Solar Hot Water Systems Design Course

This document provides an overview of a 6-hour continuing education course on solar hot water systems design. The course objectives are to assist engineers with recommendations on optimal configurations of large-scale solar hot water systems that serve clusters of buildings. The document discusses solar radiation intensity across the US, how cloud cover affects solar energy availability, and different types of solar thermal systems. It also outlines the course content which includes solar energy fundamentals, components of solar hot water systems, design considerations, system maintenance, and a quiz.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
131 views89 pages

Solar Hot Water Systems Design Course

This document provides an overview of a 6-hour continuing education course on solar hot water systems design. The course objectives are to assist engineers with recommendations on optimal configurations of large-scale solar hot water systems that serve clusters of buildings. The document discusses solar radiation intensity across the US, how cloud cover affects solar energy availability, and different types of solar thermal systems. It also outlines the course content which includes solar energy fundamentals, components of solar hot water systems, design considerations, system maintenance, and a quiz.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 89

Solar Hot Water Systems

Design
Six (6) Continuing Education Hours
Course #ME1115

Approved Continuing Education for Licensed Professional Engineers

EZ-pdh.com
Ezekiel Enterprises, LLC
301 Mission Dr. Unit 571
New Smyrna Beach, FL 32170
800-433-1487
[email protected]
Solar Hot Water Systems Design Ezekiel Enterprises, LLC

Course Description:
The Solar Hot Water Systems Design course satisfies six (6)
hours of professional development.
The course is designed as a distance learning course that
overviews the benefits and design of solar water heating
systems.

Objectives:
The primary objective of this course is to assist an engineer
with recommendations on optimal and reliable configurations
of solar water heating systems in different climates along
with design specifications, planning principles, and
guidelines for such systems that serve building clusters with
significant domestic hot water needs.

Grading:
Students must achieve a minimum score of 70% on the
online quiz to pass this course. The quiz may be taken as
many times as necessary to successful pass and complete
the course.
A copy of the quiz questions are attached to last pages of
this document.

ii
Solar Hot Water Systems Design Ezekiel Enterprises, LLC

Table of Contents
Solar Hot Water Systems Design

1. Introduction ................................................. 1
2. Solar Energy ................................................ 2
3. Solar Hot Water Thermal System .............. 11
4. DOD Installation Solar Hot Water
Applications ............................................... 50
5. Design Considerations.............................. 68
6. System Maintenance ................................. 82
Quiz Questions ................................ 83

iii
Ezekiel Enterprises, LLC

1. Introduc tion
Solar thermal systems are commonly used for the domestic water heating, space heating,
(industrial) process heating, and even for cooling of goods and buildings. The Energy Independence
and Security Act (EISA) 2007 SEC. 523 requires that “if lifecycle cost-effective, as compared to
other reasonably available technologies, not less than 30% of the hot water demand for each new
Federal building or Federal building undergoing a major renovation be met through the installation
and use of solar hot water heaters.” In the United States, different types of solar water heating
systems are available and primarily used for standalone buildings. Different design guidelines are
available from the National Renewable Energy Laboratory (NREL) and American Society of
Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) for small size systems. These
systems are relatively complex and application of solar based heating in the United States is often
limited by economical considerations when compared to traditional heating systems and local cost
of fossil fuels.

In recent years, numerous innovations in solar thermal technologies have resulted in cost effective
large scale systems including integrated solar supported heating networks. Examples of such
systems installed in Denmark, Germany, Austria and other countries have proven that such systems
are reliable and may be more economical compared to small scale systems. Such systems may be
cost effective for clusters of buildings containing e.g., Army barracks, dining facilities, gyms, child
development centers and swimming pools. Similar opportunities exist on large hospital campuses,
family housing complexes, etc.

This course will assist an engineer with recommendations on optimal and reliable configurations of
solar water heating systems in different climates along with design specifications, planning
principles, and guidelines for such systems that serve building clusters with significant domestic hot
water (DHW) needs (e.g., homes, dining facilities, Child Development Center [CDC], Gyms) that
operate in combination with central heating systems. Note that, throughout the industry, the terms
“district heating system” and “central heating system” are commonly used interchangeably. For the
purposes of this course, the term “Central Solar Hot Water System” is used to denote systems that
serve clusters of buildings from a large centralized solar thermal field(s) (in contrast with small size
solar thermal systems that serve standalone buildings). The guidelines are complemented by
numerous case studies of successfully implemented solar supported thermal networks along with
results of exemplary simulations of different system options based on real world scenarios. This
course also discusses the benefits and disadvantages of large scale centralized versus
decentralized solar thermal systems.

Solar Hot Water Systems Design 1


Ezekiel Enterprises, LLC

2. S olar E nergy
2.1 S olar radiation intens ity

The efficiency and performance of solar water heating systems depend on a site’s solar energy
resource. Solar resource is measured by the solar radiation intensity of an area, but cloud cover
and latitude must also be factored into the system purchase decision. The amount of solar energy
available for heating water varies by geographical location. Figures 2.1 and 2.2 show that tilted flat
plate collectors located in the United States at an angle equal to the latitude receive the most
sunlight in the desert Southwest and the least sunlight in the Pacific Northwest and states in the
Northeast. Table 2.1 lists the maximum daily solar radiation and average daily solar radiation for
selected US locations. Detailed monthly solar radiation information for a multitude of locations in the
United States is available from the National Renewable Energy Laboratory at:
www.nrel.gov/gis/solar_map_development.html

F igure 2.1. Map s howing the maximum daily s olar res ourc e available for tilted flat plate s olar
c ollec tors in the United S tates .

Solar Hot Water Systems Design 2


Ezekiel Enterprises, LLC

F igure 2.2. Map s howing the average daily s olar res ourc e for tilted flat plate c ollec tors in the United
S tates .

Table 2.1. Daily solar radiation values for specific


locations, I [kWh/m2/day].
L ocation I Max I Ave
Anchorage, AK 4.6 3.0
Austin, TX 6.3 5.3
Boston, MA 5.6 4.6
Chicago, IL 5.7 4.4
Denver, CO 6.1 5.5
Fargo, ND 6.5 4.6
Honolulu, HI 6.5 5.5
Jacksonville, FL 6.1 4.9
Knoxville, TN 5.6 4.7
Sacramento, CA 7.2 5.5
San Diego, CA 6.5 5.7
Seattle, WA 5.7 3.7

Solar Hot Water Systems Design 3


Ezekiel Enterprises, LLC

The energy delivery of solar water heating systems depends on the environmental conditions of
sunlight and temperature. The output of a solar energy system is proportional to the intensity of the
sunlight, but its efficiency also depends on temperature. Efficiency decreases as the solar collector
gets hotter and more heat is lost to the ambient environment.

2.2 C loud c over

The power of solar radiation entering the atmosphere, or the “solar constant,” is 1367 W/m2
(50,169 Btu/hr/sq ft). Within the atmosphere, this power is reduced by absorption, scattering, and
reflection effects to about 1000 W/m2 (36,700 Btu/hr/sq ft) on the earth’s surface if there is a clear
sky (Figure 2.3). The solar radiation that reaches the earth’s surface is further reduced by clouds,
which reflect part of the radiation back into space, and absorb another part. In addition, a part of the
radiation is dispersed into diffuse radiation by multiple reflections. Diffuse irradiation on the earth’s
surface consists of the irradiation coming from angles different than the solar incidence angle (i.e.,
the actual sun position). Therefore, cloud cover reduces the total amount of irradiation (global
radiation), and (due to scattering), it also changes the relation between beam and diffuse radiation.
As cloud cover changes with the seasons, these effects are also seasonal dependent. The diffuse
fraction of the total annual global radiation can be higher than 50%, depending on the location.

Even on a clear day a significant amount (>10%) of solar radiation is scattered due to the effects of
molecules in the atmosphere. This causes the sky at daytime to appear blue and colors the sun red
at sunset, when the distant light waves that enter the atmosphere are longer.

2.3 Site latitude

The latitude of the site will affect the solar radiation collected, so it is important to tilt panels based
on the latitude of the installation site. The United States lies closer to the middle latitudes, which
means it receives more solar energy in the summer when the sun's path is most perpendicular to
locations below. The sun slants far south during the shorter days of the winter months when the sun
follows a southern path in the sky. For this reason, solar collectors should face true south in the
northern hemisphere, i.e.:
Collector tilt angle = latitude to maximize annual gain

F igure 2.3. L eft: S olar C ons tant and proportions of beam and diffus e s olar radiation in relation to
c loud c over; R ight: P hoto of the effec ts of s c attering at s uns et taken at 1640 ft (500 m) height.

Solar Hot Water Systems Design 4


Ezekiel Enterprises, LLC

2.3.1 Season of year

The height of the sun's travel on the horizon varies by season of the year. In the summer, it is more
directly overhead; in the winter, it is much lower. Figure 2.4 shows the different paths* of the sun
over the sky for Washington, DC. The maximum incidence angle during (solar) noon for the location
in this example is 75 degrees on the 21st of June (the summer solstice). The minimum incidence
angle occurs on the 21st of December (the winter solstice). And the average incidence angle occurs
on the 21st of March and the 21st of September (the autumnal and vernal equinoxes). For locations
further north, these curves will be flatter, and for locations further south, steeper.

90
21. June
75 21. December
21 March/September
Zenith angle γ [°]

60

45

30

15

0
-135 -90 -45 0 45 90 135
Azimuth angle α [°]

F igure 2.4. P ath of the s un for latitude = 38° 53" (W as hington, DC ) relative to a horizontal plane.

Thus, the amount of solar energy that can be collected varies throughout the year. Monthly
available solar radiation values are used to determine the size of the solar collector system required
to satisfy the heating demand. Figure 2.5 shows the variation of beam and diffuse radiation over the
year for three locations. (The values apply to a collector surface tilted 40 degrees south facing.)

9
Fayette, NC
8
El Paso, TX
Anchorage, AK
7
Irradiation [ kWh/m 2/day]

0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

F igure 2.5. V ariation of daily month average beam and diffus e radiation over the year for three
loc ations . T he beam (bar) and diffus e (s tic k) daily radiation are s hown for a 40-degree tilted, s outh
fac ing c ollec tor s urfac e.

* The relative movement of the Sun around a position on Earth consists of two movements. The daily movement consists of a
circular movement around a tilted axis. The annual movement consists of a sinusoidal variation of the tilted axis over the year. In
addition, the latitude of the location of the solar thermal system adds an offset to the tilted axis, due to the curvature of the
Earth's surface. The latitude (‘offset’) is equal to the average tilt angle of the sun above the horizon.

Solar Hot Water Systems Design 5


Ezekiel Enterprises, LLC

The sum of beam and diffuse radiation falling on a horizontal surface is usually called “global solar
radiation.” The annual total in the figure above, 40-degree tilted south facing, for Fayette NC is
~507,504 Btu/y*sq ft (~1600 kWh/y*m2); and for El Paso, TX, 697,818 Btu/y*sq ft (2200 kWh/y*m2);
and for Anchorage, AK, 272,783 Btu/y*sq ft (860 kWh/y*m2). This results in an annual daily average
of 1,396, 1,935, and 761 Btu/sq ft*day (4.4, 6.1, and 2.4 kWh/m2)*day respectively. The fraction of
diffuse radiation is 44%in Fayette, 21% in El Paso, and 53% in Anchorage. Day and seasonal
variation can be very high; a nice summer day may provide as much as 2,030.02 Btu/sq ft*day (6.4
kWh/m2)*day in Fayette and 2664 and 1459 Btu/sq ft*day (8.4 and 4.6 kWh/m2 *day) in El Paso and
Anchorage and a cloudy winter day may have as little as 63.44 Btu/sq ft*day (0.2 kWh/m2*day) on
average in the month of December in Anchorage (Figure 2.6).

2.3.2 Solar collector tilt


Solar systems should be designed to match the heating demands with the solar energy intensity
that varies throughout the year. In the northern hemisphere, a solar thermal system will receive less
solar radiation in the winter than in summer. To improve the seasonal solar energy collection, the
solar collector can be tilted so that it would be more perpendicular to the sun's path when the
heating demand is greatest. Tilting of collectors (from horizontal) should be done to maximize the
radiation collection skewed for usage. Thus a system that is providing heat for the winter should
have a tilt angle equal to the site's latitude, plus up to 15 degrees; a system for year round heating
should have a tilt angle equal to the site's latitude. Table 2.2 lists collector tilt angles at selected
locations for maximizing winter solar energy collection.
Maximum radiation can be collected when the collector is faced due South in the Northern
Hemisphere. If the system must be East or West facing, using a Westerly azimuth is more optimal
than an Easterly one since the collector can take advantage of the warmer part of the day.

100% 9.00

90% Fayetteville 8.00


El Paso
80% 7.00
Anchorage
70%
6.00
60%
5.00
50%
4.00
40%
3.00
30%
2.00
20%

10% 1.00

0% 0.00
Diffuse fraction Beam fraction Daily Average Total Average Summer (June)
(Ann. Av.) (Ann. Av.) [kWh/day]: day [kWh/day]:

F igure 2.6. Annual average beam and diffus e frac tions (left) and daily J une average total radiation for
three loc ations (right).

Table 2.2. Tilt angles corrected for maximum winter season energy collection.
Angle at +15
L atitude degrees
25 degrees (Key West, Florida) 40 degrees
30 degrees (Houston, Texas) 45 degrees
35 degrees (Albuquerque, New Mexico) 50 degrees
40 degrees (Denver, Colorado) 55 degrees
45 degrees (Minneapolis, Minnesota) 60 degrees

Solar Hot Water Systems Design 6


Ezekiel Enterprises, LLC

2.4 Orientation to path of sun

Two angles describe the orientation of the collector:


• The azimuth * angle α, also called “compass orientation”: The angle in a horizontal surface
between the collector and the due south direction. Due south, towards the equator, is by
definition an orientation of 0˚.
• The tilt angle β (“sky ward orientation”): The angle between the collector and the horizontal
surface. †

Costs for supporting structures can be saved by mounting collectors flush with an existing, suitable
surface or structure. Tools (brackets etc.) are usually available from the supplier of the collector,
which will suit various common surface types like tiled or sheet metal roofs, brick or wood walls etc.
The fittings should provide sufficient strength to endure extreme weather conditions like wind and
snow loads. It is important that the mounting and structure comply with local standards and
regulations.

If mounted in line with an existing structure (e.g., a wall surface) the orientation may be less than
optimal, in many cases. The effects of these compromises are often less than expected. This is
shown in Figure 2.7. A deviation from the maximum yield tilt and orientation can be compensated
for by a larger collector area, if space and costs permit.

A rule of thumb for optimum exposure to solar radiation is that a collector should face the equator
(orientation of 0 degrees, due south) with a tilt angle of 0.7 times the Latitude of the location (but at
least 10 degrees, or the minimum working angle of the collector). This applies to heating domestic
water systems.

The optimum collector tilt angle for the usage of solar energy during winter months is higher
because the average sunlight incidence angle is lower. Choosing a larger tilt angle provides a yield
that is geared towards winter heat demands. The optimum collector tilt angle for the winter months
is higher than the latitude, for example 50 degrees for a site at 45 degrees latitude. Deviations up to
60 degrees from these optimum angles generally will lead to a loss of solar radiation of less than
15% compared to optimum angles. Note that the annual yield also depends on many other factors
such as the heat demand characteristics or the storage capacity.

F igure 2.7. Influenc e of tilt and orientation on the perc ent of total s olar radiation rec eived annually . In
this example the maximum annual radiation on a 45-degree tilted s urfac e fac ing s outh at L atitude = 50
degrees is indic ated by 100%.

* Azimuth: The angular deviation of the collector surface with respect to the direction of due south. Deviation to the west is positive
and deviation to the right is negative.
† “Tilt” = angle between horizontal and tilted plane. “Zenith angle” which is the angle between the vertical and the tilted plane, thus
“Tilt” = 90˚-“’Zenith angle’”)

Solar Hot Water Systems Design 7


Ezekiel Enterprises, LLC

Choosing a smaller tilt angle gears the yield towards the summer. Usually a summer bias increases
the potential overall annual yield of a collector, but only if this extra yield can be used. Solar thermal
systems are thus often sized by matching the collector yield during the summer period with the hot
water heating need (called economical collector sizing), any increase in collector area will increase
the fraction covered in winter, but will also increase the stagnation periods and duration during
summer. Refer to Section 3.4.2 (p 33) for an explanation of stagnation.

2.5 Shading

Shading causes less radiation to reach the collector surface. The positioning decision of the
collector may be influenced by anything that can cause shade on the collector surface such as
mountain ranges on the horizon, nearby or tall buildings, nearby trees (in particular when carrying
leaves during winter), and nearby roof construction. Local fog conditions can also cause a loss in
sunlight. Shading should be avoided during the peak sun hours of the day, 9 a.m.–3 p.m.

The loss of incoming radiation due to shading must be taken into account during simulations for
calculating the prospective yield and usually involves mapping the obstacles on the horizon and sky
in the face of the collector orientation (Figure 2.8).

Causes of shade such as fallen leaves and snow depend on location and climatic conditions and
should also be considered.

2.6 Collector placement within a building cluster

The solar collectors can be placed on buildings or on the ground. In some cases they could be
placed in an elevated position over parking lots providing shade below as an additional benefit.
Placement on a building is normally on the roof where a sloped or flat roof exists. Placement on a
sloped roof normally creates a collector tilt similar to that of the roof. Also, the orientation may not
be directly to the south. In these cases, heating energy obtained from the collector must be derated
from that of an optimum placement. Such a placement normally gives a better appearance than that
of tilted collectors on a flat roof. Building integrated collectors are assimilated into the original
construction of the roof or can be placed slightly above the pitched roof. In either case, the
collectors will use the structure framework of the roof as the main support.

90
21. June
75 21. December
21 March/September
Zenith angle γ [°]

60

45

30

15

0
-135 -90 -45 0 45 90 135
Azimuth angle α [°]

F igure 2.8. Influenc e of s truc tures on s hading of inc oming s olar radiation. Height and dis tanc e both
need to be taken into ac c ount.

Solar Hot Water Systems Design 8


Ezekiel Enterprises, LLC

The most important considerations for collector placement is to encourage integration in existing
infrastructure, and to avoid shading at periods when solar radiation is plentiful and heating is
needed. For large central systems the option of creating a large collector field is usually chosen.
This system can be integrated with carport roofing or placed on the flat roof of a large building.

Figures 2.9 and 2.10 show examples of installed collector fields. Integration into new building
structures may be more aesthetic and may provide for savings in roof cover material otherwise
used. Specially constructed flat plate collectors can provide a closed, insulated surface, which may
serve as a roof cover (Figure 2.11).

F igure 2.9. Placement of flat plate air collectors on a flat roof.

F igure 2.10. F lat plate c ollec tors on mounting c ons truc tion.

F igure 2.11. T wo examples of aes thetic plac ements of c ollec tors . At the right the c ollec tors are
integrated into the roof c over together with P V c ollec tors at either s ide.

Solar Hot Water Systems Design 9


Ezekiel Enterprises, LLC

Collectors placed on the ground or on flat roofs need a supplemental support to generate the
collector tilt to the sun. The rows of collectors must be separated by a short distance so that one
row does not shade the row behind it. The distance to assure no shading on the winter solstice can
be calculated by:
Separation distance = collector height X tangent of the angle (90 - latitude- 23.5)

Since the energy collected in the winter is a small percentage of the total, then the spacing between
rows can be slightly reduced with only minor loss in performance. Figure 2.12 shows how the winter
midday sun-angle is (usually) used to determine the angle.

F igure 2.12. Flat plate collectors with mounting construction.

Solar Hot Water Systems Design 10


Ezekiel Enterprises, LLC

3. Solar Hot Water Thermal System


The main components added to a conventional heating system when solar thermal energy is used
are:
• collector field with collector field piping and support structure
• heat transfer fluid (water or water glycol mixture)
• a storage tank system
• pump for solar loop and other pumps for other loops
• heat exchangers to transfer heat from one loop to another
• expansion and safety devices for each closed loop
• a controller with temperature sensors in collector field and storage tank and that turns the pump
on and off.

Since a solar thermal system does not usually act as the main heat source, an auxiliary (back-up)
heater is necessary to cover periods of high energy demand or too little solar radiation (usually in
winter). Figure 3.1 shows a schematic of a solar domestic hot water system.

3.1 Collector performance indices

Various performance characteristics are used to assess and compare solar thermal systems. The
most important ones are the “solar fraction” (SF), the “specific solar energy yield” (SE), and the
“solar system efficiency” (SN). The following sections discuss these indices.

To ensure that the reference quantities and energy flows can be clearly assigned, the essential
parameters are entered in accordance with their definition and their “position within the system”
(Figure 3.2). When selecting the proper components of a large solar hot water thermal system it is
best to use analytical modeling tools such as f-Chart or TRNSYS. These computer programs can
estimate annual energy collected, storage and heat exchanger effects, system heat losses, etc.
Refer to Section 3.3.2 (p 23) for information regarding these modeling tools.

F igure 3.1. A s c hematic example of a s olar domes tic hot


water s ys tem, s howing the c harac teris tic c omponents .

Solar Hot Water Systems Design 11


Ezekiel Enterprises, LLC

F igure 3.2. Alloc ation of the heat flow and referenc e values in the s olar thermal s ys tem.

3.1.1 Solar frac tion (f s olar or S F ) and F s ave

A commonly used solar system performance measure is the solar fraction, which identifies the
fractional amount of the building heating energy needed is supplied by the solar thermal system.
This Design Guide defines the solar fraction for solar supported heating networks as:
QSolar
SF =
QBioler + QSolar (3.1)

where:
SF solar fraction [%]
QSolar annual energy produced by collector loop (measured on secondary side) [kWh/a]
QBoiler annual heat input of the auxiliary heating system (boiler) [kWh/a].

Thus, a building that requires 10.24 MBtu (3000 kWh) per year to generate hot water and obtains
6.83 MBtu/yr (2000 kWh/yr) from its solar system has a solar fraction of 67%. A very similar
indicator is the “f-save” ratio. This indicator shows the thermal heating energy saved by the supply
of solar energy as compared to the heating energy that would have been used by a non-solar
thermal (reference) system for the same purpose. For example, when a non-solar heating system
(the reference system) requires 10.24 MBtu/yr (3000 kWh/yr) to provide for a certain hot water use,
and the solar thermal system requires 6.8 MBtu/yr (2000 kWh/yr) auxiliary heating, then the f-save
of the solar thermal system is 33% (i.e., the fraction of auxiliary energy saved compared to the
reference system). The formula for f-save (thermal) is:
Qbackup
f sav ,thermal = 1−
Qboiler ,ref
[-]
f save,thermal = Auxiliary energy saved by the solar (sub-)system [kWh]

Qbackup
= Energy used by the backup heater [kWh]

Solar Hot Water Systems Design 12


Ezekiel Enterprises, LLC

Qboiler ,ref
= Energy would have been used by a reference system without the solar thermal installation
[kWh]

For both indicators it must be specified whether direct energy (heating energy demand), primary
energy, or secondary energy is used in their calculations. The major difference is what is included in
the building heating energy use (the reference system) and the impact of thermal system losses
and supporting equipment energy use such as by pumps, etc.

Higher solar fractions mean higher energy and CO2-savings relative to the conventional energy
source. However, one must also consider that the higher losses of the solar thermal system
negatively affect the solar system efficiency. An economic optimum has to be found.

3.1.2 Solar system efficiency (SN)

In addition to the solar fraction, economic investigations of solar thermal systems are often affected
by another parameter, the solar system efficiency (SN). The solar system efficiency describes the
ratio between the annual amount of energy supplied to the heat storage unit and the global
irradiation that strikes the collector surface:
QSolar
SN = (3.2)
Gactive _ solar

where:
SN = solar system efficiency [%]
QSolar = annual energy produced by collector loop (measured on secondary side) [kWh/a]
Gactive_solar = annual global irradiation onto active solar collector area [kWh/a].

3.1.3 Specific solar energy yield (SE)

The specific solar energy yield describes the annual amount of energy supplied to the heat storage
unit from 11 sq ft (1 m2) of collector surface area. Compared to other calculation results, the kind of
surface (absorber, aperture or gross collector area) must always be indicated for the specific yield
result.
QSolar
SE = (3.3)
Acollector _ REF

where:
2
SE = specific annual solar energy yield [kWh/m ]
QSolar = annual energy produced by collector loop (measured on secondary side) [kWh/a]
2
Acollector_REF = collector area on which the solar yield refers to (gross, aperture or absorber area) [m ].

The specific solar energy yield is often said to be the crucial parameter for measuring the capacity
of a solar energy system. For a correct interpretation of this parameter, the size of the system, the
solar fraction and the system losses (storage and heat distribution losses) must be considered.
Solar collector ratings provided by Solar Rating and Certification Corporation and the Florida Solar
Energy Center use the gross area of the collector (not the net area) in their performance efficiency
rating information. ASHRAE Standard 93-2010 (for testing to determine thermal performance of
solar collectors) also uses the gross area of the collector.

Solar Hot Water Systems Design 13


Ezekiel Enterprises, LLC

3.1.4 Collector testing and certification organizations

Several organizations provide certification of solar collector and solar collector system performance
in the United States, the most recognized of which are:
• Solar Rating and Certification Corporation (SRCC). This is the principle rating organization for
solar domestic hot water collectors. The SRCC offers OG-100 certification for solar collectors
and OG-300 for entire systems. OG-300 certification is for smaller residential systems. Website:
http://www.solar-rating.org/ratings/ratings.htm
• Florida Solar Energy Center (FSEC). Mandated by the state of Florida to perform testing of solar
energy products, the FSEC is a good source for performance characteristics on both solar
thermal collectors and entire solar thermal systems. Although specifically geared towards the
solar industry in Florida, the FSEC is a good resource for the Southeast region as a whole.
FSEC Standard 101-09, which was revised May 2009, is the institute’s solar collector
certification. It supersedes FSEC Standard 102-05. Website:
http://www.fsec.ucf.edu/en/industry/testing/index.htm
• North American Board of Certified Energy Practitioners (NABCEP). The NABCEP provides
certification programs for solar electric and thermal system installers. A NABCEP-certified
installer provides for an extra level of assurance as to the qualifications of the installer.
However, because the solar thermal certification is a relatively recent development, NABCEP-
certified installers are not especially common. Certified installers can be found on the website:
http://www.nabcep.org/installer-locator-agreement

3.2 T ypes of hot water s olar s ys tems

3.2.1 P as s ive s ys tems

“Passive” systems solar hot water systems do not have a pump or other moving parts. These
heating systems rely on temperature changes in the water located in the solar collectors on the roof
to move the water through the system. They are typically less expensive than systems having a
pump (active systems) because they have no mechanical parts, but they are usually not as efficient.
However, passive systems can be more reliable and may last longer. There are two basic types of
passive systems: batch and thermosiphon.

Batch or Integrated collector-storage (ICS) systems. These systems work best in areas where
temperatures rarely fall below freezing. They also work well in buildings with significant daytime and
evening hot-water needs. Batch collectors (Figure 3.3) or ICS, use one or more black tanks or tubes
in an insulated, glazed box. Cold water first passes through the solar collector and is preheated.
The water then continues on to the conventional backup water heater, providing a reliable source of
hot water. This type of collector should be installed only in mild-freeze climates because the outdoor
pipes can freeze in severely cold weather.

Thermosiphon systems. Thermosiphon systems (Figure 3.4) move water through the system due to
density differences (warm water rises as cooler water sinks). Neither pumps or electricity are used.
However, the collector must be installed below the storage tank so that warm water can rise into the
tank. These systems are reliable, but contractors must pay careful attention to the roof design
because of the heavy storage tank. Although they are usually more expensive than ICS systems,
they can be used in areas with less sunshine.

Passive solar water heating systems are used on individual buildings or for a single heating
demand. They are not for central heating systems that service several buildings. They are also
inefficient in cooler climates. Since the purpose of this design guide is to focus on systems that can
serve multiple buildings, these systems will not be further discussed.

Solar Hot Water Systems Design 14


Ezekiel Enterprises, LLC

F igure 3.3. A s imple pas s ive s olar water heating s ys tem with a batc h c ollec tor.

F igure 3.4. S c hematic of a typic al thermos iphon s ys tem.

Solar Hot Water Systems Design 15


Ezekiel Enterprises, LLC

3.2.2 Ac tive s ys tems

Solar water heating systems that rely on electric pumps to circulate fluid through the collector are
called “active systems.” Active systems are generally categorized into two types: direct and indirect,
which simply means that water in the storage tank is either directly filled using the hot water flowing
from the solar collectors (one loop) or indirectly using two water circulating loops separated by a
heat exchanger. The latter type is normally used in locations where outdoor winter temperatures
below freezing may occur. These systems use an anti-freeze solution such as a water glycol
mixture as a heat transfer medium that circulates through the collectors to avoid freezing.

Direct circulating active system (no anti-freeze). These systems use pumps to transfer the sun's
energy directly to potable water by circulating this water through the collector tubing and storage
tank; no anti-freeze solution or heat exchanger is used. The pumps circulate water through the
collectors, into the building, and back again. They work well in climates where it rarely freezes.

A direct active system (Figure 3.5) has one or more solar energy collectors installed and a nearby
storage tank. The system uses a differential controller that senses temperature differences between
water leaving the solar collector and the coldest water in the storage tank. When the water in the
collector is about 15 to 20 °F (-9 to -7 °C) warmer than the water in the tank, the pump is turned on
by the controller. When the temperature difference drops to about 3 to 5 °F (-16 to -15 °C), the
pump is turned off, so the stored water always gains heat from the collector when the pump
operates. A flush-type freeze protection valve installed near the collector provides freeze protection.
Whenever temperatures approach freezing, the valve opens to let warm water flow through the
collector. The collector should also allow for manual draining by closing the isolation valves (located
at a height above the storage tank) and opening the drain valves. Automatic recirculation is another
means of freeze protection. When the water in the collector reaches a temperature near freezing,
the controller turns the pump on for a few minutes to warm the collector with water from the tank.

Another type of direct active solar water heating system is called “a drainback-system” (Figure 3.6),
which is also designed for cold climates. This type of system typically uses regular water as a heat
transfer fluid, and is designed to allow all of the water in the solar collector to “drain back” to a
holding tank in a heated portion of a building. When no sunlight is available for heating, the solar
pump turns off and the water flows into the drainback tank by means of gravity. Since these
systems use water, they can be designed with or without a heat exchanger.

F igure 3.5. An ac tive, direc t s olar water heating s ys tem. T hes e s ys tems offer no freeze protec tion,
have minimal hard water toleranc e, and have high maintenanc e requirements .

Solar Hot Water Systems Design 16


Ezekiel Enterprises, LLC

F igure 3.6. An ac tive, drainbac k s olar water heating s ys tem. T hes e s ys tems offer good freeze and
overheat protec tion, tolerate hard water well, and have high maintenanc e requirements .

F igure 3.7. S c hematic of an indirec t ac tive s ys tem that us es a heat exc hanger to trans fer heat from
the c ollec tor to the water in the s torage tank. T hes e s ys tems offer ex c ellent freeze protec tion, tolerate
hard water well, and have high maintenanc e requirements .

Indirect circulating active system (anti-freeze used). This system operates similar to the direct active
system except that there are two circulating heat transfer fluid loops. In the first (solar primary) loop
non-freezing, heat-transfer fluid such as a water-glycol mixture circulates through the collector field.
A heat exchanger transfers the heat from the water-glycol mixture into the potable water. The heat
exchanger can either be directly integrated into a storage (internal heat exchange) or the storage
can be connected to a second loop (solar secondary loop) via an external plate heat exchanger
(Figure 3.7). These systems are popular in climates that are prone to freezing temperatures.

If the solar collector is extremely well insulated and is not prone to freezing like an evacuated tube
collector, water can be the heat transfer fluid. By using water the heated water from the collector
can be sent directly to the storage tank; no heat exchanger is needed. Figure 3.8 shows the portion
of this system before the storage tank (and, if used, before the heat exchanger).

Solar Hot Water Systems Design 17


Ezekiel Enterprises, LLC

F igure 3.8. S c hematic of a rec irc ulating loop s ys tem. T hes e s ys tems require well ins ulated c ollec tors
s uc h as evac uated tube to provide protec tion for freezing and overheating.

Indirect circulating solar water heating systems used on individual buildings or groups of buildings
are consistent with the US Army's needs. They can easily be applied to central heating systems for
domestic hot water and building heating. Since the purpose of this design guide is to focus on
systems that can serve multiple buildings, these systems will be emphasized in further sections of
this course.

3.3 S olar thermal energy c ollec tors

The collector is a key part in a solar thermal heating installation. The following sections discuss the
working principle of collectors, and the most common collector types. Most relevant for the
application in domestic hot water and space heating systems are glazed flat plate and evacuated
tube collectors. A collector should be selected based on the quantity and quality (temperature) of
the demanded heat.

In principle, heat gain and loss mechanisms in different collector types are the same. In general,
one differentiates between optical losses (reflection, absorption) and thermal heat losses due to
heat transfer mechanisms (conduction, convection and radiation). Figure 3.9 shows the
mechanisms for a flat plate collector (FPC).

3.3.1 G eneral c ons truc tion

Figure 3.9 shows how heat from the sun is collected by the absorber and is carried away by the
fluid flowing through the tubes attached to the absorber. Since these collectors are located outside
and normally in a cooler environment, the heated absorber can lose heat its surroundings. To
reduce this heat loss, a cover is placed over the absorber and the sides and back of the absorber
are insulated. The cover must allow solar radiation to penetrate and, since glass is typically used,
some of this radiation will be reflected and radiated out to the atmosphere. The following sections
will provide a brief overview and details of the solar collector parts.

Solar Hot Water Systems Design 18


Ezekiel Enterprises, LLC

F igure 3.9. A S c hematic of a flat plate c ollec tor (F P C ) s howing the heat gain and los s mec hanis ms
that P lay a role in determining the thermal effic ienc y of a c ollec tor (R egenerative E nergies ys teme).

3.3.1.1 Absorber

The function of the absorber is to effectively convert solar radiation into heat. The absorber surface
is often coated to maximize this energy collection. The absorber coating is thus designed with a
high absorption coefficient, α, for the sun’s radiation spectrum (typically α = 0.92 to 0.96).
Absorptivity is the fraction of incident sunlight captured (not reflected) by the absorber. The
reflectance is the complement of the absorption and is given by: ρ= 1 - α. For best performance, the
absorber should have a low emission coefficient ε (typically, ε = 0.05 to 0.1) for infrared radiation to
keep the losses from long wave radiation emission low as the collector heats up.

Emissivity is the ratio of radiant heat loss off the absorber relative to that of a perfectly black surface
(“blackbody”). Most common materials, such as black paint, have an absorptivity equal to the
emissivity, and the second law of thermodynamics requires that all materials have a=e at a given
wavelength of incident light. However, special surface treatments (semiconductor coatings,
blackened nickel layer) have an absorptivity in the short-wavelength solar spectrum that is much
higher than emissivity in the long-wavelength infrared radiant heat loss spectrum. Such surfaces
are called “selective surfaces” and improve the performance of solar collectors, especially when
operating at elevated temperatures where radiant heat loss is more important.

Absorber coatings that possess high absorptivity and low reflectance are called “selective
absorbers.” Figure 3.10 shows this selective effect where the absorption/reflection characteristics of
a selective surface are identified at various wavelengths of the solar spectrum. These wavelength
values are taken with an atmospheric thickness of 1.5 of the thickness taken directly above (AM =
1.5). This is important since the atmosphere affects the spectral nature (wavelength distribution) of
the solar radiation, and properties reported at AM=1 refer to one thickness of atmosphere. If the sun
is not directly overhead, the sun's rays will have to go through more than one thickness of
atmosphere. For example, AM = 1.5 corresponds to a zenith angle of around 48.2 degrees, and
AM=0 refers to the wavelength outside of the earth’s atmosphere.

Solar Hot Water Systems Design 19


Ezekiel Enterprises, LLC

F igure 3.10. S pec tral dis tribution over the wave length (W ellenlänge) of the s olar radiation (AM 1.5)
and of the thermal infrared radiation from an abs orber at 212 °F (100 °C ) (graph on the right). T he
s pec tral reflec tivity (R eflec tion) of a s elec tive abs orber is indic ated by the red line.

For spectral irradiance originating from the sun the solar constant (1.367 W/m2) is defined as AM =
0. AM = 1 is defined as the spectral irradiance on a horizontal plane (zenith angle = 0°). AM = 1.5 is
equal to a zenith angle of around 48.2 degrees and the global radiation accounts for 36,700
Btu/hr/sq ft (1000 W/m2). (Tables of these standard spectra are given in ASTM G 173-03. The
extraterrestrial spectral irradiance (i.e., that for AM0) is given in ASTM E 490-00a).

3.3.1.2 Transparent cover

The purpose of the transparent cover is to reduce the convection losses from the absorber, while
allowing the maximum amount of radiation to reach the absorber. The cover must also provide the
mechanical strength to protect the absorber from the environment.

Special solar glass with low iron content is used. It is occasionally called “water white glass” and its
typical transmittance is τ = 0.89 to 0.91 for the wavelength range of the solar radiation. This can be
enhanced to τ = 0.94 to 0.96 when anti reflective coatings are applied. This glass should be
tempered to reduce breakage by impact.

3.3.1.3 Housing

The housing of a collector must provide the necessary mechanical strength to protect the absorber
and the insulation to minimize heat loss to the environment. It must withstand wind and snow loads
that occur in the area where the collector is installed. It also must be tight enough against rain

Solar Hot Water Systems Design 20


Ezekiel Enterprises, LLC

penetration. These features need to be ensured over the entire lifetime of the system (20 to 25 yrs).
Housings are typically made from aluminum sheet stock or extruded sections, galvanized and
painted steel, molded or extruded plastic parts, or composite wood products.

3.3.1.4 Insulation

Insulation is added behind the absorber plate and on the sides of the collector to reduce thermal
heat losses. The insulation must use a minimum of binders because it is intended for high
temperatures (up to about 400 °F [204 °C] for flat plate collector stagnation); otherwise, the binders
will outgas and form a film on the underside of the collector glazing blocking solar radiation.
Common insulating materials include, for example, mineral fiber, ceramic fiber, glass fiberglass, and
plastic foams. Sometimes polyurethane foam is used, though its resistance to temperature and
moisture is limited so it should not be allowed to contact the absorber plate inside the collector. The
insulation provides low heat conductivity, some mechanical strength, and temperature and fire
resistance.

3.3.2 T ypes of s olar thermal energy c ollec tors

Figure 3.11 shows the four different types of solar hot water collectors. The type of collector chosen
for a certain application depends mainly on the required operating temperature and the given
ambient temperature range. Due to the design and simplicity of design each type has a maximum
temperature that they are best suited to provide:
• Unglazed EPDM * collector - below 90 °F (32 °C)
• Flat plate - below 160 °F (71 °C)
• Evacuated tube - up to 350 °F (177 °C)
• Parabolic trough - up to 570 °F (299 °C).

F igure 3.11. T ypes of s olar thermal energy c ollec tors .

* ethylene propylene diene M-class [rubber]

Solar Hot Water Systems Design 21


Ezekiel Enterprises, LLC

In the Army, the major hot water requirements are heating for domestic hot water, reheat for
humidity control, and building heating. These requirements need a hot water source with a
temperature of at least 140 °F (60 °C). This eliminates the unglazed EPDM collector from
consideration. The ability of the parabolic trough greatly exceeds these requirements and thus
would be a poor selection due to its high cost. This leaves the flat plate and the evacuated tube
collectors as appropriate choices for Army applications. Both types of collector would be a good
choice for most Army installations, but several factors could influence the selection:
• Cost (from RS Means Green Building Project Planning and Cost estimating, 3rd ed.)-
o Flat plate - ~$17/sq ft = ~129€/m2
o Evacuated tube - ~$24/sq ft = ~182€/m2
• Freeze Protection
o Flat plate - Use non freeze liquid (glycol solution)
o Evacuated tube - some are well insulated so they could use water as collector fluid with the
strategy of cycling warm water into the collector from the storage tank if the collector fluid
gets too cold.
• Stagnation Issues. Stagnation is caused when the flow through the collector stops and the solar
energy heats the collector fluid to extremely high temperatures causing the collector fluid to boil.
At what temperature this boiling occurs is dependent on the fluid and the operating pressure on
the system. This boiling will push a portion of the collector fluid from the pipes in the collector
and can hamper later collector performance. Section 3.4 (p 32) discusses this topic in more
detail.

3.3.2.1 Unglazed flat plate

Unglazed flat plate collectors (Figure 3.12) are usually plastic collectors that are rolled out onto a
roof and that are generally used for low temperature heating of such things as swimming pools or
preheating of domestic hot water. Due to the absence of a glass cover they have no optical losses
and therefore are most suitable for low temperature applications since heat losses increase more
with higher temperatures compared to the other collector types. The manufacturers use plastic
materials that reduce production and installation costs. Extensive testing and analysis have so far
confirmed that the technology meets or exceeds reliability goals. They are generally less expensive,
but less efficient than standard solar water heating collectors used throughout all seasons.

F igure 3.12. An unglazed s olar mat-type s olar c ollec tor


made by F AF C O ins talled on a roof in C alifornia.

Solar Hot Water Systems Design 22


Ezekiel Enterprises, LLC

3.3.2.2 Glazed flat plate

Flat plate collectors (FPC) are essentially insulated boxes that have a flat dark plate absorber that is
covered by a transparent cover (Figure 3.13). The solar energy heats the absorber and heat is
carried away by a heat transfer fluid that flows through riser tubes that are connected to the
absorber. The riser tubes are attached to the absorber in a parallel pattern or they meander from
one side to the other.

The cover (usually a sheet of glass) is held in place by a frame above the absorber. The frame also
seals the collector at the sides and at the back. It must provide mechanical strength and rain
tightness, and must be designed to enable simple roof- and facade attachment or even integration
into these building elements. The back and sides of the collector are insulated. Flat plate collectors
are usually installed in stationary systems, i.e., they do not rotate to follow the path of the sun. The
advantages of flat plate collectors are their simple, robust, low-maintenance design, and their large
and effective aperture area.

Flat plate collectors are most commonly used for commercial or residential domestic hot water
systems. These collectors generally increase water temperature to as much as 160 °F (71 °C).
Special coatings on the absorber maximize absorption of sunlight and minimize re-radiation of heat.
These collectors are prone to freezing and in climates where this can occur a mixture of about 60%
water and 40% polypropylene glycol is used as the collector fluid (heat transfer medium).

3.3.2.2.1 Design considerations

Flat plate collectors similar to today's design have been manufactured for over 30 yrs and
experience has been gained as to the proper materials to use for best performance and long life.
The casing is typically made of aluminum. The absorber plate is made of copper or aluminum; steel
is seldom used. To maximize the absorption of the solar energy the absorber plate is typically
coated with black chrome, which is a selective covering providing good absorption and weak
reflection of solar radiation.

Copper is normally used as the flow channel (tubing) through which the heat transfer fluid flows. It
must be well bonded to the absorber plate for good heat transfer. The tubes are commonly placed
in parallel rows (as shown in Figure 3.13) where the flow is released in a header at the top of the
collector and is collected at the bottom.

F igure 3.13. F lat plate c ollec tor with s elec tive c oating on the abs orber. T he parallel lines indic ate
where the ris er tubes are c onnec ted to the abs orber by ultra-s onic welding.

Solar Hot Water Systems Design 23


Ezekiel Enterprises, LLC

Another tube arrangement is for the flow to meander across the surface of the absorber in a back
and forth serpentine fashion. In this case the volume of heat transfer fluid spends more time on the
collector surface and a greater temperature increase occurs. To obtain proper heat transfer from
the absorber to the collector fluid the spacing between the runs of tubing cannot be too great and a
tube interval of 4 to 5 in. (102 to 127 mm) is typical. In all cases, the tubes in a collector need to be
placed so that the fluid can completely drain from the collector by gravity.

The housing around the absorption plate is mainly to minimize the heat loss to the environment and
to provide a weather tight enclosure to prevent corrosion and other types of deterioration. Behind
the absorption plate, rock or glass wool, or an insulating foam may be used an the insulating
material. Typically a depth of 1-1/2 to 3 in. (38 to 76 mm) of insulating material is used. The
insulating material must have the thermal stability to withstand the high temperatures that occur
during times of collector stagnation. A glass cover is placed above the absorption plate that allows
the solar radiation to pass through while limiting heat loss. Plastic covers deteriorate over time and
are not recommended. Double pane glass covers retard the transparency to the solar radiation and
thus are not commonly used. For sealing materials, EPDM or silicone rubber type materials should
be used as the seal between the casing and the glass cover; adhesives should be silicon based
and openings for pipes should be sealed with silicon based products.

3.3.2.2.2 Applications

Flat plate collectors are used mainly for producing domestic hot water and, in some cases, where
building space heating is also accomplished. Standard flat plate collectors typically perform best
providing hot water below 160 °F (70 °C). There are high performance flat plate collectors (those
with a double, anti reflective cover) that perform well providing up to 200 °F (93 °C) hot water.
These are seldom used due to their high cost. Above that temperature, the efficiency drops
significantly due to the higher temperature difference between the collector fluid and the ambient
air.

It is possible to reduce the thermal heat losses by avoiding convective losses such as by using
vacuum tube collectors. The following section discusses this option.

3.3.2.3 Evacuated Tube

Evacuated tube collectors (Figure


3.14) can be designed to increase
water/steam temperatures to as high
as 350 °F (177 °C). They may use a
variety of configurations, but they
generally encase both the absorber
surface and the tubes of heat transfer
fluid in a vacuum sealed tubular
glass for highly efficient insulation.
Evacuated tube collectors are the
most efficient collector type for cold
climates with low level diffuse
sunlight.

There are three types of evacuated


tube collectors: (1) direct flow,
(2) heat pipe, and (3) Sydney tube F igure 3.14. Evacuated-tube collector.
type. The direct flow type has the

Solar Hot Water Systems Design 24


Ezekiel Enterprises, LLC

heat transfer fluid flowing through copper tubes attached to a absorber plate mounted inside the
evacuated tube. The heat pipe type uses a heat pipe attached to the absorber plate. The heat pipe
transfers the heating energy to the condensing section of the heat pipe where the collector fluid is
warmed. This occurs in the header where the evacuated tubes are connected. The last type has an
evacuated tube called a Sydney tube (Figure 3.15) that encapsulates a heat conductor sheet
(absorber) with heat transfer fluid carrying tubes. The Sydney tube slides over the absorber section
and locks into the collectors header forming a tight seal. Within the Sydney tube the space between
inner and outer glass tube is evacuated. The selective coating is sputtered onto the outside of the
inner glass tube. A heat conductor/transfer sheet is located inside the inner glass tube that
conducts the heat from the glass into the U-form tubes carrying the heat transfer fluid. The Sydney
tube type collector's performance can be enhanced through the use of a compound parabolic
concentrator located behind each tube. This device will reflect the solar radiation that passes
between each evacuated tube back to the underside of the cylindrical absorber in the collector
tubes. There are various other construction methods like flat or round absorber, and single- or
double-walled glass.

All evacuated tube collectors have the following in common:


• A collector consists of several evacuated glass tubes positioned in parallel and are joined by an
insulated manifold at one end for the supply and removal of the heat transfer fluid (Figure 3.16).
• Due to the vacuum insulation (pressure < 10-2 Pa) heat loss caused by conduction and
convection are minimal.
• The upper end of the tubes is connected to the “header.”
• The tubes are circular to withstand the outside pressure.

F igure 3.15. B as ic elements of an evac uated S ydney tube c ollec tor. T he ends of the tubes in the
drawing are c ut to s how the internal tubing. On the left the tube is additionally equipped with an
optional C P C (c ompound parabolic c onc entrating) reflec tor.

Solar Hot Water Systems Design 25


Ezekiel Enterprises, LLC

F igure 3.16. S unMaxx evac uated tube s olar c ollec tors on the roof of a c ommerc ial building.

3.3.2.3.1 Design considerations

Evacuated tube collectors have only insulated tubes and a pipe header to which the evacuated are
connected. The collector fluid tubes use copper and typically black chrome is used as the selective
absorber coating. The pipe header is insulated and has a protective cover.
3.3.2.3.2 Applications

This type of collector is used when there is a need for hotter water than would be necessary for
domestic hot water heating. Hotter water is needed for applications that have cooling in the summer
as a requirement and in some cases where building heating is a major need. Solar assisted cooling
uses an absorption or adsorption chiller, which requires hot water temperatures in the range of 130
to 350 °F (55 to 180 °C).

An evacuated tube type collector may also be chosen as an alternative for a flat plate collector in
areas where winter time freezing occurs. In this case, water would be used as the heat transfer fluid
in the collector and warm water would be pumped into the outside piping and collector when
freezing of those components is threatened. This would required a small amount of heated water
due to the insulating quality of the evacuated tubes. As a result, the cost and inferior heat transfer
characteristics of a water glycol mixture is avoided. Also the a hotter water could be produced in the
collector providing a lower heat transfer fluid flow thereby reducing distribution pipe and storage
tank sizes. Also, the heat exchanger between the collector and the storage tank could be avoided
thus reducing the required leaving collector temperature. As a total system, the evacuated tube
collector could have a total cost competitive with a flat plate collector system. The use of evacuated
tube type collectors obviates most of the stagnation concerns associated with an anti-freeze heat
transfer fluid.

3.3.2.4 Concentrating Collectors

These collectors use curved mirrors to focus sunlight onto a receiver tube (sometimes encased in
an evacuated tube called CPC or compound parabolic collectors) running through the middle or
focal point of the trough (Figure 3.17). They can heat their heat transfer fluid to temperatures as
high as 570 °F (299 °C). Such high temperatures are needed for industrial uses and for making
steam in electrical power generation. Because they use only direct-beam sunlight, parabolic-trough
systems require tracking systems to keep them focused toward the sun and are best suited to areas
with high direct solar radiation like the desert areas of the Southwest United States. These collector
systems require large areas for installation, so they are usually ground mounted. They are also
particularly susceptible to transmitting structural stress from wind loading and being ground
mounted helps with the structural requirements.

Solar Hot Water Systems Design 26


Ezekiel Enterprises, LLC

Parabolic-trough collectors generally require


greater maintenance and supervision and
particularly benefit from economies of scale, so
are generally used for larger systems. Because of
their higher cost and greater maintenance needs
this type of collector is not recommended for US
Army heating needs in their standard buildings.

3.3.3 Hot air c ollec tors

Air collectors currently do not have a large market


share (e.g., 0.5% in Germany in 2009).
Nevertheless they can be considered as an
alternative in certain situations (e.g., space
heating, when an air heating system is used). As
the type name indicates air collectors use air as
F igure 3.17. P arabolic trough c ollec tors us ed
the heat transfer medium (instead of water and
to heat water at a large pris on fac ility in
glycol). This has some advantages:
C olorado.
• Air does not freeze or evaporate and air does
not degrade when exposed to high
temperatures. Freezing and stagnation thus does damage the system. Air collectors are usually
intrinsically safe.
• Fresh air may be used directly as heat transfer fluid; a volume of air has no cost and is non-
toxic. Leakage in the system does not cause damage to the system nor the environment.

On the other hand some disadvantages are:


• Air has lower heat transfer attributes and a lower heat capacity (a factor of 4 times lower
compared to water and glycol).
• Higher driving power by a fan is needed for a comparable mass flow [kg/h] to a fluid pump.
• Larger cross sections for conduction pipes are necessary.
• If water is to be heated, an additional heat exchanger is needed.

3.3.4 Solar hot water collector efficiency

The efficiency of the solar collector is directly related to heat losses from the surface of the
collector. Heat losses are predominantly governed by the thermal gradient between the temperature
of the collector surface and the ambient temperature. Efficiency decreases when either the ambient
temperature falls or when the collector temperature increases. This decrease in efficiency can be
mitigated by increasing the insulation of the unit by sealing the unit in glass (for flat collectors), or
providing a vacuum seal (for evacuated tube collectors). Figure 3.18 shows efficiency curves of
these collectors. When comparing collector efficiencies, it is important to assume the same type of
area (net vs. gross), and the same irradiation level.

The thermal performance of solar hot water collectors is characterized by:


• The power curve as shown in Figure 3.18, parameters: η0, a1 and a2
• Incidence Angle Modifier (IAM) because of the optical efficiency of the collector
• Thermal capacity (Ceff), which is the measure of thermal response to heating and cooling.
• The quantity of heat input into the collector to heat it by -457.87 °F (1 °K). This information
would be available from the collector manufacturer. This value is used in the solar collector
simulation computer programs as it relates to the small time steps in the program to the
estimated heat removed. The larger the Ceff, the more energy that will be lost when switching off
and on the solar heat transfer pump, which can happen as the weather changes during the day.

Solar Hot Water Systems Design 27


Ezekiel Enterprises, LLC

3.3.4.1 Power curve 100%

90% Optical losses


For the power curve, collector
80%

Instantaneous Collector Efficiency [-]


performance is measured at different
operating temperatures and with 70%

perpendicular insolation of G > 29,360 60% Thermal losses


Btu/hr/sq ft (800 W/m2). The collector’s
performance is represented by: 50%

∆T ∆T 2 40%
η = η0 − a1 ⋅ − a2 ⋅
Gglob Gglob 30% Useful heat
3.4
20%

where:
η = Instantaneous efficiency of a
10%

0%
collector at given operating 0 0.05 0.1 0.15
conditions [-] Difference to ambient Temperatur normalized to irradiation dT/G [Km²/W]
η0 = Conversion factor at normal
incidence of radiation [-]. This value F igure 3.18. T ypic al s olar c ollec tor effic ienc y c urve with
determines the starting point of the los s es and us eful heat indic ated.
collector efficiency curve, e.g., 0 =
η
80% (at dT = 0  no thermal, only optical losses!).
2
a1 = Linear heat loss coefficient [W/m K]. This factor determines the starting downward slope of the
collector efficiency curve (conduction + convection losses).
2 2
a2 = Quadratic heat loss coefficient [W/m K ]. This factor determines the downward curvature of the
collector efficiency curve and is assumed to cover all non-linear losses (losses due to radiation).
∆T = The temperature difference between the mean fluid temperature in the collector and the ambient air
temperature [K]
Gglob 2
= Global irradiation intensity [W/m ].

Figure 3.19 shows the power curves of four low * temperature collectors. A “rule of thumb” is to
select a collector type that achieves an efficiency η ~ 50% for the working temperature range.

For use in water and low temperature space heating, both flat plate collectors (with solar glass and
selective coating) and evacuated tube collectors are applicable. Both have certain advantages in
specific applications especially when freezing, leaving water temperature, available space and
installation cost are concerns. For applications with large collector fields, these two collector types
should always be considered, and the final decision to select one technology over the other should
be based on annual simulation results.

* Per definition low temperature collectors are applied in the range up to 176.0 °F (80 °C), medium temperature collectors up to
482.0 °F (250 °C) and above these: high temperature collectors.

Solar Hot Water Systems Design 28


Ezekiel Enterprises, LLC

Efficiency for different solar collectors

0.9

0.8

0.7

0.6
vacuum tube collector
efficiency [-]

0.5 uncovered absorber

state of the art flat plate collector

0.4 non-selective flat plate collector

0.3

0.2

0.1

0
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18
difference to ambient Temperatur normalized to irradiation dT/G [K m²/W]

F igure 3.19. Power curves for four typical low temperature collectors.

3.3.4.2 Incidence angle modifier

The IAM [-] describes the modification of the conversion factor η0 of the collector for non-
perpendicular solar incidence angles. By definition, an IAM equal to 1 is for normal incidence. The
IAM has a significant effect on the performance of stationary installed collectors as the incidence
angle changes throughout the day and the year. Incidence angles less than 50 degrees do not have
a significant effect on the solar thermal collector efficiency while an Incidence angle of 90 degrees
is equal to a total reflection of the sun rays. Figure 3.20 shows the IAM curves of a typical FPA and
a typical ETC.

The longitudinal IAM (i.e., in the direction parallel to the tubes for the ETCs) of the ETCs is similar
to the flat plate collector’s while the transversal IAM of most ETCs shows a characteristic increase
at intermediate angles.

Collectors with a flat absorber surface, which includes some types of evacuated tubes, only have
100% efficiency at midday. Other evacuated tube collectors collect solar radiation in a
perpendicular fashion over a longer period of the day since the collecting absorber surface is
cylindrical. This feature can be enhanced by placing an optimally designed reflective compound
parabolic concentrator (CPC) mirror behind the collectors, causing the sunlight to strike the collector
at a perpendicular angle for a great percentage of the day. This provides most of the advantages of
tracking systems while avoiding their high costs. The advantages of the CPC ETC include:
• longer usable daylight time
• more continuous power in the course of the day
• high target temperatures over the entire day
• higher daily and yearly energy yields.

Solar Hot Water Systems Design 29


Ezekiel Enterprises, LLC

1.2

1
Incidence Angle Modifier (IAM) [ - ]

0.8

0.6
ETC_Trans
ETC_Long
0.4 FPC_Trans
FPC_Long

0.2

0
0 10 20 30 40 50 60 70 80 90
Angle of Incidence [ ° ]

F igure 3.20. T he graph s hows the Inc idenc e Angle Modifier (IAM) for evac uated tube and flat plate
c ollec tors in trans vers al and longitudinal direc tions ac ros s the c ollec tor.

3.3.4.3 Thermal capacity

The thermal capacity ( Ceff ) of the collector has an effect on the system performance. Every time
the collector heats up, energy is absorbed by the collector. This energy is not fully recovered as
useful energy. In simulations, this factor is taken into account when calculating the annual energy
yield. The thermal capacity ( Ceff ) of the collector is expressed in kWh per m2 collector area per
degree K. The influence of this parameter is comparably small. Nevertheless, the lower the thermal
capacity of the collector, the better.

3.4 Heat trans fer fluid

As the solar collector heats up, the fluid in the collector increases in temperature. This fluid is then
moved out of the collector so the heat can be extracted for some useful purpose. Larger solar
systems either use the heat immediately, or use heat stored in a tank of heated fluid. When the
solar system is located in a freezing climate, the fluid flowing through the collector is often an anti-
freeze solution. When storing heated fluid in a tank, water is often the preferred medium (to reduce
cost). If this is the case, a second fluids is used and flow through a heat exchanger is required to
transfer the heat from the collector to the storage tank. There also may be a third fluid, potable
water, which is used directly for domestic purposes, in which case another heat exchanger would
be required. The heat transfer fluids used in a solar hot water system are very important and must
meet a number of requirements to ensure good performance:
• a high heat capacity and conductivity allowing efficient heat transportation from the collector
• anti-corrosive-protection, if mixed or corrosion prone materials are present in the collector
• non-toxicity and environmental-friendliness
• low viscosity for easy pumping of the fluid
• low cost and availability.

Except where freezing is a concern, water is the fluid of choice in solar energy hot water systems. It
has a low cost, is plentiful, and is compatible with the materials used in these systems. Water also
has high heat capacity, good conductivity, a low viscosity, and can withstand the hot temperatures

Solar Hot Water Systems Design 30


Ezekiel Enterprises, LLC

that are experienced during stagnation periods of time. Passive solar systems normally use water in
the solar collector. Water is also often used in evacuated tube collectors. In freezing climates an
anti-freeze liquid must be used in flat plate collectors.
Water used for domestic hot water is a potable water source that must be kept safe to drink and not
be contaminated by chemicals. Because of this, large systems must have at least two fluid
circulating systems, one that flows through the solar collector, and another that is heated and
dispensed as domestic hot water. A heat exchanger is placed between the two piping systems for
the movement of captured heat from the collector heat transfer fluid to the domestic water. Figure
3.6 shows such a system. Separating the collector fluid from the domestic water allows for water
treatment to prevent corrosion of the piping and collector materials. To protect the potable water a
double wall heat exchanger must be used when the heated fluid is not-potable. This separation also
allows for an anti-freeze solution to be used in the solar collectors if needed.

3.4.1 Anti-freeze fluids


The typical anti-freeze solution is a mixture of water and propylene glycol, but a water/ethylene
glycol solution, silicon oil, hydrocarbon oil, or refrigerant could also be used. With the
water/propylene glycol fluid the percent glycol should be 40% or less. A 40% solution begins to
freeze at –11 °F; below that temperature, an ice slurry develops that does not readily freeze solid
causing pipes to burst. A glycol solution greater than 50% is not recommended due to a higher
viscosity and lower heat capacity. Systems using glycol should be aware that it has a greater
tendency to seep through piping joints than water and thus the piping system should be sealed with
care and checked for leaks at scheduled intervals. Glycol is not compatible with zinc so galvanized
pipes should not be used.
The use of automatic water makeup to heat transfer fluids selected to be an anti-freeze should be
avoided. This is because the water makeup will dilute the anti-freeze mixture and making the fluid
more likely to freeze when exposed to cold outdoor temperatures. The anti-freeze fluid should be
periodically checked to assure proper performance.

3.4.2 S tagnation
The heat transfer fluid used in the collector must also withstand the high stagnation temperatures.
Stagnation occurs when the heat transfer fluid stays in the collector too long and a high temperature
is reached greater than the normal due to the heat from solar radiation. This could happen when
there is a pump or control failure, when the heating demand of the users and the storage tank are
satisfied or when the system is down for maintenance. Under normal operation the heat transfer
fluid is under a pressure to avoid vaporization. Most collector systems are designed to operate at
pressures below 125 psig (833 kPa). This is to allow the use of standard piping components (class
125) and avoid using more costly components. Since the solar collector is generally placed at a
higher elevation than other parts of the system the static head of the fluid column must be added to
the operating pressure in the collector when determining the pressure on components. This means
pressures at or just below 75 psig (500kPa) are common in the solar collector. At this pressure, a
60/40 mixture of water/glycol will begin to vaporize at 320 °F (160 °C). If the pressure is dropped to
45 psig (310 kPa), then vaporization would begin at a temperature of 284 °F (140 °C). Vaporization
of water at these pressures is 307 °F and 275 °F (153 and 135 °C), respectively.
When vaporization begins to occur, the resulting gas displaces the liquid in the collector and to
some degree in the nearby piping. This displaced fluid should be directed to a recapturing tank so
that it can be used again to fill the system when the temperature cools down. There are safety
valves in the piping system that must be certified for the highest temperature that may occur. They
should be placed on connections to the lines leading to the recapture tanks.

Solar Hot Water Systems Design 31


Ezekiel Enterprises, LLC

The disadvantages of frequent vaporizations are:


• Water/glycol mixtures will have a shorten life when exposed to at temperatures in the 300 °F –
320 °F (149 – 160 °C) range.
• Anti-corrosion additives and contaminants may stick to the interior of pipes and absorbers flow
channels.
• Operating personnel need to spend time refilling the system.

All glycol systems should use the Pressure Stagnation Protection (PSP) method. This method
allows over sizing of the pressure relief valve to 150 psi (1034 kPa), which allows the system
pressure to rise with stagnation temperature. This protects the fluid from overheating and preserves
the properties of the glycol by keeping it in a liquid form at all times.

Since glycols begin to break down and start to become corrosive when heated to temperatures
greater than 240 °F (116 °C). One way to avoid this condition is to send excess heat to a nearby
low priority heat user such as a swimming pool when the temperature in the storage tank is
satisfied. Such a connection to a swimming pool is established using another heat exchanger with
redundant, multiple pumps. Another solution may be to route external fluid to air heat exchangers,
or in some cases, to a ventilated recooling device. For smaller applications (up to several hundred
m2) it is sufficient to design the solar loop expansion vessel in a way that both the additional volume
of the heat transfer medium (due to the decreasing density), and the volume of the evaporated heat
transfer medium (in case of stagnation) can be absorbed.

3.5 P iping arrangements

3.5.1 Collector piping alternatives

It is advised to choose collectors that feature a good emptying behavior during stagnation. This will
reduce the strain on the heat transfer fluid and reduce the steam production of the collector field.
During periods of stagnation, it is likely that steam will develop in the collectors. The steam will push
the fluid out of the collectors. The fluid will later be sent back into the collector field when the
collector field is cooled down again.

Tables 3.1 to 3.9 list a selection of collector designs. The pipe manifolds are shown in relation to the
arrangement of the tubes attached to the collector absorbers. Both flat plate and evacuated tube
collectors are addressed. An attempt is made to assess the different absorber piping designs with
respect to:
• steam producing power (SPP) (a low SSP is a positive property with respect to a smaller
expansion vessel needed)
• glycol strain (a low glycol strain is a positive property)
• air vent possibility (a good air vent behavior is a positive property).

For the designs listed in Tables 3.1 to 3.9, real measurements of the SPP were carried out on
sample collectors. For the other designs, estimations are provided that are deduced from the
experience made in the investigations. In these tables, note that:
• A question mark “?” in the tables means that even no rough estimation on the expected
behavior can be given. The assessment is very rough and the given collection of piping designs
is not complete.
• ETC = Evacuated tube collector
• FPC = Flat plate collector.

Solar Hot Water Systems Design 32


Ezekiel Enterprises, LLC

Table 3.1. Evacuated tube


collector 1 (ETC), SPP 14,130
Btu/hr/sq ft (385 W/m2).

SPP High

Glycol
High
strain

Air vent Good

Table 3.2. Flat plate collector


1 (FPC), SPP 5,505 Btu/hr/sq
ft (150 W/m2).

SPP High

Glycol
High
strain

Air vent Good

Table 3.3. ETC 3, SPP 2, 202


Btu/hr/sq ft (60 W/m2), The
collector does produce steam.
Whether it is too much or not
depends on the system.

SPP ?

Glycol
High
strain

Air vent ?

Solar Hot Water Systems Design 33


Ezekiel Enterprises, LLC

Table 3.4. FPC 2, SPP 551 Btu/hr/sq


ft (15 W/m2).

SPP Low

Glycol strain Low

Air vent Good

Table 3.5. ETC 1 upside down.

SPP Low

Glycol
Low
strain

Air vent Bad

Table 3.6. FPC.

SPP Low

Glycol
Low
strain

Air vent Bad

Solar Hot Water Systems Design 34


Ezekiel Enterprises, LLC

Table 3.7. FPC,


horizontal.

SPP Low

Glycol
Low
strain

Air
?
vent

Table 3.8. FPC.

SPP ?

Glycol
?
strain

Air
Bad
vent

Table 3.9. FPC,


horizontal.

SPP ?

Glycol
?
strain

Air
?
vent

Solar Hot Water Systems Design 35


Ezekiel Enterprises, LLC

There are two methods connecting a row of collectors together - with an external manifold or an
internal manifold. The external manifold uses a supply and return header and all the collectors in
the row have supply connections to the supply header and also have a flow outlet connected to the
return header. The internal manifold type connection has the supply pipes of each collector
connected to the next collector. The same applies to the return side of the collector piping. The
piping of the collector is similar to that listed in Table 3.9. Internal manifolds offer the following
advantages:
• less piping reducing costs and heat loss
• more attractive installation.

Disadvantages of internal manifolds are that they:


• make it more difficult to achieve a drainable system
• make it difficult to balance collector flow for a long row of collectors
• make it hard to remove a single collector
• create more significant expansion and contraction issues for a long row.

3.5.2 S olar S ys tem piping arrangements

Large solar systems serving multi-buildings typically have several heat transfer loops. First, there is
one with the fluid flowing through the solar collector (solar primary loop). This one may contain an
anti-freeze solution. Second, there is one that circulates from the heat exchanger with the collector
fluid to the thermal storage tank (solar secondary loop). Third, may be a circulating fluid that heat
the domestic hot water. Finally, there may be a circulating system going to a district or building
heating system. Normally circulating systems use water as their heat transfer fluid. The types of
piping systems can be characterized as:
• Solar supported local heating system with a two-pipe network:
o two-Pipe Networks with Decentralized Domestic Hot Water Storages
o two-Pipe Networks with Decentralized Heat Transfer Units
• Solar supported local heating system with a four-pipe network:
o four-pipe networks with centralized energy storage and centralized domestic hot water
storage
o four-pipe networks with centralized energy storage and decentralized domestic hot water
storage
• Solar supported district heating network with direct interconnection of a centralized solar
thermal system:
o solar thermal plant directly feeding the supply line of an existing district heating network
o solar thermal plant directly preheating the return line of an existing district heating network.

3.5.2.1 Two pipe networks

In two-pipe networks, the heat supply to the heat sinks (buildings), including both domestic hot
water and space heating, is by means of a pair of pipes. Domestic hot water is heated in a
decentralized manner for the individual consumers using continuous flow water heaters, or by
means of decentralized DHW storages using the charge-store principle. The two-pipe network
shown in Figure 3.21 consists of centralized energy storage and decentralized heat transfer units
for each building or unit connected to the network.

The energy storage is the central point for all heat flows and acts as a hydraulic gateway. To
guarantee a reliable supply of heat with this design, it is essential that adequate reserves are
permanently stored in the upper region of the energy storage (stand-by volume) so as to cover peak
demand.

Solar Hot Water Systems Design 36


Ezekiel Enterprises, LLC

F igure 3.21. S olar s upported two-pipe network with c entralized energy s torage and dec entralized heat
trans fer units .

Domestic hot water is heated in a decentralized manner using continuous flow water heaters
(usually via plate heat exchangers – no additional storage needed).

Two-pipe networks in combination with decentralized heat transfer units are ideally suited for use in
compact unit blocks (medium to high energy densities). For less energy dense clusters of
buildings (lower heating requirements per length of heat distribution pipe), a two-pipe network in
combination with decentralized daily storages is preferable (Figure 3.22).

Solar-supported heating networks in combination with decentralized heat transfer units are also
highly suitable for use in existing buildings. This includes buildings that are equipped with central
space heating, but that also have a decentralized supply of domestic hot water (off-peak energy
storage units). Whenever these energy storage units have to be renewed, they could then be
replaced by decentralized heat transfer units. At the same time, improvements to the heat insulation
(insulation of the building envelope, new windows) will mean that the space heating system can
operate at lower temperatures.

Figure 3.23 shows a modified two-pipe network with decentralized energy storage for each building
connected and additional decentralized solar thermal systems. The single consumers within the
building are supplied via decentralized heat transfer units.

This concept is recommended for local heating grids with high energy densities (high heating
requirements of buildings per length of heat distribution pipe), especially for new-built facilities that
are constructed in several construction stages (modular enlargement).

Solar Hot Water Systems Design 37


Ezekiel Enterprises, LLC

F igure 3.22. S olar s upported two-pipe network with c entralized energy s torage and dec entralized
domes tic hot water s torages .

F igure 3.23. Modular expandable s olar s upported two-pipe network with dec entralized energy
s torages for all buildings c onnec ted.

3.5.2.2 Four-pipe networks with centralized energy storage and centralized domestic hot water
storage

In four-pipe networks, the heat is distributed through four pipes. In addition to flow and return lines
for the space heating system, four-pipe networks also have two pipes for the supply of domestic hot
water (distribution pipe for domestic hot water and circulation line).

The four-pipe network shown in Figure 3.24 consists of centralized energy storage and centralized
domestic hot water storage. The energy storage is the central point for all heat flows and acts as a
hydraulic gateway. Domestic hot water is heated in a centralized manner using the charge-store
principle.

Solar Hot Water Systems Design 38


Ezekiel Enterprises, LLC

F igure 3.24. S olar s upported four-pipe network with c entralized energy s torage and c entralized hot
water s torage.

F igure 3.25. S olar s upported four-pipe network with c entralized energy s torage and dec entralized hot
water s torage.

Due to the high distribution losses in the DHW supply and circulation lines, this concept is
especially recommended for local heating grids with high energy densities (high heating
requirements per length of heat distribution pipe) such as Army New-Recruit Troop Training Sites.

The four-pipe network shown in (Figure 3.25) consists of centralized energy storage and
decentralized domestic hot water storages in the buildings.

The energy supply for space heating and domestic hot water is performed by two pairs of
distribution pipes using the heating water as the heat transfer medium within the whole heating
network.

Solar Hot Water Systems Design 39


Ezekiel Enterprises, LLC

F igure 3.26. S olar s upported dis tric t heating network with direc t interc onnec tion of a c entral s olar
thermal s ys tem.

Due to its higher specific investment costs, this concept is especially recommended for local
heating grids with high energy densities (high heating requirements per length of heat
distribution pipe) such as Army New-Recruit Troop Training Sites.

The direct interconnection of a solar thermal system to an existing district heating network (Figure
3.26) is applied to provide some base load energy directly to the grid. In general, two different
applications are most commonly used:
• solar thermal system directly preheating the return line of an existing district heating network
• solar thermal system directly feeding the supply line of an existing district heating network.

Applications of this kind are commonly designed based on the available space and the existing
dimensions of the district heating branch on site, and not on the actual load in a specific building.
The solar collectors can either be roof- or ground-mounted. The majority of these systems can be
operated without additional storage as they use the district heating network as storage (as long as
they provide a small amount of heat in comparison to the total load in the district heating system).

3.5.3 B alanc ing fluid flow in c ollec tor field

A large solar hot water system will flow through many solar collectors. The flow through each solar
collector should have basically the same pressure drop. This will ensure that the system is
balanced such that each collector is receiving the same flow rate of heat transfer fluid. Thus the
fluid temperature increase of each collector will be equal to the others. With several collectors, a
reversed return piping system is used to achieve the equal pressure drop. This assumes each
collector is arranged to have parallel fluid flow. In some systems, the collectors are arranged for
flow in series. Here the fluid goes from one collector to the next collector picking up heat along the
way. Figure 3.27 shows the parallel and series flow arrangements. There is a limit to the number of
collectors that can be arranged in series due to the pressure drop of the flow through so many
collectors.

Solar Hot Water Systems Design 40


Ezekiel Enterprises, LLC

F igure 3.27. P iping arrangements of c ollec tors for balanc ed flow.

In large collector systems a combination of parallel and series flow is used. An arrangement of
collectors that have series flow are placed in a group or zone. Each group is then arranged to have
parallel flow with the other collector groups. Figure 3.27 shows such arrangement. The collector
layout could also have a group collectors with parallel flow placed in series with another collector
group having parallel flow.

The design objective is for the pressure drop of each group to be equal. This is accomplished using
a reverse return piping layout (Figure 3.27). The amount of piping should be kept at a minimum to

Solar Hot Water Systems Design 41


Ezekiel Enterprises, LLC

keep installation costs low and to minimize the system resistance to flow, which helps keep the
required pump pressures at acceptable levels. A rule of thumb is for the pressure drop per pipe
length in the collector to be slightly more than three times the pressure drop per pipe length in the
general piping system

With these large solar thermal systems it is advised to design the collector loop system as a low
flow system. That means that the flow rate is ~0.37 gal/sq ft*h (15 l/m2). By contrast, in the so called
high flow type the flow rate is in the range of 1.23–1.72 gal/sq ft*hr (50–70 l/m2*hr). This type
system is well suited for small (less than 161sq ft [15 m2]) solar DHW systems and for applications
having a small temperature rise such as solar cooling applications. It is possible with a low flow
system to connect more collectors that are piped for series flow. The flow through an individual
collector is then less compared to a high flow operation mode and a higher temperature rise is
possible. The benefits of a low flow system are its:
• lower investment costs due to smaller pipe sizes required
• lower piping lengths, as more collectors are connected in series (lower investment) and reduced
heat losses
• smaller pump requirements (lower investment), which use less pump energy (lower operation
costs) due to lower volume flow
• requirement for less fluid in the solar loop, and consequently less glycol (lower investment)
• quicker response to achieving the target temperature in heat storage tanks including those
using stratified charging
• ability to achieve a useful temperature in a single flow cycle a greater percentage of the time.

Table 3.10 lists the range of specific mass flow rates of the various operating modes of the solar
installations and the differences in the total mass flow rate in the feed and return piping of an
assumed collector area of 10,760 sq ft (1000 m2). This example shows that larger manifold pipe
sizes and higher electric pump power are required when the high-flow operating mode is used in
large-scale solar thermal systems. The costs of installing and operating this type of system would
therefore soon exceed acceptable limits.

3.5.4 Freeze protection

When water freezes, it expands. Frozen water in pipes is likely to rupture them. This is a major
cause of breakdown of solar heating systems. Water thus must be prevented from freezing inside
the collector loop. The following options will protect against freezing of the piping system:
• Provide drain-back pipe design.
• Use an antifreeze solution in the outdoor collector and piping, a water-glycol mixture.
• Add heat from the storage tank to the outside piping and collector field.

Each solution has its benefits and drawbacks. Some general aspects are discussed here. The
freeze protection implemented is usually not a free choice, but depends on the selected collector
technology and supplier; it is usually based on environmental conditions, operating temperature,
maintenance, costs, and local availability.

Table 3.10. Comparison of mass flow rates for high flow, low flow and matched flow systems.
R ange of the s pecific Mas s flow rate for a collector
Des ignation mas s flow rate area of e.g., 1,000 m 2
Low-Flow 5 – 20 kg/(m2·h) 0.12 – 0.49 gal/(sq ft) 5,000 kg/h to 20,000 kg/h 11,025 to 44,100 lb/h
High-Flow 50 – 70 kg/(m2·h) 1.23 – 1.72 gal/(sq ft) 50,000 kg/h to 70,000 kg/h 110,250 to 154,350 lb/h
Low-Flow — speed-controlled 5 – 20 kg/(m2·h) 0.12 – 0.49 gal/(sq ft h) 5,000 kg/h to 20,000 kg/h 11,025 to 44,100 lb/h

Solar Hot Water Systems Design 42


Ezekiel Enterprises, LLC

In a drain-back system design the water drains from the collector when the collector pump is
stopped. This requires that the collector is constructed and the piping is installed so that no water
remains in any part that could freeze. A continuous downward gradient for all the draining pipes is
needed to avoid locations where pipes sag and where water can be trapped; this can be difficult to
achieve. After a system draindown, the system pump is started to fill the pipes and solar collector
with water. This means that the pump must be able to push the circulating fluid up the piping
system when starting. The extra amount of pump pressure needed is equal to the height difference
between the top of the collector and the position of the drain-back storage vessel. The drain-back
approach can also be used during stagnation periods, preventing the formation of steam, and
avoiding the resulting expansion and high pressures within the collector. Refer to Section 3.5 for
various collector piping arrangements.

Please note: Common practice of solar system designers in Europe is to use a water glycol
mixture in drain back systems nevertheless. This way it is ensured that heat transfer fluid
does not freeze if draining does not work perfectly. The remaining advantage of drainback
systems is: Overheating of oversized collector fields does not necessarily lead to problems
during stagnation.

When using a water-glycol mixture the freezing temperature of the mixture is lowered (lower than
water alone). The mixing ratio determines the lowest operating temperature. It is important to follow
the manufacturer's or installation engineer’s recommendations. The different types of glycol that
could be used vary in their properties. See Section 3.4.1 (p 33) for more information. The pipes still
need to be pitched to drains so that the collector field can be emptied for maintenance even when a
anti-freeze collector fluid is used.

The main drawbacks of using a glycol antifreeze water mixture are that:
• The heat capacity of the fluid is reduced while the viscosity is increased. This causes a
reduction in efficiency of the collector field. In addition, for a comparable mass flow more pump
energy is needed.
• Glycol deteriorates when heated up to common collector stagnation temperatures that occur in
evacuated tube collectors. Deteriorated glycol forms solid particles that can block and even
destroy the collector loop. The glycol mixture then must be replaced.
• Care must be taken when an antifreeze solution is used to heat domestic water (which is a
potable water source). The two fluids must be kept separate with a leak detection device at the
point of heat exchange. This affects the efficiency of the heat transfer.

The third option is to use water in a closed, always filled loop, and to heat up the collector loop by
turning on the pump when near freezing temperatures are sensed. This means that heat from the
storage tank is used to prevent the collector and piping from freezing. This has the obvious
drawback of wasting captured heat and using pump power. Therefore, the viability strongly depends
on the site with the specific occurring ambient temperatures in winter. It would probably be the
logical choice at locations where freezing temperatures are not normally experienced. This option
also requires a reliable power supply because if no power is available, this option will fail to protect
the collector loop.

3.5.5 Air elimination

When the piping system is filled with the heat transfer fluid air is pushed out of the pipes as the fluid
enters. This air must be removed for proper flow to occur. To remove this air, valved openings in
the pipe system are installed at high points. These are called “air vents”; their valves are opened to
allow air to escape. Usually a 3/8-in. (9.52 mm) ball valve is used. This is a manual operation and
when fluid begins to be released at these high points the valve is closed with the captured air is

Solar Hot Water Systems Design 43


Ezekiel Enterprises, LLC

removed. This air removal exercise must be done not only at the initial fluid fill, but also a short time
after operation begins and then on a routine basis thereafter. Gases are released from the fluid as it
is heated and trapped air can be moving through the system as bubbles. With a fluid velocity
greater than 1.3 ft/second (40cm/second), these gas bubbles will move with the fluid until they
reach the air vents in the system and there they can be released. The air vents consist of a short
section of an expanded pipe section with a valved pipe outlet placed on the top of the expanded
pipe section. The larger pipe volume allows the gas to collect without disturbing fluid flow and thus
the gases can be removed when the air vent is opened.

3.5.6 Heat loss

The collector loop piping system between collectors and storage tank must be insulated to avoid
energy losses. The thickness of insulation on pipes of up to 1 in. (22mm) (outside diameter) should
be at least 0.8 in. (20 mm), pipes up to 1-1/2 in. (42mm) should have at least 1.18 in. (30 mm)
insulation. * Mineral wool is a widely used insulation of solar system installations. Any pipes and
insulation material that are exposed (to weather and animals) should be resistant to damage (e.g.,
UV degradation and removal by birds) as not to fail. Zinc coated steel, aluminum, or stainless steel
are all common materials used for the pipe insulation covering.

3.6 Storage tank

3.6.1 T ank c onfiguration and us e

A challenge in applying renewable energies is often the mismatch between the time energy is
needed and the time energy is available. Thus storage tanks are a necessary part of any hot water
system since they couple the timing of the intermittent solar resource with the timing of the hot
water load.

For systems that provide heat for domestic hot water, 1 to 2 gal (3.8–7.5 L) of storage water per
square foot of collector area are generally adequate. The storage fluid can either be potable water
or non-potable water if a load side heat exchanger is used. For small systems, storage is most often
in the form of glass-lined steel tanks. Solar heated water may be stored in a “one-tank” system, or it
may be stored in a separate tank that feeds into the tank of a conventional gas or electric water
heater (a “two-tank” system). Whether one or two tanks are used, solar energy heats the water
before use. On sunny days, a typical solar system can raise water to 140 °F (60 °C).

Bigger commercial solar hot water systems are basically the same as those used for homes, except
that the thermal storage tank, heat exchanger, and piping are larger. The storage tanks in these
applications are commonly steel tanks with an enameled interior coating. The sizes of these
components are proportional to the size of the collector array. Most systems include a backup
energy source such as an electric heating element or are connected to a gas or fuel fired central
heating system that will heat the water in the tank if it falls below a minimum temperature setting,
enabling the system to work year-round in all climates.

If the solar hot water system provides for some of the building heat, a larger storage tank may be
advisable. Figure 3.28 shows a breakdown of common storage types.

* See EN 12976 Appendix B. In addition the thermal conductivity (λ) of the insulation should be equal or less than 0.2
Btu/hr-sq ft °F (0.035 W/mK).

Solar Hot Water Systems Design 44


Ezekiel Enterprises, LLC

F igure 3.28. Overview of s torage s ys tem types and their applic ation.

Most large systems have stratified storage tanks where cooler temperatures are at the tank bottom
and the hotter temperatures are at the top. The cooler fluid is drawn off the tank bottom and is sent
to the collector system for heating. It may go directly to the collector or be used to cool the heat
transfer fluid that is then sent to the collectors. Using this cooler water, increases the collector
efficiency. The heat transfer fluid is held in the collector until it reaches the desired hot temperature.
This is accomplished by stopping the fluid flow or by slowing the flow in the collector until the
desired temperature is reached.

Thermal losses from the storage tank are a significant part of the heat balance of the solar thermal
system. The losses are proportional to the surface area of the storage tank. Because the volume of
a solid body (e.g., cylindrical storage tanks) increases faster than its surface, larger storage tanks
have a lower heat loss per volume than smaller tanks. Combining multiple storage tanks into one
large storage tank is thus beneficial regarding reducing storage heat losses. All storage tanks need
to be insulated to reduce the amount of heat lost from the system. It is good practice to limit the
heat losses to 10% of that in the storage tank over 24 hrs. An insulation value of R-16 is the
minimum insulation required. If the tank is placed outdoors the insulation should have a weather
proof cover.

The storage tank temperature must satisfy the required service temperature and quantity. For
DHW, this would be 140 °F (60 °C). For other heating needs the temperature could be hotter. A
hotter temperature than the service requirements in the storage tank allows for greater storage of
heat, but reduces the collector efficiency. This consideration for the storage tank normally results in
a design that provides a stratified water condition in the tank with the hot water on the top and the
cold water at the bottom. Stratification of the water is naturally achieved and maintained if mixing of
the water is minimized since the cooler water has a higher density and tends to stay at the tank
bottom. For good stratification, the tank should be as tall as possible, which means a high, narrow
tank is best. Such a tank could be divided into several shorter tanks plumbed in series where the
outlet at the top of the first is connected to the inlet near the bottom of the second and later tanks
similarly piped. Up to four tanks are often installed in this manner for large systems. If one large
tank is used, there may be a pipe connection in the middle section that allows for the entry of water
at a temperature warmer than the cold water at the bottom, but not as hot as that in the upper part
of the tank. Using this technique minimizes the mixing of the stored water and helps keep the water
column stratified.

Solar Hot Water Systems Design 45


Ezekiel Enterprises, LLC

For larger storage tanks it is common not to store drinking


water in the whole storage volume, but to use an internal
or external heat exchanger through which drinking water
flows for heating (see Figure 3.29). This avoids Legionella
growth at mid temperatures, eliminating the need to heat
to higher temperatures, more than 140 °F (60 °C).

The most commonly used storage tank systems are used


for short-term storage, and are designed to store surplus
solar energy for 1–2 days (diurnal storages). This limits
the possible solar fraction * (SF) to 10 – 20% of the total
heat demand (space heating + DHW) supplied by the
solar system, but provides the lowest system investment
cost.

Long-term storage tank systems can compensate for


seasonal fluctuations in solar irradiation between winter
and summer, which can include solar fractions in the
range between 40 and 70%. The negative effects are
higher system investment costs and higher heat losses of
the system. Between short and long-term storages,
weekly or medium-term storages have been realized in
Austria. F igure 3.29. E x ample of internal heat
exc hanger in a s torage tank for
heating domes tic hot water.
3.6.2 Legionella considerations

One should exercise caution to avoid the risk of the


growth of the Legionella Pneumophila bacterium. These bacteria are naturally found in water, but at
low concentrations. They can multiply quickly when the water temperature is between 86 and
113 °F (30 and 45 °C). † Their numbers start to diminish at temperatures above 122 °F (50 °C), and
almost instantly die above 150 °F (66 °C). The greatest health danger is not in drinking
contaminated water, but in inhaling contaminated dispersed water droplets, which can happen
when taking a shower. Storing large quantities of water at temperatures in the range of 86 to 113 °F
(30 to 45 °C)should be avoided when it is intended to be used (from a tap) later. Local legal
requirements may apply to this issue and should be taken into account.

Table 3.11. Techno-economic comparison of different storage concepts for local heating networks†
T ype of S torage C onnected to S hort-Term Medium-Term L ong-Term
S ys tem (Diurnal S torage) (Weekly S torage) (S eas onal S torage)
Solar thermal generated heat for: DHW DHW + space heating DHW + space heating
Solar fraction (in% of the total 10 – 20% 30 – 40% 40 – 70%
heating demand)
2 2 2 2
Collector area (m ) per 1076 sq ft 6 - 12 m 65 –129 sq ft 12 - 30 m 129– 323 sq ft 30 - 120 m 323– 1,291 sq ft
(100 m2) heated floor area
Specific storage capacity (L/m2 50 – 70 l/m2 1.23 – 1.72 gal/sq ft 200 – 400 l/m2 4.91 – 9.82 gal/sq ft 2,000 - 4,000 l/m2 49.10 – 98.20 gal/sq ft
collector area)
2
Specific solar thermal system 20 – 25 €/m $2.65 – $3.31 /sq ft 30 – 50 €/m2 $3.97 – $6.62/sq ft 90 - 150 €/m2 11.91 – 19.85 $/sq ft
costs (€/m2 heated floor area)
†A tempering valve must be used to prevent scalding.

* Within this report solar fraction SF is defined as the ratio between the energy produced via the solar thermal system and the total
energy demanded for DHW + space heating
† All temperatures mentioned here are indicative only; refer to local requirements for actual temperatures.

Solar Hot Water Systems Design 46


Ezekiel Enterprises, LLC

The typical approach in the United States to avoiding the Legionella bacteria issues is to store the
hot water at 140 °F (60 °C). Other design options are to limit the quantity of usable hot water by
means of a heat exchanger or tank-in-tank construction, where the temperature of the delivered
water is 140 °F (60 °C). In Europe, other options include periodically reheating the water above
150 °F (66 °C) (setting the controller for the auxiliary heater to do this when solar heat alone cannot
achieve this), or instantly heating the water just before use to above 185 °F (85 °C). *

3.7 Heat exchangers

In the solar hot water system heat exchangers transfer the heat from one moving fluid to another.
To achieve the temperature transfer the fluid from the collector will be hotter than the leaving
temperature of the secondary fluid. This higher temperature from the collector has a negative effect
on system performance. To keep this temperature difference as small as possible a plate-and-
frame heat exchanger is used. Where this temperature difference is not a large concern a shell-
and-tube heat exchanger can be used.

When the solar thermal system is used to heat domestic water there must be a guarantee that the
heat transfer fluid is kept isolated from the potable water source. This is normally accomplished by
separating the two fluids by a vented open space, or by using a third fluid that could be monitored
for fluid leakage. The double wall or additional heat exchanger also protects the solar collector fluid
from being diluted by water and becoming prone to freezing. (Refer to Section 5.3.5 [p 80]).

All heat exchangers have a small pressure drop of the fluid passing through them. This must be
considered in selecting the pumps. Their materials of construction need to be compatible with the
heat transfer fluids and with other materials in the piping system. They also need to be able to
withstand the temperatures and pressures that will be experienced in the system. To achieve good
heat transfer and to adhere to the other requirements, stainless steel and copper are the normal
materials used in these heat exchangers.

The pipe design at the heat exchanger that transfers energy from the collector to the storage tank
may need a by-pass pipe circuit around the heat exchanger for the collector heat transfer fluid if an
antifreeze solution is used. The antifreeze solution on cold days during system startup could be
several degrees below freezing and thus could freeze the water in the heat exchanger from the
storage tank when flow begins. The pipe bypass would be opened when the collector pump is
started. The valves would be closed to allow flow through the heat exchanger when there is usable
heat in the heat transfer fluid (a temperature ~80 °F [27 °C]). This action will also avoid cooling the
heat exchanger during the initial flow of the collector heat transfer fluid that was downstream of the
solar collectors.

A comparison between the two types of heat exchangers will show the following results. Plate-and-
frame heat exchangers have small passageways and thus have a higher pressure drop and are
more prone to flow blockage due to contaminants in the circulating fluids. They have a quicker
reaction time and typically take less space in the piping system. A shell-and-tube heat exchanger
can handle fluids having more contamination. These heat exchangers are easier to clean and have
a lower pressure drop for the fluids flowing through them.

Selection of the size of the heat exchanger depends on the amount of heat that must be transferred
and the desired leaving temperature. An increased heat transfer surface area is needed for
improved performance. Note that heat exchanger ratings are established using water as the heat

* A tempering valve must be used to prevent scalding.

Solar Hot Water Systems Design 47


Ezekiel Enterprises, LLC

transfer fluids. With the use of an anti-freeze fluid, heat exchange performance will decrease and
the exchanger surface area will need to increase. A water-glycol mixture has a higher viscosity and
lower heat capacity. Heat exchanger manufactures can provide useful information to aid selection.

3.8 Pumps

Pumps move the heat transfer fluids through their piping circuits. The pump associated with the
collector fluid will be exposed to the highest temperature and the greatest pressure. To minimize the
high temperature in this loop, the pump is placed in the pipe going to the collectors. But even here
there will be short term periods when the pump is handling temperatures greater than the design
collector discharge temperature. Such a time is when the hot heat transfer fluid has been forced out of
the collector into the recapture tank due to stagnation. If using an anti-freeze solution as the collector
heat transfer fluid, the pump components will need to be compatible with the water/glycol mixture.
These considerations will affect the materials used in the construction of the pump.

The pump will also need to operate through the flow range that is designed for the system. In some
solar thermal systems, the heat transfer fluid flow is slowed when the solar radiation is not at its
peak. At this lower flow the pump must still provide the required pressure to obtain fluid movement
through the pipe system. Having clean fluid strainers/filters, a minimum of valves, and properly
operating sensors will aid in keeping the system pressure drop as low as possible. In large systems,
the piping system flow is modeled to define the pump pressure needed for proper operation. It is
important to take into account that glycol/water mixtures have a different viscosity than water alone.
The manufacturer of the heat transfer medium should provide the necessary data. The energy
needed to pump the heat transfer fluid is considered parasitic energy; it must be kept as low as
possible. The pump should thus not be oversized.

3.9 Expansion tank

As the heat transfer fluid increases in temperature its volume also increases thus an expansion tank
is used to capture the addition fluid as it is pushed out of the piping loop. The expansion tank also
helps prevent the loss of heat transfer fluid that would escape the piping system through the safety
valves during high temperature periods. When the heat transfer cools, fluid in the expansion tank
can then flow back into the system.

Most expansion tanks are a steel tank with a rubber membrane inside. On one side of the
membrane is a gas such as nitrogen, which is under a pressure equal to the system operating
pressure. On the other side of the membrane is the space where the extra heat transfer fluid goes
when expansion of the fluid occurs. The membrane material will begin to deteriorate when exposed
to temperatures above 160 °F (71 °C). To protect the expansion tank from such high temperatures,
they should be connected to the piping that goes to the collector. This will be where the coolest fluid
will be found. If temperatures exceeding 160 °F (71 °C) are expected in this pipe then a buffer tank
or auxiliary reserve tank should be placed between piping loop and the expansion tank. This is a
normal steel tank filled with heat transfer fluid. Since it is not circulating in the collector piping
system loop, it will be somewhat cooler. When expansion occurs, the extra hot fluid will enter the
auxiliary reserve tank causing the residing cooler fluid then to enter the expansion tank protecting
its membrane.

The membrane expansion vessel may need to be designed to compensate not only the additional
volume of heated up fluid, but also the volume of steam that is produced by the collector field. That
can be more than just the volume of the collectors. Water in pipes above the collector field, for
example, can drain into the collectors after they are already empty and then start to produce even
more steam.

Solar Hot Water Systems Design 48


Ezekiel Enterprises, LLC

3.10 Back-up/supplemental heater

Each solar thermal system must have a back-up heating supply. Often gas or electricity and
sometimes biomass (wood) are used as a heat source. Due to the 20+ year lifecycle of heating
systems, including solar thermal systems, possible changes in energy supply options should also
be considered.

It is important to control the solar energy system to provide the required temperature to the building
energy systems. So if the domestic hot water must be 140 °F (60 °C), the heat transfer fluid must be hot
enough to deliver that temperature. If it is not, then the supplemental heating system will be energized
causing additional energy costs to occur. Running the supplemental heater is often very inefficient for
this use since it would be cycling on/off and would not be operating at its normal firing rate.

3.11 Controls

The controller controls the flow of the heat transfer fluid in the collectors by modifying the pump
operation. Normally the pump is just turned on/off in small systems. The most common pump
controller used in solar thermal systems is the “differential controller.” This controller requires two
different temperature settings, one for “on” (upper band) and one for “off” (lower band). The system
temperatures are measured on an absorber in a collector (usually one whose flow is a short
distance to the storage tank) and in the storage tank (near the tank outlet to the collectors) or in this
discharge pipe adjacent to the tank. If the collector temperature exceeds the storage tank
temperature plus the upper band the pump will turn on. If the collector temperature drops below the
store temperature plus the lower band the pump will turn off. A common upper band (“on”)
temperature difference is 41–46 °F (5–8°C) and for the lower band (“off”) 36–39 °F (2–4 °C). Proper
location of these sensors is very important. Good placement guarantees that the pump only runs
when this is beneficial for collecting solar energy that can be stored in the tank. Failing to measure
the temperature difference correctly will affect the overall system performance significantly; this
requires care and verification at the installation.

The controller also must turn off the pump when the maximum storage temperature (e.g., 194 °F
(90 °C) is reached, or when the collector exceeds the maximum flow temperature (e.g., 68.00 °F
[20 °C]).

Some pump-controller combinations offer different power settings (often step-wise) to be able to
match the mass flow rate with the amount of solar radiation available. This limits the temperature
increase in the solar circuit and prevents unnecessary pumping.

More advanced controllers offer additional functionality: insolation and heat measurement, data-
logging, error diagnostics, and auxiliary heater (boiler) regulation, and a graphical user interface.

Solar Hot Water Systems Design 49


Ezekiel Enterprises, LLC

4. DOD Installation Solar Hot Water Applications


4.1 Areas of potential Army use

There are a number of Army installations in the United States. They break down into several
general types: Introductory troop training, General troop installations, Proving Grounds, Depots, and
Arsenals. The installations that emphasize the training and support of troops have a large number
of housing units and corresponding dining facilities. Both of these types of buildings have a high
domestic hot water use and are good candidates for solar hot systems. All Army installations have
recreational and health care facilities, which also could be large domestic hot water users. The
administration, maintenance, training, storage, manufacturing, and service facilities are typically low
domestic hot water users and thus are poor candidates for a central solar hot water system to heat
their domestic water.

Air-conditioning system reheat for humidity control is another year-round heating energy use and
thus is a candidate for a solar hot water system. Humidity control is required in some administration,
data processing, communication, and health care buildings. To accomplish this control, the air in
the air-conditioning system is chilled to a low temperature for moisture removal. This air is normally
too cold to introduce into occupied spaces so it is reheated to a more comfortable temperature. The
energy to accomplish this reheat is a good candidate for the heat provided by a solar hot water
system.

Building profiles found at the different types of Army installations are:


• Army Introductory Troop Training Sites (Fort Benning, Fort Jackson, and Fort Sill)
o High density barracks and lodging
o Dining facilities
o Administration buildings
o Company Operation Facility (COF)
o Maintenance facilities (motor pools, aircraft wash areas, car washes)
o Recreational (Fitness centers, pools)
o Training
o Healthcare
o Service (Fire and police stations, PX, AAFES)
o Storage
o Central heating plants
• Army Troop Locations (Fort Bragg, Fort Campbell, etc.)
o Barracks and lodging
o Dining facilities
o Administration buildings
o Company Operation Facility (COF)
o Maintenance facilities (motor pools, aircraft wash areas, car washes)
o Recreational (fitness centers, pools)
o Training
o Healthcare
o Service (fire and police stations, PX, AAFES)
o Storage
• Army Proving Grounds
o Research and manufacturing buildings
o Lodging
o Storage facilities
o Administration buildings

Solar Hot Water Systems Design 50


Ezekiel Enterprises, LLC

o Recreational (fitness centers, pools)


o Healthcare
o Maintenance facilities (motor pools, aircraft wash areas, car washes)
o Service (fire and police stations, PX, AAFES)
• Army Depots
o Research and manufacturing buildings
o Lodging
o Storage facilities
o Administration buildings
o Recreational (fitness centers, pools)
o Maintenance facilities (motor pools, aircraft wash areas, car washes)
o Service (fire and police stations, PX, AAFES)
• Army Arsenals and Ammunition Plants
o Manufacturing buildings
o Lodging
o Storage facilities
o Administration buildings
o Recreational (fitness centers, pools)
o Maintenance facilities (motor pools, aircraft wash areas, car washes)
o Healthcare
o Service (fire and police stations, PX, AAFES).

The size of these installations can be small with as few as 50 occupied buildings. Others are very
large, having a population more than 70,000 people. Some are in very cold climates and others in
extremely hot/humid climates. A better description of each can be obtained by doing a internet web
search on a specific installation.

There is no “average size” Army installation; they have grown over time to serve a number of
different needs. Perhaps the best way to approach Army building groups is to look at what the Army
is doing now. The Army has recently standardized on a grouping of buildings to support the
supervising, housing, and training of combat troops. The troops are organized into a Brigade size
fighting unit and thus is called a Brigade Combat Team (BCT). The group of buildings are arranged
in a manner shown in Figure 4.1. Looking at this layout, the BCT consist of Barracks (light blue)
with a Dining Facility (purple) in the middle. Then the Headquarter Building (orange) is close by on
a through street. South of this street are green buildings called Company Operation Facilities (COF)
and red buildings called Tactical Equipment Maintenance Facilities (TEMF). The total building floor
space is about 1,402,000 sq ft (130,386 m2), which is divided into Barracks with 567,000 sq ft
(52,731 m2), Dining Facility with 31,000 sq ft (2,883 m2), Tactical Equipment Maintenance with
229,000 sq ft (21,297 m2), Company Operation Facilities with 447,000 sq ft (41,571 m2), and
129,000 sq ft (11,997 m2) for the Headquarters building.

The buildings that have the major DHW heating requirements are the barracks and the dining
facility. Some healthcare and recreational facilities also have a high DHW heating need. The rest of
the buildings have a very small DHW heating requirement that is most often satisfied with small
local heaters. As can be seen below there are 11 barracks buildings and one dining facility in the
BCT cluster. The average barracks size is 51,500 sq ft (4790 m2). Each barracks will house ~260
soldiers. The dining facility is 31,000 sq ft (2880 m2).

Solar Hot Water Systems Design 51


Ezekiel Enterprises, LLC

F igure 4.1. BCT building grouping at Fort Bliss.

The heating of these buildings can be from a central source such as a boiler plant that serves the
entire installation or a group of buildings within the installation. Another method often seen is
individual boilers in each building with one for heating the building and the other for generating
DHW. Even with a central boiler system heating the DHW is often by local building boiler
equipment.

Few Army installations have a cogeneration system where both electricity and heating hot water are
generated in the central plant. Most Army central boiler plants provide heating only and thus it can
be desirable to turn this system off during the nonheating season. About half the central systems
are steam distributed at a pressure in the range of 60 to 100 psi (414 to 689 kPa). The others are
hot water with temperatures as hot as 400 °F (204 °C).

The most common system is the use of local heating systems within a building. In this case DHW is
generated using a hot water boiler. The next most likely situation is a central heating system that is
used to heat the buildings, but the DHW is generated by a hot water boiler as above.

4.2 Building hot water demands

The barracks and dining facilities are large DHW users. The estimated DHW needs for a barracks
building is 30 gal (114 L) of hot water per soldier per day at a temperature of 140 °F (60 °C). Most
soldiers take two showers per day and one of them is in the morning, from 7:30 am to 8:00 am. To
handle this peak usage DHW is stored in a tank having the size of ~22.5 gal (85 L) per soldier.
Figure 4.2 graphs the heating rate throughout a typical week for a person's DHW use in a barracks.
Such a high DHW heating energy use makes a barracks a good candidate for a central solar hot
water system.

Solar Hot Water Systems Design 52


Ezekiel Enterprises, LLC

F igure 4.2. W eekly barrac ks domes tic hot water heating profile, B tu/s q ft by hour.

F igure 4.3. W eekly domes tic hot water heating profile, B tu/s q ft by hour for a dining fac ility.

The other building in the cluster that should be included in the central solar hot water system is the
dining facility. Figure 4.3 graphs DHW heating energy needs. Typically, these facilities are occupied
from 5:30 am to 7:30 pm. Three meals are served per day - breakfast (7:30 to 9:00 am), lunch
(11:00 am to 1:00 pm) and supper (5:00 pm to 6:30 pm). The schedule will change slightly on the
weekend. The hot water use of this facility is ~2.4 gal (9 L) per meal served. Assume that a dining
facility of this size would serve 7500 meals each day.

The office buildings have a hot water use of ~1 gal (3.79 L) per person per day. If the occupancy of
the building is not known, use 100 sq ft (9.3 m2) per person.

Solar Hot Water Systems Design 53


Ezekiel Enterprises, LLC

Another source for domestic hot water use is provided by NREL (shown below). Some guideline for
determining hot water loads for sizing commercial SHW systems are:
• Apartments: 20 gal (76 L) /day of 120 °F (49 °C) set temperature water per bedroom
• Hotels/Motels: 15 gal (57 L)/day of 125 °F (51.67 °C) set temperature water per room
• Laundries: 20 gal/10 lb (76 L/4.5kg). wash of 130 °F (54 °C) set temperature water
• Restaurants: 24 gal (91 L)/day of 140 °F (60 °C) set temperature water per 10 full meals served
• Retirement Homes: 18 gal (68 L)/day of 120 °F (49 °C) set temperature per room
• Office Buildings (without showers): 1 gal (3.79 L)/day of 120 °F (49 °C) set temperature
water per person.

4.3 Basic solar system design

Selecting the right solar water heating system for a federal facility will depend on three key factors:
climate, budget, and water usage needs. Solar water heating systems are economical, especially in
commercial buildings where the energy used to heat water is significant. There are a number of
technologies available to heat water efficiently. However, before implementing these technologies, it
is important to first reduce hot water use with water-saving fixtures and appliances.

Solar water heating systems can be used throughout the United States on any building with a
south-facing roof or unshaded grounds for installation of a collector. In addition, reliable off-the-shelf
systems can be selected from the Directory of the Solar Rating and Certification Corporation at:
www.solar-rating.org/ratings/ratings.htm

The Arizona Solar Center Albuquerque, NM uses system sizing estimates based on climate:
• Sunbelt—use 1sq ft (0.09m2) of collector per 2 gal (7.61 L) of tank capacity (daily usage).
• Southeast and Mountain states—use 1 sq ft (0.09 m2) of collector per 1.5 gal (5.71 L) of tank
capacity.
• Midwest and Atlantic states—use 1 sq ft (0.09 m2) of collector per 1.0 gal (3.79 L) of tank
capacity.
• New England and the Northwest—use 1 sq ft (0.09 m2) of collector per 0.75 gal (2.81 L) of tank
capacity.

Estimates will be affected by water temperature, consumption amount, and the solar resource
available at the site.

4.3.1 Simple system calculation

A simple evaluation procedure can help to determine if solar water heating is appropriate.
Traditional solar hot water heating systems are most cost effective in facilities with:
• Constant water heating load throughout the week and year; housing units and dining facilities
are good candidates.
• High fuel costs to heat water; this is area specific.
• Sunny climates (which helps, but is not required); this is area specific.

The economic viability of a solar system depends on:


• amount of annual sunshine
• heating energy requirements throughout the year
• cost of the solar system
• price of conventional fuels (are the utility rates high in your area?)
• financing and incentives available (for 3rd party investors)
• what temperature of hot water is required (e.g., swimming pool vs. laundry)
• annual operation and maintenance costs.

Solar Hot Water Systems Design 54


Ezekiel Enterprises, LLC

The step-by-step method listed in Table 4.1 can be used to estimate the solar system size and its
cost effectiveness. Table 4.2 lists general data for water heating loads for building types, solar
resource, etc. Numbers are included for a sample building in Denver, CO and assume that the
building uses electricity to heat water. The sample building group is four barracks, each housing
120 soldiers for a total of 480 soldiers. With a hot water use rate of 30 gal (114 L)/day/person, the
hot water use would be 14,400 gal (54,000 L)/day. The heating energy to make this hot water is:
Q = 14,400 gal/day x (140 °F – 60 °F) x 1 Btu/lb/°F x 8.3 lb/gal /3413 Btu/kWh = 2800 kWh)/day
= 9,556 MBtu/day

4.3.2 E quation 1 – S olar water s ys tem s ize


Estimate collector size using the following equation:
L kWh
Ac = =700 kWh/day /(0.25×6.1 /day)=459m2 [4939 sq ft]
ηsolar Imax m2

where:
2
Ac =collector area [m ]
L =Daily Load [kWh/day]
ηsolar =efficiency of solar system (assumed to be 0.40)
2
I max =maximum daily solar radiation [kWh/m /day] (Imax in the equation above means the system is
designed to meet the load on the sunniest day of the year, which eliminates excess capacity and
optimizes economic performance).
The paper “Annual System Efficiencies for Solar Water Heating” by Craig Christensen of National
Renewable Energy Laboratory and Greg Barker of Mountain Energy Partners presents calculated
efficiency for domestic solar water heaters that varies between 26.4% and 44.3% depending on
location and hot water load with an average of 40.2% for all locations and load profiles.
Table 4.1. Method to estimate solar system size and cost effectiveness.
E valuation Method S ample B uilding
Estimate daily water heating load 9,556,400 Btu/day 2,800 kWh/day
2
Determine the solar resource (kWh/day) 1,934.86 Btu/sq ft Maximum 6.1 kWh/m /day Maximum
2
1,744.55 Btu/sq ft/day Minimum 5.5 kWh/m /day Minimum
2)
Calculate solar system size 12,352.48 sq ft (1,148 m
- for water heating load on the sunniest day
- undersize rather than oversize the system
Calculate annual energy savings 3,576.82 Btu/yr (1.048,000 kWh/yr)
Calculate annual cost savings $88,000/yr
Estimate system cost $746,000
Calculate savings-to-investment ratio 2.8
Calculate simple payback period 8.5 yrs

Table 4.2. Typical daily water heating loads.


B arrac ks 30 gal/day/pers on (114 L /day/pers on)
Motel 15 gal/day/person (57 L/day/person)
Hospital 18 gal/day/person (68 L/day/person)
Office 1 gal/day/person (3.79 L/day/person)
Food Service 2.4 gal/meal (9 L/meal)
Residence 40 gal/day/person 151 L/day/person
School 1.8 gal/day/student 6.8 L/day/student

Solar Hot Water Systems Design 55


Ezekiel Enterprises, LLC

4.3.3 E quation 2 – Annual energy s avings

Annual energy savings (electricity in this example) can be estimated using the following equation:
Es = Ac Iave ηsolar365 / ηboiler = 1148 m2 X 5.5 kWh/m2/day X 0.40 X 365/0.88 = 1048,000 kWh/yr
= 3,576,824 MBtu/yr

Where:
Es = annual energy savings [kWh/yr]
2
I ave = average solar radiation [kWh/m /day]
ηboiler = auxiliary heater efficiency.
*

Typical auxiliary heater efficiencies are:


• Gas: 0.43 to 0.86, assume 0.57
• Elec: 0.77 to 0.97, assume 0.88
• Heat pump: assume 2.0
• Prop: 0.42 to 0.86, assume 0.57
• Oil: 0.51 to 0.66, assume 0.52.

4.3.4 E quation 3 – Annual c os t s avings

Annual cost savings can be estimated using the following equation:


S = Es Ce = 1048,000 kWh/yr X 0.084/kWh = $88,000/yr
= 3,576,824 MBtu/yr X $0.0246/MBtu = $88,000/yr

where:
S = annual cost savings [$/yr]
Ce = cost of auxiliary energy
Typically:
Electricity: $0.084/kWh[= $0.0246/MBtu
Natural Gas: $0.020/kWh = $0.0059/MBtu
Propane: $0.040/kWh = $0.012/MBtu
Oil: $0.025/kWh = $0.0073/MBtu.

4.3.5 E quation 4 – S olar s ys tem c os t

Solar system cost can be estimated using the information in Figure 4.4 and the following equation:
C = csolar Ac = $650/m2 X 1148 m2 = $746,000
(C = csolar Ac = $60.41/sq ft X 12,349 sq ft = $746,000)

where:
2
csolar = per-unit-area cost of installed solar system [$/m ], typically:
2
$650/m ($60.41/sq ft) for large system
2
$1600/m ($148.70/sq ft) for small systems
2
$1080/m ($100/sq ft) for medium size system.

* Gas Appliance Manufacturer’s Association.

Solar Hot Water Systems Design 56


Ezekiel Enterprises, LLC

F igure 4.4. S olar s ys tem c os ts .

4.3.6 E quation 5 – S avings -to-inves tment ratio

The savings-to-investment ratio can be calculated using the following equation:


SIR = S * pwf / C = $88,000/yr X 24/ $746,000 = 2.8 (project is cost effective if SIR>1)

where:
pwf = present worth factor for future savings stream
= 24 for 40-yr lifetime and 3% real discount rate (specified by NIST for 2009).

4.3.7 E quation 6 – S imple paybac k period


SPB = C / S = $746,000/$88,000 = 8.5 yrs

Another system sizing analysis would be:

For a location receiving 2,220 – 2,854 Btu/sq ft (7–9 kWh/m2) on a high-radiation day a system that
will provide heat for a domestic hot water system located will have a degree of utilization of ~50%.
The result is 1,110 to 1,427 Btu/sq ft (3.5 to 4.5 kWh/m2) of collector area provided as useful heat
for generating the hot water. The value of 4.0 kWh/m2 is equal to 13,650 Btu/m2 or 1,270 Btu/sq ft of
collector. This amount of heat can raise 19.2 gal water/m2 from 55 to 140 °F. A sq ft of collector
area can heat 1.8 gal. A solar storage system for this application should be in the range of 60 to
70% of the normal daily use. If the daily use is 1.8 gal/sq ft, then the storage tank size would be
~1.2 gal per sq ft

4.3.8 More ac c urate s izing approac hes

Consider a typical solar system providing heat to maintain domestic hot water at 140 °F (60 °C) in
the domestic hot water storage tank. There is an heat exchanger between the solar system storage
tank and domestic hot water system. To achieve a DHW temperature of 140 °F (60 °C), the

Solar Hot Water Systems Design 57


Ezekiel Enterprises, LLC

incoming stored water temperature must be 5 °F (2.7 °C) warmer or 145 °F (63 °C) as it enters the
heat exchanger, assuming a plate-and-frame type. The design temperature in the storage could be
as warm as 15 °F (-9 °C) to provide a few degrees for temperature loss and extra storage capacity.
There is another heat exchanger between the water storage system circulation and the collector
fluid circulation, which means the collector fluid should be a hot as 160 °F (71 °C) entering the
plate-and-frame heat exchanger.

Thus the solar collector leaving temperature will be a minimum 160 °F (71 °C), which will establish
the collector efficiency and the amount of heating energy the collector will produce per sq ft area.
Knowing the domestic hot water demands and the incoming cold water temperature this will
establish the energy demands for heating the domestic water. The size of the solar collector can be
determined from this information. In sizing the collector system, an important consideration in the
design is the selection of peak solar radiation. As the peak value chosen is reduced closer to an
average solar radiation value for a specific installation, there will be periods when the collector will
generate heat that the DHC system cannot consume. At these times, the collector system will have
no place to send the heat. The flow through the collector will stop and the collector system will go
into stagnation with the temperature of the heat transfer fluid going above the design 160 °F
(71 °C). If it goes high enough the heat transfer fluid will begin to vaporize.

In Section 4.3.1 (p 57) “rules of thumb” were used to determine the solar collector size. A more
accurate evaluation for determining the size of a solar hot water system would use values specific
to the collectors that are planned to be used in the system. The Solar Rating and Certification
Corporation (SRCC) provides such Information and efficiency ratings for collectors available in the
United States. This independent organization tests and provides a certification rating of various
solar collectors and solar water heating systems. Equipment that has certified and rated by SRCC
must show their certification label that provides the products performance rating. Information from
the SRCC is available through URL: www.solar-rating.org/ratings/ratings.htm

The SRCC performance ratings in Btu/sq ft/day are provided under three different solar weather
conditions - clear, mildly cloudy, and cloudy skies. Table 4.3 lists the five levels of service. The
ratings also include durability and efficiency. This information can be used to compare different
types of collectors. Although these ratings give the heat output for collectors, they do not provide
cost information. Look at the amount of heat (BTUs) the collector delivers per day relative to its
cost.

To compare two panels, first look at the service category (A through E) that represents water use.
Then look at the output of the three solar weather conditions for each panel. To determine the
collectors that produce the most heat for the least cost, figure the price per square foot of the
panels by dividing the panel price by the panel area. When comparing panels, some may perform
better in sunny conditions and some will perform better under cloudy conditions. Unless the system
will be located in an area with lots of cloudy days such as the Pacific Northwest, it is more important
for a collector to do better under sunny conditions than under cloudy conditions because there is
more heat to capture on sunny and partly sunny days than on cloudy days.

Table 4.3. Solar collector categories.


Us e Temperature
C ategory differenc e Typic al Applic ation
A -9 °F (-5 °C) Swimming pools and solar assisted heat pumps
B 9 °F (5 °C) Swimming pools and solar assisted heat pumps
C 36 °F (20 °C) Service hot water and space heating - air systems
D 90 °F (50 °C) Service hot water, space heating - liquid systems and space cooling
E 144 F (80 °C) Space heating - liquid systems, space cooling and industrial process heating

Solar Hot Water Systems Design 58


Ezekiel Enterprises, LLC

SRCC also tests and provides performance ratings for small hot water systems. Information is
provided on the storage tanks size and the total system performance for locations that can be
selected from a pull-down list. The computer program TRNSYS is used to determine the values,
which provide the Solar Energy factor (SEF), equivalent Solar Fraction, and equivalent solar
savings (QSOLAR).

The performance of a solar hot water system (its “ability to capture solar radiation” and its “ability to
deliver hot water”) depends on the configuration of the system (collector area, controller setting,
storage volume etc.), the current state of the system (i.e., temperature of the hot water in the
storage tank) and factors from its environment (notably the ambient temperature and insolation
patterns over the year). Indicators (SF, SN, and SE) that are used to measure the performance of
solar thermal systems are discussed in Section 3.1 (p 13). Another indicator is the standby hot
water volume, which is the amount of water at the desired delivery temperature that the system can
deliver at any time without any instant additional heating required for this delivery. With the following
situation, the standby hot water volume is 83 (= 50x[65-15]/[45-15]) liters of water (22 gal) without
any additional instant heating.
• Standby storage tank: 26 gal (100 L)
• Backup fraction: 13 gal (50 L)
• Set temperature of the backup: 149 °F (65 °C)
• Tapping temperature: 113 °F (45 °C)
• Cold water feed: 59 °F (15 °C).

The performance parameters SF, SN and standby hot water volume, together with the costs for the
heat form a triangle; that by maximizing one, others may be affected negatively. For example:
• Maximizing for SF means that the collector area and the store volume accordingly will be
maximized as to make more solar energy available, reducing SN, increasing the costs.
• Maximizing for SN means that the collector area will be undersized, because then excess
available energy is avoided, but less solar energy will be available for the user reducing.
• Maximizing for standby hot water volume means that a larger fraction of the store will be at a
higher temperature, which requires more auxiliary heating (lower SF) and also has a negative
effect on the efficiency of the collectors.´

Optimization thus involves a prioritizing and compromising (Figure 4.5).

Independent evaluation of single components of a solar system provides limited predictability of the
performance of the system as a whole (i.e., yield). With larger components (in particular the
collector area and the storage tank) the “principle of diminishing returns” applies. This means that
although the yield will increase when the collector area or storage tank volume is increased, the
marginal increase becomes smaller with increasing area and volume. In addition, maximizing one
component over others also has a strongly diminishing effect. A diminishing effect usually also
means an increase in energy costs (increase of marginal and average $/kWh). Simulations with
various component sizes aid in the design of an (cost) optimal system.

Solar Hot Water Systems Design 59


Ezekiel Enterprises, LLC

There are design tools available for sizing the


solar collector system. The National Renewable
Energy Laboratory (NREL) developed the
Federal Renewable Energy Screening Assistant
(FRESA) software that can help facility managers
determine if their building is a possible candidate
for a solar water heating system. This Windows-
based software tool screens federal renewable
energy projects for economic feasibility and
evaluates renewable technologies including solar
water heating systems, photovoltaic, and wind
energy systems. The Federal Energy
Management Program is developing a new
version, but information about the current version
is available at: www.wbdg.org/tools/fresa.php

A somewhat more detailed screening tool is F igure 4.5. Sizing is a compromise between
provided by the Canadian Retscreen at costs and yield.
www.retscreen.net/. This computer program is
available as a free download and it will model
glazed, unglazed and evaporative cooling solar hot water collectors. It uses f-chart to calculate the
estimated collector area required, annual solar energy yield, solar system efficiency, solar fraction
and pumping energy needed. The analysis is based on the input of average monthly solar radiation,
outdoor temperature and relative humidity and wind speed. The building's hot water use is input for
an average day over the year. This use cannot be varied. The results of this simulation compares
favorably with other year-long evaluations. If a more detailed engineering and economic analysis is
required, consider using the following software programs
• F-CHART, correlation method, available from the University of Wisconsin, available at
http://sel.me.wisc.edu/fchart/new_fchart.html.
• TRNSYS, software, available from the University of Wisconsin, available at
http://sel.me.wisc.edu/trnsys/.

F-Chart is available for the purchase price of $400 for a single user. It has the capability of modeling
flat plate, evacuated tubes, CPC and 1 or 2 axis tracking collectors. It can handle water storage
heating, building storage heating, domestic water heating, and integral collector storage heating.
The output can provide a life cycle analysis with cash flow.

Other computer programs that can be used for sizing the solar system are T*SOL and Velasoris
Poly Sun. The Federal Energy Management Program (FEMP) Help Line (800-DOE-EREC) provides
manuals and software for detailed economic evaluation and for the Energy Savings Performance
Contracting Program, which allows federal facilities to repay contractors for solar water heating
systems through bills for energy savings instead of paying for initial construction.

4.4 Cost effectiveness

4.4.1 C os t of c entralized vers us de-c entralized s ys tems

Cost of Collectors Vs System Cost. When comparing solar thermal system alternatives: system
size, configuration, types of collectors, etc., all cost components over the full lifecycle of the system
should to be taken into account. This requires detailed information on the system hardware and
results of system’s performance simulation.

Solar Hot Water Systems Design 60


Ezekiel Enterprises, LLC

Advanced technology and production economies of scale have led to significant cost reductions in
solar hot water collectors. The value of shipped low-temperature collectors was $1.89/sq ft
(~14 €/m2) in 2008. The average cost of thermosyphon systems with the storage integral to the
collector was $24.27/sq ft (~183 €/m2) ; the price of flat-plate collectors was $17.40/sq ft
(~131 €/m2); the price of evacuated tube solar collectors was $25.69/sq ft (~194 €/m2); and the price
of parabolic trough solar collectors was $11.96/sq ft (90 €/m2) These values are based on collector
factory revenue divided by output, so retail prices would roughly double (not including labor for
installation), and the installed system price with all the other components is on the order of $75 to
$225/sq ft (565 to 1696 €/m2) depending on project size and location. New construction systems
usually have better economics than retrofit projects because of reduced installation expenses.

Independent evaluation of a single system component cost and its performance, e.g., solar
collector, provides limited information for the whole system evaluation. Increasing the size of a
single component (e.g., the collector area or the storage tank volume) results in “diminishing
returns.” This means that, although the yield will increase when the collector area or storage tank
volume is increased, the marginal increase becomes smaller with increasing area and volume.
Also, maximizing one component over others has a strongly diminishing effect, which usually
results in increased energy costs ($/kWh). Simulation of the system with variation of component
sizes aid the design and energy cost optimization. Figure 4.6 shows approximate composition of the
large system first cost.

Large central solar water heating systems are normally more cost effective due to economies of
scale in installation, operation and maintenance compared to several small systems. This includes
higher efficiencies possible * for backup heating systems in centralized systems. Table 4.4 lists the
approximate effect of the solar thermal system size on investment cost generated from analysis of
case studies described in Section 4.5 (p 71).

Collector field (incl.


Control Other costs Support structure
Buffer storage & 4.5 % 2.9 % and installation)
heat exchanger 48.4 %
11.4 %

Planning
14 %

Piping (other)
14.3 % Piping (collector
field)
4.5 %

F igure 4.6. Dis tribution of c os ts for a large s olar thermal s ys tem ins tallation (R egenerative
E nergies ys teme).

* This depends on the specific configuration, but in particular equipment costs and boiler operating efficiencies are meant here.

Solar Hot Water Systems Design 61


Ezekiel Enterprises, LLC

Table 4.4. Economies of scale.


P ric e R anges - Total Inves tment S olar S ys tem
Large scale systems Medium scale systems Small scale Systems
2
>10,000 sq ft (930m ) 1,000 – 10,000 sq ft 500 – 1000 sq ft
2 2
93 – 930 m 46 – 93 m
av. $50/sq ft av. $100/sq ft av. $150/sq ft
2 2 2
~377 €/m ) ~754 €/m ) 1,130.55 €/m

The values in Table 4.4 represent a first approximation and do not apply to every large building or
cluster of buildings. The main criterion is the heat demand of the building or a cluster of buildings
and their density (required distribution system).

4.4.1.1 System efficiency factor

Losses in heat distribution increase with distance and have an additional negative effect on overall
system efficiency. For example, for large centralized systems the required storage temperature and
delivery temperatures increase (above the operating temperature) due to heat losses through the
walls of a storage tank and in the distribution system. Simulations of specific system is required to
determine the overall performance (e.g., distribution losses as a fraction of the energy supplied).

4.4.1.2 Operation

In the particular situations with high peak loads and long periods when there is no hot water use in
some buildings (e.g., in barracks during soldiers’ deployment) central system will simplify
adjustments needed to control such situations and potentially reduce the damage to the system. In
the case of compounds with multiple barracks, large central SWH system can be more easily
installed, maintained, and operated. Even finding a location for the solar collectors may be simpler.
Large SWH systems also have the advantage in that the influence of individual users is minimal on
their operation.

Small SWH systems require periodic checking and maintenance. Scheduling of maintenance for
many distributed systems may be an issue of prioritization. On the other hand, maintenance of large
central systems is more critical since a larger number of users could be affected and thus system
monitoring and preventative maintenance are required activities to assure good performance.

4.4.1.3 Storage

Thermal losses from the storage tank have a significant effect on the efficiency of the solar thermal
system. Heat is lost via the surface. The capacity of a sensible storage tank (e.g., water steel tanks)
is defined by its volume. The volume grows with the 3rd potency of its circumference. The surface
grows with the 2nd potency. Thus storage tank losses are reduced when one large store is used in
comparison with many small storage tanks.

4.4.1.4 Back-up /auxiliary heating

Each solar thermal system must have a back-up heating supply. Oil, gas, electricity, or biomass is
used as a heat source. Due to the 20+ year lifecycle of heating systems, including solar thermal
systems, possible changes in energy supply options should also be considered. This could, for
example, relate to future auxiliary (back-up) heating options from biomass (bio-waste) and waste
heat supplies. In the case centralized systems, these options are often more easily integrated later.

Solar Hot Water Systems Design 62


Ezekiel Enterprises, LLC

4.4.2 Large scale SWH cost effectiveness

Monetary savings from installing a solar water heater depends on a variety of factors, including
climate, the amount of hot water used at your location, the cost of conventional fuels, and system
performance. Using these parameters for a large solar hot water system that could be applied to a
cluster of buildings, the cost effectiveness can be illustrated with regional coloring presented on the
maps of the United States shown in Figures 4.7 to 4.10. The information presented in these figures
are for solar hot water systems that are replacing electrical or gas heating of hot water. An average
efficiency of 40% for the solar system is assumed and a life of 40 yrs is used in the analysis. Two
solar system costs are used: $50 per sq ft of collector, and $75 per sq ft (~377 €/m2 and 565 €/m2).

2
F igure 4.7. C os t effec tivenes s of s olar hot water s ys tems pric ed at $50/s q ft (~377 €/m ) replac ing
elec tric al heating us e.

Solar Hot Water Systems Design 63


Ezekiel Enterprises, LLC

2
F igure 4.8. C os t effec tivenes s of s olar hot water s ys tems pric ed at $75/s q ft (~565 €/m ) replac ing
elec tric al heating us e.

2
F igure 4.9. C os t effec tivenes s of s olar hot water s ys tems pric ed at $50/s q ft (~377 €/m ) replac ing
gas -fired heating us e.

Solar Hot Water Systems Design 64


Ezekiel Enterprises, LLC

2
F igure 4.10. C os t effec tivenes s of s olar hot water s ys tems pric ed at $75/s q ft (~565 €/m ) replac ing
gas -fired heating us e.

This course is focused on large centralized solar thermal systems with short and medium-term
storages connected to heating networks and they provide much lower specific system costs than
decentralized small-scale solar systems. As can be seen in Figure 4.11, the cost/benefit-ratio
(investment cost/ energy savings per year) for large solar systems with collector areas > 1,076 sq ft
(100 m2) is about half that of small, decentralized systems, and can even be reduced by more than
20% when using large scale systems combined with seasonal storages.

A general rule of thumb for federal facilities is that a renewable energy installation should pay for
itself within about 10–15 yrs. System life spans can be as much as 30 yrs, which means a facility
can look forward to as much as 20 yrs of “free energy.”

Appendix A (Not in Course) provides includes descriptions of a number of case studies, which
illustrate the application of solar hot water collector systems that supply buildings with hot water
and heat.

There are very few large solar collector systems in the United States. In Europe the use of such
systems is more commonplace. Table 4.5 lists the selected systems size, cost, and performance
values.

Solar Hot Water Systems Design 65


Ezekiel Enterprises, LLC

F igure 4.11. C os t/B enefit ratios of s mall dec entralized s olar thermal s ys tems vs . large s olar thermal
s ys tems with different s torage c apac ities c onnec ted to heating networks .

Table 4.5. Summary of selected solar system case studies.


S olar E nergy
C ollected,
T ype S ize S torage Vol. MB tu/yr/s q ft S ys tem Temp., out/in
L ocation C ollector s q ft (m 2) gal (L ) C os t (kW h/m 2) °F (°C )

Austria - AEE
Gneis Moos, Flat Plate 4,412 (410) 26,420 (99,999) $218,530 119.9 (377) 149(65) / 86–95 (30–35)
Salzburg
Wasserwerk Flat Plate 41,481 (3,857) 17,067 (64,599) $1,950,000 131.6 (415) 167–248 (75–120) / 140 (60)
Andritz
UPC arena Graz- Flat Plate 15,139 (1,407) - $223,860 114.2 (360) 167–248 (75–120) / 140 (60)
Liebenau
Demark- ARCON
Ulsted, Denmark Flat Plate 53,929 (5,015) $1,700,000 377.1 (1,189) 167– 248 (75–120) / 140 (60)
Strandby, Flat Plate 86,769 (8,069) 396,423 (1,500,461) $2,900,000 314.0 (990) 194–185 (90–85) / 68–50 (20–
Denmark 10)
Frederikshavn, Flat Plate 1,614 (150) 1,320 (4,996) $50,000 149.1 (470) 140 (60)/60 (16)
Denmark
Skørping, Flat Plate 5,918 (550) 396,423 (1,500,461) $190,000 124.7 (393) 149 (65) / 77 (25)
Denmark
Braedstrup, Flat Plate 86,769 (8,069) 528,564 (2,000,614) $2,500,000 125.9 (397) 158–194 (70–90) / 95–101 (35–
Demark 38)

Frankfurt/Main, Flat Plate 2,712 (252) 775 (10,503) 182,838E 83.1 (262) DHW
Germany
Old Flat Plate 5,864 (545) 26,428 (100,029) 357,020E 59.4 (187) 153 (67) / 90–99 (32–37)
Slaughterhouse
Speyer, Germany
Residential area Flat Plate 3,077 (286) 6,607 (25,007) 189,200E 92.9 (293) 160–180 (71–82) / 126–140
Speyer, Germany (52–60)
Residential area Flat Plate 2,098 (195) 2,640 (9,992) 208,851E 97.9 (309) 149–176 (65–80) / 132–135
Nordemey, (56–57)
Germany

Solar Hot Water Systems Design 66


Ezekiel Enterprises, LLC

S olar E nergy
C ollected,
T ype S ize S torage Vol. MB tu/yr/s q ft S ys tem Temp., out/in
L ocation C ollector s q ft (m 2) gal (L ) C os t (kW h/m 2) °F (°C )
Residential area Flat Plate 9,218 (857) 10,570 (40,007) 549,570E 129.1 (407) 149–203 (65–95) / 97–106 (36–
Hennigsdorf, 41)
Germany
Residential area Flat Plate 4,049 (376) 11,100 (42,013) 234,561E 100.3 (316) 155–161 (68–72) / 113–123
Heilbronn, (45–51)
Germany
Apt. Bldgs. Flat Plate 1,333 (123) 1,586 (6,003) 99,410E 99.8 (315) 162–175 (72–79) / 117–135
Hannover, (47–57)
Germany
Residential area Flat Plate 16,613 (1,545) 23,780 (90,007) 797,788E 96.7 (305) 171 (77) / 122 (50)
Stuttgart,
Germany

Saint Paul, MN, Flat Plate 21,034 (1,956) System uses district $2,200,000 (Less than 180 °F – 190 °F (82 – 88 °C)/
USA heating distribution 1 year’s data 160 °F (71.1 °C) (design
system as tank; solar available) temperatures)
storage volume: 1200
gal (4542 L)

Paradigma paper
Trade Park, Vac Tube 667 (62) 1,585 (5,999) $52,500 168.8 (532) 140–194 (60–90) / 77–144 (25–
Housing Estate 60)
Ritter, Karlsbad,
Germany
Festo, Esslingen, Vac Tube 14,310 (1,330) 4,491 (16,998) $825,000 124 (391) 176–203 (80–95) / 167–185
Germany (75–85)
Cooney Island, Vac Tube 1,761 (163) 3,963 (14,999) 203.4 (641) 140–194 (60–90) / 77–140 (25–
New York 60)
Alta Leipziger, Evac Tube 1,268 (117) 1,849 (6,998) $135,000 145.3 (458) 149–194 (65–90) / 95–158 (35–
Oberunsel, 70)
Germany
Panoramasauna, Evac Tube 1,057 (98) 0 $84,000 193.4 (610) 158–194 (70–90) / 149–176
Holzweiler, (65–80)
Germany
Wohnheim Evac Tube 505 (46) 1,321 (4,999) $38,000 162.2 (511) 140–194 (60–90) / 95–158 (35–
Langendamm, 70)
Nienburg,
Germany
Kraftwerk, Halle, Evac Tube 241,024 (22,415) 9,511,200 (35,999,892) $12,900,000 124.6 (393) 176–203 (80–95) / 131–149
Germany (55–65)
Wels, Austria Evac Tube 39,629 (3,685) 0 $3,000,000 146.4 (461) 194– 239 (90–115) /167–221
(75–105)
AWO Rastede, Evac Tube 1,054 (98) 0 $112,500 174.4 (550) 167–185 (75–85) / 140–158
Oldenburg, (60–70)
Germany

METRO Istanbul, Evac Tube 11,063 (1,028) 3,963 (14,999) $760,000 200.1 (631) 176–203 (80–95) / 167–185
Turkey (75–85)
USA - NREL
Edison, NJ Evac Tube 150 (13) 280 (1,059) $26,000 121.7 (384) 180 (82) / 60 (16)
Philadelphia, PA Evac Tube 576 (53) None $58,000 248.3 (783) 140 (60) / 60 (16)

Phoenix, AZ Parabolic 17,040 (1,584) 23,000 (87,055) $650,000 3.964 (12) 140 (60) / 60 (16)
Modesto, CA Parabolic 57,969 (5,391) None 14,600 (46,016) 460 (238) / 420 (216)

Solar Hot Water Systems Design 67


Ezekiel Enterprises, LLC

5. Des ign C ons iderations


5.1 Collector site placement

In an US Army installation, solar collectors can be placed on building roofs or on the ground
adjacent to the buildings they would serve. Rooftop is limited by useful area and maintenance is a
greater issue than with ground-placed systems. Access to roof mounted systems is more difficult;
stairs or ladders need to be climbed, and space for safe movement between the collectors and the
roof edge must be provided and maintained. Ground placement of the collectors can displace green
spaces that are desired in building clusters, thus limiting the number of buildings to a given ground
area. A compromise may be to place large collector systems above parking spaces in the soldier
parking lots so the collectors can shade vehicles, and still remain close to the buildings and to the
ground level for ease of maintenance. Figure 5.1 shows solar collectors located in a parking area.

When using a roof placement make sure that the predicted life of the roof is about equal to or longer
than that of the solar system. Avoid placing a solar system having a life of 20 yrs on a roof
scheduled for replacement in a shorter time.

Increasing the collector field distance to the mechanical room and storage tank increases losses
and should always be minimized. The maximum distance should be less than 600 ft (1823 m) one
way.

F igure 5.1. S olar hot water c ollec tors plac e above automobiles where they are parked.

Solar Hot Water Systems Design 68


Ezekiel Enterprises, LLC

5.2 S truc tural (foundation)

The support of the rooftop solar collector becomes part of the building's structural system. For small
collectors serving a single wood frame building the collector system can typically be secured
directly into the roof rafters. For larger installations more typical of that on US Army barracks, dining
facilities, and other buildings, an engineered substructure is generally required to meet local codes
and to support the collector arrays. The design object would be to use less material and fewer roof
penetrations. Considerations of the supporting structure design are:
• Penetrations though the roof for connection to the existing structure must be water tight using
properly sealing methods. Apply insulation where needed.
• Dynamic loads of wind and snowfall (see Figure 5.2) must be included in the structural analysis
• Expansion and contraction of system components must be considered.
• Where geographically required, seismic loads shall also be included in the structural design.
• The system design must provide access for maintenance and safe movement near roof edges.

Snow

Collector

Wind

Base Plates

F igure 5.2. F orc es on s olar c ollec tor that determine s truc tural requirements .

Solar Hot Water Systems Design 69


Ezekiel Enterprises, LLC

A major concern with the installation of solar collectors is the wind impact on the structure.
Increased wind loading on the support substructure can be offset by increasing the securing
mounting points and reducing the tilt of the solar collector. A taller solar collector has a greater wind
resistance and thus a higher wind load.

A typical engineered substructure supporting the solar collectors consists of beams or open web
joists mounted on supports attached to the building structure below the roof. These reasonable
spaced attachments are optimized with the cost of the rest of the supporting structure. The cost on
a flat roof is ~$10/sq ft (~75.4€/m2). If the use of reasonably spaced support points is not desired,
the support structure must span longer distances up to the width of the roof. The cost of using the
longer span can approach 2.5 times the structure having intermediate supports. The frame that
supports the solar collectors should be made using a non-corrosive metal such as aluminum.

Collectors mounted on sloped roofs typically take the roof slope as their tilt angle. This should be
between 20 and 50 degrees. Slopes within this range on a sun facing roof will have only a slight
reduction in performance when compared with the optimum tilt angle. These collectors may be
attached a few inches above the roof to allow for rain water to flow underneath. Another style of
placing solar collectors on a sloped roof is to integrate them into the roof surface. Figure 5.3 shows
how these collectors form part of the roof replacing the roof materials being used. Pipe connects
directly to the collectors from the ceiling space below. In-roof placement typically requires roofs with
a slope of not less than 20 degrees to avoid standing water on the glazing, which may void the
manufacturers water tightness guarantee.

Collectors can also be placed in a vertical wall (Figure 5.4). Flat plate collectors attached to a full
surface of the building façade can eliminate the need for insulation and a weatherproof covering for
the affected wall area, thus providing avoided cost savings that will offset the reduction in solar
energy collection performance.

Collectors placed on flat roofs or the ground need to be arranged so that the optimum performance
can be achieved. The materials used for constructing the structural supports need to be protected
from corrosion. The use of steel hardware and fasteners in contact with aluminum collector frames
and copper piping create a high likelihood of corrosion. Separating dissimilar materials with
fluorocarbon polymer, phenolic, or neoprene rubber materials is recommended,

F igure 5.3. C ollec tors integrated into the F igure 5.4. C ollec tors integrated
roof as a s truc tural element. into the faç ade as a s truc tural
element.

Solar Hot Water Systems Design 70


Ezekiel Enterprises, LLC

Placement distance between rows must be such that shading of one row by the next row behind is
minimized. A slight amount of shading in the winter when the sun is lowest in the horizon can be
permitted if the space for collectors is limited or piping costs are a concern since the solar radiation
lost is a small percentage of the total annual amount. In areas where snowfall is normal a space of
at least 12 in (30.5 cm). between the roof and the lowest collector part should be provided to allow
for the collection of snow that has slid off the collectors. There also should be space for safe human
movement between the collectors and around the end of collector rows. The space between the
roof edge and the collector row must satisfy local building codes. Figure 5.5 shows a diagram of the
space between collector rows (located on the ground or flat roofs) when the collectors are placed
one behind the other on a horizontal surface.

When placing the collector on a roof, care must be taken not to damage the roof surface or interfere
with other roof functions. Placement should allow for proper operation roof drains, HVAC and
exhaust systems, plumbing vents, flues, or chimneys and antennas. Space for maintenance of the
roof and those system placed on the roof shall also be provided. If the roof can handle the addition
load of the solar collectors, then the collector supports can be attached to concrete slabs placed on
the roof. To avoid harming the roofing below them these pads need to be placed on protective
mats. Roof penetrations for structural connections and piping need to be made water tight. This is
typically done using sleeves that surround the connecting structural or piping components, and that
pass through the roof. A sealant is placed in the sleeve to form a watertight barrier and the top of
the sleeve is ~3 in (77 mm). above the probable roof water level. The sleeve is appropriately
flashed around for a good weather tight roof penetration. Figures 5.6 to 5.8 show several methods
of supporting solar collectors on the ground or on a flat roof. It is advised that the roofing company
that installed the roof be used to perform the roof work required to install the solar collector to
preserve the remaining roof warranty.

F igure 5.5. S pac ing between c ollec tor rows .

Solar Hot Water Systems Design 71


Ezekiel Enterprises, LLC

Figure 5.6. Collectors mounted on a trapezoidal sheet filled with a rock material.

Figure 5.7. Collectors mounted on concrete slab.

Solar Hot Water Systems Design 72


Ezekiel Enterprises, LLC

F igure 5.8. R oof s upport c ons truc tion example.

5.3 Mechanical

5.3.1 Piping

Generally Type L copper, black steel and stainless steel are appropriate materials for the piping
system. When using copper tubing, hard soldering is recommended for the collector loop. Care
must be taken in using Teflon tape to seal threaded pipe joints when water /glycol is being
circulated in the pipes. With proper dielectrics, black steel piping can be used on the collector side
for use with glycol systems.

All piping shall be sloped at 1/4 in/ft (6.35 mm/0.30 m) of run back to the drain back tank. High
points shall be kept to a minimum and combination automatic air vent valve/vacuum breakers shall
be placed at all high points. Discharge of automatic air vents shall be piped back to the drain back
tank and be provided with an in-line sight glass.

Piping should be designed for low pressure drop and the shortest routes used. All exposed piping
should be well insulated with approved weather resistant insulation. Dielectric unions should be
used at connections between dissimilar metals. Rubber or silicone hose used for connections must
be of a high temperature type. The pipe ends should have ferrules to provide a good seal with the
hose.

Pipe sizing should be in accordance with recognized methods. Figure 5.9 shows an example of a
pipe layout with sizes for a collector field. The pipe sizes shown are metric sizes for copper tube.
The equivalent nominal US copper pipe sizes are:
• 16u = 1/2 in.
• 19u = 5/8 in.
• 29u = 1 in.
• 35u = 1-1/4 in.
• 41u = 1-1/2 in.
• 54u = 2 in.

Solar Hot Water Systems Design 73


Ezekiel Enterprises, LLC

F igure 5.9. Pipe sizes used in a reversed return piping system.

The piping system (valves, pumps, fittings, flanges, connections, and insulation) should be
designed to withstand the special conditions caused by the extreme temperatures of stagnation,
e.g., 320 °F (160 °C) plus, and frost, e.g., -5 °F (-21 °C); expansion of pipe-length; pressure (e.g.,
steam) and working fluid (e.g., corrosion). An expansion vessel of sufficient size should also be part
of each closed piping network. The system should be designed to operate at a pressure less than
125 psig (861.75 kPa), which will allow the use of standard piping components (class 125). A
discussion of system temperatures and pressures is found in Section 3.4.2 “Stagnation” (p 33).

Collector piping must be able to withstand the expansion and contractions of components caused
by the changes in temperatures that could be experienced. These temperature changes typically

Solar Hot Water Systems Design 74


Ezekiel Enterprises, LLC

occur daily, which is significantly higher number of cycles than experienced by a normal heating
system. The use of offset elbows, high pressure hoses, and expansion couplings should be
considered rather than expansion loops unless they are placed horizontally due to drainage
difficulties they would create.

Corrosion is a major concern in the solar hot water system. The two types of corrosion that cause
the most galvanic damage and pitting corrosion. Solar energy systems generally contain a number
of different metals such as aluminum, copper, brass, tin, and steel. This makes the solar system a
prime candidate for galvanic corrosion. Heat transfer fluids can contain chemicals and heavy metal
ions that would cause local or pit corrosion.

Galvanic corrosion is a type of corrosion caused by an electrochemical reaction between two or


more different metals in contact with each other. A chemical reaction between the metals causes a
small electrical current that erodes material from one of the metals. If the dissimilar metals are
physically joined or if they are contacted by a common storage or heat-transfer fluid, the possibility
of galvanic corrosion becomes much greater. Pitting corrosion is a highly localized form of corrosion
resulting in deep penetration at only a few spots. This type of corrosion can take years to form, but
can be very troublesome since it causes leaks that are difficult to locate.

Pit corrosion occurs when heavy metal ions such as iron or copper plate on a more anodic metal
such as aluminum causing a small local galvanic cell can be formed. This corrosion spot or “pit”
usually grows downward in the direction of gravity. Pits can occur on vertical surfaces, although this
is not as frequent. The corrosion pits may require an extended period (months to years) to form, but
once started they may penetrate the metal quite rapidly. Heavy metal ions can either come as a
natural impurity in a water mixture heat transfer fluid or from corrosion of other metal parts of the
solar system.

Pitting corrosion has the same mechanism (concentration cell) as crevice corrosion. Thus, it can
also be aggravated by the presence of chloride or other chemicals that can be part of the water
mixture or a contaminant from solder fluxes. Aluminum is very susceptible to pitting corrosion, while
copper generally is not.

Several preventive measures will eliminate or at least minimize galvanic and pitting corrosion in
collector systems that use an aqueous collector fluid. The best method to prevent galvanic
corrosion is to avoid using dissimilar metals. Where this is not possible or practical, the corrosion
can be greatly reduced by using nonmetallic connections between the dissimilar metals, thus
isolating them. Galvanic protection in the form of a sacrificial anode is another method of protecting
the solar system metals. Also, use of similar metals reduces the problems of fatigue failure caused
by thermal expansion. Pitting corrosion is essentially eliminated if copper absorber plates are used
in the solar collectors. Corrosion inhibitors can minimize pitting corrosion in aluminum absorbers.

When sacrificial anodes are to be used Their placement is important to obtain good protection and it
depends on what is being protected, the anode material being used and the electrical conductivity
of the heat transfer fluid.

5.3.2 V alves

Valves are used in the solar hot water system for balancing flow, flow adjustment, component
isolation, and for temperature and pressure control. These valves should be of the same material as
the pipe. At drainage locations of the collector piping ball valves should be used.

For solar collector arrays, the piping design can create nearly equal flow, but a balancing valve may
be needed for a final adjustment. Use of these valves should be minimized since their use adds to

Solar Hot Water Systems Design 75


Ezekiel Enterprises, LLC

the pressure drop in the piping system. Each collector array should also have a ball valve at the
inlet, and a three-way valve at the outlet, with the third port open to atmosphere for isolation. Use of
these valves will allow parts of the system to be taken out service for maintenance, repair, etc. while
the remaining parts of the system are operating. These valves can also be used to stop flow as part
of a freeze protection plan. Both of these valves are manually operated. The balancing valve should
be set during fluid flow system set-up and then fixed at that position.

At heat exchangers, fluid flow adjustment may be necessary to assure the appropriate temperature
is being delivered by the solar system components. For example, a mixing valve is used to blend
hot water with cooler return water so that a 140 °F (60 °C) domestic hot water is delivered to users.
Another example is flow control valves that can be used to direct heated water to the proper height
of the storage tank to minimize mixing of different water temperatures. Figures 3.21 through 3.25
show such arrangements.

Valves, other than seasonal or emergency shut-off valves, should be electrically operated and
located out of the weather or well protected. A vent must be provided at the high point in liquid
systems to eliminate entrapped air and it should also serve as a vacuum breaker to allow draining
of the system. To avoid multiple venting, systems should be piped to avoid having more than one
high point. Pressure relief by safety relief valves must be provided at some location in each flow
circuit that can be isolated by valves. The safety valves must be sized for flow conditions that could
occur under stagnation. Check valves can be added to prevent thermally induced gravity circulation.
A flow-check valve (used in the hydronic heating industry) will also accomplish the same purpose.

When the solar storage tank contains hot water to be used as DHW, an anti-scald valve is often
required on the leaving DHW pipe to limit the outlet temperature, which can reach temperatures of
176 °F (80 °C). Care should be taken to compensate for any pressure drop this valve adds to the
DHW circulating piping system.

5.3.3 S trainers and filters

Piping accessories such as fluid strainers and filters are those that would be used with any heating
system. They should be place at the inlet of pumps and before control valves.

5.3.4 F luid pumps

The type pump to be used is a centrifugal type that is used in building heating systems. If the loss of
fluid to the environment is a concern a seal-less magnetic drive centrifugal pump should be
considered. The pump components (seals, gaskets, bearings, etc.) must be able to withstand hot
temperatures that could reach may reach 300 °F (149 °C) for short periods. Basically, three types of
pumps are available:
• constant flow pumps
• electronic pressure controlled pumps (variable flow)
• high efficient pressure controlled pumps (variable flow).

Variable speed wet rotor circulators are preferred since they can operate the collectors either at a
setpoint, or the most efficient range, while minimizing the electricity used to drive the pump. The
use of variable flow is a method for achieving the desired temperature rise of the heat transfer fluid
in the solar collectors. If the solar radiation is not very intense, then the fluid flow is reduced,
causing the fluid to spend more time in the collector. Figure 5.10 shows the difference in energy use
of these different methods of pump operation.

Solar Hot Water Systems Design 76


Ezekiel Enterprises, LLC

Power Consumption Heating Pumps

High efficient pressure controlled

Electronic pressure control

Constant flow

kWh / year (at 6.100 hrs / year and 18 EUR-Cent / kWh)

F igure 5.10. Pump motor energy use under various modes of operation.

Sizing of the pump is accomplished in the normal way of heating pump selection. An estimate of the
flow rate can be made using the common flow rate for the collector field of 0.020m gpm per sq ft of
collector area (when using water as the collector fluid). If a 40% glycol mixture at 140 °F (60 °C) is
the collector fluid, then the flow rate would be ~10% more than a water solution. For a more
accurate value, use of the computer programs identified in Section 4.3.2 (p 58).

If water is the circulated fluid and the system is open to the atmosphere or the water is potable then
the pump wetted components should be made from stainless steel or bronze to minimize corrosion.
Solar collector pumps should be placed in locations where leakage would not cause serious
damage

5.3.5 Type of heat exchangers used

There are two types of heat exchangers to chose from: plate-and-frame, and tube-and-shell. Plate-
and-frame heat exchangers are most economical for commercial systems as they take up little
space and do not need insulation. They provide the highest approach temperature (the leaving
temperature of the secondary fluid compared to the entering temperature of the hotter primary
fluid). Plate-and-frame exchangers need very clean surfaces to obtain this performance and thus
require a nightly reverse backflush to break free any accumulated deposit on the water side.

Tube-and-shell heat exchangers are a good option for light commercial applications since they are
also practical in this setting (in terms of size), and because they have having good resistance to
fouling since the water passages are large. The leaving temperature of the secondary fluid will be
lower with this type of heat exchanger.

Conversely, water quality also affects system components; for areas with hard water (hardness >
100ppm), a closed loop or water softener should be used.

Generally stainless steel or copper is selected as a material for heat exchanger construction
because of their good heat transfer properties and corrosion resistance.

If the heat transfer fluid is not safe for human consumption or is toxic (like ethylene glycol) then a
double wall heat exchanger is required. Figure 5.11 shows an example of this type of heat
exchanger where a volumetric space is filled with a nontoxic heat transfer fluid between the two
circulating fluids.

Solar Hot Water Systems Design 77


Ezekiel Enterprises, LLC

F igure 5.11. S hell and double tube heat exc hanger us ed to protec t potable water from harmful heat
trans fer fluid leaks .

A leak in one side would become visible and the other fluid could not become contaminated. Leak
detection would involve noting a change in the fluid level in the interim space or a change in color of
the interim fluid. When plate-and-frame heat exchangers are used leak detection can be provided
by an additional heat exchanger circulating loop filled with a colored fluid for detection fluid between
the glycol used in the collector circulating loop and the domestic water system. A check of the
current building code should be made to determine the acceptable method of isolation.

To help minimize pumping energy, the pressure loss of the heat transfer fluids passing through the
heat exchanger should be limited to 1 to 2 psi (6.9 to 14 kPa). Heat exchangers used to heat
domestic water are exposed to the potable water pressure and thus should be rated for that
pressure, typically above 75 psi (517 kPa).

5.3.6 T ype s torage tank us ed

The storage tank or tanks for a large hot water heating system should be placed near the solar
collectors. These tanks are normally a non-pressurized type, which is open to the atmosphere using
a vent in the top cover. The reason for this is the high cost difference of big tanks needed in large
solar thermal systems. Pressurized tanks must be ASME rated in accordance with the maximum
possible pressures and temperatures. (System designer to reference the requirements of the ASME
boiler and pressure vessel Code for determination of requirements.) Non-pressurized systems are
allowed and may be necessary to make the system LCCA attractive due to the high cost of ASME
rated tanks. In instances where the tanks are non-pressurized, ASME rated tanks are not required.
When using a non-pressurized tank, it must be the high point of that circulating fluid system

Domestic hot water storage tanks should be in the building where the hot water is consumed.
These tanks would be typically smaller than the system storage tank and should be of a pressurized
type. The tank can be piped so its water is warmed by water flowing from the solar heated storage
tank and non-solar methods. Here a fossil fuel or electric heater can assure the proper domestic hot
water temperature is being maintained.

Solar Hot Water Systems Design 78


Ezekiel Enterprises, LLC

Storage tanks can be made using steel, fiberglass/plastic, or concrete. Steel tanks make
connections with the piping easy, are subject to corrosion; large tanks may require on-site
fabrication. Fiberglass/plastic tanks do not corrode, but have a maximum temperature in the range
of the temperature that could be expected during stagnation, they cannot be pressurized, and they
are more costly. Concrete tanks are low cost, but must be site fabricated, cannot be pressurized,
and can make plumbing connections difficult. Steel tanks should be lined with glass, epoxy, or other
corrosion resistant material rated for the highest system temperature and working fluid.
Alternatively, stainless steel tanks may be provided. Tank life should be at least 15 yrs.

Fiberglass and plastic tanks are corrosion resistant and easily installed, and are available in many
shapes and sizes. Although many commonly fabricated tanks will begin to soften at temperatures above
the temperature range of 140 to 160 °F (60 to 71 °C). There are more expensive, specially fabricated
tanks available that can withstand temperatures up to 250 °F (121 °C). The types of plastics needed to
store large quantities of water at high temperatures can be more expensive than steel.

All storage tanks require insulation with a rating at least R-19.It is a good practice to insulate tank
supports from the ground if possible. Additional information on tank insulation can be found in the
Solar Energy Equipment Chapter of the ASHRAE Handbook - HVAC Systems and Equipment.

All storage tanks for liquids should be located so that if they leak, damage to the building will be
prevented. The drain back tank needs a drain line piped to a nearby floor drain. The cost of housing
the tank or burying it must be included in the total cost of the solar heating system. Buried tanks
must be protected from ground water, and buoyant forces resisted. Underground tanks are not
preferred, if other options are available. Tanks must be reasonably accessible for repairs. Tank
connections should comply with local codes with regards to backflow preventers, safety relief
valves, etc.

5.3.7 Integration of s olar c ollec tor s ys tem into exis ting hot water dis tribution s ys tem

Solar water heating systems maximize solar heat production when installed in a preheat
configuration, i.e., the cold water supply is redirected to the solar storage tank where it can be
preheated, and on a draw, the preheated water is directed into the backup or boiler tank for a final
bump to temperature before servicing the usage. Of course this requires operation of the boiler
equipment adding to the annual fuel use. Also, the firing rates in this mode may not be in the most
efficient firing range of boiler operation.

One method to minimize the back-up boiler operation is to heat the DHW entirely by the solar
collectors. One method to accomplish is to recirculate the water leaving the collector again through
the collectors if it is not hot enough. This set-up requires a three-way valve between the return and
either solar storage tank. This will allow the heat transfer fluid warmed by the collector to be
directed either to the storage tank or to the line going back to the solar collectors. The control logic
is when the solar tank temperature is higher than the return of the recirculation water; the solar
collectors can heat it up further. When the solar tank temperature is below the temperature of the
heat transfer fluid leaving the collector, it is directed to the tank.

5.3.8 C ontrols

There should be an automatic control system that senses system performance and properly
transfers collected heat to the intended users. Since the amount of heat being collected can vary as
does the demand for heat by the users, the control system must tract both of these variables and
operate the systems equipment to achieve the maximum performance. The control system
accomplishes this by taking information from sensors and, through the controllers, operates pumps,
adjusts valves, and activates the auxiliary heating system.

Solar Hot Water Systems Design 79


Ezekiel Enterprises, LLC

To correctly monitor the solar hot water system, is important to understand system operation and to
maintain good efficiencies. The collection of operational data will assist in the tracking of system
performance and aid in scheduling system maintenance. This monitored information shall be
collected every day of the year on 15-minute interval. All monitor systems should be centrally
monitored for consistency; operating personnel must maintain a familiarity with the hardware and
software, and the system must be properly managed through trend tracking and effective
dispatching of service personnel. The minimum monitoring points are:
• tank temperature
• solar array circulating pump start/stop
• solar array circulating pump status
• solar controller alarm
• solar array inlet temperature
• solar array discharge temperature
• solar array discharge temperature alarm high limit.

The temperature sensors that measure the collector discharge temperature should be monitor the
absorber plate temperature near the collector outlet. The storage tank temperature should be at the
tank bottom to obtain the coldest temperature. These sensors send this collected information to a
controller called a differential temperature thermostat, which then compares it with the adjustable
setpoints - usually the high and low values. When the high value is reached (typically 12 °F to 15 °F
(-11 to -9.44 °C) an action to withdraw the heat from the collector is initiated; for example starting a
pump. As the pump runs the temperature differential drops and after some period of time the low
setpoint is reached (typically 4 °F [-15.56 °C]). At this temperature difference, the pump is stopped.
The pump is restarted when the high limit of the thermostat is again reached.

When a system has freeze and/or overheating protection, the controller takes the appropriate
actions. For example, when freeze setpoint is reached at the collector, the pump could be activated
to pump warm water from the storage tank into the collector. The freeze protection setpoint should
be set at 40 °F (4 °C) since heat can radiate from the collector to the night sky creating collector
freezing conditions above 32 °F (0 °C) outdoor temperatures. The freeze protection sensor must be
placed on the collector so that it will sense the coldest water in the collector. This location may be
the collector intake or return manifold, the back of the absorber plate near the bottom or center of
the collector. The collector center is identified to monitor the irradiation leaving the collector at night.
More than one sensor can be used for this function.

The energy produced by solar energy shall be determined by a Btu meter that will measure the
domestic hot water flow from the storage tank, the incoming cold make-up water temperature, and
the hot water temperature leaving the domestic hot water storage tank. These values should be
continually evaluated and compared to previous values to assure proper performance is
maintained.

Overheating controls would be initiated when the collector temperature reaches a temperature in
the range of 200 to 250 °F (93 to 121 °C) depending on the system. The sensor monitoring this
condition would be placed on the back of an absorber plate in the collector. When the collector
reaches the high temperature setpoint due to a pump failure or some other event, the controller can
take actions to relieve the heat and protect the system. See section 2.4.2 for more information.

The control components are the same that would be used on a commercial hot water heating
system.

A typical sequence of operation for the operation of the solar collector circulation pump that sends
water to the storage tank is:

Solar Hot Water Systems Design 80


Ezekiel Enterprises, LLC

• System run command:


If solar array temperature is above the solar tank temperature by 12 °F (-11 °C), energize solar collector
circulation pump P-1. Pump shall be energized during daylight hours only. On command to start, pump
must remain energized for an adjustable period of time (initial setting of 20 minutes).
• System stop command (high temperature):
If solar collector circulation pump P-1 is energized and if solar storage tank temperature rises above
185 °F (85 °C) (adjustable), activate a high temperature alarm. If solar storage tank temperature rises
above 195 °F (91 °C) (adjustable), de-energize solar circulation pump P-1.
• System stop command (low temperature):
If solar collector circulation pump P-1 is energized and solar array discharge temperature falls below the
solar tank temperature for a period of 10 minutes (adjustable), solar collector circulation pump shall de-
energize.
• Thermal shock prevention:
If solar circulation pump P-1 is de-energized during daylight hours and if solar array temperature is below
180 °F (82 °C) (adjustable), solar circulation pump shall be enabled.

If solar circulation pump P-1 is de-energized and if solar array temperature is 180 °F (82 °C) or
above (adjustable), solar circulation pump P-1 shall be disabled for an adjustable time period (8 hr
initial setting).

The sequence of control assumes a constant speed pump circulating the heat transfer fluid through
the collectors. If a variable speed pump is used, then the pump speed could be altered instead of
stopping and starting the pump. Of course the pump operation would be stopped when night begins
and when excessive temperatures are reached in the collector. Another option would have a three-
way valve that would allow the heat transfer fluid to circulate through the collector again if it is not
hot enough to be placed in the storage tank.

5.4 S ys tem s tartup c ons iderations

All pumps, valves and sensors need to be checked for proper operation before starting of fluid flow
systems.

5.4.1 Method of filling system and removal of air

Before filling the piping systems with heat transfer fluids the pipes need to be flushed to remove any
foreign material and debris. A high head, low flow filling pump will produce the best results. For
commercial systems, the arrays must be staggered so air can be methodically purged from the
system.

5.4.2 Method of leak detection

On completion of the piping system, it should be pressure tested for leaks. All piping systems
should always include a pressure gauge (digital or dial) for monitoring the fluid pressure. The
system should be filled first with water and put under pressure of 1½ times the operating pressure
for a minimum of 2 hrs, while the pressure is monitored and the distribution is inspected for leaks.
The leak inspection should be completed before installing any piping insulation.

Solar Hot Water Systems Design 81


Ezekiel Enterprises, LLC

6. System Maintenance
6.1 General maintenance

Operation and maintenance (O&M) costs of each solar water heating system is estimated at ½ of
1% of initial cost per year. O&M is similar to that required of any hydronic heating loop and may be
provided by site staff, with experts called in if something should fail. Regularly scheduled
maintenance includes:
• Check the solar collectors and structure components for any damage. Note location of panel
glazing or broken evacuated tubes needing replacement. Note any surface damage on absorber
panel and that tubing containing heat transfer fluid is in good condition.
• Check tightness of mounting connectors. Repair any bent or corroded mounting components.
• Drain energy storage tanks for sediment removal.
• Check condition of heat transfer fluids.
• Determine if any new objects, such as vegetation growth, are causing shading of the array and
remove them if possible.
• Clean outer surface of collector array annually with plain water or mild dishwashing detergent.
Do not use brushes, any types of solvents, abrasives, or harsh detergents.
• Check all connecting piping for leaks. Repair any damaged components.
• Check plumbing for signs of corrosion.
• Check condition of corrosion inhibitors in heat transfer fluids and the state of the sacrificial
anodes in the system.
• Observe operational indicators of temperature and pressure to ensure proper operation of
pumps and controls.
• Observe that the collector heat transfer fluid pump is running on a sunny day and not at night.
• Use insolation meter to measure incident sunlight and simultaneously observe temperature and
energy output values given by system controller. Compare the values with original efficiency of
system.
• Check status indicators provided by system controller. Compare indicators with measured
values.
• Document all operation and maintenance activities in a workbook available to all service
personnel.
• Check proper position of all valves.
• Flush entire piping system to remove mineral deposits every 10 yrs.

A more through checklist can be found in the Solar Energy Use Chapter of the ASHRAE Handbook
— HVAC Applications.

6.2 Glycol fluid care

The decomposition rate of glycol varies according to the degree of aeration, high temperature
exposure and the service life of the solution. Most water/glycol solutions require periodic monitoring
of the pH level and the corrosion inhibitors. The pH should be maintained between 6.5 and 8.0.
Replacement of the water/glycol solution may be as often as every 12–24 months or even sooner in
high temperature systems. If these solutions are used in the collector loop, the installer should
specify the expected life of the solution and the amount of monitoring required. The cost of periodic
fluid replacement and monitoring should be considered in the economic analysis. For best
performance, the glycol should be replaced every few years. Since glycol-water mixtures do require
a lot of maintenance (and since users can be quite negligent) it is recommended that glycols not be
used in family housing solar heating and DHW systems, and that glycol-water solutions be reserved
for use in large-scale installations, which have regular maintenance schedules.

Solar Hot Water Systems Design 82


Solar Hot Water Systems Design Quiz Ezekiel Enterprises, LLC

1. Which of the following locations in the United States get the most daily solar radiation?
o a. Austin, TX
o b. Fargo, ND
o c. Jacksonville, FL
o d. Sacramento, CA
o
2. True or False? A system for year-round heating should have a tilt angle equal to the site’s
latitude.
o True
o False
o
3. Of the following, which are the performance characteristics that are used to assess and compare
solar thermal systems?
o a. Solar fraction (SF)
o b. Specific solar energy yield (SE)
o c. Solar system efficiency (SN)
o d. All of the above
o
4. What system would be recommended for a location with outdoor winter temperatures that are
below freezing?
o a. Passive system
o b. Direct circulating active system
o c. Indirect circulating active system
o d. Any of the above
o
5. True or False? The purpose of the transparent cover is to reduce the radiant losses from the
absorber, while allowing the maximum amount of radiation to reach the absorber.
o True
o False
o
6. Which of the following collectors is designed to increase water/steam temperatures up to 350°F
and also are the most efficient for cold climates?
o a. EPDM collector
o b. Flat plate
o c. Evacuated tube
o d. Parabolic trough
o
7. True or False? Rather than water as a medium, a hot air collector uses air. This configuration
may be an alternative in certain situations.
o True
o False
Solar Hot Water Systems Design Quiz Ezekiel Enterprises, LLC

o
8. What is the term for the potential hazard when the heat transfer fluid stays in the collector too
long and a high temperature is reached greater than the normal due to the heat from solar
radiation?
o a. Stagnation
o b. Thermal capacity
o c. Steam producing power
o d. glycol strain
o
9. The flow through each solar collector should have basically ____________ pressure drop.
o a. zero
o b. the same
o c. substantial
o d. an imbalanced
o
10. True or False? A challenge in applying renewable energies is often the mismatch between the
time energy is needed and the time energy is available.
o True
o False
o
11. The greatest health danger is not in drinking contaminated water, but in inhaling contaminated
dispersed water droplets, which can happen when taking a shower. What hazard is this referring
to especially susceptible in solar water heating systems?
o a. Lead poisoning from antiqued piping systems
o b. Radiation sickness from large quantities of free radicals in solar heated water
o c. Second degree internal burns due to high water temperature fluctuations in an
operating system
o d. Legionella Pneumophila bacterium which flourishes in water between 86 to 113 °F
o
12. The expansion tank has essentially two chambers, one filled with nitrogen at the system
pressure and one which can fill with the expanded heat transfer fluid; the chambers are
separated by a membrane material which cannot exceed this temperature?
o a. 100°F
o b. 160°F
o c. 200°F
o d. 450°F
o
Solar Hot Water Systems Design Quiz Ezekiel Enterprises, LLC

13. What is the independent organization that tests and provides a certification rating of various
solar collectors and solar water heating systems?
o a. The Solar Rating and Certification Corporation (SRCC) http://www.solar-rating.org/
o b. Leadership in Energy and Environmental Design (LEED) https://new.usgbc.org/leed
o c. Solar Energy Industries Association (SEIA) https://www.seia.org/
o d. American Solar Energy Society (ASES) https://www.ases.org/
o
14. Which of the following equations can be used to estimate annual energy savings?
(Ac=collector area, L=Daily Load, ηsolar=efficiency of solar system, Es=annual energy savings,
Imax=maximum daily solar radiation, Iave=average solar radiation, ηboiler=auxiliary heater
efficiency, Ce=cost of auxiliary energy, csolar=per-unit-area cost of installed solar system)
o b. = Ac * Iave * ηsolar * 365 / ηboiler
o c. = Es * Ce
o d. = csolar * Ac
o a. = L / (ηsolar * Imax)
o
15. True or False? Large central solar water heating systems are normally more cost effective due to
economies of scale in installation, operation and maintenance compared to several small
systems.
o True
o False
o
16. The maximum distance from the collector field to the mechanical room and storage tank should
be less than?
o a. 100 ft.
o b. 300 ft.
o c. 600 ft.
o d. 1,000 ft.
o
17. Can collectors be placed on a vertical wall and if so, what is the benefit?
o a. Yes, the benefit being having a more optimum tilt angle
o b. Yes, the benefit being eliminating the cost of insulation and weatherproofing to
offset the reduction in solar energy collection performance
o c. No, the system will have too much of a pressure differential between collectors
o d. No, there is will be zero benefit due to increased cost of installation and decreased
efficiency
o
Solar Hot Water Systems Design Quiz Ezekiel Enterprises, LLC

18. All piping shall be sloped at ________ of run back to the drain back tank.
o a. 1/4 in/ft
o b. 1/8 in/ft
o c. 1.0 in/ft
o d. 2.0 in/ft
o
19. Which of the following pumps are suggested to be used on a solar hot water system?
o a. Constant flow pumps
o b. Electronic pressure-controlled pumps (variable flow)
o c. Highly efficient pressure-controlled pumps (variable flow).
o d. All of the above
o
20. Operation and maintenance (O&M) costs of each solar water heating system is estimated at
________ of initial cost per year.
o a. ½ of 80%
o b. ½ of 25%
o c. ½ of 10%
o d. ½ of 1%