Pressure reducing valves 9.
681
Pressure reducing valves
made of gunmetal with
→ Series 681 threaded connections
SUITABLE FOR
Liquids neutral and non-neutral
Air, gases and vapours neutral and non-neutral
Warm water
EXAMPLES OF USE
For the protection of:
- domestic water supply systems
- commercial and industrial plants
against too high supply pressure.
Pressure reducers are used, if within a piping system despite of varying
pressures on the inlet side a certain pressure must not be exceeded on
the outlet side.
• potable water supply according to DIN 1988
• process water supply in industrial-and building technology
• snow-making equipment
• fire-fighting equipment and sprinkler systems
• shipbuilding industry and offshore plants
APPROVALS
DIN-DVGW type examination
Type approval ACS
MATERIAL
Type approval WRAS
Type approval SINTEF
TR ZU 032/2013 - TR ZU 010/2011
Requirements
SPECIFICATION
DIN DVGW guidelines DIN EN ISO 3822
DIN EN 1567 PED 2014/68/EU
DIN 1988
Classification society
Inlet pressure:
1/2“ – 2“ – 10°C to + 95°C Germanischer Lloyd GL
up to 40 bar
Outlet pressure: Lloyd’s Register EMEA LR EMEA
0,5 to 15 bar American Bureau of Shipping ABS
depending on version Bureau Veritas BV
Russian Maritime Register of Shipping RS
MATERIALS
Component Material DIN EN ASME
Inlet body Gunmetal CC499K CC499K
Outlet body Gunmetal CC499K CC499K
Internal parts Gunmetal CC499K CC499K
Stainless Steel 1.4404 316 L
Spring Spring steel with anti-rust protection 1.1200 ASTM A228
Strainer Stainless Steel 1.4404 316 L
Version 2016 / 02 www.goetze-armaturen.de | [email protected] | Phone: +49(0)7141.48894-60
VALVE VERSION
High-quality, heat-resistant moulded elastomere, fabric-reinforced diaphragm.
m with diaphragm Adjustment by means of non-rising spindle.
Insert with balanced single seat valve made of gunmetal.
Complete valve insert SP/HP (order code: 681 Insert-DN..-seal) available as replacement part can be exchanged without removing the valve.
Complete valve insert LP (order code: 681 LP Insert-DN..-seal) available as replacement part can be exchanged without removing the valve.
Built-in dirt trap made of stainless steel.
DN 15 to DN 32 0,60 mm
Mesh size:
DN 40 and DN 50 0,75 mm
MEDIUM
for water, neutral and non-sticking liquids, compressed air and neutral gases; optionally with
GF gaseous and liquid
FPM elastomere seals for non-neutral media i.e. oils, fuels, oil-laden compressed air, etc.
T YPE OF LIF TING MECHANISM
O without lifting device
OUTLET PRESSURE RANGES
SP Standard version Inlet pressure: up to 40 bar Outlet pressure: from 1 to 8 bar
HP High-pressure version Inlet pressure: up to 40 bar Outlet pressure: from 5 to 15 bar
LP Low-pressure version Inlet pressure: up to 25 bar Outlet pressure: from 0,5 to 2 bar
Fixed setting at a required outlet pressure against surcharge .
AVAIL ABLE NOMINAL DIAMETERS AND CONNECTION SIZES
Nominal diameter DN 15 20 25 32 40 50
Inlet 1/2“ (15) 3/4“ (20) 1“ (25) 1 1/4“ (32) 1 1/2“ (40) 2“ (50)
Outlet 1/2“ (15) 3/4“ (20) 1“ (25) 1 1/4“ (32) 1 1/2“ (40) 2“ (50)
T YPE OF CONNECTION INLET / OUTLET THREADED CONNECTIONS
BSP-Tm / BSP-Tm Standard threaded connections Male thread BSP-T / Male thread BSP-T DIN EN 10226, ISO 7-1 / DIN EN 10226, ISO 7-1
f/f Version with female thread Female thread BSP-P / Female thread BSP-P DIN EN ISO 228-1 / DIN EN ISO 228-1
available in sizes DN15, DN20 and DN25
SEALS
Elastomere moulded diaphragm and seals
EPDM Ethylene propylene diene –10°C to +95°C
approvals according to drinking water directive
Against surcharge
FKM Fluorocarbon Elastomere moulded diaphragm and seals –10°C to +95°C
OPTIONS
Against surcharge
Pressure gauges 36, 39 or 40 Chapter Accessories
Valve insert SP/HP completely made of stainless steel Order code: 481 Insert-DN…seal
Valve insert LP completely made of stainless steel Order code: 481 LP Insert-DN...seal
Version 2016 / 02 www.goetze-armaturen.de | [email protected] | Phone: +49(0)7141.48894-60
NOMINAL DIAMETERS, CONNECTIONS, INSTALL ATION DIMENSIONS
Series 681: Connection, installation dimensions, ranges of adjustment
Connection DN 15 20 25 32 40 50
Inlet DIN EN 10226 G1 1/2" 3/4" 1" 1 1/4" 1 1/2" 2"
Outlet DIN EN 10226 G2 1/2" 3/4" 1" 1 1/4" 1 1/2" 2"
Inlet pressure SP, HP up to bar 40 40 40 40 40 40
Inlet pressure LP to bar 25 25 25 25 25 25
Outlet pressure bar 0,5 - 2 0,5 - 2 0,5 - 2 0,5 - 2 0,5 - 2 0,5 - 2
1-8 1-8 1-8 1-8 1-8 1-8
5 - 15 5 - 15 5 - 15 5 - 15 5 - 15 5 - 15
Installation dimensions in L 142 158 180 193 226 252
mm l 80 90 100 105 130 140
l1 85 95 105
H (H1) 102 (128 1) 102 (128 1) 130 (150 1) 130 (150 1) 165 (1851) 165 (1851)
h 33 33 45 45 70 70
SW1 30 37 46 52 65 75
SW2 28 35 43 48 57 68
Weight kg 1,2 (1,51) 1,3 (1,61) 2,4 (2,9 1) 2,6 (3,11) 5,5 (6,2 1) 6,0 (6,71)
Coefficient of flow K VS m³/h 3 3,5 6,7 7,6 12,5 15
¹for type 681mGFO-LP
2
The K VS value was determined according to DIN EN 60534-2-3. Instructions on how to determine size and capacity are to be found under section 2.
MAIN DIMENSIONS, INSTALL ATION DIMENSIONS
INDIVIDUAL SELECTION / VALVE CONFIGURATION
Series Valve Medium Lifting Outlet Nominal Connection type Connection size Seal Options Optional: Quantity
version device pressure diameter fixed
DN Inlet Outlet Inlet Outlet setting
Pressure
681 m GF O SP 20 BSP-T m BSP-T m 20 20 EPDM
Gauge 36
8
681 m GF O SP 15 f f 15 15 EPDM 4
681 m GF O
681 m GF O
In this table you can configure a valve according to your Name
individual requirements (similar to the example shown, which
should be deleted before you enter your own data). Please First Name
complete the table by hand using the abbreviations in this
datasheet and then fax it to: +49(0)7141.4889488
Please do not forget to add your personal data so that our sales Company
team can contact you.
Telephone
E-Mail
Version 2016 / 02 www.goetze-armaturen.de | [email protected] | Phone: +49(0)7141.48894-60
CAPACIT Y CHARTS
Series 681:
Dimensioning by pressure loss on the outlet pressure side
Flow chart water
Flow rate V in [m³/h]
Pressure drop delta p [bar]
Dimensioning by fl ow velocity
For liquids:
With help of the chart you can determine the nominal diameter (DN) for a given fl ow volume V (m³/h). According to DVGW-guidelines (DIN 1988) a fl ow
velocity of 2 m/s in domestic water supply systems should not be exceeded.
For compressed air and other gaseous media:
The usual fl ow velocity for compressed air is 10 - 20 m/s. For gaseous media the fl ow volume V should always be shown in actual cubic meters/hour.
If the fl ow volume is given in standard cubic meters, these should be converted into actual cubic meters before using the diagram.
Actual cubic meters are based on the prevailing pressure of the medium on the outlet side of the pressure reducer.
Compressed air
Flow velocity c [m/s]
Water
Flow volume V [m3 /h]
Version 2016 / 02 www.goetze-armaturen.de | [email protected] | Phone: +49(0)7141.48894-60