0% found this document useful (0 votes)
558 views60 pages

Logix 5000 Controllers Security: Programming Manual

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
558 views60 pages

Logix 5000 Controllers Security: Programming Manual

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Programming Manual

Logix 5000 Controllers Security


1756 ControlLogix, 1756 GuardLogix, 1769 CompactLogix, 1769 Compact GuardLogix,
1789 SoftLogix, 5069 CompactLogix, 5069 Compact GuardLogix, Studio 5000 Logix Emulate
Important user information
Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment
before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions
in addition to requirements of all applicable codes, laws, and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by
suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer,
the protection provided by the equipment may be impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this
equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated
with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and
diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this
manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to
personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic
loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence

Important: Identifies information that is critical for successful application and understanding of the product.

Labels may also be on or inside the equipment to provide specific precautions.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be
present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous
temperatures.

ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc
Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work
practices and for Personal Protective Equipment (PPE).

Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of changes

This manual includes new and updated information. Use these reference tables to
locate changed information.

Grammatical and editorial style changes are not included in this summary.

Global changes

None in this release.

New or enhanced features

This table contains a list of topics changed in this version, the reason for the
change, and a link to the topic that contains the changed information.

Topic Name Reason


Add an LV instruction to monitor license status Added information on the License Validation (LV) instruction.
on page 35

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 3


Table of contents

Summary of changes Studio 5000 environment....................................................................................................7


Additional resources .............................................................................................................7
Legal notices ...........................................................................................................................8
Preface
Chapter 1

Security overview Introduction ........................................................................................................................ 11


FactoryTalk Security ......................................................................................................... 11
Permission sets and Logical Names ........................................................................ 11
Source Protection ............................................................................................................... 12

Chapter 2

Configuring source Introduction ........................................................................................................................ 15


Considerations and limitations for License protection and locked
protection in the Logix
components ................................................................................................................. 16
Designer application Enable source protection .................................................................................................. 18
Disable the Configure Source Protection menu option ............................................. 18
Protect components with Source Keys .......................................................................... 19
About source keys....................................................................................................... 20
Source key names ........................................................................................................ 21
Source key file .............................................................................................................. 21
Apply Source Key protection to a component ..................................................... 22
Specify a Source Key file and location ............................................................ 25
View components without a key ..................................................................... 26
Verify source key protection on a component .............................................. 27
Remove access to a protected routine ............................................................. 28
License Source Protection for components .................................................................. 28
Protect components with Licenses ......................................................................... 28
Add Execution Protection to License-protected components .......................... 30
Apply License Protection to one or more components ...................................... 31
Lock a component ...................................................................................................... 34
Lock all License-Protected content ........................................................................ 35
Add an LV instruction to monitor license status................................................. 35
Share License privileges with other users on your network ............................... 35
Provide License privileges to other users........................................................ 36
Provide license privileges for remote desktop users ..................................... 39

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 5


Table of contents

Appendix A

Securing a ControlLogix Accessing a secured controller ......................................................................................... 46


Removing security from a controller with the CPU Security Tool ......................... 48
controller with the Logix CPU
Removing a password ........................................................................................................ 50
Security Tool
Appendix B

Product policies and Product policies and securable actions ........................................................................... 54


securable actions supported
by FactoryTalk Security

Index

6 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Preface

This manual explains how to configure security for the Logix Designer™
application. It also explains how to set up source protection for your logic and
projects. This manual is one of a set of related manuals that show common
procedures for programming and operating Logix 5000 controllers.

For a complete list of common procedures manuals, refer to the Logix 5000
Controllers Common Procedures Programming Manual , publication 1756-
PM001 .

The term Logix 5000 controller refers to any controller based on the Logix 5000
operating system.

Studio 5000 environment The Studio 5000 Automation Engineering & Design Environment® combines
engineering and design elements into a common environment. The first element is
the Studio 5000 Logix Designer® application. The Logix Designer application is
the rebranding of RSLogix 5000® software and will continue to be the product to
program Logix 5000™ controllers for discrete, process, batch, motion, safety, and
drive-based solutions.

The Studio 5000® environment is the foundation for the future of


Rockwell Automation® engineering design tools and capabilities. The Studio 5000
environment is the one place for design engineers to develop all elements of their
control system.

Additional resources These documents contain additional information concerning related products
from Rockwell Automation.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 7


Preface

Resource Description
Industrial Automation Wiring and Grounding Guidelines , Provides general guidelines for installing a Rockwell
publication 1770-4.1 Automation industrial system.
FactoryTalk Security System Configuration Guide , Provides additional information on FactoryTalk™
publication FTSEC-QS001 security.
Product Certifications website, Provides declarations of conformity, certificates, and
[Link] other certification details.

You can view or download publications at


[Link] . To order paper copies of
technical documentation, contact your local Allen-Bradley™ distributor or
Rockwell Automation™ sales representative.

Legal notices Copyright Notice

Copyright © 2018 Rockwell Automation Technologies, Inc. All Rights Reserved.


Printed in USA.

This document and any accompanying Rockwell Software products are


copyrighted by Rockwell Automation Technologies, Inc. Any reproduction
and/or distribution without prior written consent from Rockwell Automation
Technologies, Inc. is strictly prohibited. Please refer to the license agreement for
details.

End User License Agreement (EULA)

You can view the Rockwell Automation End-User License Agreement ("EULA")
by opening the [Link] file located in your product's install folder on your hard
drive.

Other Licenses

The software included in this product contains copyrighted software that is


licensed under one or more open source licenses. Copies of those licenses are
included with the software. Corresponding Source code for open source packages
included in this product are located at their respective web site(s).

Alternately, obtain complete Corresponding Source code by contacting Rockwell


Automation via the Contact form on the Rockwell Automation website:
[Link]
Please include "Open Source" as part of the request text.

A full list of all open source software used in this product and their corresponding
licenses can be found in the OPENSOURCE folder included with the Release
Notes. The default installed location of these licenses is C:\Program Files

8 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Preface

(x86)\Common
Files\Rockwell\Help\<Product>\ReleaseNotes\OPENSOURCE\[Link].

Trademark Notices

Allen-Bradley, ControlBus, ControlFLASH, Compact GuardLogix, Compact


I/O, ControlLogix, CompactLogix, DCM, DH+, Data Highway Plus,
DriveLogix, DPI, DriveTools, Explorer, FactoryTalk, FactoryTalk Administration
Console, FactoryTalk Alarms and Events, FactoryTalk Batch, FactoryTalk
Directory, FactoryTalk Security, FactoryTalk Services Platform, FactoryTalk
View, FactoryTalk View SE, FLEX Ex, FlexLogix, FLEX I/O, Guard I/O, High
Performance Drive, Integrated Architecture, Kinetix, Logix5000, Logix 5000,
Logix5550, MicroLogix, DeviceNet, EtherNet/IP, PLC-2, PLC-3, PLC-5,
PanelBuilder, PowerFlex, PhaseManager, POINT I/O, PowerFlex, Rockwell
Automation, RSBizWare, Rockwell Software, RSEmulate, Historian,
RSFieldbus, RSLinx, RSLogix, RSNetWorx for DeviceNet, RSNetWorx for
EtherNet/IP, RSMACC, RSView, RSView32, Rockwell Software Studio 5000
Automation Engineering & Design Environment, Studio 5000 View Designer,
SCANport, SLC, SoftLogix, SMC Flex, Studio 5000, Ultra 100, Ultra 200,
VersaView, WINtelligent, XM, SequenceManager are trademarks of Rockwell
Automation, Inc.

Any Rockwell Automation logo, software or hardware product not mentioned


herein is also a trademark, registered or otherwise, of Rockwell Automation, Inc.

Other Trademarks

CmFAS Assistant, CmDongle, CodeMeter, CodeMeter Control Center, and


WIBU are trademarks of WIBU-SYSTEMS AG in the United States and/or
other countries. Microsoft is a registered trademark of Microsoft Corporation in
the United States and/or other countries. ControlNet is a trademark of
ControlNet International. DeviceNet is a trademark of the Open DeviceNet
Vendors Association (ODVA). Ethernet/IP is a trademark of ControlNet
International under license by ODVA.

All other trademarks are the property of their respective holders and are hereby
acknowledged.

Warranty

This product is warranted in accordance with the product license. The product’s
performance may be affected by system configuration, the application being
performed, operator control, maintenance, and other related factors. Rockwell
Automation is not responsible for these intervening factors. The instructions in
this document do not cover all the details or variations in the equipment,
procedure, or process described, nor do they provide directions for meeting every

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 9


Preface

possible contingency during installation, operation, or maintenance. This


product’s implementation may vary among users.

This document is current as of the time of release of the product; however, the
accompanying software may have changed since the release. Rockwell Automation,
Inc. reserves the right to change any information contained in this document or
the software at any time without prior notice. It is your responsibility to obtain the
most current information available from Rockwell when installing or using this
product.

Environmental Compliance

Rockwell Automation maintains current product environmental information on


its website at [Link]
us/sustainability-ethics/[Link]

Contact Rockwell

Customer Support Telephone — 1.440.646.3434

Online Support — [Link]

10 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Chapter 1

Security overview

Introduction This chapter provides an overview of the security features available in the Logix
Designer application.

The following features are the main security features that protect controller
projects:

• FactoryTalk® Security software, which provides permission-based control.


• Source Protection, which protects the logic in controller projects.

FactoryTalk Security FactoryTalk® Security integrates a common security model across all FactoryTalk
enabled products. FactoryTalk® Services Platform (FTSP) includes the
FactoryTalk Administration Console that provides the interface for configuring
your system. FactoryTalk Services Platform (FTSP) software is installed during
the installation of the Logix Designer application.

Use FactoryTalk Security to control access to the logic in your projects with
centrally managed, role-based policy enforcement.

For more information about FactoryTalk Security, see the FactoryTalk Security
System Configuration Guide , publication FTSEC-QS001 .

Permission sets and Logical Permission sets and Logical Names identify a set of actions that are allowed or
denied for one or more user groups or computer groups. You use permission sets
Names
and Logical Names to define user permissions in the FactoryTalk Administration
Console. Use permission sets to apply the same permissions to multiple controllers
or project components. Use a Logical Name to associate permissions with a
specific controller. When you use a Logical Name, it must match the name of the
controller.

When a user opens a project that has been secured with a permission set or a
Logical Name and configured to use only the selected security authority, the Logix
Designer application checks the ID of the FactoryTalk Directory to see if it
matches the ID stored in the project.

• If the ID matches, the Logix Designer application checks the directory and
finds the Logical Name (that matches the controller name), or the

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 11


Chapter 1 Security overview

permission set associated with the project, and gets the permissions for the
current user/computer combination.
• If the ID does not match, the project uses the Guest User permissions
defined for that permission set or Logical Name.

When a user opens a project that has been secured but has not been configured to
use only the selected security authority, the Logix Designer application checks the
connected FactoryTalk Directory, finds the Logical Name or the permission set
associated with the project, and gets the permissions for the current
user/computer combination. Rockwell recommends configuring the project to use
only the selected security authority to maintain control over the directory that
secures the project.

Permissions for Guest Users

When you configure permission sets and logical names in the FactoryTalk
Administration Console, you can also configure permissions for Guest Users. The
permissions for Guest Users determine the level of access for users who are not
authenticated on the same FactoryTalk directory that the project was secured
with.

Permissions for Guest Users are cached in the project file to which they are
associated. However, the permissions are only stored in the project file for
permission sets that have been applied to objects by a user of the primary
FactoryTalk directory.

Refer to the FactoryTalk online help for more information on permissions for
Guest Users.

Source Protection Source Protection limits users' ability to view and edit routines and Add-On
Instructions, including equipment phase state routines, without the associated
source key or license. Apply Source Key Protection or License Source Protection
to routines and Add-On Instructions. Apply Execution Protection to license-
protected components to allow execution only on controllers with a specific
execution license.

When protecting a component with License Source Protection, optionally lock


the the component. A locked component does not require the source license to
open the project or execute the locked component, allowing more secure
distribution. A user with the correct license must unlock a component to allow
viewing or editing. Rockwell recommends locking unlocked components in
projects that are distributed from trusted development environments to unsecured
environments to safeguard your intellectual property.

12 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Security overview Chapter 1

Tip: Routines and Add-On Instructions are currently the only project component types that support Source
Protection.
Tip: Execution Protection and component locking is supported only on Compact GuardLogix 5380, CompactLogix
5380, CompactLogix 5480, ControlLogix 5580, and GuardLogix 5580 controllers in versions 30 and 31 of the
Logix Designer application.

License Source Protection and Execution Protection Licenses require the use of
CmSticks and CmCards:

• On the computer running the Logix Designer application, a CmStick,


CmCard, or other compatible Wibu device that contains licenses required
for opening a license-protected project and working with project
components.
Tip: On CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, Compact GuardLogix 5380, and GuardLogix
5580 controllers, a CmStick, CmCard, or other compatible Wibu device is not required to open a project
containing locked components.

• On the controller, a CmCard that contains execution licenses required to


run a project that contains components protected with Execution
Protection. If a required execution license is missing, the project does not
download to the controller. If the project has already been downloaded and
the license expires or the CmCard is removed, a major fault occurs when the
controller is switched to Run mode.

The following table describes the types of Source Protection available.

Protection option Supported controllers Description


Source Key (Password-based) All Logix 5000 controllers Simple legacy protection, not recommended for hardened
Source Protection intellectual property protection.
• Component source code (logic) is protected with a password.
• Password must be available to view or edit protected
components.
• Optionally, can be configured to allow logic to be viewed
when password is not available.
License Source Protection CompactLogix 5370, ControlLogix Hardened intellectual property protection for sensitive content:
5570, Compact GuardLogix 5370, and • Component source code (logic) is protected with a License on
GuardLogix 5570 controllers a CmStick installed on the computer running the Logix
Designer application.
• License must be present to open or import the file containing
the protected components.
• Licenses can be configured with different access levels to
allow viewing or editing protected components.
License Source Protection (Locked) CompactLogix 5380, CompactLogix Provides hardened intellectual property protection for sensitive
5480, ControlLogix 5580, Compact content and allows easy transfer of projects:
GuardLogix 5380, and GuardLogix • Component source code (logic) is protected with a license on
5580 controllers a CmStick installed on the computer running the Logix
Designer application.
• Executable code is protected and stored separately from the
source code.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 13


Chapter 1 Security overview

Protection option Supported controllers Description


License Source Protection CompactLogix 5380, CompactLogix Provides protection and access control based on permissions in
(Unlocked) 5480, ControlLogix 5580, Compact the license:
GuardLogix 5380, and GuardLogix • Users without a dongle can work with unprotected parts of
5580 controllers the project, but users cannot view or edit the protected
content. The dongle is required to work with the protected
content.
• To lock or unlock a component, the source license must be
present on a CmStick plugged into the computer running the
Logix Designer application, and the license must contain the
View permission.
License Source Protection + CompactLogix 5380, CompactLogix Limits execution of valuable content to only authorized
License Execution Protection 5480, ControlLogix 5580, Compact controllers:
GuardLogix 5380, and GuardLogix • Provides same protection as License-based Source
5580 controllers Protection.
• Additionally, components can be protected with an
Execution License.
• Protected components can only be downloaded and
executed on a controller that contains a CmCard with the
correct execution license.

14 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Chapter 2

Configuring source protection in the Logix


Designer application

Introduction This chapter describes how to enable and apply source protection for your Logix
Designer components, such as routines and Add-On Instructions. You can
protect project components using Source Key protection or License protection.
You can also apply Execution Protection to source-protected components to allow
execution only on controllers with a specific execution license.

Source Key protection:

• Protects components using existing source keys.


Tip: You can optionally allow source-protected components to be available in a read-
only format on a system that does not have the source key required for access.

License protection:

• Protects components with specific licenses.


Tip: License Source Protection is not supported on Sequential Function Chart routines in
versions 30 and later of the Logix Designer application.

• Execution Protection is an extension of License-Based Source Protection.


You can apply Execution Protection to limit the execution of routines and
Add-On Instructions, including equipment phase state routines, to
controllers that contain a specific execution license.
• When you protect a component with License Source Protection, you can
also lock it. When you lock a component, the routine's logic is compiled
into executable code and encrypted. It is only decrypted by the controller
when it is ready to be executed. As a result, project files containing locked
components can be shared with users without licenses to work with the
locked components. Those users can work with unprotected parts of the
project, upload and download the project file, and even copy and paste
locked components into other project files. Rockwell recommends locking
unlocked components in projects that are distributed from trusted
development environments to unsecured environments in order to
safeguard your intellectual property.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 15


Chapter 2 Configuring source protection in the Logix Designer application

Tip: Execution Protection and component locking is supported only on Compact GuardLogix 5380, CompactLogix
5380, CompactLogix 5480, ControlLogix 5580, and GuardLogix 5580 controllers in version 30 of the Logix
Designer application.

Considerations and limitations Keep the following considerations and limitations in mind when using License
Source Protection with routines and Add-On Instructions for CompactLogix
for License protection and
5380, CompactLogix 5480, ControlLogix 5580, Compact GuardLogix 5380, and
locked components GuardLogix 5580 controllers.

• Sequential Function Chart routines cannot be protected with License


Source Protection and execution protection.
• Function Block Diagram routines cannot be protected with License Source
Protection and execution protection.
• You cannot overwrite a locked routine with a locked routine of a different
language. If a locked routine needs to be replaced with a locked routine of a
different language, first unlock the routine in the target file.
• You cannot overwrite a locked routine with an unlocked routine, and vice
versa. To replace a locked routine with an unlocked routine, and vice versa,
first delete the routine to be replaced.
• If you overwrite a locked ladder logic routine that contains label (LBL)
instructions with a locked ladder logic routine that contains similar labels,
other workstations can lose correlation with the project. To recover
correlation, upload the project on the affected workstations.
• The controller SD card holds a maximum of 63 active or expired licenses,
plus the Rockwell activation license for Execution Protection. If the SD
card contains more than 64 licenses, downloads with license-protected
content fail to the controller. To remove unwanted licenses, use the removal
option on the Wibu administration portal.
• When you lock an Add-On Instruction, the data included in tags is
protected but not to the extent that the logic is protected. If your tags
contain sensitive data, Rockwell recommends putting that data in literals
rather than in tags. Literals are protected at the same level as the logic in
locked routines and Add-On Instructions. In programmable logic, a literal is
a value that is expressed as itself rather than as a variable's value or the result
of an expression.

Limitations for locked components

After a routine or an Add-On Instruction (AOI) is locked, strict limits apply to


changes made to the routine or to other components the routine references. This
table lists limitations that apply to locked components. An authorized user can
run a locked component. To view or edit a component an authorized user must

16 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Configuring source protection in the Logix Designer application Chapter 2

unlock the component.

Limitation Affects routines Affects AOIs


Cannot resize an array that is referenced by a locked routine. x
Cannot change the target of an alias that is referenced by a locked routine. x

Cannot change a BOOL alias that targets the bit of an integer to target a different x
bit. However, changing the alias to target a different integer is allowed.
Cannot change the target of an alias that is referenced by a locked routine to a tag x
of a different type.
Cannot change the target of an alias of a member of a UDT or array element to a x
target at a different offset from the beginning of the tag.
Cannot change an alias referenced by a locked routine to a base tag. x
Cannot change a base tag that is referenced by a locked routine to an alias. x
Cannot change an InOut program parameter that is referenced by a locked routine x
to anything other than an InOut program parameter.

Cannot change a Produced tag to anything other than a Produced, Consumed, x


Module Input tag or Module Output tag when the Produced tag is:
• Referenced by a locked routine, and
• Used in a COP, CPS, MAOC or as an InOut argument to an AOI in that locked
routine.
Cannot change a Produced tag that is used in an IOT instruction to anything other x
than a Produced or Module Output tag.
Cannot change a Consumed tag to anything other than a Produced, Consumed, x
Module Input tag, or Module Output tag when the Consumed tag is:
• Referenced by a locked routine, and
• Used in a COP, CPS, MAOC or as an InOut argument to an AOI in that locked
routine.
Cannot change a Module Input tag to anything other than a Produced, Consumed, x
Module Input tag, or Module Output tag when the Module Input tag is:
• Referenced by a locked routine, and
• Used in a COP, CPS, MAOC or as an InOut argument to an AOI in that locked
routine.
Cannot change a Module Output tag to anything other than a Produced, x
Consumed, Module Input tag, or Module Output tag when the Module Output tag
is:
• Referenced by a locked routine, and
• Used in a COP, CPS, MAOC or as an InOut argument to an AOI in that locked
routine.
Cannot change a Module Output tag that is used in an IOT instruction to anything x
other than a Produced or Module Output tag.
Cannot change a standard tag referenced by a locked routine to a Produced, x
Consumed, Module Input, or Module Output tag, if that tag is used by a COP, CPS,
MAOC or used as an AOI InOut argument in that locked routine.
Cannot re-order the members of a User Defined Type of a tag that is referenced by x x
a locked routine or AOI.
Cannot change the data type of a tag that is referenced by a locked routine. x

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 17


Chapter 2 Configuring source protection in the Logix Designer application

Limitation Affects routines Affects AOIs


Cannot update a profile in a way that changes the data type of a Module Defined x x
Tag that is referenced by a locked routine.
Cannot add, remove, or change the data type of a member of a User Defined Data x x
Type of a tag that is referenced by a locked routine or AOI.
Cannot reorder, add, change the data type of, or remove parameters in an AOI x x
referenced by a locked routine or AOI.
Cannot convert a project containing locked routines or AOIs to a different x x
controller family.
Cannot move locked routines or AOIs to a project of a different controller family. x x
Cannot change the target of an AOI output parameter that aliases a local tag if the x
AOI is used in a locked AOI.
Cannot change the targets of two aliases referenced by a locked routine currently x
targeting different base tags to the same base tag.
Cannot change the targets of two aliases referenced by a locked routine currently x
targeting the same base tag to target different base tags.
Cannot change the type of a base tag targeted by an alias that is referenced by a x
locked routine.
Cannot change an external Output that is referenced by a locked routine to a non- x
Output.
Cannot change an external Output that is referenced by a locked routine to a local x
Output.
Cannot change a local tag that is referenced by a locked routine to an external x
Output.

Enable source protection If Source Protection is unavailable and is not listed in the Tools > Security menu,
enable the Source Protection feature by running the [Link] tool on the
installation CD. The menu item is also enabled when a CmStick containing a
license with protect permissions is inserted into any USB port on the computer.

Follow these steps to enable Logix Designer source protection.

1. Open the ENU\Tools\Source Protection Tool\[Link] folder on the


Logix Designer installation CD.

2. Run the [Link] file.

Disable the Configure You can disable the ability to configure source protection on a workstation by
removing the Configure Source Protection option from the Tools > Security
Source Protection menu menu.
option
Important: Write down the source keys or make a copy of the [Link] file and store in a secure location before
deleting the [Link] file.

1. Open the protected project in the Logix Designer application.

2. Click Tools > Security > Configure Source Protection.

18 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Configuring source protection in the Logix Designer application Chapter 2

3. In the Source Protection Configuration dialog box, click Source Key


Configuration.

4. In the Source Key Configuration dialog box, click Disable Ability To


Configure.

5. In the dialog box that prompts you to confirm the action, click Yes.

6. In the dialog box that asks if you want to delete the source key file ([Link]),
click Yes to remove the source key file from the computer, or select No to
keep the source key file.

Configure Source Protection is removed from the Tools > Security


menu.

Tip: The menu item will not disappear if a CmStick containing a license with the
Protect permission is connected to the computer.

Protect components with When Source Key protection is applied to a component, that component is
source-protected. Source keys are user-generated, case-sensitive passwords that
Source Keys lock Logix Designer components from being viewed or modified by third parties.

Important: Source Protection can be applied only on a project file that is offline.

Tip: For Add-on Instructions, Source Protection settings cannot be modified if the Add-On Instruction is sealed. If
you wish to source protect and seal an Add-On Instruction, you must apply the source protection settings
before sealing.
Tip: Password source protection is designed to work with a relatively small number of source keys in the [Link] file.
When the number of source keys becomes large, there is a corresponding performance impact when opening
source protected projects in the Logix Designer application or opening the Source Protection dialog box.

When a component is protected with a Source Key, users without the source key
cannot alter the logic of the component. This affects the following features:

• Editing - The Language editor does not open, and the edit menus in the
Controller and Logical Organizers are unavailable. The component icon
is also unavailable. If the component is protected with the Viewable option,
users can open the routine editor in read-only mode.
• Printing - Routines cannot be printed. Add-On instruction can be printed,
but the routines and local tags are not included in the print out. Routine
logic and Add-On Instruction local tags can be printed if components are
protected with the Viewable option.
• Exporting - The protected component is written to the export file in an
encoded format.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 19


Chapter 2 Configuring source protection in the Logix Designer application

• Component Properties - All controls on the dialog boxes of the components


are read-only.
• Search and Replace - Find All is the only available search type source. Find
Next, Replace All, and Replace Next skip the protected component.
When the protected component is skipped, a message appears on the status
bar indicating the source is not available. This message is also logged to the
Search Results tab when performing a Replace All search. If a component
is protected with the Viewable option, search is permitted but replace is still
prevented.

Because users cannot view the logic of a protected routine, the Find All search
results items do not navigate to the found locations. This affects the following:

• Navigation - Users cannot navigate to a protected component.


• Verification - Users cannot navigate to an error in a protected component.
• Cross Reference - Cross reference information is displayed for items
referenced within a protected component, but users are not allowed to
navigate to the location within the protected component. Double-clicking
to navigate to a protected component beeps and displays a message on the
status bar indicating that users are unable to edit the component and that
the source is not available.

The Go to Location menu item is unavailable.

• Go To - There is no edit item in the Go To dialog box for a protected


component.
• Cut, Copy, Paste - Users can copy, paste, and drag and drop protected
components from the Controller and Logical Organizers.
Important: Use caution when copying and pasting components between different versions of the Logix
Designer application. The application only supports pasting to the same version or newer version of
the application. Pasting to an earlier version of the application is not supported. When pasting to
an earlier version, the paste action may succeed, but the results may not be as intended. You
cannot paste protected components from later versions of the application into earlier versions of
the application. For example, attempting to paste from version 19 into version 18 or from version
20 into version 19 will fail.

About source keys In version 18 and earlier of RSLogix 5000 software, only IEC-61131 compliant
source keys are recognized. Each source key must begin with a lowercase character
a-z or underscore character ( _ ), and contain only characters lowercase a-z, 0-9,
and an underscore character ( _ ). You can enter uppercase A-Z characters in
RSLogix 5000 software or in the source key file, but the uppercase characters are
converted to lowercase. Source keys are limited to 40 characters in length.

20 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Configuring source protection in the Logix Designer application Chapter 2

In version 19 and later of the application, source keys are case-sensitive and may
contain any printable ASCII character, excluding the space character. This
includes uppercase A-Z, lowercase a-z, numbers 0-9, and symbols such as "!@#$%.
Source keys are limited to 40 characters in length.

Source key names Version 19 and later of the Logix Designer application supports associating names
with source keys. Source key names are descriptive text that help identify source
keys. Where appropriate, the Logix Designer application will display the source
key name in place of the source key itself to provide an additional layer of security
for the source key.

Use descriptive names to help identify the purpose of the source. For instance, a
source key used to secure components that field engineers require access might be
named, Field Engineer.

Important: If the same source keys will be used with version 18 and earlier and version 19 and later of the
Logix Designer application, begin each source key with a lowercase character a-z, or an underscore
character ( _ ), and use only characters lowercase a-z, 0-9 , or an underscore character ( _ ) within
the source keys.
If you use source key names in version 19 and later of the application, and your source keys are
IEC61131-3 compliant, your source keys will still work in version 18 and earlier.

Source key file Source keys that are available to the application through an [Link] file are
unencrypted. We recommend that you write down your source keys or back up
and store the [Link] file in a secure location. If necessary, the individual keys can be
distributed or provided to the necessary parties.

Important: Source key files are created in an ANSI format in Logix Designer versions 18 and earlier. In versions 19
and later, the Logix Designer application creates UTF-8 formatted [Link] files, and modified ANSI
[Link] files are converted to UTF-8 [Link] files.
Source keys must not appear on the first line of a UTF-8 formatted [Link] file. The first line of UTF-8
formatted [Link] files is ignored in Logix Designer versions 18 and earlier. Versions 19 and later insert
a header on the first line of the [Link] file if one is not already present.

Follow these steps to assign a name to an existing source key.

1. Click Tools > Security > Configure Source Protection.

2. In the Source Protection Configuration dialog box, click Source Key


Configuration.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 21


Chapter 2 Configuring source protection in the Logix Designer application

3. In the Source Key Configuration dialog box, click View to open the [Link]
file with a text editor, such as Notepad.

4. Click at the end of an existing, unnamed source key, and press Enter.
Source keys are case sensitive and may use special characters, such as
@#$%(){}[].

5. Press Tab, and type a name for the source key.

Tip: Source keys always begin in the first column of the line in the text editor. A source
key name must be on the line immediately following the source key that it is
associated with, preceded on the line by at least one space. Subsequent lines after
the source key that are preceded with spaces are ignored by the application, and
can be used for comments.

6. Save the file. If you used an editor other than Notepad, make sure you save
the file as a text file.

7. Close the Source Key Configuration dialog box and the Source
Protection Configuration dialog box.

8. Click Tools > Security > Configure Source Protection to re-open the
Source Protection Configuration dialog box. The source key name that
you added to the [Link] file appears as the source key name.

Apply Source Key protection to Follow this procedure to apply Source Key protection to a project component.
a component

22 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Configuring source protection in the Logix Designer application Chapter 2

Important: Source Protection can be applied only on a project file that is offline.

Tip: For Add-on Instructions, Source Protection settings cannot be modified if the Add-On Instruction is sealed. If
you wish to source protect and seal an Add-On Instruction, you must apply the source protection settings
before sealing.

Follow these steps to apply a source key to one or more components.

1. Open an offline project file in the Logix Designer application.

2. On the menu bar, click Tools > Security > Configure Source Protection.

3. In the Source Protection Configuration dialog box, select one or more


components that require protection, and click Protect.

By default, the dialog box shows the Protection view in which components
are organized based on the protection applied to them. When you select the
Container view, the components are organized based on the folder
structure in the Controller Organizer and the Logical Organizer.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 23


Chapter 2 Configuring source protection in the Logix Designer application

4. In the Protect dialog box, on the Protection Type list, click Source Key.

5. In the Source Key to Apply Selected Components list, select the


individual source key for the component.

6. If appropriate, retype the new key in Confirm New Source Key. To display
the source keys in a readable format, select the Show Source Key check box.

7. If you want to apply a source key name, type the name in Source Key
Name. Do not exceed 40 characters.

8. To allow users to view the logic and local tags on a system that does not have
the source key required for access, select the Allow viewing of
component(s) check box.

9. After you enter the applicable information, click OK.

10. (optional) In the Source Protection Configuration dialog box, click


Source Key Configuration to open the Source Key Configuration dialog
box and complete details about the source key file location:

• Click Specify to change the path to the source key file location.
• Click View to view the source key file.
• Click Clear to remove the location of the source key file ([Link]). You
are then given the option to delete the source key file.
• Click Disable Configuration to remove the menu item that invokes
the Source Protection Configuration dialog box. You can then clear

24 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Configuring source protection in the Logix Designer application Chapter 2

the file location, which is the path listed under Source Key Provider,
or delete the source key file.

11. Close the Source Protection Configuration dialog box and save the
project file.

Specify a Source Key file and location Follow these steps to configure a source key file location.

1. Open an offline project file in the Logix Designer application.

2. On the menu bar, click Tools > Security > Configure Source Protection.

Tip: This option is not available until you run [Link] on your workstation. See Enabling source
protection on page 18.

3. In the Logix Designer dialog box, click Yes to specify a file location. Source
protection requires that you specify a source key file location on your
workstation.

4. In the Specify Source Key File Location dialog box, click Browse .

5. In the Browse for Folder dialog box, click the folder to store the key file,
and click OK.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 25


Chapter 2 Configuring source protection in the Logix Designer application

You can save the key file in any accessible folder. In this example the path to
the key file folder is C:\RSLogix 5000\Projects folder.

6. In the Specify Source Key File Location dialog box, click OK.

The location you selected appears in the Source Protection Configuration


dialog box under Source Key Provider.
If the application does not find a key file in the specified location, the
application prompts you to create a new key file.

Tip: To check for a specific location, on the Source Protection Configuration dialog box, click Specify. A
window appears with the location if one exists on your workstation.

7. Click Yes to create a new key file.

View components without a key Follow these steps to allow source-protected components to be viewed in a read-
only format on a system that does not have the source keys.

1. On the menu bar, click Tools > Security > Configure Source Protection.

2. In the Source Protection Configuration dialog box, select one or more


components that require protection and click Protect.

3. Apply a source key to the component.

26 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Configuring source protection in the Logix Designer application Chapter 2

4. Select the Allow viewing of components check box, and click OK. In the
Source Protection Configuration dialog box, +View appears for
components that are viewable on workstations that do not have the source
key.

5. Click Close.

6. Save the project file and download it to the controller.

Users can open the routine as read-only on a system that does not contain
the source key for the routine, but cannot modify the routine. Routines or
Add-On Instructions that are protected, but are not configured as viewable,
cannot be opened.

Tip: Source-protected content cannot be copied from Logix Designer versions 19 and later and pasted into earlier
software versions. The pasting function is disabled in previous software versions when source-protected
content is placed on the clipboard.

Verify source key protection on a


After you apply source key protection to a component, you can verify that the
component
source key protection is working. To verify a component is protected, temporarily
disable the source key on your workstation.

Follow these steps to verify source key protection by specifying the path to an
empty [Link] file.

1. On the Source Protection Configuration dialog box, click Specify.

2. On the Specify Source Key File Location dialog box, select a directory that
does not contain an [Link] file. For example, C:\RSLogix
5000\Projects\Empty.

3. When a message appears asking if you want to create a new file, click Yes.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 27


Chapter 2 Configuring source protection in the Logix Designer application

4. When the message appears asking if you want to create a new directory,
click Yes. The software points to an empty [Link] file, which mimics a user
who does not have a source key.

5. Verify that you cannot access the protected component.

6. On the Specify Source Key File Location dialog box, switch back to the
directory that contains your original [Link] file.

Remove access to a protected routine You can delete a source key file ([Link]) from a workstation.

Important: Write down the source keys or make a copy of the [Link] file and store it in a secure location
before deleting the [Link] file.

1. Open the protected project.

2. Click Tools > Security > Configure Source Protection to open the
Source Protection Configuration dialog box.

3. Click Source Key Configuration.

4. On the Source Key Configuration dialog box, click Clear.

5. When a dialog box asks for confirmation that you want to delete the source
key file, select Yes to remove the source key file from the workstation.

License Source Protection License Source Protection limits access to projects to only users with the required
license. Users without the required license cannot open the project or import
for components components protected by the license. A CmStick containing the corresponding
license must be plugged into a USB port on the computer to open the project
containing the component.

License protection uses licenses that you create and administer through a license
portal. Refer to your license portal help for details on using the portal.

Tip: License Source Protection is not supported on the following routine types on Compact GuardLogix
5380, CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, and GuardLogix 5580 controllers:
• Sequential Function Chart routines.
• Function Block Diagrams, unless the Function Block Diagram is included in an Add-On Instruction.

When using License Protection on CompactLogix 5380, CompactLogix 5480,


and ControlLogix 5580 controllers, you can also apply Execution Protection for
the component, which allows execution of the component only on a specific
controller family, or only on controllers in a specific controller family that contain
the execution license.

Protect components with The permissions provided by licenses are:


Licenses

28 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Configuring source protection in the Logix Designer application Chapter 2

Permission Description
Use The minimum permission available for a license. Allows a user to open, import,
upload, or download the project.
Important: On CompactLogix 5370, ControlLogix 5570, Compact GuardLogix
5370, and GuardLogix 5570 controllers, insert a CmStick containing a license
with Use permission in any USB port on the computer. A network license server
cannot provide Use permission. Either the local CmStick or a license server on the
network can contain all other license privileges.
Tip: On Compact GuardLogix 5380, CompactLogix 5380, CompactLogix 5480,
ControlLogix 5580, and GuardLogix 5580 controllers, a Use license is not required
to open, import, upload, or download a project containing a License-Protected
component when that component is locked.
View View routine logic for the component or local tags for an Add-On Instruction.
Enables printing, searching, and cross referencing. Limits the components editors
and properties dialog boxes to read-only, and prevents changes.
Tip: To unlock, view, and re-lock a License-Protected component requires a View
license.
Edit Edit the routine or Add-On Instruction.
Tip: To unlock, view, and re-lock a License-Protected component requires a View
license.
Copy Copy the logic in the routine or Add-On Instruction.
Export Export the routine or Add-On Instruction in a non-encrypted format.

Protect Enable or remove license protection from a component.


Important: Add or remove protection from a component only when the Protect
permission exists on the license currently protecting that component.

License Source Protection on a component affects:

• Editing - If the license does not contain the View permission, the Language
editor does not open, the edit menus are unavailable in the Controller
Organizer and the Logical Organizer, and the component icon is dimmed.
With View permission, the editor opens in read-only mode. Allows editing
if the license contains Edit permission.
• Printing -The license must contain View permission to print routines. Can
print Add-On instructions, but the routines and local tags do not print
without View permission.
• Exporting - Writes the protected component to the export file in an
encoded format unless the license contains Export permission. To export in
non-encrypted text, the license must contain the Export permission, and
when saving the export file, deselect the Encode Source Protected
Content option. Locked components are always exported encoded.
Tip: To export protected components in non-encrypted text, uncheck the Always Encode Protected Content on
Export check box on the General tab of the Workstation Options dialog box.

• Component Properties - All controls on the components dialog boxes are


read-only unless the license contains Edit permission.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 29


Chapter 2 Configuring source protection in the Logix Designer application

• Search and Replace - Find All is the only available search type. Find Next,
Replace All, and Replace Next skip the protected component. When
skipping the protected component, a message appears on the status bar
indicating the source is not available. This message is logged to the search
results tab for a Replace All search. Edit and View permissions control
users' ability to search and replace.

When the license does not contain the View permission, users cannot view the
logic of a protected routine, and the Find All search result items do not navigate
to the found locations. This affects the following features:

• Navigation -Cannot navigate to a protected component.


• Verification - Cannot navigate to an error in a protected component.
• Cross Reference - Cross reference information displays for items referenced
within a protected component, but users cannot navigate to the location
within the protected component. Double-clicking to navigate to a protected
component displays a message on the status bar indicating that users are
unable to edit the component and that the source is not available.
Tip: Find does not search locked components even when a View license is present.

The Go to Location menu item is unavailable.

• Go To -No edit item in the Go To dialog box for a protected component.


• Cut, Copy, Paste - Can copy, paste, and drag and drop source protected
components from the Controller Organizer or Logical Organizer. Cannot
copy, paste, or drag and drop logic contained within the source protected
component unless the license contains Copy permission.
Important: Use caution when copying and pasting components between different versions of the Logix Designer
application. The application only supports pasting to the same version or newer version of the
application. Does not support pasting to an earlier version of the application. When pasting to an
earlier version, the paste action may succeed, but unintended results may occur. Cannot paste
protected components from later versions of the application into earlier versions of the application.
For example, attempting to paste from version 19 into version 18 or from version 20 into version 19
fails.

Add Execution Protection to Execution Protection is an extension of License-Based Source Protection. You can
License-protected components apply Execution Protection to limit the execution of routines and Add-On
Instructions, including equipment phase state routines, to controllers that contain
a specific execution license.

When you apply Execution Protection to a component, you first apply License-
Based Source Protection. Therefore, a user applying Execution Protection must
have the same credentials that are required to apply License-Based Source
Protection:

30 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Configuring source protection in the Logix Designer application Chapter 2

• A CmStick containing a license with Use permission must be present locally


on any USB port on the computer. Use permission cannot be obtained from
a network license server. All other license privileges can be contained on the
local CmStick, or provided by a license server on the network.
• A license containing the Protect permission, either on a local CmStick or
provided by a license server on the network. When components are locked,
unauthorized users cannot view or edit the component, but authorized
users can run the project without a CmStick.

The following credentials are required to run a component that is protected by


Execution Protection:

• After a component is locked, the controller running the component must


be of the same controller family as the controller on which you locked the
component. For example, when you apply License-Based Source Protection
and Execution Protection to a component on a 5580 controller and lock the
component, you can only execute that component on another 5580
controller. A component that was protected on a 5580 controller cannot be
executed on a 5380 controller. To execute the component on a controller
from a different family, you must unlock the component and re-lock it on
the different family controller.
• The controller running the component must contain the following licenses
on a CmCard:
• The required Execution license (if any)
• A valid FactoryTalk Activation license for Execution Protection

Apply License Protection to one Follow these steps to apply License Protection to one or more components.
or more components

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 31


Chapter 2 Configuring source protection in the Logix Designer application

Tip: Version 32 of the Logix Designer application, License Source Protection does not support these routine types:
• Safety routines.
• Sequential Function Chart routines.
• Function Block Diagrams on Compact GuardLogix 5380, CompactLogix 5380, CompactLogix 5480,
ControlLogix 5580, and GuardLogix 5580 controllers, unless the Function Block Diagram is included in an
Add-On Instruction. However, License-protected Function Block Diagrams are supported are supported in
both routines and Add-On Instructions on CompactLogix 5370, ControlLogix 5570, Compact GuardLogix
5370, and GuardLogix 5570 controllers.
Tip: Cannot modify the Source Protection settings if the Add-On Instruction is sealed. To source protect and seal an
Add-On Instruction, apply the source protection settings before sealing.
Important: On CompactLogix 5380, CompactLogix 5480, ControlLogix 5580, Compact GuardLogix 5380, and
GuardLogix 5580 controllers, to open a project when a component is license-protected but not
locked, insert a CmStick containing the corresponding license into a USB port on the computer. A
locked component does not require a corresponding license to open the project or use the
component.

1. Click Tools > Security > Configure Source Protection to open the
Source Protection Configuration dialog box.

2. Insert the CmStick containing the license that you want to use to protect
the component into the USB port on the computer. Note that licenses must
contain the Protect permission to be used to protect components. If a
license does not contain the Protect permission, it will not appear in the list
of licenses.

3. In the Source Protection Configuration dialog box, select the component


to be protected and click Protect.

32 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Configuring source protection in the Logix Designer application Chapter 2

4. In the Protect dialog box, select the license to apply.

5. On Compact GuardLogix 5380, CompactLogix 5380, CompactLogix


5480, ControlLogix 5580, and GuardLogix 5580 controllers, select the
Execution Protection type:

• Protect with controller key only. This option is selected by default.


With this option selected, the component, when locked, runs only on a
controller in the same family as the one specified for the project. For
example, if you lock a License-Based Protected component for a project
on a 5580 controller, the component can only be executed on another
5580 controller.
• Protect with controller key and specific license. When you select this
option, the component runs only on a controller in the same family as

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 33


Chapter 2 Configuring source protection in the Logix Designer application

the one specified for the project and that contains a CmCard with the
execution license that you select.
If you select Protect with controller key and specific license, select
the execution license from the list of available licenses.
On CompactLogix 5380, CompactLogix 5480, ControlLogix 5580,
Compact GuardLogix 5380, and GuardLogix 5580 controllers, after
components are protected, they can also be locked. Locking a
component prevents users from viewing or editing the component but
allows authorized users to run it.

6. Click OK to return to the Source Protection Configuration dialog box.

Tip: To save changes to a component that is protected with License-Based Source Protection, a CmStick containing
the required license must be plugged into the computer running the Logix Designer application.
Make sure you save your edits to the project or lock the protected components before removing the CmStick
containing the required license. If the license is not present, you could lose your edits to the project.

7. Close the Source Protection Configuration dialog box and save the
project file.

Lock a component After you apply License Source Protection to a routine or an Add-On Instruction,
you can lock it on Compact GuardLogix 5380, CompactLogix 5380,
CompactLogix 5480, ControlLogix 5580, and GuardLogix 5580 controllers.

When locking a component, the routine's logic is compiled into executable code
and encrypted. The code is decrypted by the controller when it is ready for
execution. As a result, sharing project files containing locked components with
users without licenses to use the locked components is possible. Those users can
use unprotected parts of the project, upload and download the project file, and
copy and paste locked components into other project files. However, if a
component is protected using the Protect with controller key and specific
license option, executing the project requires an SD card with the correct
execution license.

Tip: To lock or unlock a component, the source license must be present on a CmStick plugged into the computer
running the Logix Designer application, and the license must contain the View permission.
Important: When locking a routine or an Add-On Instruction, the data included in tags is protected, but not to
the extent that the logic is protected. If your tags contain sensitive data, Rockwell recommends
putting that data in character string literals rather than in tags. Literals are protected at the same
level as the logic in locked routines and Add-On Instructions.

Follow these steps to lock or encrypt a component.

1. Apply License Source Protection to the component.

2. In the Source Protection Configuration dialog box, select the protected


component.

34 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Configuring source protection in the Logix Designer application Chapter 2

3. Click Lock.

4. To unlock the component, select it and click Unlock.

Tip: When a component is License-Protected, lock and unlock it by selecting it in the Controller Organizer, right-
clicking, and selecting Lock or Unlock. Use the Security toolbar to lock and unlock a component or to lock all
License-Protected components at once.

Lock all License-Protected Lock a routine or Add-On Instruction that is protected by License Source
Protection and is shared outside a trust boundary, such as sent using email or to an
content
end customer. Do not distribute projects that contain unlocked components
because they are in a less secure state.

To lock all license-protected components in a project at once, use the Lock All
button on the Security toolbar.

To lock all components in a project:

1. Apply License Source Protection to the components to protect.

2. On the Security toolbar, click the Lock All button. This button is
disabled when there are no components to lock.

Or on the main menu, select Tools > Security > Lock all unlocked
content.

Tip: If an error prevents a component from locking, an error message appears. The Logix Designer
application locks other eligible components without error.

Add an LV instruction to To monitor license status and verify the license is not expired or removed, insert a
monitor license status License Validation (LV) instruction in a Ladder diagram. The LV instruction
checks that a non-expired license associated with a routine or an Add-On
Instruction is present in the controller. Insert additional logic in the routine to act
on the license status.

Share License privileges with Adjust network settings to provide additional privileges to users on the network
or to use License Source Protection when using a remote desktop connection.
other users on your network
When sharing license privileges with users on the network consider:

• Configure the network to allow communication between the devices that


need to share license privileges. Set TCP and UDP ports 22350 to open on
the computer that provides privileges.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 35


Chapter 2 Configuring source protection in the Logix Designer application

• Enable the license to share for network use. Use the License Portal to
configure licenses and optionally enable them for network use.
• The computers that receive permissions from the remote workstation must
install a CmStick that contains the same license with Use permission. Plug
the CmStick into a USB port locally on the computers.

You can share license privileges with other users and provide license privileges to
users of remote desktop.

Provide License privileges to other Follow these steps to provide license privileges to users on your network.
users
1. To open the CodeMeter Control Center™ application, on the computer
that is going to provide additional privileges, navigate to the C:\Program
Files (x86)\CodeMeter\Runtime\bin folder and run the [Link]
file.

Important: Your computer should have a CmStick installed that contains a license with all the privileges that
you want to share. The CmStick should be plugged into a USB port on your computer.

2. Click WebAdmin to open the CodeMeter WebAdmin window in your


default web browser.

36 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Configuring source protection in the Logix Designer application Chapter 2

3. Click Configuration > Server, select Run network server, and click Apply.

4. Click Configuration > Access Control and select Advanced.

5. Under Default action, select Deny and click Apply.

6. Under Access Control Mode, select Basic.

7. Click Add and enter the list of users (user names, IP addresses, user groups,
or subnets) who can access your shared license. Click Apply.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 37


Chapter 2 Configuring source protection in the Logix Designer application

8. On the CodeMeter Control Center, navigate to the Process tab to stop


and restart CodeMeter.

9. On the computers that need to receive the shared license privileges, open
the CodeMeter Control Center application.

Important: A CmStick containing a license with Use permission must be present


locally on any USB port on the computer that receives shared permissions.
Use permission cannot be obtained from a shared license.

10. Click WebAdmin to open the CodeMeter WebAdmin window.

11. On the Configuration tab, in the server list, add the name or IP address of
the computer that you configured as a license server.

12. Restart CodeMeter.

38 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Configuring source protection in the Logix Designer application Chapter 2

Tip: When the Server Search List is blank in the CodeMeter WebAdmin tool, CodeMeter searches all servers
that it finds on your subnet. When a user has a license that is also on a license server, the user's permissions
might be upgraded to match the license on the server. To prevent accidental granting of privileges and to
prevent CodeMeter from searching unnecessarily, add [Link] (the localhost IP address) to the Server
Search List.

Provide license privileges for remote


Follow these steps to provide license privileges for remote desktop users on your
desktop users
network.

1. On the remote desktop client computer, open the CodeMeter Control


Center application. To open the application, navigate to the C:\Program
Files (x86)\CodeMeter\Runtime\bin folder, and run the [Link]
file.

Important: Your computer should have a CmStick installed that contains a license with all
the privileges that you want to use remotely. The CmStick should be plugged
into a USB port on your computer.

2. Click WebAdmin to open the CodeMeter WebAdmin window in your


default web browser.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 39


Chapter 2 Configuring source protection in the Logix Designer application

3. Click Configuration > Server, select Run network server, and click Apply.

4. Click Configuration > Access Control and select Advanced.

5. Under Default action, select Deny and click Apply.

6. Under Access Control Mode, select Basic.

7. Click Add and enter the list of users (user names, IP addresses, user groups,
or subnets) who can access your shared license. Click Apply.

40 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Configuring source protection in the Logix Designer application Chapter 2

8. On the CodeMeter Control Center, navigate to the Process tab to stop


and restart CodeMeter.

9. Log onto the remote computer with remote desktop.

10. On the remote computer, open the CodeMeter Control Center


application.

Important: A CmStick containing a corresponding license with Use permission must be present locally on any
USB port on the remote desktop server. Use permission cannot be obtained from a remote
computer.

11. On the Configuration tab, in the server list, add the name or IP address of
the computer that contains the needed permissions.

12. Navigate to the Process tab on the CodeMeter Control Center to stop
and then restart CodeMeter.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 41


Chapter 2 Configuring source protection in the Logix Designer application

Tip: When the Server Search List is blank in the CodeMeter WebAdmin tool, CodeMeter searches all servers
that it finds on your subnet. When a user has a license that is also on a license server, the user's permissions
might be upgraded to match the license on the server. To prevent accidental granting of privileges and to
prevent CodeMeter from searching unnecessarily, add [Link] (the localhost IP address) to the Server
Search List.

42 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Appendix A

Securing a ControlLogix controller with the Logix


CPU Security Tool

You can secure a controller with the Logix CPU Security Tool. The Logix CPU
Security Tool is automatically installed when you install Logix Designer version
17, 18, or 19. The tool is installed under the Logix Designer menu bar on the
Tools menu.

Important: The Logix CPU Security Tool is supported only in Logix Designer application versions 17, 18, and 19. It is
not supported in versions 20 and later.

1. Click the Start button, then click All Programs, then click Rockwell
Software, then click RSLogix 5000, and then click Logix CPU Security
Tool.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 43


Appendix A Securing a ControlLogix controller with the Logix CPU Security Tool

2. In the Logix CPU Security dialog box, click the RSWho button to specify
a path to the controller.

3. Select the controller that you want to secure and click OK.

The Logix CPU Security Tool displays the current status of the controller.
Notice that the controller in the following image is currently unsecured and
there is no password set in the controller.

44 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Securing a ControlLogix controller with the Logix CPU Security Tool Appendix A

4. Click Change Password.

5. In the Change Password dialog box, in the New Password box type a
password, and then in the Confirm New Password box, retype the
password. Click OK.

The Password Status for the controller changes to indicate a Password


exists in the controller, but the controller is not secured yet.

6. Click Secure Controller.

7. In the Secure Controller dialog box, in the Password box, type the
password for the controller and then click Secure.

8. If the controller has nonvolatile memory installed, you can select the Save
to Nonvolatile Memory after controller is secured check box to save the
security state of the controller to nonvolatile memory. Refer to the Logix

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 45


Appendix A Securing a ControlLogix controller with the Logix CPU Security Tool

Designer application help for additional information on using nonvolatile


memory.

The Controller Security Status for the controller changes to indicate that
it is secured.

Accessing a secured When you try to access a controller that has been secured with the Logix 5000
controller CPU Security Tool and you do not have a local copy of the project file on your
computer, the application prompts you to select the proper file.

To access a secured controller, do the following.

1. On the menu bar, click Communications, and then click Who Active.

46 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Securing a ControlLogix controller with the Logix CPU Security Tool Appendix A

2. In the Who Active dialog box, click the secured controller and click Go
Online.

If you do not have a local copy of the project file on your computer, the
application prompts you to select a file.

3. Click Select file to find the project file.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 47


Appendix A Securing a ControlLogix controller with the Logix CPU Security Tool

4. In the Enter New or Select Existing File dialog box, click the project file
and then click Select.

5. Click Yes to create and upload the project.

An unspecified communications dialog box appears indicating that the


application is now offline.

6. Click OK to continue.

If the project file already exists on your system, an error message appears
that indicates that the controller is secured and you cannot go online.

Removing security from a To remove security from a controller, do the following.


controller with the CPU
Security Tool

48 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Securing a ControlLogix controller with the Logix CPU Security Tool Appendix A

1. Start the Logix CPU Security Tool. Click the Start button, then click All
Programs, then click Rockwell Software, and then click Logix CPU
Security Tool.

2. In the Logix CPU Security dialog box, click the RSWho button to specify
a path to the controller.

3. In the Browse for controllers to Secure/Unsecure dialog box, click the


controller that you want to be unsecured and then click OK.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 49


Appendix A Securing a ControlLogix controller with the Logix CPU Security Tool

4. In the Logix CPU Security - project_name dialog box, click Unsecure


Controller.

5. In the Unsecure Controller dialog box, in the Password box, type the
password for the controller and then click Unsecure.

The controller is now unsecured, but the controller still recognizes the
password.

6. Select Exit.

7. Click Yes. A message appears.

Click Yes to save the change. You can now go online with the controller.

Removing a password Follow these steps to remove a password.

50 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Securing a ControlLogix controller with the Logix CPU Security Tool Appendix A

1. In the Logix CPU Security - DayOfWeek dialog box, click Change


Password.

2. In the Change Password dialog box, remove the '****' empty string and
click OK.

The controller status is now UNSECURED.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 51


Appendix A Securing a ControlLogix controller with the Logix CPU Security Tool

52 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Appendix B

Product policies and securable actions supported


by FactoryTalk Security

When used with the Logix Designer application, FactoryTalk Security supports
Product Policies and Securable Actions. You configure these FactoryTalk Security
settings in the FactoryTalk Administration Console.

Product Policies are not tied to a specific project, and may include the following.

• Securing the controller


• Creating a new project (either through the New Controller dialog box, or
through the Translator Tool utility)
• Updating your firmware

Securable Actions let you perform specific tasks on a specific project or group of
projects, and may include the following.

• Viewing a project
• Going online
• Creating tags
• Creating modules

In a safety controller project, you can specify additional protection to safety


components. For example, to create a safety program, you need to have access
granted for both of the following securable actions.

• Safety: Modify Component


• Program: Create

Keep the following considerations in mind when configuring security settings for
the Logix Designer application.

• Security settings are obtained from the FactoryTalk Network Directory.


• RSSecurity Emulator is not used by the Logix Designer application, but may
be required by other software.
• FactoryTalk Local directory is not supported.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 53


Appendix B Product policies and securable actions supported by FactoryTalk Security

FactoryTalk Services Platform version 2.50 (SR5) or later supports associating the
project with a specific FactoryTalk Directory.

Product policies and Product Policies and Securable Actions

securable actions The Product Policies and Securable Actions listed here are configured in the
Network Directory using the FactoryTalk Administration Console. For details see
the FactoryTalk Security System Configuration Guide. That document is available
in the Rockwell Automation Literature Library. Click the following link to open
the Literature Library in a browser window:

Rockwell Automation Literature Library

The following table lists FactoryTalk Security Product Policies.

Grant access to these actions To allow a user to


Controller: Secure Secure a project or controller.
Firmware: Update Update controller firmware.
Tip: If the project is secured, the Securable Action (Firmware:Update) is
also required to perform firmware updates. Firmware updates can be
initiated within the Logix Designer application WhoActive dialog box if
a project is open but not when the controller is online.
Print: Modify Options Modify print options.
Project: New Create a new project, import a project or translate PLC-5/SLC.
Toolbar: Configure Move, resize, hide or show toolbars.
Workstation: Modify Options Modify workstation options.

The following table lists FactoryTalk Security Securable Actions.

Grant access to these actions To allow a user to


Add-On Instruction: Create Create a new Add-On Instruction.
Add-On Instruction: Delete Delete an Add-On Instruction.
Add-On lnstruction: Export Export an Add-On Instruction.
Export an Add-On Instruction in clear text.
Tip: Users must also be granted the Add-On Instruction: Export permission to export an
AOI, or granted the Project: Export permission to export the entire project.
Add-On lnstruction: Export Unencoded
Tip: To export in clear text, you must clear the Encode Protected Content checkbox on the
Export dialog box. You must also have the required source key or license if the component is
protected with Source Protection.
Edit Add-On Instruction properties, tags, logic or whether a user can configure source
Add-On Instruction: Modify
protection.
Add-On Instruction: View Logic View the internal information in an Add-On Instruction.
Create new tag-based alarms.
Alarm: Create When a user who is denied the Alarm: Create permission imports a project or a project
component that requires new alarms to complete the import, those alarms are created.

54 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Product policies and securable actions supported by FactoryTalk Security Appendix B

Delete tag-based alarms.


Alarm: Delete When a user who is granted the Tag: Delete permission deletes a tag that has alarms
associated with it, those alarms are deleted.

Modify the properties of a tag-based alarm.


Alarm: Modify Properties Tip: When a user who is denied the Alarm: Modify Properties permission imports a project
or a project component that requires changes to existing tag-based alarms, the import fails.

Enable or disable a tag-based alarm using the Use and evaluate alarm check box on the
Alarm: Use and Evaluate
Alarm Properties dialog box - Advanced tab.
Alarm: Clear Alarm Log Clear the contents of the alarm log from the controller.
Respond to a tag-based alarm using the Acknowledge, Shelve, Disable, and Reset buttons
Alarm: Direct Commands
on the Alarm Properties dialog box - Status tab.
Create new alarm definitions.
Alarm Definition: Create An alarm definition is associated with an Add-On Instruction (AOI) or a defined data type.
When a tag is created using a data type or an AOI that has alarm definitions, alarms are
created automatically based on the alarm definitions.

Delete alarm definitions.


When a user who is granted the Alarm Definition: Delete permission deletes an alarm
definition for a data type or an Add-On Instruction (AOI), the corresponding alarms based on
the alarm definition are deleted, even if the user has not been granted the Alarm: Delete
Alarm Definition: Delete
permission.
When a user deletes a data type or an AOI, all alarm definitions associated with that data type
or AOI are deleted, even if the user has not been granted the Alarm Definition: Delete
permission.

Modify the properties of a tag-based alarm.


Alarm Definition: Modify Properties When a user who is denied the Alarm Definition: Modify Properties permission imports a
project or a project component that requires changes to existing tag-based alarm definitions,
the import fails.

Component: Modify Permission Set Change which permission set is associated with a component.
Controller: Clear Faults Edit the fault log, including clearing faults.
Controller: Lock/Unlock Lock or unlock the controller for online edits.
Controller: Modify Mode Change controller modes.
Controller: Modify Properties Edit controller properties.
Controller: Modify Revision Convert the .acd file to a higher revision.
Controller: Modify Type Change controller types.
If a user is granted Controller: Modify Revision privilege, but is denied Controller: Modify
Type, in most situations the user will be unable to change the type of controller. However,
during database conversion, it may be necessary to change the controller type because the old
controller type is obsolete in the target revision. In this case, these users are allowed to
change the controller type during conversion.

Controller: Unsecure Unsecure a secured controller.


Data Log: Create Create a data log.
Data Log: Modify Modify a data log.
Data Log: Delete Delete a data log.
Data Log: Enable/Disable Enable or disable data logging.
Data Log: Read Log Data Value Read a data log value.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 55


Appendix B Product policies and securable actions supported by FactoryTalk Security

Data Log: Clear Log Data Value Clear a data log value.
Use the Logix Designer application to update controller firmware.
The Product Policy (Firmware:Update) is also required to perform firmware updates. Firmware
Firmware: Update
updates can be initiated within the Logix Designer application WhoActive dialog box if a
project is open, but not when the controller is online.
Associate project documentation with a language, set default language, add or delete a
Language: Modify Properties
language.
Language: Switch Language Select a different language for product documentation.
Module: Create Create modules in the Controller Organizer.
Module: Create and Safety: Modify Component Create safety I/O configuration.
Module: Delete Delete modules in the Controller Organizer.
Module: Delete and Safety: Modify Component Delete safety I/O configuration.
Module: Maintenance High Perform high impact operations such as module reset and calibration.
Module: Maintenance Low Perform low impact operations such as resetting electronic fuses.
Module: Modify Properties Edit module properties.
Module: Modify Properties and Safety: Modify Modify safety I/O configuration.
Component
View module properties.
Users with this permission can open device profiles and, when online with the controller, use
Module: View Properties the profile to directly interact with modules and carry out actions such as changing IP
addresses.
When this permission is denied, users cannot open device profiles.
Motion: Command Axis Perform axis direct commands.
Motion: Modify Configuration Modify axis, coordinate system, or motion group properties.
Nonvolatile Memory: Load Load from non-volatile memory.
Nonvolatile Memory: Store Store to non-volatile memory.
Phase: Create Create equipment phases.
Phase: Delete Delete equipment phases.
Phase: Manual Control Manually control equipment phases.
Phase: Modify Properties Edit equipment phases.
PLC/SLC: Modify Tag Mappings Map PLC or SLC messages.
Plug-In: Display Display plug-ins.
Print: Report Print reports.
Program: Create Create programs.
Program: Create and Safety: Modify Create a safety program.
Component
Program: Delete Delete programs.
Program: Delete and Safety: Modify Delete a safety program.
Component
Program: Modify Properties Edit program properties.
Program: Modify Properties and Safety: Modify properties of a safety program.
Modify Component1
Program: Modify Properties and Safety: Change class property of a standard program to safety.
Modify Component
Project: Compact Compact a project file.

56 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Product policies and securable actions supported by FactoryTalk Security Appendix B

Project: Download Download a project to a controller.


Project: Export Save a project in .L5K or .L5X format.
Project: Go Online Go online with a project.
Project: Modify Path Set, clear, or modify the controller path associated with a given project.
Project: Open Open a (read-only) version of the project.
If users do not have the ability to open and view the project, they do not have the ability to do
anything else with it.
Project: Save Save a project.
Project: Save As Save a project to a new .acd file.
Project: Upload Upload a project from a controller.
Routine: Create Create a routine.
Routine: Create and Safety: Modify Create a safety routine.
Component
Routine: Delete Delete a routine.
Routine: Delete and Safety: Modify Delete a safety routine.
Component
Routine: Export Export a routine.
Routine: Export Unencoded Export a routine in clear text.
Routine: Manual Control Manually control routine logic.
Routine: Modify Logic Edit routine logic.
Routine: Modify Logic and Safety: Modify Edit safety routine logic.
Component
Routine: Modify Properties Edit routine properties, configure routine source protection.
Routine: Modify Properties and Safety: Modify Edit safety routine properties.
Component
Routine: View Logic View the logic in a routine.
Safety: Generate/Delete Signature Generate or delete a Safety Signature.
Safety: Lock/Unlock Lock or unlock edits on safety application.
Safety: Lock/Unlock Modify safety lock or unlock passwords.
Safety: Modify Component Create, delete, or modify safety components.
Tip: The standard component privileges are required in addition to this privilege. For
example, to create safety tags, the Tag: Create privilege is required in addition to the
Safety: Modify Components privilege.
Safety: Modify Properties Modify the controller's safety configuration.
Safety: Modify Tag Mappings Create safety tag mapping.
Safety: Modify Tag Mappings Delete safety tag mapping.
Safety: Modify Tag Mappings Modify safety tags mapped to standard tags.
Sequence: Create Create an equipment sequence.
Sequence: Delete Delete an equipment sequence.
Sequence: Manual Control Take manual control of an equipment sequence.
Sequence: Modify Properties Modify the properties of an equipment sequence.
Tag: Create Create tags.
Tag: Create and Safety: Modify Component Create a safety tag.
Tag: Delete Delete tags.

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 57


Appendix B Product policies and securable actions supported by FactoryTalk Security

Tag: Delete and Safety: Modify Component Delete a safety tag.


Tag: Delete, Safety: Modify Tag Mappings, and Delete standard tag that is mapped to a safety tag.
Safety: Modify
Tag: Force Force tags and enable or disable existing forces.
Force safety tags.
Tag: Force and Safety: Modify Component

Tag: Modify Constant Property Change Constant property of a tag.

Tag: Modify Constant Tag Values Change values of a Constant Tag.

Tag: Modify Properties Edit tag properties.


Tag: Modify Properties and Safety: Modify Edit safety tag properties.
Component
Tag: Modify Properties and Safety: Modify Change class property of a standard tag to safety.
Component
Tag: Modify Properties and Safety: Modify Tag
Modify safety or standard tag properties of a tag contained in a safety mapping.
Mappings
Tag: Modify Values Change tag values.
Tag: Modify Values and Safety: Modify Change safety tag values.
Component
Task: Create Create tasks.
Task: Delete Delete tasks.
Task: Modify Properties Edit task properties, including program scheduling.
Task: Modify Properties and Safety: Modify Modify safety task properties.
Component2
Trend: Create Create trends.
Trend: Delete Delete trends.
Trend: Modify Properties Modify trend properties.
Trend: Run Run trends.
User Defined Type: Create Create user-defined data types or string types.
User Defined Type: Delete Delete user-defined data types or string types.
User Defined Type: Modify Edit user-defined data types or string types.

1
A safety program’s max scan time can be reset, regardless of the protection.
2
The safety task max scan time and max/min interval scan timers can be reset,
regardless of the protection.

58 Rockwell Automation Publication 1756-PM016N-EN-P - November 2018


Index
source protect files 23
A protect
access project 15
locked controller 48
Add-On Instructions
R
source protection 23
remove
password 52
C routine
CodeMeter 36 source protection 23
controller
accessing locked files 48
S
remove security 51
security
FactoryTalk 11
D [Link]
delete file 22
source key file 28 source key
disable delete file 28
source protection 19 source protection
disable routine 19
install 18
F types and overview 12
FactoryTalk
security 11
file
[Link] 22
source protection 23

I
install
source protection 18

L
License-based source protection 32
lock a License-protected component 35
LV instruction 36

P
password
removal 52
project
protect 15
Rockwell Automation Publication 1756-PM016N-EN-P - November 2018 59
Rockwell Automation support
Rockwell Automation provides technical information on the web to assist you in using its products. At
[Link] you can find technical and application notes, sample code, and links to software service packs. You
can also visit our Support Center at [Link] for software updates, support chats and forums, technical
information, FAQs, and to sign up for product notification updates.

In addition, we offer multiple support programs for installation, configuration, and troubleshooting. For more information, contact your local
distributor or Rockwell Automation representative, or visit [Link] .

Installation assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact
Customer Support for initial help in getting your product up and running.

United States or Canada 1.440.646.3434


Outside United States or Canada Use the Worldwide Locator available at [Link] , or contact your local Rockwell
Automation representative.

New product satisfaction return


Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if
your product is not functioning and needs to be returned, follow these procedures.

United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to
your distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.

Documentation feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the
feedback form, publication RA-DU002 [Link]

Rockwell Automation Publication 1756-PM016N-EN-P - November 2018

Supersedes Publication 1756-PM016M-EN-P - February 2018 Copyright © 2018 Rockwell Automation Technologies, Inc. All Rights Reserved. Printed in the U.S.A.

You might also like