Check List For Commissioning of Fm200 System: IR Ref. No.: Date: Ref. Documents: Discipline: Area/Location: Element

The document is a checklist for commissioning an FM200 fire suppression system. It lists 11 items to check, including verifying that installed materials match approved submittals, using approved drawings, testing smoke detector activation in two stages, checking the fire panel receives signals, and testing the functionality of abort switches, manual release stations, and cylinder solenoids. Representatives from the subcontractor, main contractor, and client must sign off after completing the checks.

Uploaded by

Umair BaBer
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views1 page

Check List For Commissioning of Fm200 System: IR Ref. No.: Date: Ref. Documents: Discipline: Area/Location: Element

The document is a checklist for commissioning an FM200 fire suppression system. It lists 11 items to check, including verifying that installed materials match approved submittals, using approved drawings, testing smoke detector activation in two stages, checking the fire panel receives signals, and testing the functionality of abort switches, manual release stations, and cylinder solenoids. Representatives from the subcontractor, main contractor, and client must sign off after completing the checks.

Uploaded by

Umair BaBer
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
  • Checklist for Commissioning of FM200 System

CHECK LIST FOR COMMISSIONING OF FM200 SYSTEM

IR Ref. No.: Date:


Ref. Documents: Discipline:
Area/Location: Element:

SN DESCRIPTION Y N N/A Remarks

1 Check all materials installed are as per approved material submittal.

2 Check the drawings used for installation are approved.

3 Check for the continuity of Fire Cables before termination

4 Check for the power supply of FM 200 Control panel

5 Check the first stage activation of smoke detector

6 Check for second stage activatin of smoke detectors

7 Check for the signal in Fire Main Panel

8 Check for the functionality of Abort Switches

9 Check for the functionality of Manual release station

10 Check for theCylinder Solenoid functionality

11 Check for the interface with Building Main Fire Alarm Control Panel

Remarks (if any):

Sub-Contractor Representative Main Contractor Representative Consultant/Client Representative

Name:

Signature:

Date: