Machine)
Digital output for Over Load from the Load Weigh system is connected to Input terminals X13 of Main
Control Board (MCB)
Digit output for Full Load from the Load weigh system can be used in NICE 1000 system by
configuring anyone of the free Input terminals (X) of Main Control Board (MCB)
Require Expansion board (MCTC-KZ-B); in which, terminals Ai & M are used for Load Weigh 0~10V
analog input
Page 41 of 49
Version : 1.4
Date of issue : 03-07-14
FAULT
RELEVANT DISPOSAL REMARK
SORT
Any kind of working condition
Level 1 Display fault code
will not be influenced
Display fault code;
Level 2 Can operate normal running
Sever lift group control (parallel) system;
Display fault code; After stop, the system will close
Level 3 Stop at the nearest landing when in distance control, then off output at once, and close
stop running; Stop running at once in other work condition. brake
Display fault code;
When in distance control, the system will close off output at The elevator can run in low
Level 4
once and close brake; after stop, low speed running (such as speed in condition of fault code
return levelling, inspection) is allowed
fault Express fault code:
Level 5 The system blank off output at once, and close brake; Running forbidden
Running forbidden
Page 42 of 49
Version : 1.4
Date of issue : 03-07-14
Error on Error on
Fault
LED On- Board Fault Probable Causes Remedy
Sort
Display Display
1. The main circuit output is
grounded or short circuited. 1. Eliminate external faults.
2. The connecting cable of the 2. Install a reactor or an output
Invert unit motor is too long. filter.
Err01 E01 5
protection 3. The working temperature is too 3. Check the air channel and the
high. cooling fan.
4. The internal connections 4. Contact the agent or Monarch.
become loose.
1. Check whether the RUN
contactor at the controller output
side is normal.
1. The main circuit output is 2. Check whether the power cable
grounded or short circuited. jacket is damaged, whether the
Over-current 2. Motor auto tuning is performed power cable is
E02 during improperly. possibly short circuited to ground
Err02 5
Acceleration 3. The load is too heavy. and whether the cable is
4. The encoder signal is incorrect. connected reliably.
5. The UPS running feedback 3. Check the insulation of motor
signal is abnormal. power terminals, and check
whether the motor winding is
short-circuited or grounded.
4. Check whether the shorting
PMSM stator contactor causes
controller output short circuit.
1. The main circuit output is 5. Check whether motor
grounded or short circuited. parameters comply with the
2. Motor auto tuning is performed nameplate.
Over- current improperly. 6. Perform motor auto-tuning
Err03 again.
during 3. The load is too heavy.
; E03 7. Check whether the brake keeps 5
deceleration 4. The deceleration rate is too
short. released before the fault occurs
5. The encoder is seriously and whether the brake is stuck
interfered with external noise. mechanically.
8. Check whether the balance
coefficient is correct.
9. Check whether the encoder
wirings are correct. For
asynchronous motor, perform
SFVC and compare the current
to judge whether the encoder
works properly.
1. The main circuit output is 10. Check whether the encoder
grounded or short circuited. lines per revolution is set
Over-current correctly, whether the encoder
2. Motor auto tuning is performed
during signal is interfered with, whether
Err04 E04 properly. 5
constant speed the encoder cable runs through the
3. The load is too heavy.
4. The encoder is seriously duct independently, whether the
interfered with external noise. cable is too long and whether the
shielding layer is grounded at one
end.
11. Check whether the encoder is
installed reliably, whether the
Page 43 of 49
Version : 1.4
Date of issue : 03-07-14
Current
Err 18 E18 Diver control Board is failed Contact with agent or factory 5
detection fault
1. Enter the motor parameters
correctly.
2. Check the motor wiring and
whether phase loss occurs on the
contactor at the output side.
1. The motor cannot rotate
3. Check the feedback encoder
Motor properly.
wiring and ensure that PPR of the
tuning 2. The motor auto tuning times
Err 19 E19 encoder is set properly. 5
fault out.
4. Check whether the brake keeps
3. The encoder for the PMSM
released during no-load auto-
fails.
tuning.
5. Check whether the inspection
button is released before the
PMSM with-load auto-tuning is
finished.
1. Check whether the encoder 1. Check whether F1-00 is set
Rotary model matches the motor. correctly.
Err 20 E20 5
encoder fault 2. The encoder wiring is 2. Check the encoder wiring.
incorrect. 3. Check whether the encoder is
Page 45 of 49
Version : 1.4
Date of issue : 03-07-14
EEPROM
Err 25 E25 EEPROM of the MCB fails. Contact the agent or Monarch. 5
failure
1. Check whether the feedback
contact (NO, NC) of the contactor
is consistent with the parameter
setting of the MCB.
2. Check whether the state of the
MCB output indicator is
consistent with the contactor
PMSM action.
U,V,W jump The shorting PMSM stator's 3. Check whether corresponding
Err 29 E29 out contactor output is inconsistent with the feedback contact acts after the 5
feedback feedback. contactor acts, and whether the
abnormity corresponding feedback input
point of the MCB acts correctly.
4. Check whether the shorting
PMSM stator contactor is
consistent with the MCB output
feature.
5. Check the coil circuit of the
shorting PMSM stator contactor.
Page 46 of 49
Version : 1.4
Date of issue : 03-07-14
Lift running The setting of the elevator The elevator is used for a long
Err 40 E40 4
time-out running time is exceeded. time and needs maintenance.
1. Check the status of the safety
circuit switches.
2. Check whether the external
Safety circuit power supply is normal.
The safety circuit signal breaks
Err 41 E41 off 3. Check whether the safety 5
off.
circuit contactor acts properly.
4. Confirm the signal feature (NO,
NC) of the feedback contact of
the safety circuit contactor.
Door lock The door lock circuit feedback 1. Check whether the landing
Err 42 E42 safety circuit breaks off during the elevator door lock and the car door lock 5
cut in running running. are in good contact.
Page 48 of 49
Version : 1.4
Date of issue : 03-07-14
Page 49 of 49
Version : 1.4
Date of issue : 03-07-14