Version 7.1.
PVsyst - Simulation report
Grid-Connected System
Project: Coya_Javier_P50
Variant: 20200917 EYE1_Solargis_P50_InverterModelChanged
Unlimited Trackers with backtracking
System power: 200.1 MWp
CoyaP50_Ruta 24 - Chile
Author
Enertis Solar S.L. (Spain)
Project: Coya_Javier_P50
Variant: 20200917 EYE1_Solargis_P50_InverterModelChanged
PVsyst V7.1.6 Enertis Solar S.L. (Spain)
VC2, Simulation date:
13/03/21 20:30
with v7.1.6
Project summary
Geographical Site Situation Project settings
CoyaP50_Ruta 24 Latitude -22.26 °S Albedo 0.20
Chile Longitude -69.48 °W
Altitude 1228 m
Time zone UTC-5
Meteo data
Ruta 24
SolarGISv2.2.9 - TMY
System summary
Grid-Connected System Unlimited Trackers with backtracking
PV Field Orientation Near Shadings
Orientation Tracking algorithm No Shadings
Tracking horizontal axis Astronomic calculation
Backtracking activated
System information
PV Array Inverters
Nb. of modules 375396 units Nb. of units 57 units
Pnom total 200.1 MWp Pnom total 195.9 MWac
Grid power limit 180.0 MWac
Grid lim. Pnom ratio 1.112
User's needs
Unlimited load (grid)
Results summary
Produced Energy 584643 MWh/year Specific production 2922 kWh/kWp/year Perf. Ratio PR 84.58 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Horizon definition 6
Main results 7
Loss diagram 8
Special graphs 9
13/03/21 PVsyst Licensed to Enertis Solar S.L. (Spain) Page 2/9
Project: Coya_Javier_P50
Variant: 20200917 EYE1_Solargis_P50_InverterModelChanged
PVsyst V7.1.6 Enertis Solar S.L. (Spain)
VC2, Simulation date:
13/03/21 20:30
with v7.1.6
General parameters
Grid-Connected System Unlimited Trackers with backtracking
PV Field Orientation
Orientation Tracking algorithm Backtracking strategy
Tracking horizontal axis Astronomic calculation Nb. of trackers 100 units
Backtracking activated Unlimited trackers
Sizes
Tracker Spacing 11.0 m
Collector width 4.46 m
Ground Cov. Ratio (GCR) 40.5 %
Phi min / max -/+ 90.0 °
Backtracking limit angle
Phi limits +/- 66.0 °
Models used
Transposition Perez
Diffuse Imported
Circumsolar separate
Horizon Near Shadings User's needs
Average Height 1.2 ° No Shadings Unlimited load (grid)
Bifacial system
Model 2D Calculation
unlimited trackers
Bifacial model geometry Bifacial model definitions
Tracker Spacing 11.00 m Ground albedo 0.21
Tracker width 4.46 m Bifaciality factor 70 %
Tracking limit angle 60 ° Rear shading factor 0.0 %
GCR 40.5 % Rear mismatch loss 5.0 %
Axis height above ground 2.20 m Module transparency 0.0 %
Grid power limitation
Active Power 180.0 MWac
Pnom ratio 1.112
PV Array Characteristics
Array #1 - 530Wp
PV module Inverter
Manufacturer Jinkosolar Manufacturer Sungrow
Model JKM530M-7TL4-TV Model SG3125HV-20
(Custom parameters definition) (Custom parameters definition)
Unit Nom. Power 530 Wp Unit Nom. Power 3437 kWac
Number of PV modules 152628 units Number of inverters 23 units
Nominal (STC) 80.89 MWp Total power 79051 kWac
Modules 5451 Strings x 28 In series Operating voltage 875-1300 V
At operating cond. (50°C) Max. power (=>25°C) 3593 kWac
Pmpp 73.79 MWp Pnom ratio (DC:AC) 1.02
U mpp 1028 V
I mpp 71800 A
13/03/21 PVsyst Licensed to Enertis Solar S.L. (Spain) Page 3/9
Project: Coya_Javier_P50
Variant: 20200917 EYE1_Solargis_P50_InverterModelChanged
PVsyst V7.1.6 Enertis Solar S.L. (Spain)
VC2, Simulation date:
13/03/21 20:30
with v7.1.6
PV Array Characteristics
Array #2 - 535Wp
PV module Inverter
Manufacturer Jinkosolar Manufacturer Sungrow
Model JKM535M-7TL4-TV Model SG3125HV-20
(Custom parameters definition) (Custom parameters definition)
Unit Nom. Power 535 Wp Unit Nom. Power 3437 kWac
Number of PV modules 222768 units Number of inverters 34 units
Nominal (STC) 119.2 MWp Total power 116858 kWac
Modules 7956 Strings x 28 In series Operating voltage 875-1300 V
At operating cond. (50°C) Max. power (=>25°C) 3593 kWac
Pmpp 108.7 MWp Pnom ratio (DC:AC) 1.02
U mpp 1031 V
I mpp 105446 A
Total PV power Total inverter power
Nominal (STC) 200074 kWp Total power 195909 kWac
Total 375396 modules Nb. of inverters 57 units
Module area 949309 m² Pnom ratio 1.02
Cell area 892481 m²
13/03/21 PVsyst Licensed to Enertis Solar S.L. (Spain) Page 4/9
Project: Coya_Javier_P50
Variant: 20200917 EYE1_Solargis_P50_InverterModelChanged
PVsyst V7.1.6 Enertis Solar S.L. (Spain)
VC2, Simulation date:
13/03/21 20:30
with v7.1.6
Array losses
Array Soiling Losses Thermal Loss factor DC wiring losses
Loss Fraction 2.0 % Module temperature according to irradiance Global array res. 0.24 mΩ
Uc (const) 29.0 W/m²K Global wiring resistance 0.096 mΩ
Uv (wind) 0.0 W/m²K/m/s Loss Fraction 1.5 % at STC
LID - Light Induced Degradation Module Quality Loss Module mismatch losses
Loss Fraction 1.5 % Loss Fraction -0.8 % Loss Fraction 1.0 % at MPP
IAM loss factor
Incidence effect (IAM): User defined profile
0° 30° 50° 60° 70° 75° 80° 85° 90°
1.000 1.000 1.000 0.999 0.989 0.964 0.922 0.729 0.000
AC wiring losses
Inv. output line up to MV transfo
Inverter voltage 600 Vac tri
Loss Fraction 0.0 % at STC
Global System
Wire section Copper 3 x 100000 mm²
Wires length 0m
MV line up to Injection
MV Voltage 33 kV
Average each inverter
Wires Copper 3 x 4000 mm²
Length 338400 m
Loss Fraction 0.5 % at STC
AC losses in transformers
MV transfo
Grid Voltage 33 kV
Operating losses at STC
Nominal power at STC (PNomac) 197075 kVA
Iron loss (night disconnect) 3.46 kW/Inv.
Loss Fraction 0.1 % at STC
Coils equivalent resistance 3 x 1.04 mΩ/inv.
Loss Fraction 1.0 % at STC
13/03/21 PVsyst Licensed to Enertis Solar S.L. (Spain) Page 5/9
Project: Coya_Javier_P50
Variant: 20200917 EYE1_Solargis_P50_InverterModelChanged
PVsyst V7.1.6 Enertis Solar S.L. (Spain)
VC2, Simulation date:
13/03/21 20:30
with v7.1.6
Horizon definition
Average Height 1.2 ° Albedo Factor 0.97
Diffuse Factor 1.00 Albedo Fraction 100 %
Horizon profile
Azimuth [°] -176 -168 -164 -156 -144 -140 -132 -128 -120 -108 -104 -96 -92 -84
Height [°] 1.4 1.4 1.4 1.6 1.8 1.8 1.8 1.8 1.8 2.2 2.4 2.2 2.2 2.2
Azimuth [°] -72 -68 -60 -56 -48 -36 -32 -24 -20 -12 -8 -1 0 1
Height [°] 2.4 2.4 2.4 2.2 2.2 1.4 1.2 0.8 0.6 0.4 0.4 0.4 0.4 0.4
Azimuth [°] 2 8 12 20 24 32 36 44 48 56 60 68 72 84
Height [°] 0.4 0.4 0.4 0.4 0.2 0.0 0.2 0.6 0.8 0.8 0.8 0.8 1.2 0.6
Azimuth [°] 92 96 104 108 120 128 132 140 144 156 164 168 176 180
Height [°] 0.4 0.4 0.6 0.8 0.8 0.8 0.6 0.4 0.4 0.4 0.6 0.8 1.0 1.2
Sun Paths (Height / Azimuth diagram)
13/03/21 PVsyst Licensed to Enertis Solar S.L. (Spain) Page 6/9
Project: Coya_Javier_P50
Variant: 20200917 EYE1_Solargis_P50_InverterModelChanged
PVsyst V7.1.6 Enertis Solar S.L. (Spain)
VC2, Simulation date:
13/03/21 20:30
with v7.1.6
Main results
System Production
Produced Energy 584643 MWh/year Specific production 2922 kWh/kWp/year
Performance Ratio PR 84.58 %
Normalized productions (per installed kWp) Performance Ratio PR
Balances and main results
GlobHor DiffHor T_Amb GlobInc GlobEff EArray E_Grid PR
kWh/m² kWh/m² °C kWh/m² kWh/m² MWh MWh ratio
January 268.9 58.20 23.12 346.6 334.5 58623 56994 0.822
February 225.5 53.10 23.25 289.4 279.2 49858 48482 0.837
March 228.5 47.94 22.43 303.6 293.2 53258 51800 0.853
April 190.1 34.38 21.25 258.0 248.8 45999 44792 0.868
May 163.3 30.31 20.23 224.7 216.5 40615 39604 0.881
June 142.5 27.46 16.42 195.9 188.7 36057 35179 0.898
July 154.3 30.21 17.27 211.3 203.5 38740 37786 0.894
August 186.6 34.33 19.23 254.2 245.0 45697 44507 0.875
September 216.4 37.26 20.97 292.7 282.7 51398 49997 0.854
October 259.8 43.44 22.01 345.8 333.9 58674 57035 0.824
November 271.2 44.09 22.62 359.2 347.3 59565 57907 0.806
December 284.4 53.31 23.24 373.5 360.9 62288 60560 0.810
Year 2591.3 494.05 20.99 3454.9 3334.2 600773 584643 0.846
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
13/03/21 PVsyst Licensed to Enertis Solar S.L. (Spain) Page 7/9
Project: Coya_Javier_P50
Variant: 20200917 EYE1_Solargis_P50_InverterModelChanged
PVsyst V7.1.6 Enertis Solar S.L. (Spain)
VC2, Simulation date:
13/03/21 20:30
with v7.1.6
Loss diagram
2591 kWh/m² Global horizontal irradiation
+33.3% Global incident in coll. plane
-0.27% Far Shadings / Horizon
-1.48% Near Shadings: irradiance loss
-0.12% IAM factor on global
-2.00% Soiling loss factor
+0.35% Ground reflection on front side
Bifacial
Global incident on ground
1223 kWh/m² on 2341345 m²
-79.00% (0.21 Gnd. albedo)
Ground reflection loss
-79.93% View Factor for rear side
+11.98% Sky diffuse on the rear side
0.00% Beam effective on the rear side
0.00% Shadings loss on rear side
4.27% Global Irradiance on rear side (142 kWh/m²)
3334 kWh/m² * 949309 m² coll. Effective irradiation on collectors
efficiency at STC = 21.08% PV conversion, Bifaciality factor = 0.70
687073 MWh Array nominal energy (at STC effic.)
-0.01% PV loss due to irradiance level
-8.01% PV loss due to temperature
+0.75% Module quality loss
-1.50% LID - Light induced degradation
-1.00% Module array mismatch loss
-0.21% Mismatch for back irradiance
-1.52% Ohmic wiring loss
610162 MWh Array virtual energy at MPP
-1.33% Inverter Loss during operation (efficiency)
-1.56% Inverter Loss over nominal inv. power
0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage
0.00% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
0.00% Night consumption
592625 MWh Available Energy at Inverter Output
0.00% AC ohmic loss
-0.95% Medium voltage transfo loss
-0.41% MV line ohmic loss
584643 MWh Energy injected into grid
13/03/21 PVsyst Licensed to Enertis Solar S.L. (Spain) Page 8/9
Project: Coya_Javier_P50
Variant: 20200917 EYE1_Solargis_P50_InverterModelChanged
PVsyst V7.1.6 Enertis Solar S.L. (Spain)
VC2, Simulation date:
13/03/21 20:30
with v7.1.6
Special graphs
Diagrama entrada/salida diaria
System Output Power Distribution
13/03/21 PVsyst Licensed to Enertis Solar S.L. (Spain) Page 9/9