Universal Process Indicator Guide
Universal Process Indicator Guide
High Alarm Ki
(High) PV
Alarm SP
(differential High)
AL SP AL SP + Deviation
Alarm
1 s to Output T1
CUSTOMIZED LINEARIZATION.
Pulse 0
6500 s Alarm Event
Three types of signals can be user-customized to fit particular
1 s to 1 s to
Alarm
Output T1 T2 T1 linearization profiles. This means that the operator can configure the
Oscillator instrument to read non-standard crescent non-linear signals with high
6500 s 6500 s Alarm Event
accuracy.
Table 3 - Timer Alarm Functions
CONFIGURATION PROTECTION
As safety measure, parameter changes can be prevented by a
combination of keys, valid for each cycle. The protected parameters
Figure 6 – Voltage input Figure 7 – Current input
can be inspected but not modified.
To protect a cycle press the and keys simultaneously for 3
seconds while in the cycle. To unlock the cycle, press and
for 3 seconds.
The display will briefly flash confirming that the cycle was
successfully locked or unlocked.
Figure 8–Connection for 0-5 V or For further protection, the keypad unlock operation can be disabled
Figure 9 – Digital Input
0-10 V
by changing the position of an internal strap inside the indicator:
Figure 10 shows the connections for a 4-20 mA transmitter powered When PROT is OFF, the user is allowed to lock and unlock the
by the 24 V power supply of the indicator. cycles using the keypad as explained above. If PROT is ON, the
cycles lock/unlock operation is disabled.
• Analog output
The N1500 can deliver either 0-20 mA or 4-20 mA analog output,
depending on how the instrument is configured. The output is
available at terminals 29 and 30.
PROGRAMMING THE INDICATOR filtr Input Digital Filter - Adjustable from 0 to 20, this is used
to reduce instability of the measured value. 0 means the
filter is off and 20 means maximum filtering. The higher the
WORK CYCLE filter value, the slower the response.
This is the first cycle. At power up the indicator will display the Process ofset Display Offset - This a value which is added to the PV to
Variable (PV). The alarm triggering points are also displayed at this offset any measurement deviation or sensor error. The
cycle (alarm Setpoints). To advance in this cycle simply press . offset is shown in the programmed engineering unit. For °F
measurements the null reference is at 32 °F.
TELA PROMPT PARAMETER DESCRIPTION
bavd Baud Rate - Serial digital communication speed in bps.
[Link].8. PV Measurement. Shows the measured variable. For Programmable: 1200, 2400, 4800, 9600, 19200, 38400
Pt100 or thermocouples the display will show the absolute and 57600 bps.
temperature value.
Adres Communication Address - A number that identifies the
For 4-20 mA, 0-50 mV, 0-5 V and 0-10 mV inputs the instrument in a multidrop network.
[Link]”
display shows the values defined in the “in. oL and
[Link]”
“in. iL parameters. CONFIGURATION CYCLE
With the hold function programmed the display shows the
koLd”.
koLd
frozen variable and alternates with the message “koLd [Link] Input Type - Selects the input signal or sensor type to be
connected to the PV terminals. Refer to Table 1 for options.
Likewise, with Peak Hold function programmed the high
Changing the input type causes all other parameters
[Link]”
limit is displayed with the “P. oLd prompt alternately.
related to PV and alarms to be changed as well, therefore,
Should any fault situation occur the indicator will display an this parameter shall be the first to be set.
error message which can be identified at item 10 of this
manual. [Link] Decimal Point Position - Defines the decimal point
position in the displayed value. It is displayed when linear
[Link] Differential Alarm Reference Value - This prompt is input types 0-50mV, 4-20 mA, 0-5 V or 0-10 V are selected
shown only when there is an alarm programmed with [Link]”
at the “in. YP prompt.
differential function. This value is used as a reference for
differential alarms triggering. Vnit Temperature Unit - Selects °C or °F indication. This prompt
is not shown for input types 0-50mV, 4-20 mA, 0-5 V or 0-10
Sp.al1 Alarms Set Points 1, 2, 3 and 4 - Defines the operation [Link]”
V are selected at the “in. YP prompt.
point of each alarm programmed with “Lo Lo”
Lo or “kiki”
ki
Sp.al2 functions. [Link] Square Root - This prompt is only shown when input types
[Link]”
0-50 mV, 4-20mA and 0-5 V are selected at the “in. YP
Sp.al3 When an alarm is programmed with a differential function, prompt.
Sp.al4 the alarm setpoint value represents the deviation value of
YES”
YES and the square root will be applied to the
Set “YES
the alarm relative to the reference [Link].
ef
[Link]”
measured value within the limits programmed in “in. oL
[Link]”.
and “in. iL
ALARM CYCLE
[Link])
The display will show the low limit (in. oL value should
fV.al1 Alarm Function - Defines functions for the alarms 1, 2, 3 the input signal be below 1 % of the range.
and 4.
fV.al2 Scale - Defines the indication range for linear inputs (0-50
oFF : Alarm off mV, -20 mA, 0-5 V and 0-10 V).
fV.al3 iErr : Broken or Shorted Sensor
0 Configurable indication from – 31000 to + 31000.
fV.al4 Lo : Low value
ki : High value 1 Configurable indication from 0 to + 60000.
[Link] : Differential low Scale
2 Configurable indication from 0 to +120000. Only even
[Link] : Differential high values will be displayed (resolution is not improved).
[Link] : Differential outside the range
[Link] : Differential within range The selected scale affects values of PV, alarm setpoints
and Offset.
Ky.al1 Alarm Hysteresis
Ky.al2 [Link] Input Low Limit - Sets the low limit for input type 0-50 mV,
This is the difference from the measured value to the point 4-20 mA, 0-5 V or 0-10 V. When the PV Retransmission
Ky.al3 where the alarm is turned ON and OFF. is used this limit defines the corresponding 4 mA (or 0 mA)
ky.al4 in relation to the input value.
Bl.al1 Alarm Blocking [Link] Input High Limit - Sets the high limit for input type 0-50
Bl.al2 Should any alarm condition occur, the alarms can be
mV, 4-20 mA, 0-5 V or 0-10 V. When the PV
Bl.al3 individually disabled when energizing the indicator.
Retransmission is used this limit defines the
bl.al4 corresponding 20mA in relation to the input value.
Low Limit for Analog Retransmission – Defines the PV
Al1t1 Alarm Timer
[Link] value that results in a 4 mA (or 0 mA) analog output current.
Al1t2 The user can set delayed, momentary or sequential alarms
Al2t1 by configuring times T1 and T2 according to Table 3.
High Limit for Analog Retransmission – Defines the PV
Al2t2 [Link] value that results in a 20mA analog output current.
Al3t1 To disable this function just set zero for T1 and T2.
[Link] Analog Output Type - Selects the analog output type to
Al3t2 either 0- 20 mA or 4-20 mA.
Al4t1
Al4t2 [Link] 4-20 mA Output behavior in case of failures – Defines the
output as 4-20 mA when there is an error in the indication.
[Link] KEY FUNCTION – Defines functions for the CUSTOMIZED LINEARIZATION CYCLE
key. The available options are:
oFF - Key not used. Inp.01 Defines the initial and end analog input values for each
custom segment line. The values must be entered in the
Hold - Hold PV Inp.30 input signal unit:
RSt - Resets Peak and Valley (MAX and values)
0-50 mV, 4-20 mA or 0-5 V. For 0-10 V select 0-5 V.
[Link] - Peak Hold
Ovt.01 Defines the corresponding indication that each custom
[Link] Digital Input Function – Defines the function for the digital segment is to show. Values are expressed in the desired
input. Refer to item 5.2. Options are: ovt.30 indication unit (within the Indication Lower and Upper
oFF - kold - rESEt - PkoLd Limits).
CALIBRATION CYCLE Different messages other than the ones above should be reported to
All input and output types are factory calibrated. This cycle the manufacturer. Please inform the serial number if this should
should only be accessed by experienced personnel. If this cycle occur. The serial number can be viewed at the display by pressing
is accidentally accessed do not touch the or keys, just the key for about 3 seconds.
press the key a few times to go back to the Work Cycle. The software version of the instrument can be viewed at the time the
unit is powered.
[Link]( Input Low Calibration - Sets the Process Variable low
calibration (offset). Several key strokes at or When not properly configured, the instrument may show false error
might be necessary to increment one digit. messages, particularly those related to the type of input selected.
[Link]( Input Hi Calibration - Sets the Process Variable span
calibration (gain). SPECIAL RECOMMENDATIONS
[Link]( Analog Output Low Calibration - Sets the analog current Should the indicator be repaired, some special handling care should be
output low calibration (offset). taken. The device must be withdrawn from the case and immediately
[Link]( Analog Output Span Calibration - Sets the analog placed in an anti-static wrap; protected from heat and humidity.
current output high calibration (span) of the analog output
(20 mA). INPUT CALIBRATION
(J lo
lo Cold Junction Calibration - Allows the user to calibrate All inputs are factory calibrated and recalibration should only be done
the cold junction temperature (at the indicator input
by qualified personnel. If you are not familiar with these procedures
terminals) directly in degrees.
do not attempt to calibrate this instrument.
[Link] Hardware Type - This parameter adapts the firmware to
The calibration steps are:
the actual indicator hardware (optional features) and
should not be changed by the user. a) Select the input type to be calibrated.
2 Alarms ..........................................3 b) Set the desired upper and lower display limits.
2 Alarms and 4-20 mA................. 19 c) At the input terminals inject an electrical signal corresponding to
2 Alarms and RS485.................... 35 a known indication value a little higher than the lower display
limit.
2 Alarms, 4-20 mA and RS485.... 51
4 Alarms ....................................... 15
d) Select the inLC prompt. Through the and keys adjust
PV so that it matches the injected signal.
4 Alarmes and 4-20 mA............... 31
e) Inject a signal that corresponds to a value a little lower than the
4 Alarmes and RS485 ................. 47 upper limit of the display.
4 Alarmes, 4-20 mA and RS485........... 63
f) Select the inkC prompt. Through the and keys adjust
PV so that it matches the injected signal.
PROBLEMS WITH THE INDICATOR g) Repeat steps c) to f) until no further adjustment is necessary.
Connection errors or improper configuration will result in
malfunctioning of the indicator. Carefully revise all cable connections Note: When verifications are proceeded, note if the Pt100
and programming parameters before operating the unit. excitation/activation current the calibrator requires is compliant to the
Some error messages will help the user identify possible problems. Pt100 excitation current used in this instrument: 0.750 mA.
MESSAGE POSSIBLE PROBLEM
VVVVV Measured value is above the value allowed for the
selected sensor or above the configured input signal limit.
nnnnn Measured value is below the value allowed for the
selected sensor or below the configured input signal limit.
----- Open input. No sensor is connected or the sensor is
broken.
Err 1 Pt100 cable resistance is too high or the sensor is
badly connected.
NOVUS ELETRONICS LTD. – WEBSITE: [Link] 6/7
Indicator N1500
• Protocol: MODBUS (RTU) ANALOG OUTPUT: ..................................... 0-20 mA or 4-20 mA, 550 Ω max.
........................................................................................... 4000 levels, Isolated
Dois parâmetros devem ser configurados para utilização da interface
RELAY OUTPUT:........ALM1, ALM2: SPDT 3 A / 240 Vac (3 A / 30 Vdc Res.)
de comunicação serial: o Baud-Rate de Comunicação (parâmetro
..........................ALM3, ALM4: SPST-NO: 1.5 A / 250 Vac (3 A / 30 Vdc Res.)
bavd)
bavd e o Endereço de Comunicação (parâmetro adres).
adres EMC : ........................................... EN 61326-1:1997 and EN 61326-1/A1:1998
SAFETY:EN61010-1:1993 and EN61010-1/A2:1995
RS485 INTERFACE: ELECTRICAL CONNECTION
START UP 3 SECONDS AFTER POWER UP.
The RS-485 signals are:
D1 = D: Bidirectional data line
ORDERING INFORMATION:
D0 = D: Inverted bidirectional data line
C = GND: Optional connection. Improves communication performance N1500 - 4R - RT - 485 - 24V
for long cable runs. A B C D E
WARRANTY
This product is covered by a 12-month warranty provided the purchaser
presents the sales receipt and the following conditions are met:
• Products are covered for one year from the original date of
purchase. Please retain the dated sales receipt as evidence of
the date of purchase. You will need it for any warranty service
• Within this period, warranty against defects in material and
workmanship under normal use is free of charge.
• For repair, send the product and the sales receipt to our address.
Expenses and transportation risks are under the purchaser’s
responsibility.
• This warranty does not cover any damage due to accident,
misuse, abuse, or negligence.
1
0019 alref Alarme Reference. 0047 Al1t2 Alarm 1 Time 2 of timer (in seconds)
Range: from inlol to inkil Range: same as al1t1.
0020 ovtty Retransmision type of PV. Range: 0 to 1 0048 Al2t1 Alarm 2 Time 1 of timer (in seconds)
0→ 4 a 20mA retransmision; 1→0 a 20mA retransmision Range: same as al1t1.
0021 Spal1 Alarm 1 Preset. Range: the minimum value is ininlol 0049 Al2t2 Alarm 2 Time 2 of timer (in seconds)
Or seted for not differential alarm or (inlol - inkil ) for Range: same as al1t1.
differential alarm; The maximum value is in inkil seted
Dfal1 0050 Al3t1 Alarm 3 Time 1 of timer (in seconds)
for not differential alarm or (inkil - inlol ) if differential
alarm. Range: same as al1t1.
0022 Alarm 2 Preset 0051 Al3t2 Alarm 3 Time 2 of timer (in seconds)
Spal2
Range: same as al1t1.
Or Range: same as spal1 or dfal1.
0052 Al4t1 Alarm 4 Time 1 of timer (in seconds)
Dfal2
Range: same as al1t1.
0023 Spal3 Alarme 3 Preset
0053 Al4t2 Alarm 4 Time 2 of timer (in seconds)
Or Range: same as spal1 or dfal1.
Range: same as al1t1.
Dfal3 - Reserved
0024 Spal4 Alarme 4 Preset
- Reserved.
or Range: same as spal1 or dfal1.
- Reserved.
dfal4 - Reserved.
0025 Fval1 Alarm 1 Function. Range: 0 to 6 - Reserved.
0→off; 1→ierr; 2→lo; 3→ki; - Reserved.
4→difl; 5→difk; 6→dif. - Reserved.
0026 Fval2 Alarm 2 Function 0061 Custom linearization first value.
Inp.01
Range: same as fval1.
0062 Inp.02 Custom linearization point #02
0027 Fval3 Alarm 3 Function
0063 Inp.03 Custom linearization point #03
Range: same as fval1.
0064 Inp.04 Custom linearization point #04
0028 Fval4 Alarm 4 Function
0065 Inp.05 Custom linearization point #05
Range: same as fval1.
0029 Alarm 1 power-up inhibit. Range: 0 a 1 0066 Inp.06 Custom linearization point #06
Blal1
0→não; 1→sim. 0067 Inp.07 Custom linearization point #07
0030 Blal2 Alarm 2 power-up inhibit 0068 Inp.08 Custom linearization point #08
Range: same as blal1. 0069 Inp.09 Custom linearization point #09
0031 Blal3 Alarm 3 power-up inhibit 0070 Inp.10 Custom linearization point #10
Range: same as blal1. 0071 Custom linearization point #11
Inp.11
0032 Blal4 Alarm 4 power-up inhibit
0072 Inp.12 Custom linearization point #12
Range: same as blal1.
0073 Inp.13 Custom linearization point #13
0033 Kyal1 Alarm 1 Hysteresis (engineering unit)
0074 Inp.14 Custom linearization point #14
Range: 0 to span do sensor
0075 Inp.15 Custom linearization point #15
0034 Kyal2 Alarm 2 Hysteresis (engineering unit)
Range: same as kyal1. 0076 Inp.16 Custom linearization point #16
0035 Alarm 3 Hysteresis (engineering unit) 0077 Inp.17 Custom linearization point #17
Kyal3
Range: same as kyal1. 0078 Inp.18 Custom linearization point #18
0036 Kyal4 Alarm 4 Hysteresis (engineering unit) 0079 Inp.19 Custom linearization point #19
Range: same as kyal1. 0080 Inp.20 Custom linearization point #20
0037 Intyp Input sensor type 0081 Value to be displayed in point #01 of custom linearization
Ovt.01
Range: 0 to 22. (in engineering units)
0→tc J; 1→tc K; 2→tc T; 3→tc E; 4→tc N; 5→tc R; 6 0082 Ovt.02 Value to be displayed in point #02 of custom linearization
→tc S; 7→tc B; 8→Pt100(degree decimal); 9→
0083 Ovt.03 Value to be displayed in point #03 of custom linearization
Pt100(degree unit); 10→Lin J; 11→Lin K; 12→Lin T; 13→
Lin E; 14→Lin N; 15→Lin R; 16→Lin S; 17→Lin B; 18→ 0084 Ovt.04 Value to be displayed in point #04 of custom linearization
Lin Pt100 degree decimal; 19→Lin Pt100; 20→0- 0085 Ovt.05 Value to be displayed in point #05 of custom linearization
50mV; 21→4-20mA; 22→0-5V
0086 Ovt.06 Value to be displayed in point #06 of custom linearization
0038 vnit Temperature Unit. Range: 0 to 1
0087 Ovt.07 Value to be displayed in point #07 of custom linearization
0→°C; 1→°F.
0088 Ovt.08 Value to be displayed in point #08 of custom linearization
0039 inlol Indication Low limit.
0089 Ovt.09 Value to be displayed in point #09 of custom linearization
Range: the minimum value depends of input type
configured in intyp and the maximum is in inkil 0090 Ovt.10 Value to be displayed in point #10 of custom linearization
seted. 0091 Value to be displayed in point #11 of custom linearization
Ovt.11
0040 inkil Indication High limit.
0092 Ovt.12 Value to be displayed in point #12 of custom linearization
Range: from inlol to the input maximum configured in
0093 Ovt.13 Value to be displayed in point #13 of custom linearization
intyp.
0041 Slave address 0094 Ovt.14 Value to be displayed in point #14 of custom linearization
adres
Range: 1 to 247 0095 Ovt.15 Value to be displayed in point #15 of custom linearization
0042 bavd Communication Baud Rate. Range: 0 to 4 0096 Ovt.16 Value to be displayed in point #16 of custom linearization
0→1200;1→2400;2→4800;3→9600; 4→19200 0097 Ovt.17 Value to be displayed in point #17 of custom linearization
0043 Serial Serial Number (High Display) 0098 Ovt.18 Value to be displayed in point #18 of custom linearization
Number High Range: 0 to 9999. Read only
0099 Ovt.19 Value to be displayed in point #19 of custom linearization
0044 Serial Serial Numbe (Low Display) 0100 Value to be displayed in point #20 of custom linearization
Number Low
Ovt.20
Range: 0 to 9999. Read only
0045 Key Remote action of pressed key. Range: 0 to 9
1→ ; 2→ ; 4→ ; 8→ ; 9→
BACK BACK
and .
0046 Alarm 1 Time 1 of timer. Range: 0 to 6500sec Digital Output States
Al1t1
See operation manual for details. Equivalent to Coil Status (reference 0XXXX). The digital output states are basically
the Boolean status of the respective digital outputs. The Read allows the actual
2
state of digital outputs, regardless of their function. If a write command sends a out-of-range value to a parameter, the indicator clamp
Writing to an output bit is only possible if the output has no function assigned to it the value to the parameter range limits, replying with a value which reflects these
(the output is configured to “OFF” in alarm cycle). limits (maximum or minimum value allowed for the parameter).
Broadcast read commands are ignored by the indicator; only broadcast write
commands are processed.
Coil Status Output Description
1 Alarm 1 Output status Error Description
Error Code
2 Alarm 2 Output status
81h Invalid command
3 Alarm 3 Output status
82h Invalid register number or out of range
4 Alarm 4 Output status
83h Invalid register quantity or out of range
Exceptions - Error conditions
The Modbus RTU protocol checks the CRC in the data blocks received.
Reception errors are detected by the CRC, causing the indicator to discard the
packet, not sending any reply to the master. After receiving an error-free packet, the V1.3X July 2002
indicator processes the packet and verifies whether the request is valid or not,
sending back an exception error code in case of an invalid request.