Apa itu VRV?
Variable Refrigerant Volume
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
WBT JP0082-1
1. Garis besar
Partisi Koneksi indoor Max 58 indoor units
(Untuk unit outdoor 36HP)
VRV Unit 0
Outdoor unit
Unit 1 Unit 0 Unit 1
Group Control Group Control
Exp. V Max. 16 Indoor units
Expansion
valve
1 sistem pipa refrigerant
Partisi dapat membagi ruang di mana saja
Karena setiap unit indoor memiliki katup
Ekspansi
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
WBT JP0082-1
Installasi kabel kontrol
Multiple systems
Indoor Indoor Indoor Indoor Master Slave
unit unit unit unit outdoor outdoor
unit unit
OUT-OUT
F1 F2
Master outdoor unit Slave outdoor unit
Remote Control
Indoor Indoor Indoor Indoor
unit unit unit unit
Centralized controller
OUT-OUT
F1 F2
Remote Control
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
F1WBT JP0082-1
F2
Installasi kabel listrik
1. Contoh pekerjaan kabel listrik untuk power suplai
Power suplai
1ϕ220V
Earth leakage
circuit breaker
Indoor unit Indoor unit Indoor unit Indoor unit
Power suplai
1. Melakukan pekerjaan kabel listrik sesuai
dengan regulasi negara.
3ϕ380V 2. Jangan berbagi installasi listrik dengan
perangkat lain
Earth leakage 3. Melakukan pekerjaan kabel ground.
circuit breaker
Outdoor unit
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
WBT JP0082-1
Kontrol Refrigeran Saat Cooling Operation
RXYQ6P~
Compressor
Accumulator
Oil
separator
sv
cv
Capi.
Evaporators
sv Condenser
Pressure
regulating valve
Indoor Exp.V
SC Heat Outdoor
exchanger Exp.V
Outdoor Heat sink PCB
Exp.V
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
WBT JP0082-1
Standard Operasi bagian (Pendinginan)
[Air-cooled R410A]
Suction gas temp.
Indoor unit Evaporator
Superheat temp.
3~16 ℃
Discharge gas temp.
Condenser
Outdoor unit
3~8 ℃ 70~115 ℃
Udara dingin Temp. Outdoor Udara panas
ruangan. air
Compressor
D
Low-temp. A Liquid temp.
low-pressure liquid
Expansion 36~52 ℃ C
B valve High-temp.
high-pressure liquid
Low-temp.
low-pressure gas
Temp subcool 5±2℃
High-temp.
high-pressure gas
Temp. evaporation. 0~8 ℃ Temp udara outdoor. 28~35 ℃
0.7~0.93 MPa Temp. condensation 43~55 ℃
Low pressure
High pressure 2.1~3.3 MPa
Perbedaan tempA-B= 9 ~15 ℃
udara Indoor.
Perbedaan temp. C-D= 9 ~15 ℃
udara outdoor
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
WBT JP0082-1
Mendeteksi kode kerusakan RA, SkyAir & VRV
Kode kerusakan terdiri dari dua digit (Contoh “C4”)
4 Group kode Kerusakan
1. Indoor : A & C
2. Outdoor : E, F, H, & J
3. Inverter : L & P
4. System : U
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
7
WBT JP0082-1
Tampilan kode kerusakan
Kode kerusakan Kerusakan yang terjadi
A0 Proteksi eksternal perangkat aktif
A1 PCB indoor bermasalah
A3 Sistem drain bermasalah
A5 Frezee up Proteksi aktif
A6 Fan motor bermasalah
Unit Indoor
A7 motor swing flap bermasalah
A9 Electronic expanstion valve bermasalah
AF Drain level di atas limit
AJ Setting kapasitas bermasalah (PCB indoor)
C4 Thermistor (R2T) pipa liquid bermasalah
C5 Thermistor (R3T) pipa gas bermasalah
C9 Thermistor (R1T) inlet udara bermasalah
CA Thermistor discharge udara bermasalah
CC Sensor humidity bermasalah
CJ Sensor thermostat dalam RC bermasalah
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
18
WBT JP0082-1
Tampilan kode kerusakan
Kode kerusakan Kerusakan yang terjadi
E0 Keamanan perangkat aktif
E1 PCB outdoor bermasalah
E3 High pressure switch aktif (HPS)
E4 Low pressure switch aktif (LPS)
E5 Kompresor inverter over heat
Unit Outdoor
E6 Kompresor STD macet atau over current
E7 Motor fan outdoor bermasalah
E8 Kompresor inverter over current
E9 Electronic expansion valve bermasalah
F3 Temp. pipa discharge tidak normal
F6 HPS tidak normala / kelebihan refrigerant
H3 High pressure switch bermasalah (HPS)
H4 low pressure switch bermasalah (LPS)
H7 Signal motor fan outdoor bermasalah
H8 Kompresor input (CT) bermasalah
H9 Thermistor udara (R1T) outdoor bermasalah
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
19
WBT JP0082-1
Tampilan kode kerusakan
Kode kerusakan Kerusakan yang terjadi
J1 Pressure sensor bermasalah
J2 Current sensor kompressor bermasalah
J3 Thermistor pipa discharge (R31 ~ 33T) bermasalah
J5 Thermistor pipa suction (R2T) bermasalah
Unit Outdoor
J6 Thermistor heat exchanger (R4T) bermasalah
J7 Thermistor pipa liquid (R6T) refrigerant circuit
J8 Thermistor pipa liquid (R7T) refrigerant circuit
J9 Thermistor pipe gas (R5T) bermasalah
JA High pressure sensor bermasalah
JC Low pressure sensor bermasalah
JH Thermistor oli bermasalah
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
20
WBT JP0082-1
Tampilan kode kerusakan
Kode kerusakan Kerusakan yang terjadi
L0 Sistem Inverter bermasalah
L1 PCB Inverter bermasalah
L4 Temperatur fin radiasi inverter bermasalah
L5 Arus inverter naik tiba-tiba (DC)
L6
Inverter
Arus inverter naik tiba-tiba (AC)
L8 Kompresor inverter kelebihan arus
L9 Startup kompresor inverter bermasalah
LA Power transistor bermasalah
LC Transmisi control & PCB inverter bermasalah
P1 Voltase tidak seimbang, (phase putus)
P4 Sensor temperatur fin bermasalah
PJ Capacity setting outdoor bermasalah
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
21
WBT JP0082-1
Tampilan kode kerusakan
Kode kerusakan Kerusakan yang terjadi
U0 Kekurangan refrigerant
U1 Phase bermasalah atau phase terbuka
U2 Voltase kurang tiba-tiba
U3 Belum dilakukan dilakukan cek operasi
U4 Transmisi antara unit indoor & outdoor terganggu
U5 Transmisi antara RC & unit indoor terganggu
Sistem
U6 Transmisi anatara unit indoor terganggu
U7 Transmisi antara unit outdoor terganggu
U8 Transmisi antara remote kontrol terganggu
U9 Transmisi antara unit indoor & outdoor dalam sistem yang sama bermasalah
UA Jumlah unit indoor terlalu banyak
UC Seting alamat centralized salah
UE Transmisi antara indoor dan centralize bermasalah
MC Alamat indoor double
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
22
WBT JP0082-1
3. Functional Parts Layout (RXQ16TY1)
No Pictures Name
1
7 Segments LED
3 1
(SEG1~SEG3)
2
4
BS Buttons
2
(BS1~3)
DIP Switches
(DS1-1~4)
3
&
(DS2-1~4)
5
Micro-computer
4 normal monitor
(HAP)
Connection
A1P – Outdoor Control PCB 5 terminal
(F1F2)
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Asia Oceania Training 13
Center
WBT JP0082-1
4. Field Settings:
4.4 Settings by BS Buttons:
iii. Mode 1 (Monitor Mode) – For retrieval of system information (Addresses, number of connected unit, errors)
Overview of monitoring items
*2: Represents the number
of indoor units connected to
a single outdoor.
*3: Represents the number
of outdoor units connected
to a single DIII-Net.
*4: Represents the number
of indoor units connected to
a single DIII-Net.
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg98 Asia Oceania Training 14
Center
WBT JP0082-1
4. Field Settings:
4.4 Settings by BS Buttons:
iii. Mode 1 (Monitor Mode) – For retrieval of system information (Addresses, number of connected unit, errors)
Overview of monitoring items
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg99 Asia Oceania Training 15
Center
WBT JP0082-1
4. Field Settings:
4.4 Settings by BS Buttons:
iii. Mode 1 (Monitor Mode) – For retrieval of system information (Addresses, number of connected unit, errors)
Overview of monitoring items
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg99 Asia Oceania Training 16
Center
WBT JP0082-1
4. Field Settings:
4.4 Settings by BS Buttons:
iii. Mode 1 (Monitor Mode) – For retrieval of system information (Addresses, number of connected unit, errors)
Overview of monitoring items
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg99 Asia Oceania Training 17
Center
WBT JP0082-1
4. Field Settings:
4.4 Settings by BS Buttons:
iii. Mode 1 (Monitor Mode) – For retrieval of system information (Addresses, number of connected unit, errors)
Procedures for checking error codes/retries
Refer to SiMT341406E;
Pg101~110 for errors
descriptions
Only Outdoor errors are
detected and display on
the 7 segment LEDs
For indoor errors, refer
to the local remote
controller
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg100 Asia Oceania Training 18
Center
WBT JP0082-1
4. Field Settings:
4.4 Settings by BS Buttons:
iii. Mode 1 (Monitor Mode) – For retrieval of system information (Addresses, number of connected unit, errors)
Overview of Error descriptions (Example: E3)
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg101 Asia Oceania Training 19
Center
WBT JP0082-1
5. Troubleshooting:
5.2 Error Codes:
i. Error codes and Sub Codes will be shown when using the Navigation Remote Controller (BRC1E62). This
will also be displayed on the 7 segments LED under the monitor mode for checking of errors.
Error Code Sub Code
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg138 Asia Oceania Training 20
Center
WBT JP0082-1
5. Troubleshooting:
5.2 Error Codes:
i. Error codes and Sub Codes will be shown when using the Navigation Remote Controller (BRC1E62). This
will also be displayed on the 7 segments LED under the monitor mode for checking of errors.
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg138 Asia Oceania Training 21
Center
WBT JP0082-1
5. Troubleshooting:
5.2 Error Codes:
i. Error codes and Sub Codes will be shown when using the Navigation Remote Controller (BRC1E62). This
will also be displayed on the 7 segments LED under the monitor mode for checking of errors.
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg138 Asia Oceania Training 22
Center
WBT JP0082-1
5. Troubleshooting:
5.2 Error Codes:
i. Error codes and Sub Codes will be shown when using the Navigation Remote Controller (BRC1E62). This
will also be displayed on the 7 segments LED under the monitor mode for checking of errors.
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg139 Asia Oceania Training 23
Center
WBT JP0082-1
5. Troubleshooting:
5.2 Error Codes:
i. Error codes and Sub Codes will be shown when using the Navigation Remote Controller (BRC1E62). This
will also be displayed on the 7 segments LED under the monitor mode for checking of errors.
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg139 Asia Oceania Training 24
Center
WBT JP0082-1
5. Troubleshooting:
5.2 Error Codes:
i. Error codes and Sub Codes will be shown when using the Navigation Remote Controller (BRC1E62). This
will also be displayed on the 7 segments LED under the monitor mode for checking of errors.
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg139 Asia Oceania Training 25
Center
WBT JP0082-1
5. Troubleshooting:
5.2 Error Codes:
i. Error codes and Sub Codes will be shown when using the Navigation Remote Controller (BRC1E62). This
will also be displayed on the 7 segments LED under the monitor mode for checking of errors.
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg140 Asia Oceania Training 26
Center
WBT JP0082-1
5. Troubleshooting:
5.2 Error Codes:
i. Error codes and Sub Codes will be shown when using the Navigation Remote Controller (BRC1E62). This
will also be displayed on the 7 segments LED under the monitor mode for checking of errors.
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg140 Asia Oceania Training 27
Center
WBT JP0082-1
5. Troubleshooting:
5.2 Error Codes:
i. Error codes and Sub Codes will be shown when using the Navigation Remote Controller (BRC1E62). This
will also be displayed on the 7 segments LED under the monitor mode for checking of errors.
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg140 Asia Oceania Training 28
Center
WBT JP0082-1
5. Troubleshooting:
5.2 Error Codes:
i. Error codes and Sub Codes will be shown when using the Navigation Remote Controller (BRC1E62). This
will also be displayed on the 7 segments LED under the monitor mode for checking of errors.
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg140 Asia Oceania Training 29
Center
WBT JP0082-1
5. Troubleshooting:
5.2 Error Codes:
i. Error codes and Sub Codes will be shown when using the Navigation Remote Controller (BRC1E62). This
will also be displayed on the 7 segments LED under the monitor mode for checking of errors.
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg141 Asia Oceania Training 30
Center
WBT JP0082-1
5. Troubleshooting:
5.2 Error Codes:
i. Error codes and Sub Codes will be shown when using the Navigation Remote Controller (BRC1E62). This
will also be displayed on the 7 segments LED under the monitor mode for checking of errors.
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg141 Asia Oceania Training 31
Center
WBT JP0082-1
5. Troubleshooting:
5.2 Error Codes:
i. Error codes and Sub Codes will be shown when using the Navigation Remote Controller (BRC1E62). This
will also be displayed on the 7 segments LED under the monitor mode for checking of errors.
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg141 Asia Oceania Training 32
Center
WBT JP0082-1
5. Troubleshooting:
5.2 Error Codes:
i. Error codes and Sub Codes will be shown when using the Navigation Remote Controller (BRC1E62). This
will also be displayed on the 7 segments LED under the monitor mode for checking of errors.
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg141 Asia Oceania Training 33
Center
WBT JP0082-1
5. Troubleshooting:
5.2 Error Codes:
i. Error codes and Sub Codes will be shown when using the Navigation Remote Controller (BRC1E62). This
will also be displayed on the 7 segments LED under the monitor mode for checking of errors.
PT DAIKIN AIRCONDITIONING INDONESIA.
Technical Support
Ref: SiMT341406E;Pg142 Asia Oceania Training 34
Center
WBT JP0082-1